The table below can be used as a guide to required area (square metre or square feet) per person inside some typical buildings and rooms. The
values can be used to calculate human sensible and latent heat load.

Area per Person


Type of Building Type of Room
(m2) (ft2)
Apartments 100 - 400
Lecture room 0.6
Library 5
Assembly building Cinema 0.6
Concert hall 0.6
Theater 0.6
Banks 50 - 150
Bars 15 - 50
Cafeterias 10 - 50
Churches 5 - 20
Clubhouses 15 - 50
Cocktail Lounges 15 - 50
Computer Rooms 80 - 150
Court Houses 50 - 150
Dental Centers Clinic and Offices 50 - 150
Department Stores 15 - 75
Dining Halls 10 - 50
Drug Store 15 - 50
Factories Assembly hall 2-5
Factories Light manufacturing 10 - 20
Factories Heavy manufacturing 20 - 30
Fire Stations 100 - 500
Rooms 5
Hotels Lobby 0.6
Assembly room 1.5
General Areas 50 - 150
Hospitals
Patient Rooms 80 - 150
Kindergarten 2-3
Kitchens 50 - 150
Libraries 30 - 100
Luncheonettes 10 - 50
Lunch Rooms 10 - 50
Malls 50 - 100
Medical Centers Clinic and Offices 50 - 150
Public Spaces 100 - 200
Motels, Dormitories
Guest Rooms, Dormitories 100 - 200
Municipal Buildings 50 - 150
Museums 30 - 100
Nightclubs 15 - 50
Nursing Home Patient Rooms 80 - 150
Single office 10
Offices
Meeting room 1.5
Police Stations 100 - 500
Post Offices 100 - 500
Precision Manufacturing 100 - 300
Residential 200 - 600
With service 1.5
Restaurant
Without service 1
Retail Stores 15 - 75
Lecture rooms 0.6
Class rooms 2
Schools
Corridors 2
Laboratory 3
Retail 2
Shops
Supermarkets 2
Gymnasium 15
Gymnasium 1.5
Sports
engineeringtoolbox.com
Swimming pools 4
Supermarkets 50 - 100
Taverns 15 - 50
Town Halls 50 - 150

1 m2 = 10.764 ft2
1 ft2 = 0.0929 m2

Note! - be aware of local restrictions, codes and their minimum values. They may diverge considerably from the numbers above.