Академический Документы
Профессиональный Документы
Культура Документы
Harish K. Pillai
Department of Electrical Engineering,Indian Institute of Technology, Bombay, Powai, Mumbai 400076, India
Water management addresses the problem of optimal allocation of reusable water among different water-
using operations. Wastewater management deals with optimal design of effluent treatment units to respect
environmental norms. However, optimal design of effluent treatment units should be solved in conjunction
with the problem of optimal allocation of water among different processes that use water. A new methodology
for targeting minimum effluent treatment flow rate satisfying minimum freshwater requirement is proposed
in this paper. The proposed methodology can be applied to fixed-flow-rate as well as fixed-contaminant-load
problems having a single contaminant. A source composite curve is proposed for directly targeting generation
of wastewater. Freshwater can be indirectly targeted using overall mass balance. To target distributed generation
of wastewater, wastewater composite curve is proposed. On the basis of this wastewater composite curve,
targets for effluent systems can be set. All these targets can be set on a single concentration-contaminant
load diagram before designing the detailed water-allocation network. Analytical algorithms are proposed to
solve the integrated water and wastewater management problem. The minimum contaminant removal ratio of
the effluent treatment system and the minimum number of required effluent treatment units are also reported
in this paper.
interaction between operations that use water and effluent Table 2. Generation of Source Composite Curve and Targeting
treatment systems. In this method, they plotted limiting com- Wastewater for Example 1
posite curve, freshwater curve, and effluent treatment curve on contaminant net cum. mass cum. wastewater
a single concentration-contaminant load diagram. However, this concentration flow rate flow rate load mass load flow rate
(ppm) (t/h) (t/h) (kg/h) (kg/h) (t/h)
method is only applicable to fixed-contaminant-load operations.
In this paper, a novel methodology is developed for simul- 250 60 60 0 0 40
200 -70 -10 3 3 35
taneously targeting distributed effluent treatment system and 150 70 60 -0.5 2.5 50
minimum freshwater requirement. A source composite diagram 100 20 80 3 5.5 45
is introduced to target minimum wastewater production both 50 -50 30 4 9.5 10
for fixed-contaminated-load and fixed-flow-rate problems. In 20 -50 -20 0.9 10.4 -20
the proposed methodology, freshwater requirement is calculated 0 0 -20 -0.4 10 0
through the overall mass balance. The source composite diagram
is then used to develop the wastewater composite curve. The
Step 4. Calculate the entries of the fourth column by the
minimum effluent flow rate for treatment, minimum contaminant
formula Pi ) Qi-1(Ci-1 - Ci). Note that Q0 is assumed to be
removal ratio, and minimum number of treatment units required
zero.
for the overall effluent treatment process are also targeted in Step 5. The fifth column contains the cumulative contaminant
this paper. Graphical representations as well as analytical
mass load ∆mi ) ∑j)1 i
Pj.
algorithms are proposed to address integrated process water
Step 6. Calculate the corresponding wastewater flow rate fww,i
management issues. The conceptual approach presented in this
) (∆mT - ∆mi)/(Ci - Cfw) where Cfw is the concentration of
paper is restricted to a single contaminant.
the freshwater and ∆mT ()∆mn) is the total contaminant load
of the process. Note that wastewater flow rates are calculated
2. Wastewater Targets for concentrations such that Ci > Cfw.
Now the fifth column (cumulative mass load) may be plotted
In the following subsections, a new methodology is proposed against the first column (concentration) to obtain the source
to target simultaneously the minimum freshwater requirement, composite curve. The largest entry in the last column is the
maximum water reuse, minimum wastewater generation, and minimum wastewater flow-rate target.
minimum effluent to be treated to meet environmental norms. The last entry in the third column gives water loss/gain in
In the proposed method, minimum wastewater produced is the overall process. A negative entry suggests water loss, and
targeted directly. In this method, a novel limiting composite a positive entry indicates an overall water gain in the process.
curve, called source composite curve, is proposed. The source For a fixed-contaminant-load problem, the last entry should be
composite curve is plotted on a concentration (C) vs contaminant zero. This is expected because there is no water gain/loss in
load (∆m) diagram. any process.
2.1. Source Composite Curve and Targeting Wastewater. In step 6 of the previous algorithm, minimum wastewater is
Every fixed-contaminant-load problem may be converted to a targeted from the source composite diagram. This is similar to
fixed-flow-rate problem at the targeting stage with the limiting the freshwater targeting approach of Wang and Smith.2 Similar
water flow rate being the specified flow rate for each process.4 to eq 1, the equation for the wastewater line is given as
Therefore, a water allocation problem may be modeled with
outlet streams leaving at a specified concentration and flow rate ∆m ) ∆mT - fww(C - Cfw) (2)
(sources of wastewater), while the inlet streams have a
maximum allowable concentration and a specified flow rate. At any concentration, the wastewater line cannot pickup more
The outlet of any process may be viewed as a source of contaminant load than what is available (given by the source
wastewater, while the inlet to any process represents the scope composite curve). The minimum wastewater can be targeted
of reusing wastewater or demands of wastewater. The source by rotating the wastewater line with (∆mT, Cfw) as the pivot
composite curve represents the maximum contaminant load at point such that it just touches the source composite curve. Note
different contaminant concentrations. Physically, the source that the wastewater line has a negative slope (eq 2), and the
composite curve is equivalent to the grand composite curve in slope is inversely proportional to the wastewater flow rate. This
heat-exchanger network synthesis23 and invariant rectifying and is equivalent to targeting nonpoint utilities in a heat-exchanger
stripping curves in distillation.24 An algebraic procedure for the network. Step 6 represents the analytical procedure equivalent
generation of source composite curve and targeting minimum to this graphical targeting of wastewater on the concentration
wastewater production is given below. (C) vs contaminant load (∆m) diagram.
2.1.a. Minimum Wastewater Targeting Algorithm. Minimum wastewater targeting algorithm is applied on
example 1. The limiting process data for example 1 is given in
Step 1. Arrange all the distinct concentrations (of freshwater,
Table 1.8 Values calculated by applying this proposed algorithm
demands, and sources together) in descending order in the first
are shown in Table 2. In Table 2, the last entry in the third
column. Without loss of generality, the entries of the first
column is -20. It suggests that there is an overall water loss of
column are C1 > C2 > C3 > ... > Cn.
20 t/h. The bottom entry in the fifth column signifies the total
Step 2. For each concentration Ci (in the first column), put contaminant load of the process, and the same has to be picked
the corresponding net flow Fi in the second column. The net up by the wastewater (∆mT ) 10 kg/h). The maximum entry in
flow Fi is calculated by taking the algebraic sum of flow rates the sixth column sets the minimum wastewater targets as 50
corresponding to a concentration Ci. We adopt the convention t/h.
of positive flow rates for sources and negative flow rates for The source composite curve and wastewater line for example
demands. 1 are shown in Figure 2. The maximum slope of the wastewater
Step 3. The corresponding entries in the third column are line corresponds to the minimum wastewater flow rate, since
cumulative flow rates given by the formula Qi ) ∑j)1 i
Fj. they have an inverse relationship (eq 2). So the minimum
5290 Ind. Eng. Chem. Res., Vol. 45, No. 15, 2006
Figure 2. Source composite curve and wastewater line for example 1. Figure 3. Source composite curve, wastewater line, and wastewater
composite curve for example 1.
wastewater flow rate target comes out to be 50 t/h, and the Table 3. Generation of Wastewater Composite Curve for Example 1
corresponding pinch composition (CP) is 150 ppm. Total water wastewater cum.
demand for this example is 300 t/h, and total available water cum. flow rate, mass
flow rate is 280 t/h. Therefore, there is a net loss of 20 t/h of contaminant mass wastewater after first cum. load
conc load flow rate pinch wastewater removed
water (last entry of third column in Table 2). Thus, the minimum (ppm) (kg/h) (t/h) (t/h) (t/h) (kg/h)
freshwater target comes out to be 70 t/h. It may be noted that,
250 0 40 25 25 0
for a fixed-contaminant-load problem, the minimum wastewater 200 3 35 -10 25 1.25
target is equal to the minimum freshwater target, as there is no 150 2.5 50 50 2.5
water loss/gain. 100 5.5 45 50 5
2.2. Wastewater Composite Curve. Wastewater line rep- 50 9.5 10 50 7.5
20 10.4 -20 50 9
resented by eq 2 gives the total wastewater available from the 0 10 0 50 10
unit. This information is sufficient for designing a centralized
effluent treatment plant and end-of-the-pipe solution. However, 2.2.a. Algorithm for Wastewater Composite Curve.
for the most efficient effluent treatment plants, the optimal Step 1. Determine overall wastewater flow rate, corresponding
design of treatment units must be solved in conjunction with pinch point (CP), and contaminant load removed up to pinch
the optimal freshwater allocation problem.18 It has been observed point (∆mTP) using minimum wastewater targeting algorithm.
that, for optimum design of the effluent treatment unit, Step 2. Repeat step 6 of previous algorithm considering ∆mT
wastewater streams should not be merged together to form a ) ∆mTP and Cfw ) CP. Therefore, wastewater flow rate is
single wastewater stream.17,18 Therefore, it is of utmost impor- calculated using the formula fww,1,i ) (∆mTP - ∆mi)/(Ci - CP)
tance to identify wastewater sources at different concentrations. for concentrations such that Ci > CP. The maximum of this
To identify wastewater streams at different concentration, Kuo column is the wastewater that can be generated (fww,1) that
and Smith18 suggested a simple procedure. First, the minimum corresponds to a new pinch point (CP,1).
freshwater requirement is determined. Since they have addressed Step 3. Repeat step 2 until the pinch concentration coincides
problems with fixed contaminant load, the freshwater line and with the top concentration (C1). Every repetition produces a
the wastewater line are identical. Up to the pinch point, the wastewater flow rate (fww,k) that corresponds to a pinch point
minimum freshwater targeted cannot be reduced further. After (CP,k).
the pinch point, the limiting composite curve and the freshwater Step 4. Cumulative wastewater flow rates are tabulated in
line diverge from each other. Considering the pinch point as a the next column using the formula Ri ) fww,k for Cp,k g Ci >
pivot, the freshwater line can be further rotated to minimize Cp,k-1.
the freshwater requirement. This procedure is equivalent to the Step 5. The last column contains the cumulative contaminant
removal of pockets for the grand composite curve in the context mass load removed by wastewater ∆mww,i ) ∑j)1 i
Rj-1(Cj-1 -
of heat-exchanger network design.23 Cj). Note that R0 is assumed to be zero.
The previous methodology can be followed on the source Similar to the source composite curve, plotting the last column
composite curve to obtain the wastewater composite curve. This against the concentration gives the wastewater composite curve.
procedure, in essence, removes all local concavities or pockets Results obtained by using the algorithm for the wastewater
and produces an outer convex curve. For a problem having only composite curve for example 1 are given in Table 3. For better
wastewater sources and no demand, the outer convex curve or readability, the first, fifth, and sixth columns of Table 2 are
the wastewater composite curve coincides with the source reproduced in the first three columns of Table 3. As indicated
composite curve. before, for example 1, minimum wastewater generated is 50
The wastewater composite curve divides the source composite t/h, which corresponds to a pinch concentration of 150 ppm
curve into different regions. Each region, in the order of (CP ) 150 ppm), and load removed up to pinch concentration
decreasing concentrations, cumulatively produces more waste- is 2.5 kg/h (∆mTP ) 2.5 kg/h). In example 1, only one step is
water than the previous one. Whenever there is an addition of sufficient for removing all pockets. Step 2 produces a pinch
wastewater at a particular concentration, the slope of the point that coincides with the top concentration of the first
wastewater composite curve decreases. This is essentially due column, i.e., 250 ppm. Both the wastewater line and the
to the convexity of the wastewater composite curve. This wastewater composite curve, for example 1, are plotted in Figure
property may be used to prove optimality of effluent treatment 3.
targets. From Table 3, it can be interpreted that wastewater is
Similar to the wastewater targeting approach, to avoid a generated at two different concentration levels (corresponding
tedious graphical targeting, an analytical algorithm is developed. to two pinch points): 25 t/h of wastewater is generated at 250
Ind. Eng. Chem. Res., Vol. 45, No. 15, 2006 5291
Table 4. Generation of Source Composite Curve, Targeting Wastewater, and Generation of Wastewater Composite Curve for Example 1 with
Cfw ) 20 ppm
wastewater wastewater cum.
cum. flow rate, flow rate, mass
contaminant net cum. mas mass wastewater after first after cum. load
conc flow rate flow rate load load flow rate pinch second wastewater removed
(ppm) (t/h) (t/h) (kg/h) (kg/h) (t/h) (t/h) pinch (t/h) (t/h) (kg/h)
250 60 60 0 0 45.22 36.67 25 25 0
200 -70 -10 3 3 41.11 25 -10 25 1.25
150 70 60 -0.5 2.5 60.77 60 60 2.5
100 20 80 3 5.5 61.25 61.25 5.5
50 -50 30 4 9.5 30 61.25 8.56
20 -50 -20 0.9 10.4 0 61.25 10.4
ppm (second pinch point) and (50 - 25) t/h, i.e., 25 t/h, of curves can be obtained simultaneously before designing the
wastewater is generated at 150 ppm (first pinch point). water-allocation network.
A network satisfying fresh and wastewater targets for example Let us denote Ce as the concentration below which wastewater
1 may be obtained using the nearest-neighbor algorithm,4 and may be discharged from the treatment plant (as the environ-
it is shown in Figure 4. It may be noted that the concept of mental regulations imposed on the overall plant). The contami-
water mains, introduced by Kuo and Smith,22 is not necessary nant load has to be treated and removed in the effluent treatment
to design a water-allocation network satisfying distributed plant. This can be explained better through Figure 5. We then
wastewater targets. draw a vertical line on the concentration vs contaminant load
Example 1 is slightly modified to observe the applicability diagram that meets the wastewater composite curve at Ce. The
of the proposed methodology and algorithm for contaminated vertical line divides the wastewater composite curve and, hence,
freshwater (Cfw > 0). Freshwater is assumed to have a the total contaminant load into two parts. Let us denote the
concentration of 20 ppm (Cfw ) 20). Note that 20 ppm is the contaminant load left of the vertical line as ∆mTef and the
maximum limit for concentration up to which freshwater can contaminant load right of the vertical line as ∆ms. If the total
be supplied. Beyond this, example 1 will become unsolvable, wastewater is discharged with a contaminant load of ∆ms, the
as the maximum allowable concentration limit for the purest concentration of the wastewater has to be Ce. Therefore, the
demand (P1 in Table 1) is 20 ppm. Results related to source contaminant load right of the vertical line (∆ms) can be
composite curve, wastewater line, and wastewater composite discharged safely to the environment, and the remaining load
curve are tabulated in Table 4. The minimum wastewater flow (∆mTef) has to be treated. Thus, ∆mTef kg/h amount of load has
rate target comes out to be 61.25 t/h, and the corresponding to be removed from the system to satisfy environmental
pinch composition is 100 ppm. Through the overall mass regulation (see Figure 5).
balance, this corresponds to a freshwater target of 81.25 t/h. The performance of the effluent treatment system is given
Note that, because of an increase in the contaminant level in by the removal ratio (r) of the contaminant load from the
the freshwater, the freshwater requirement increases by 16%. system.2 It is defined as
In this case, wastewater is generated at three different concen-
tration levels (corresponding to three pinch points): 25 t/h of fTCTin - fTCTout CTin - CTout ∆mTef
r) ) ) (3)
wastewater is generated at 250 ppm (third pinch point); (60 - fTCTin CTin ∆mTef + m0
25) t/h, i.e., 35 t/h, of wastewater is generated at 150 ppm
(second pinch point); and (61.25 - 60) t/h, i.e., 1.25 t/h, of To remove ∆mTef kg/h of contaminant load in the effluent
wastewater is generated at 100 ppm (first pinch point). treatment unit, the input load for the treatment plant must be
2.3. Targeting Effluent System. After targeting the waste- some (∆mTef + m0) kg/h. Equation 3 may be rewritten to
water, the next step is to find out the effluent treatment flow calculate the input load (∆mTef + m0).
rate for a given set of operations. As discussed in previous
subsections, the source composite and wastewater composite ∆mTef
∆mTef + m0 ) (4)
r
Table 7. Limiting Process Data for Example 2 2.4.b. Case (ii): Minimum Recycle Flow Rate across the
inlet/demand outlet/source Treatment Unit. The treatment unit reduces the concentration
contaminant flow rate contaminant flow rate
of the effluent stream. If some amount of the treated effluent is
processes conc (ppm) (t/h) conc (ppm) (t/h) recycled across the treatment unit, the inlet concentration of
the combined effluent may be reduced to meet the environmental
P1 0 120 100 120
P2 50 80 140 80 norms. On the basis of the definition of removal ratio for a
P3 50 80 treatment unit (eq 3), the outlet concentration of the treatment
P4 140 140 180 140 unit can be expressed as
P5 170 80 230 80
P6 240 195 250 195 CTout ) (1 - r)CTin (8)
Cfw ) 0 ppm, Ce ) 20 ppm, and r ) 0.95
As the outlet concentration is limited by the environmental
Minimum removal ratios for example 1 with freshwater (C0 norms, the inlet concentration has to be Ce/(1 - r). Using mass
) 0 ppm) and contaminated freshwater (C0 ) 20 ppm) are balance, the minimum amount of recycle flow rate (fr) to achieve
calculated to be 0.75 and 0.737, respectively. It is interesting this concentration is calculated to be
to note that an increase in contaminant level in freshwater
increases the minimum wastewater output by 22.5%. However, (1 - r)∆mTef
in the case with contaminated freshwater, the minimum removal fr ) - fww (9)
rCe
ratio of the treatment unit is reduced slightly (1.8%).
The minimum removal ratio indicates the limit up to which
For example 1 with r ) 0.7, eq 9 implies that at least 14.29
only one treatment unit is sufficient to meet the environmental
t/h of treated effluent has to be recycled across the treatment
norms. If the removal ratio of a particular treatment unit is <rmin,
unit to satisfy environmental regulations.
then any one of the three cases may be considered to meet the
2.4.c. Case (iii): Minimum Number of Treatment Units
environmental limit.
in Series. A single treatment unit is sufficient whenever CTout
2.4.a. Case (i): Minimum Freshwater Flow Rate to Dilute
is not more than the environmental limit Ce. However, for a
the Effluent. As the removal ratio of the treatment unit is <rmin,
treatment unit with a removal ratio less than the minimum
removal of required amount of the contaminant load from the
removal ratio (r < rmin), multiple (say n) such treatment units
wastewater is not possible. By treating all the available
are required to meet the environmental norm. In the case of a
wastewater (fww), the amount of contaminant removed from the
series arrangement, the outlet concentration of the effluent
systems can be calculated to be r(∆mTef + fwwCe) and the
treatment may be expressed as
concentration of the treated effluent is expressed as (1 - r)-
(∆mTef/fww + Ce). To achieve the environmental limit, the
CTout ) (1 - r)nCTin ) Ce (10)
additional amount of freshwater (fadd) required can be expressed
as
This is equivalent to a single treatment unit with minimum
removal ratio.
(1 - r)∆mTef rfwwCe
fadd ) - (7)
Ce - Cfw Ce - Cfw CTout ) (1 - rmin )CTin ) Ce (11)
To illustrate, let us consider example 1 with a removal ratio Rearranging the above equations, the minimum number of
of 0.7, a value less than the minimum removal ratio of 0.75. treatment units can be calculated as
[ ]
Application of previous methodology results in targeting 64.29
fwwCe
t/h of effluent treatment flow rate. This is clearly not possible, ln
as the total wastewater available is 50 t/h. To satisfy the ln(1 - rmin ) ∆mTef + fwwCe
n) ) (12)
environmental limit, as per eq 7, an additional 10 t/h of ln(1 - r) ln(1 - r)
freshwater is required.
In this case, more than the minimum freshwater is required Thus, eq 12 gives the minimum number of treatment units
to satisfy the environmental limit. Though it defeats the original required to meet the environmental norm. However, eq 12 may
objective of designing the effluent treatment system utilizing predict the number of treatment units in fraction. The smallest
the minimum freshwater requirement, it still serves as an integer greater than this fraction should be considered as the
alternate solution for the design engineer. target for the minimum number of treatment units. In other
Table 8. Generation of Source Composite Curve, Targeting Wastewater, and Generation of Wastewater Composite Curve for Example 2
wastewater cumulative cumulative
contaminant net cumulative mass cumulative wastewater flow rate, wastewater mass load treatment
concentration flow rate flow rate load mass load flow rate after second flow rate remove flow rate
(ppm) (t/h) (t/h) (kg/h) (kg/h) (t/h) pinch (t/h) (t/h) (kg/h) (t/h)
250 195 195 0 0 110.20 85 85 0 105.89
240 -195 0 1.95 1.95 106.67 66.67 85 0.85 106.77
230 80 80 0 1.95 111.30 80 85 1.7 107.71
180 140 220 4 5.95 120.00 120 5.95 114.02
170 -80 140 2.2 8.15 114.12 120 7.15 113.67
140 -60 80 4.2 12.35 108.57 120 10.75 112.31
100 120 200 3.2 15.55 120.00 120 15.55 109.24
50 -160 40 10 25.55 40.00 120 21.55 98.47
20 0 40 1.2 26.75 40.00 120 25.15 66.18
0 -120 -80 0.8 27.55 0.00 120 27.55
5294 Ind. Eng. Chem. Res., Vol. 45, No. 15, 2006
∆m ) 1 -
[ 1 - rmin
(1 - r) n-1 ]( )
∆mTef
rminr
- fTC (14)
Figure 9. Water allocation network including treatment unit for example
For the modified example 1 with two treatment units in series, 2. (The values show flow rate in t/h with contaminant concentrations in
only 9.52 t/h of most contaminated effluent has to be treated in ppm within braces.)
the first treatment unit, and the combined wastewater has to be
treated in the second unit to achieve the environmental discharge 3.1. Example 2: Six-Process Example. Limiting process
limit of 50 ppm. It may be noted that, in thse case of local data for this example is given in Table 7.7 Freshwater
recycle, the total amount of treated effluent flow rate (64.29 t/h concentration is 0 ppm. The environmental limit and the removal
for modified example 1) is always more than that of the last ratio of the effluent treatment unit are assumed to be 20 ppm
case (for modified example 1, it is 59.52 t/h). and 0.95, respectively. Results concerning generation of the
The appropriate choice of a particular method to meet the source composite curve, wastewater line, and wastewater
environmental regulation primarily depends on the economic composite curve are tabulated in Table 8. Wastewater can be
tradeoffs between the operating cost and the capital investment targeted directly as 120 t/h. Freshwater targets can be set through
for extra treatment units. The process designer should be able overall mass balance as (120 + 80) t/h, i.e., 200 t/h. Interest-
to take a proper decision based on cost of freshwater, availability ingly, in this problem, there are two pinches, at 100 and 180
of freshwater, operating cost of effluent treatment, types of ppm. However, the upper pinch controls for wastewater genera-
contaminants, capital cost for setting multiple treatment unit, tion. In this example, wastewater is generated at two concentra-
turndown ratio for the overall plant, availability of space, etc. tion levels: 85 t/h of wastewater is generated at 250 ppm and
(120 - 85) t/h, i.e., 35 t/h, of wastewater is generated at 180
ppm. Note that no wastewater is generated at 100 ppm. A
3. Illustrative Examples
minimum removal ratio for example 2 is calculated to be 0.913.
To demonstrate the applicability of the methodologies Hence, only one treatment plant is sufficient. Results for effluent
developed in this paper, several published examples are solved treatment flow-rate targets are also tabulated in Table 8. The
in this section. target for minimum treatment flow rate is 114.02 t/h. Source
Table 10. Generation of Source Composite Curve, Targeting Wastewater and Generation of Wastewater Composite Curve for Example 3
cumulative wastewater cumulative cumulative
contaminant net cumulative mass mass wastewater flow rate, wastewater mass load treatment
concentration flow rate flow rate load load flow rate after first flow rate removed flow rate
(ppm) (t/h) (t/h) (kg/h) (kg/h) (t/h) pinch (t/h) (t/h) (kg/h) (t/h)
500 90 90 0 0 88 86.67 86.67 0 40.53
300 -10 80 18 18 86.67 80 86.67 17.33 9.79
200 50 130 8 26 90 90 26 -28.7
100 -80 50 13 39 50 90 35 -147.3
20 0 50 4 43 50 90 42.2 -1096.7
0 -50 0 1 44 90 44
Ind. Eng. Chem. Res., Vol. 45, No. 15, 2006 5295
Table 12. Generation of Source Composite Curve, Targeting Wastewater, and Generation of Wastewater Composite Curve for Example 4
cumulative wastewater cumulative cumulative
contaminant net cumulative mass mass wastewater flow rate wastewater mass load treatment
concentration flow rate flow rate load load flow rate after first flow rate removed flow rate
(ppm) (t/h) (t/h) (kg/h) (kg/h) (t/h) pinch (t/h) (t/h) (kg/h) (t/h)
1000 20 20 0 0 41.45 20 20 0 17.94
700 50 70 6 6 50.64 50.64 6 17.06
200 -50 20 35 41 2.25 50.64 31.32 -66.8
100 -35 -15 2 43 -15.50 50.64 36.39 -184.3
50 0 -15 -0.75 42.25 -16.00 50.64 38.92 -419.2
10 -5 -20 -0.6 41.65 -20.00 50.64 40.94 -2298
0 -20 -40 -0.2 41.45 0.00 50.64 41.45
5296 Ind. Eng. Chem. Res., Vol. 45, No. 15, 2006
Nomenclature
C ) contaminant concentration, ppm
f ) flow rate, t/h
∆m ) contaminant mass load, kg/h
Figure 13. Water allocation network for example 4 incorporating two m0 ) excess mass load of contaminant at treatment unit inlet,
treatment units. (The values show flow rate in t/h with contaminant kg/h
concentrations in ppm within braces.)
n ) number of treatment units
may be recycled across the treatment unit is calculated to be P ) contaminant load in a concentration interval, kg/h
35.85 t/h. On the other hand, two treatment units may be Q ) cumulative flow rate, t/h
operated in series. Results for effluent treatment flow-rate targets R ) cumulative wastewater flow rate, t/h
are tabulated in Table 12. The target for minimum treatment r ) removal ratio
flow rate is 17.94 t/h for one unit and combined effluent to be Subscripts
treated in the next treatment unit. Source composite curve,
wastewater composite curve, and treatment line are plotted in add ) additional
Figure 12. The corresponding water-allocation network and the e ) environmental
treatment unit are shown in Figure 13. ef ) effective
i, j, k, l ) index number
4. Conclusion in ) inlet
min ) minimum
Integrated water management in a chemical process industry out ) outlet
consists of optimal allocation of reusable water among different P ) pinch
water-using operations to reduce freshwater requirement and r ) recycle
optimal design of effluent treatment units to honor environ- T ) total, treatment
mental norms. A new methodology for targeting minimum w ) water
freshwater and minimum effluent treatment flow rate is proposed ww ) wastewater
in this paper. Optimal design of effluent treatment units is 1, 2, ... ) index number
addressed in conjunction with the problem of optimal allocation fw ) freshwater
of water among different water-using units. The proposed
methodology can be applied to fixed-flow-rate as well as fixed- Literature Cited
contaminant-load problems with a single contaminant. For every
example, one of the many possible networks has been designed (1) El-Halwagi, M.; Manousiouthiakis, V. Synthesis of Mass Exchange
to show that these targets can actually be achieved. Network. AIChE J. 1989, 35, 1233.
(2) Wang, Y. P.; Smith, R. Wastewater Minimization. Chem. Eng. Sci.
A source composite curve is proposed for directly targeting 1994, 49, 981.
minimum generation of wastewater, and hence, minimum (3) Dhole, V. R.; Ramchandani, N.; Tanish, R. A.; Wasilewski, M. Make
freshwater requirement can be indirectly targeted using overall Your Process Water Pay for Itself. Chem. Eng. 1996, 103, 100.
mass balance. Distributed generation of wastewater can be (4) Prakash, R.; Shenoy, U. V. Targeting and Design of Water Networks
for Fixed Flowrate and Fixed Contaminant Load Operations. Chem. Eng.
targeted through wastewater composite curve, generated from
Sci. 2005, 60, 255.
the source composite curve. Wastewater composite curve can (5) Wang, Y. P.; Smith, R. Wastewater Minimization with Flowrate
further lead to targeting effluent systems. All these targets can Constraints. Trans. Inst. Chem. Eng. 1995, 73A, 889.
be set prior to designing the detailed water-allocation network (6) Hallale, N. A New Graphical Targeting Method for Water Minimi-
and can be set on a single concentration-contaminant load sation. AdV. EnViron. Res. 2002, 6, 377.
(7) Sorin, M.; Bedard, S. The global pinch point in water reuse network.
diagram and through analytical algorithms. Trans. Inst. Chem. Eng. 1999, 77B, 305.
The minimum contaminant removal ratio of effluent treatment (8) Polley, G. T.; Polley, H. L. Design Better Water Networks. Chem.
systems has been identified in this paper. For treatment units Eng. Prog. 2000, 96, 47.
with a removal ratio less than the minimum removal ratio, the (9) Tan, Y. L.; Zainuddin, A. M.; Chwan, Y. F. Water minimization by
process designer has to choose and design effluent treatment pinch technologysWater Cascade Table for Water and Wastewater Target-
ing. Presented at APCChE Meeting, New Zealand, 2002.
units based on many possibilities. Additional freshwater may (10) Prakash, R. Resources Optimisations in Process Industries: Water
be used to dilute the effluent streams, a portion of the treated Management. M.Tech. Thesis, Department of Chemical Engineering, Indian
effluent may be recycled across the treatment unit, or multiple Institute of Technology, Bombay, India, 2002.
treatment units may be used in series. Closed-form formulas to (11) El-Halwagi, M. M.; Gabriel, F.; Harell, D. Rigorous graphical
calculate additional freshwater requirements, recycle flow rate, targeting for resource conservation via material recycle/reuse networks. Ind.
Eng. Chem. Res. 2003, 42, 4019.
and the minimum number of required effluent treatment units (12) Alva-Argeaz, A.; Vallianatos, A.; Kokossis, C. A multi-contaminant
are reported in this paper. On the basis of the relative freshwater transshipment model for mass exchange networks and wastewater mini-
cost, effluent treatment unit operating cost, and capital cost of misation problems. Comput. Chem. Eng. 1999, 23, 1439.
Ind. Eng. Chem. Res., Vol. 45, No. 15, 2006 5297
(13) Savelski, M.; Bagajewicz, M. On the optimality conditions of water the Synthesis of Distributed Wastewater Treatment Networks. Ind. Eng.
utilization systems in process plants with single contaminants. Chem. Eng. Chem. Res. 2004, 43, 2175.
Sci. 2000, 55, 5035. (21) Takama, N.; Kuriyama, T.; Shiroko, K.; Umeda, T. Optimal water
(14) Benko, N.; Rev, E.; Fonyo, Z. The use of nonlinear programming allocation in petroleum refinery. Comput. Chem. Eng. 1980, 4, 251.
to optimal water allocation. Chem. Eng. Commun. 2000, 178, 67. (22) Kuo, W. C. J.; Smith, R. Designing for the Interactions between
(15) Foo, C. Y.; Manan, Z. A.; Yunus, R. M.; Aziz, R. A. Synthesis of Water Use and Effluent Treatment. Trans. Inst. Chem. Eng. 1998, 76A,
mass exchange network for batch processes. Part I: Utility targeting. Chem. 287.
Eng. Sci. 2004, 59, 1009. (23) Shenoy, U. V. Heat Exchanger Network Synthesis; Gulf Publishing
(16) Foo, C. Y.; Manan, Z. A.; Yunus, R. M.; Aziz, R. A. Synthesis of Co.: Houston, TX, 1995.
mass exchange network for batch processes. Part II: Minimum units target (24) Bandyopadhyay, S.; Malik, R. K.; Shenoy, U. V. Invariant
and batch network design. Chem. Eng. Sci. 2005, 60, 1349. rectifying-stripping curves for targeting minimum energy and feed location
(17) Wang Y. P.; Smith, R. Design of Distributed Effluent Treatment in distillation. Comput. Chem. Eng. 1999, 23, 1109.
Systems. Chem. Eng. Sci. 1994, 49, 3127.
(18) Kuo, W. C. J.; Smith, R. Effluent Treatment System Design. Chem.
ReceiVed for reView March 6, 2006
Eng. Sci. 1997, 52, 4273.
(19) Galan B.; Grossmann, I. E. Optimal design of distributed wastewater ReVised manuscript receiVed May 5, 2006
treatment networks. Ind. Eng. Chem. Res. 1998, 37, 4036. Accepted May 10, 2006
(20) Hernández-Suaı̀rez, R.; Castellanos-Fernández, J.; Zamora, J. M.
Superstructure Decomposition and Parametric Optimization Approach for IE060268K