WDZ-430EX Motor Management Relay Technical Instruction

WDZ-430EX Motor Management Relay Technical Instruction


1. Description
WDZ-430EX motor management relay(shortened form is equipment), which has normal protection,
measurement and control function, is mainly applied in large or medium three-phase asynchronous motor. As
for super large motor (2000KW and more, or disqualification of main protection accuracy), WDZ-431EX motor
differential relay should be added as required. Equipment can be configured with independent operation circuit
and anti-trip circuit, and can be applied to all kinds of exporting motor circuit.

Perfect protection function:


 Instantaneous over current relay(back power latch)
 Negative sequence current relay 1
 Negative sequence current relay 2
 Earth fault protection
 Motor thermal relay
 Thermal trip blocking startup
 Mechanical jam relay
 Long-time startup relay
 Positive sequence current relay
 Over load relay
 Under voltage relay(27)
 VT circuit off
 FC circuit fault-current latch trip
 Fuse relay
 Phase current unbalance relay
 Independent control circuit and anti-jump circuit(selected)
 Fault wave record and wave record during motor startup
 Independent control circuit and anti-jump circuit(selected)

Function of measurement and control:


 10 channel remote switch data, remote signal and event remote signal inside device.
 Breaker remote control trip or close.
 Remote measurement values: 3-phase voltage, 3-phase current, P, Q, power factor, frequency,
zero-sequence current.
 2-way impulse input to automatic record outside power energy.
 Embedded high-precision smart power energy meter to elide outside power meter (optional) .
 One channel 4 ~ 20 mA DC analog signal output, instead of transfer device as DCS
measurement interface (optional).

Function of communication(optional) :
 Smart communication card: normal configuration includes high-speed RS485 bus with
communication speed up to 115.2 kbps, supporting dual net and industrial Ethernet optional.
Specifications of the equipment:
 Advanced 32-bit embedded microprocessor, multi-CPU structure.

3-1
WDZ-430EX Motor Management Relay Technical Instruction

 English/ Chinese characters LCD display, easy for operation.


 Serial EEPROM to store protection fixed set values.
 5 sets pre-configured settings to adapt all kinds of working modes.
 Retentive SOE and self-check report.
 Software and hardware redundancy design, with high anti-interference ability.
 Software and hardware self-check, with two-level watchdog.
 Full-sealed embedded machine box, with small volume, light, and convenience to be applied
on switch cabinet directly.
 Reliable high-speed bus, supporting dual net and Ethernet.
 Perfect and adaptive protection interface, comprehensive, exact and reliable measurement and
control function
 DCS metering interface, with 4 ~ 20 mA analog signal output.
 Independent operation circuit and anti-tripping circuit, adaptable to trip and close current
automatically.

2.Main technical data


2.1 Rated data
DC source: 220V  20% or 110V  20%
AC source 220V  20%

AC voltage: 110/ 3 V, 110V


AC current: 5A or 1A
Frequency: 50Hz

2.2 Power consumption


DC circuit: normal  15w
trip  20w
AC voltage circuit: < 0.5VA/phase (when rated is 63.51V)
AC current circuit: < 0.5VA/phase (when rated is 5A)
< 0.1VA/phase (when rated is 1A)

2.3 Working environment


 
Environment temperature: -10 C ~ +55 C normal is guaranteed.
Relative humidity: 5 ~ 95%
Atmosphere pressure: 86 ~ 106KPa

2.4 Precise working scope


Current: 0.1In ~ 20In
Voltage: 0.4V ~ 120V
Frequency: 45Hz ~ 55Hz
df/dt: 0.03Hz/s ~ 10Hz/s
2.5 Thermal stability
Working continuously under twice rated current.

3-2
WDZ-430EX Motor Management Relay Technical Instruction

Working lasts 10 seconds under 10 times rated current.


Working lasts 1 second under 40 times rated current.

2.6 Fixed set value error


Current and voltage set value error: <  3% set value
Frequency set value error: < 0.02Hz
Time set value error:
 Relay inherent action time < 30ms  10ms
 No delay relay inherent action time
 Definite time delay <  1% time settings + relay inherent action time
 IDMT delay conforms to IEC IDMT curve

2.7 DCS measurement interface output


Full scale current I bm : 5A/1A
Full scale voltage U bm : 120v
Output scope: 4 ~ 20mA
Output precision: level 0.5

2.8 Contact capacity


Trip and close coil outputs: 0.5 ~ 5A self-adaptive (with operation board)
Trip and close outputs(normal open contact): 5A, DC 220V (pickup)
Signal outputs(normal open contact): 1A, DC 220V (pickup)
Switch inputs: idle contact inputs, breakover current < 10mA

2.9 Measurement precision


Voltage, current: level 0.5
Frequency: 0.02Hz
AP, RP, COS  : level 1
Remote signal differentiability: < 2ms
Electric power energy precision: level 0.5
GPS time precision: < 1ms

2.10 Communication
RS485: Communication baud rate 9.6 ~ 115.2 kbps, adjustable, supporting dual net.
Communication medium supporting shield twisted pair line.
Ethernet: 10M industrial Ethernet, RJ45 plug-in.
Communication medium: 5 kinds non-shield twisted pair line.

2.11 Fault wave record


Startup mode: protection startup, local/remote startup, motor startup
Wave record time: 40ms before protection startup, 80ms after protection output
the longest time of protection action is 10s

3-3
WDZ-430EX Motor Management Relay Technical Instruction

wave record time for motor startup is fixed 10s


debug startup time can be set from 20ms to 10s
Sampling frequency: 12 point per cycle
Analog channel: 9
Status channel: 16

2.12 Anti-disturbance ability


 Can stand static discharge test of strict class Ⅲ regulated by GB/T14598.14-1998 (idt IEC255-22-2)
standard.
 Can stand radiation electromagnetic disturbing test of strict class Ⅲ regulated by GB/T14598.9-1995
(idt IEC255-22-3) standard.
 Can stand 1MHz impulse cluster disturbing test of strict class Ⅲ regulated by GB/T14598.13-1998 (idt
IEC255-22-1) standard.
 Can stand fast instantaneous change disturbing test of strict class Ⅲ regulated by GB/T14598.10-1996
(idt IEC255-22-4) standard.

2.13 Impact voltage


Standard thunder shock wave test can be endured between AC circuit and DC circuit, and between AC
current and AC voltage, with each input/output port grounded.

2.14 Weight
No more than 4 kg.

2.15 Other data satisfy DL478-92 Common Technology Terms For Static Relay Protection And Safe Automatic
Equipment.

3. Main protection function and principle


Principle diagram shows in figure 1.

3-4
WDZ-430EX Motor Management Relay Technical Instruction

Back Power Block


Instantaneous Over
Current Relay(launch)
A phase positive direction
I a >I sdg &
Back Power Block
Instantaneous Over
Current Relay(launch)
B phase positive direction
& ≥1
Ib >I sdg
Instantaneous Over
Back Power Block Current Relay
Instantaneous Over Trip ACT
(Motor Startup State)
Current Relay(launch) & tsd
c phase positive direction
& BTJ
I c >I sdg

t< tqd (Motor Startup Time)

t>70ms
Back Power Block
Instantaneous Over
Current Relay(launch)
A phase positive direction
I a >I sdd &
Back Power Block
Instantaneous Over
Current Relay(launch) Instantaneous Over
Current Relay
B phase positive direction (After Motor Startup)
& ≥1
Ib >I sdd
Back Power Block
Instantaneous Over Trip ACT
Current Relay(launch) & tsd
c phase positive direction
& BTJ
I c >I sdd

t≥tqd (Motor Startup Time)

t>70ms Trip ACT


Negative Sequence
I 2 > I21dz t21dz Current Relay1
BTJ

Trip ACT
Negative Sequence
I 2 > I 22dz t22dz
Current Relay2
BTJ

Imax ≤1 . 05I e
Trip ACT
&
t0dz
I 0 > I0dz Instantaneous Zero
≥1 BTJ
Sequence Current
Imax >1 . 05I e Alarm Relay
& t0dz FLT
I0≥[1+ (Imax/Ie -1.05 )/4]I0 dz

Trip

&
θr >θa

≥1 FLT
Alarm
Motor Thermal Relay
&

θr >1 . 0
ACT
Trip
&
BTJ

3-5
WDZ-430EX Motor Management Relay Technical Instruction

Ia >I ddz
Trip ACT
Ib >I ddz ≥1
tddz
Ic >I ddz & Mechanical Jam Relay
BTJ
Speed Switch On
Alarm
tddz FLT
Ia >1 . 125Ie
Trip ACT
Ib >1 . 125Ie ≥1
Ic >1 . 125Ie & Long-Time Startup
BTJ
t>tqdj Relay
Alarm
FLT
I a <1 . 125Ie
I b <1 . 125Ie &
I c <1 . 125Ie Trip ACT
≥1
& t1gl
t>tyd Positive Sequence
BTJ Current Relay
I1 >I1gl Alarm
t1gl FLT

Ia >Igfh Trip ACT


Ib >Igfh ≥1 tgfh
Ic >Igfh BTJ Over Load Relay
Alarm
tgfh FLT
Uab < Uqy
Ubc < Uqy &
U ca < Uqy
VT Cut Off &
Trip ACT
Pre-start
Umax >1 . 05Uqy ≥ t qy
Under Voltage Relay
BTJ
Umax<5V
&
Imax<Ie/8

Switch On

Imax>Ie/4
&
Umax<5V Alarm
≥ 15S FLT
Imax>Ie/4 PT circuit off
Umax>20V &

(Umax-Umin)/Umax>30%

FC circuit
Ia> Ifcbs F-C Circuit Block(Launch) Lock Output
fault-current
Ib> Ifcbs ≥1 block trip
Ic> Ifcbs FLT

Ia> Isd
Ib > Isd ≥1 Fuse Relay(Launch)
Ic > Isd &
ACT Fuse relay
Switch On Ia< Ie/8
t fuse
Ib < Ie/ 8 &
BTJ
Ic < Ie/ 8
LEGEND: Umax =Max(Uab,Ubc,Uca), I max = Max(Ia,Ib,Ic),other Symbols See Protection Setup Table
BTJ : Trip Relay
ACT : Sigal Relay
FLT : Alarm Relay
Figure 1 : WDZ-430 Protection Principle

3-6
WDZ-430EX Motor Management Relay Technical Instruction

3.1.Instantaneous over current relay(back power latch)


Criterion of action:
Imax=max(Ia, Ib, Ic)
Imax>Isdg during motor rated startup time
Or Imax>Isdd after motor rated startup time
t>tsd
In formula,
Imax:maximum value of phase A,B,C current(I a, Ib, Ic)(A)
Isdg:instantaneous over current relay high level(instantaneous over current value during motor
startup)(A)
Isdd:instantaneous over current relay low level(instantaneous over current value after motor
startup)(A)
tsd:instantaneous over current relay delay time(s)
The protection can avoid transient peak current during motor startup.
To prevent instantaneous over current relay misacting because of motor reverse high-current when
external fault, the protection sets the function of back power block Instantaneous over current relay. If
back power latch Instantaneous over current launch, when current and voltage have the same direction,
opening the protection; when current and voltage have different direction, latching the protection.

3.2. Negative sequence current relay 1 (46)


Criterion of action:
I2>I21dz
t>t21dz
In formula,
I 2: negative sequence current(A)
I21dz:negative sequence current relay 1 level(A)
t21dz:negative sequence current relay 1 delay time(s)
negative sequence current relay 1 delay time should avoid longest clear fault time of motor outside
quarter-phase short circuit. In FC loop, negative sequence current relay 1 should avoid fuse break time
of unsymmetrical short circuit.

3.3. Negative sequence current relay 2 (46)


Criterion of action:
I2>I22dz
t>t22dz
In formula,
I22dz:negative sequence current relay 2 level(A)
t22dz:negative sequence current relay 2 delay time(s)

3.4.Instantaneous zero sequence relay(50N)


Zero sequence current of motor, obtained by zero sequence current transformer, makes up motor
single-phase ground protection. In prevention of mis-operation created by unbalanced current with higher

3-7
WDZ-430EX Motor Management Relay Technical Instruction

motor startup current, the protection adapts maximum of phase current I max as restraint value. Action
characteristic shows in figure 3.2.
I0>I0dz When Imax≤ 1.05Ie
Or I0>[1+(Imax/Ie-1.05)/4]I0dz When Imax>1.05Ie
t0>t0dz
In formula,
I0:zero sequence multiple current of motor
I0dz:instantaneous zero sequence relay level(times)
Ie:motor rated current(A)
t0dz:instantaneous zero sequence relay delay time(s)
Zero sequence rated current determined by neutral point ground current. The equipment supply two
options, I0e=0.02A and I0e=0.2A. When neutral point low ground current, I0e=0.02A;when of neutral point
high ground current, I0e=0.2A.

I0/I0dz

Action area
2

1
Restraint area

1 2 3 4 5 Imax /Ie

Figure 3.2 Characteristic curve of instantaneous zero sequence relay

3.5.Motor thermal relay


The equipment can operate under any work condition. With the consideration of difference between
positive sequence and negative sequence current heat effect, create motor thermal model, which can supply
accuracy motor thermal relay. Adopt heat equivalent current Ieq in heating model, expression is:

I  K I2  K I2
eq 11 2 2
In formula,
K1 =0.5 during motor rated startup time
=1 after motor rated startup time
K2 =3-10 this equipment is 6

3-8
WDZ-430EX Motor Management Relay Technical Instruction

K1 changes during startup, K2 means negative sequence current heat effect in heating model, in scale
K2 equals to two times of ratio of rotor AC resistance and DC resistance because heat effect of
negative sequence current in rotor is much higher than positive sequence current. According to
theory and experience, this equipment adopts 6.
Motor accumulative superheating value θ Σ is:

t
θ 2   1.05 I  2dt   I 2   1.05 I  2Δt
  I eq
Σ e   eq e 
0   
In formula,
Δ t:accumulative thermal value calculating interval, this equipment adopts Δ t=0.1s.
Motor trip thermal value(permission) θ T is:

 T  I e2  Tfr
In formula,
Tfr:motor radiate thermal time coeff(s)
When θ Σ >θ T, motor thermal relay act, θ Σ =0 means motor reached heat balance, without
accumulative thermal value. To express convenience, degree of motor accumulative thermal value
is expressed by overheat ratioθ r:
θ Σ
θ r=
θ T

When θ r>1.0, motor thermal relay act. In order to make operation personnel known, when θ r

exceed overheat alarm definite value θ a, the equipment alarm first.


On condition of cold position(initial overheat value θ Σ =0), motor thermal relay action time is:
Tfr
t=
K1(I1/Ie)2+K2(I2/Ie)2-1.052
When motor stops, accumulative thermal value will decay step by step. Thermal value decay according
to principle of index value. Decay time constant is four times of motor radiat thermal time Tsr , that is to say,
after Tsr, radiating end, motor reach heat balance again.

3.6. Thermal trip blocking startup


After motor stops because of motor thermal relay, this protection immediately check whether overheat
ratio θ r degrade under set thermal blocking startup level θ b , if not, output relay not return, forbid motor
startup again. It can avoid heating up trigged by startup current too high to damage motor. When overheat ratio
θ r high, motor needs emergent startup, push “ reset” on panel of equipment, artificially clear memorized
overheat ratio θ r.

3.7.Mechanical jam relay


Mechanical jam relay is made up of motor speed switch (switch 1) and phase current.
Criterion of action:
Imax>Iddz
t>tddz
speed switch is on
In formula,

3-9
WDZ-430EX Motor Management Relay Technical Instruction

Iddz:mechanical jam relay current value(A)


tddz:mechanical jam relay delay time(s)
This protection needs motor speed switch signal.

3.8.Long-time startup relay


Firstly, calculate start time during motor startup tqdj:
Iqde
tqdj=( )2×tyd
Iqdm

In formula ,
tqdj:calculated start time(s)
Iqde:motor rated startup current(A)
Iqdm:maximum of motor startup current(A)
tyd:motor permitted mechanical jam time(s)
Identifying, if during the calculated start time tqdj, Imax<1.125Ie, motor successful start, long-time
startup relay algorithm end; if after the calculated start time t qdj, Imax>1.125Ie, motor unsuccessful start,
long-time startup relay start.
The longest time of Long-time startup relay is 10s.

3.9. Positive sequence current relay


The flowing conditions satisfied, positive sequence current relay enabled.
The long-time startup relay algorithm end;
Start time exceed set motor permitted mechanical jam time, t>tyd;
If one of the flowing conditions satisfied, considering the long-time startup relay algorithm end
If long-time startup relay launch: reference long-time startup relay logic;
If long-time startup relay withdraw, Imax<1.125Ie;
Criterion of action:
I1>I1gl
t1>t1gl
In formula,
I1gl:positive sequence current relay level(A)
t1gl:positive sequence current relay delay time(s)
Customer not launch long-time startup relay should be noted that, this protection need to set not only
positive sequence current relay level I1gl and positive sequence current relay delay time t1gl but also motor
rated startup current Iqde and motor permitted mechanical jam time tyd.

3.10.Overload relay
Criterion of action:
Imax>Igfh
t>tgfh
In formula,
Igfh:overload relay level(A)
tgfh:overload relay delay time(s)

3-10
WDZ-430EX Motor Management Relay Technical Instruction

3.11. Under voltage relay(27)


When motor bus voltage under Uqy and time is longer than delay time tqy , relay trip to protect motor.
In order to prevent VT circuit off mis-operation , under voltage relay set to be latched when VT circuit off.
Criterion of action:
Umax=max(Uab, Ubc, Uca)

Umax<Uqy
t>tqy
Before under voltage relay start, Umax>1.05Uqy
In formula,
Uqy:under voltage relay voltage value(V)
tqy:under voltage relay delay time(s)
In order to assure the electrical locking of power plant can operate reliably, when bus without
voltage、motor without current、switch on, and the upper criterion of action can’ t startup under
voltage relay, using the flowing auxiliary criterion to startup under voltage relay trip.

U max  5V

 I max  I e / 8

switch on
t  t
 qy

before relay startup, U max  1.05U qy

3.12. VT circuit off


This device have the function of detecting VT circuit off. When VT circuit off,under voltage relay to be
latched instantly, and after 15s sendout alarm signal.
When three phase VT circuit off simultaneously, at this time it has current but no voltage, criterion of VT
circuit off:
U max  5V

 I max  I e / 4
When one or two phase VT circuit off, at this time it has high unbalanced voltage, criterion of VT circuit
off::
U max  5V

 I max  I e / 4
(U  U ) / U
 max min max  30%

After the voltage recovery normal, release VT circuit off latch and alarm.

3.13.FC circuit fault-current latch trip


In FC circuit, if current is higher than the rated drop-out current of contactor, and trip through contactor,
the contactor can be burn-out. At this time should break the fault current through fuse.
Principle and criterion of action:
When the current is higher than drop-out current of contactor, latch local and remote trip.

3-11
WDZ-430EX Motor Management Relay Technical Instruction

I max  I fcbs
In formula,
Ifcbs: F-C overflowing latch current level(A).

3.14. Fuse relay


In FC circuit, when current is higher than the burn-out current of fuse, the fuse begin to burn out. When
the fuse completely burn out, switch of contactor trip off. Because the burn-out current of fuse is curve, can’ t
gain the value accurately, so using the instantaneous over current relay level.
Attention: if device provides I/O board, should lead in switch position through switch 4.
The startup condition of fuse relay:
 I max  I sdg

switch on
The trip condition of fuse relay:
 I max  I e / 8

t  t fuse

switch on
In formula:
Isdg:instantaneous over current relay high level (A).
Tfuse: fuse relay delay time(s).
3.15. Communication
Smart communication card in equipment support two kinds of bus communication, customer can select
high-speed RS485 or industrial Ether net according to practical project. Main content of communication list
below:
 Metering value(analog variable, switch variable, impulse variable etc.)
 Inquiry and modify of protection set fixed value
 State of device, default information and fault wave record
 Remote control
 Remote reset
Communication function of device should be declared when order.

3.16. DCS metering interface


Device meter motor AC parameters and send one channel 4-20mA DC analog variable to DCS system
through D/A.(metering current)

3.17. Auxiliary function


3.17.1. If fault has not switch out after one protection act, other protections will sequently act under certain
condition.
3.17.2. Protection can react if equipment is not reset after protection action. That is to say protection multiply
act.
3.17.3. Equipment can record all kinds of devices and motor information automatically, including:
 64 protection SOE events record

3-12
WDZ-430EX Motor Management Relay Technical Instruction

 256 remote signal changed SOE record


 16 self-check information record of equipment
 Reserve maximum of nearest 16 times startup current、startup time.
 Record the number of times about motor startup and stop.
3.17.4. Equipment fault wave record can record all analogue and switching in the nearest times fault
automatically, including:
 2 cycle before fault、4 cycle after equipment trip and the data in fault state, the longest time of wave
record is 10s.
 Motor startup state, the longest time of wave record is 10s.

4. Parameter setting
4.1. Power impulse setup
Serial Default
Name Unit Range
number Value
1 Impulse1 Initial Value Integer KWH 0-9999 0
2 Impulse1 Initial Value Decimal KWH 0-99 0
3 Impulse1 Amounts per KWH Amounts/KWH 1-65535 100
4 Impulse2 Initial Value Integer KWH 0-9999 0
5 Impulse2 Initial Value Decimal KWH 0-99 0
6 Impulse2 Amounts per KWH Amounts/KWH 1-65535 100
4.2. Relay system setup
Serial Default
Name Unit Range
number Value
1 Relay Address 1-99 99
2 Password 0-9999 1233
3 Backlight Set S 0-1800 30
4 Net1 Set Off/Launch Off
4 Net2 Set Off/Launch Off
6 Debug Net Set Off/Launch Launch
Off/Power Board
7 Power mode Off
Energy/ Integral Energy
8 CT secondary rated 5A、1A 5A
The Phase Of Protection
9 2 Phase、3 Phase 3 Phase
Current
I/O Board、Operation
10 Relay Output Mode I/O Board
Board
11 Wave Record Debug Time S 0.20~10.00 0.20
12 Wave Record Sendout Off/Launch Launch
Times of Motor Startup And
13 0~32766 0
Stop

3-13
WDZ-430EX Motor Management Relay Technical Instruction

4.3. Protection setup


Serial Range Range
Name Symbol Unit
number (Rated 1A) (Rated 5A)
1 Motor Rated Current Ie A 0.20-1.20 1.00-6.00
Instantaneous Over
2 Isdg A 0.40-16.00 2.00-80.00
Current Relay High Level
Instantaneous Over
3 Isdd A 0.40-16.00 2.00-80.00
Current Relay Low Level
Instantaneous Over
4 tsd S 0.00-9.99 0.00~9.99
Current Relay(50) Delay
5 Motor Startup Time tqd S 1.00-99.99 1.00-99.99
Negative Sequence
6 I21dz A 0.10-4.00 0.50-20.00
Current Relay1(46) Level
Negative Sequence
7 t21dz S 0.20-20.00 0.20-20.00
Current Relay1(46) Delay
Negative Sequence
8 I22dz A 0.10-4.00 0.10-20.00
Current Relay2(46) Level
Negative Sequence
9 t22dz S 0.50-20.00 0.50-20.00
Current Relay2(46) Delay
Instantaneous Zero
Time
10 Sequence Relay(50N) I0dz 0.50-40.00 0.50-40.00
s
Level
Instantaneous Zero
11 Sequence Relay(50N) t0dz S 0.06-9.99 0.06-9.99
Delay
Thermal Relay Alarm
12 θ a 0.50-1.00 0.50-1.00
Level
13 Thermal Time Coeff Tfr Min 1.00-80.00 1.00-80.00
Radiate Thermal Time
14 Tsr Min 1.00-300.00 1.00-300.00
Coeff
Thermal Trip Blocking
15 θ b 0.50-1.00 0.50-1.00
Startup Level
Mechanical Jam Relay
16 Iddz A 0.20-12.00 1.00-60.00
Level
Mechanical Jam Relay
17 tddz S 1.00-99.99 1.00-99.99
Delay
Motor Rated Startup
18 Iqde A 0.40-12.00 2.00-60.00
Current
Motor Jamed Permitted
19 tyd S 1.00-99.99 1.00-99.99
Time
20 Positive Sequence Current I1gl A 0.20-12.00 1.00-60.00

3-14
WDZ-430EX Motor Management Relay Technical Instruction

Serial Range Range


Name Symbol Unit
number (Rated 1A) (Rated 5A)
Relay Level
Positive Sequence Current
21 t1gl S 0.50-99.99 0.50-99.99
Relay Delay
22 Over Load Relay Level Igfh A 0.20-12.00 1.00-60.00
23 Over Load Relay Delay tgfh S 10.0-650.00 10.0-650.00
Under Voltage Relay(27)
24 Uqy V 10.00-100.00 10.00-100.00
Level
Under Voltage Relay(27)
25 tqy S 0.10-30.00 0.10-30.00
Delay
FC Overflowing Latch
26 Ifcbs A 1.20~24.00 6.00-120.00
Current Level
27 Fuse Relay Time Trqd S 0.06-99.99 0.06-99.99
Instantaneous Over
28 Off/Trip Off/Trip
Current Relay(50)
29 Back Power Latch Off/Trip Off/Trip
Negative Sequence
30 Off/Trip Off/Trip
Current Relay1(46)
Negative Sequence
31 Off/Trip Off/Trip
Current Relay2(46)
Instantaneous Zero
32 Off/Alarm/Trip Off/Alarm/Trip
Sequence Relay(50N)
33 Motor Thermal Relay Off/Alarm/Trip Off/Alarm/Trip
34 Mechanical Jam Relay Off/Alarm/Trip Off/Alarm/Trip
35 Long-time Startup Relay Off/Alarm/Trip Off/Alarm/Trip
Positive Sequence Current
36 Off/Alarm/Trip Off/Alarm/Trip
Relay
37 Over Load Relay Off/Alarm/Trip Off/Alarm/Trip
38 Under Voltage Relay(27) Off/Trip Off/Trip
VT Circuit Off Blocking
39 Off/Alarm Off/Alarm
Enabled
FC Fault-current Latch Trip
40 Off/Trip Off/Trip
Relay
41 Fuse Relay Off/Trip Off/Trip

4.4. Values gain set


4.4.1. Measurement values gain
Serial
Name Range Step length Remark
number

3-15
WDZ-430EX Motor Management Relay Technical Instruction

1 Uab 0.5-2 0.001


2 Ubc 0.5-2 0.001
3 Uca 0.5-2 0.001
4 Ia 0.5-2 0.001
5 Ib 0.5-2 0.001
6 Ic 0.5-2 0.001
7 Active Power 0.5-2 0.001
8 Reactive Power 0.5-2 0.001

4.4.2. Protection values gain


Serial
Name Range Step length Remark
number
1 Uab 0.5-2 0.001
2 Ubc 0.5-2 0.001
3 Uca 0.5-2 0.001
4 Ia 0.5-2 0.001
5 Ib 0.5-2 0.001
6 Ic 0.5-2 0.001
7 I0 0.5-2 0.001

5. Back board post and elementary diagram


If switch cabinet has not operation circuit, customer need to select control board. Control board of this
device can be configured with independent operation circuit and anti-trip circuit, applicable for all kinds of
outputs and can suit trip current automatically.
 AC circuit elementary diagram
AC circuit elementary diagram shows in figure 3, WDZ-430EX series management relay AC circuit
elementary diagram.
 DI、DO elementary diagram and back board post diagram with operation circuit
Operation circuit elementary diagram showed in figure 2.4, WDZ-400EX series management relay
operation circuit elementary diagram.
DI、DO elementary diagram showed in figure 4, WDZ-430EX motor management relay DI、DO elementary
diagram(with operation circuit).
Back board post diagram showed in figure 5, WDZ-430EX motor management relay back board post
diagram (with operation circuit).
 DI、DO elementary diagram and back board post diagram without operation circuit
DI、DO elementary diagram showed in figure 6, WDZ-430EX motor management relay DI、DO elementary
diagram(with I/O board).
Back board post diagram showed in figure 7, WDZ-430EX motor management relay back board post
diagram (with I/O board).

5.1. Back board signal indicated lamp

3-16
WDZ-430EX Motor Management Relay Technical Instruction

Name Definition Name Definition


Inside equipment 5V light at RUN Flash one time each second
5V Light(Red)
normal time Lamp(Red) when CPU normal
Inside equipment 24V light at NUL
24V Light(Red) Disable
normal time Lamp(Red)
Trip TXD Communication message
Light at the time of protection trip
Light(Yellow) Light(Yellow) light at debug port
Fault Light at the time of equipment RXD Communication message
Light(Green) fault and voltage lower than 24V Light(Green) light at debug port
5.2. Relay and control power
Terminal
Terminal Definition Remarks
Number
XA1-1 Relay power + Relay power positive
XA1-2 Relay power - Relay power negative
XA1-3 Ground Ground
XC1-1
Control power + Control board has, I/O board has not
XC1-2
XC2-15 Control power -/Public Control power - on control board,24V switch public
XC2-16 terminal terminal on I/O board

5.3. Remote/Local power


Terminal Number Terminal Definition Remarks
XC1-15 Remote Remote power, control board has, I/O board has not
XC1-16 Local Local power, control board has, I/O board has not

5.4. Switch contact


Terminal
Terminal Definition Remarks
Number
XA2-12 Switch 1 24V switch (motor speed switch contact)
XA2-13 Switch 2 24V switch
XA2-14 Switch 3 24V switch
XA2-15 Switch 4 24V switch (breaker position on I/O board)
XA2-16 Public terminal 24V switch public terminal
On I/O board 24V switch, +KM switch on control
XC2-9 Switch 5
board
On I/O board 24V switch, +KM switch on control
XC2-10 Switch 6
board
On I/O board 24V switch, +KM switch on control
XC2-11 Switch 7
board
On I/O board 24V switch, +KM switch on control
XC2-12 Switch 8
board

3-17
WDZ-430EX Motor Management Relay Technical Instruction

On I/O board 24V switch, +KM switch on control


XC2-13 Switch 9
board
On I/O board 24V switch, +KM switch on control
XC2-14 Switch 10
board
XC2-15 Operational -/Public Control power – on control board, 24V public switch
XC2-16 terminal on I/O board

5.5. Signal output contact


5.5.1. Central signal output
Terminal Terminal
Remarks
Number Definition
XA2-1
Action signal Close contact as protection trip
XA2-2
XA2-3 Close contact as self-check fault or
Equipment fault
XA2-4 voltage lower than 24V
XA2-5
Signal 1 Contact close as protection alarm
XA2-6
XA2-7 Contact close as protection trip or alarm, can be optioned, refer to
Signal 2
XA2-8 operating instruction
XC1-3 Control
Contact close as control circuit off
XC1-4 wire-break

5.5.2. Position signal (I/O board has not)


Terminal Terminal
Remarks
Number Definition
XC1-5 Remote/Local position signal. Contact close as remote
Remote position
XC1-6 state

5.5.3. Analog variable output


Terminal Number Terminal Definition Remarks
XB-5 AO1 4-20mA output
XB-6 AO2 Disable
XB-7 Public 4-20mA output public terminal

5.5.4. Field bus


Terminal Number Terminal Definition Remarks
XB-1 N1-A
Network N1(High-speed RS485)
XB-2 N1-B
XB-3 N2-A Network N2(High-speed RS485)

3-18
WDZ-430EX Motor Management Relay Technical Instruction

XB-4 N2-B

5.5.5. GPS signal


Terminal Number Terminal Definition Remarks
XB-11
GPS signal
XB-12

5.6. Remote trip/Remote close


Terminal Number Terminal Definition Remarks
XA2-9 Remote close Remote close through communication
XA2-10 Remote trip Remote trip through communication
XA2-11 Public terminal

5.7. Protection trip output


Terminal
Terminal Definition Remarks
Number
XC2-1 Combined trip 1(operation
Close contact as breaker off position on control board;
board)
XC2-2 Close contact as protection trip on I/O board
Protection trip(I/O board)
XC2-3 Combined trip 2(operation
Close contact as breaker off position on control board;
board)
XC2-4 Reserve output contact on I/O board
Reserve(I/O board)
XC2-5 +DYM,-DYM are low voltage combined trip input
+DYM,-DYM(operation
contact on control board only matched with
board)
XC2-6 WDZ-491EX
Combined trip 1(I/O board)
Close contact as protection trip on I/O board
XC2-7
Combined trip 2(I/O board) Close contact as protection trip on I/O board
XC2-8

5.8. AC value input definition


Terminal Number Terminal Definition Remarks
XDL-1 Ua Voltage of phase A
XDR-1 Ub Voltage of phase B
XDL-2 Uc Voltage of phase C
XDR-2 Un Voltage of public terminal
XDL-3 IA
Metering current of phase A
XDR-3 IA’
XDL-4 IB
Metering current of phase B
XDR-4 IB’

3-19
WDZ-430EX Motor Management Relay Technical Instruction

Terminal Number Terminal Definition Remarks


XDL-5 IC
Metering current of phase C
XDR-5 IC’
XDL-7 Ia
Protection current of phase A
XDR-7 Ia’
XDL-8 Ib
Protection current of phase B
XDR-8 Ib’
XDL-9 Ic
Protection current of phase C
XDR-9 Ic’
XDL-10 I0
Zero-sequence current
XDR-10 I0’
XDL-13 PE+
Power Board Pulse Output
XDR-13 PE-

5.9. Debug port


Program can be refreshed through debug port on CPU board.

5.10. Ethernet interface


10M industrial Ethernet interface(optional).

3-20
WDZ-430EX Motor Management Relay Technical Instruction

Figure 3:WDZ-430EX series management relay AC circuit elementary diagram

3-21
WDZ-430EX Motor Management Relay Technical Instruction

Figure 4:WDZ-430EX motor management relay DI、DO elementary diagram(with operation circuit)

3-22
WDZ-430EX Motor Management Relay Technical Instruction

POWER BOARD CONTROL BOARD CPU BOARD AI BOARD

EMWEX-300 EMWEX-559 EMWEX-400 EMWEX-755

Figure 5:WDZ-430EX motor management relay back board post diagram (with operation circuit)

3-23