Вы находитесь на странице: 1из 16

BRITISH STANDARD BS EN

60146-1-3:1993
IEC 146-1-3:
1991

SUPPLIED BY BSB EDGE PRIVATE LIMITED TO LARSEN & TOUBRO LIMITED - DEDICATED FREIGHT CORRIDOR CORPORATION OF INDIA LIMITED, UNDER LICENSE FROM BSI, FOR INTERNAL USE BY THE LICENSEE.
Semiconductor
convertors —
General requirements
and line commutated
convertors —
Part 1-3: Transformers and reactors

The European Standard EN 60146-1-3:1993 has the status of a


British Standard

UDC 621.314.21:621.315.59:621.318
BS EN 60146-1-3:1993

Cooperating organizations

SUPPLIED BY BSB EDGE PRIVATE LIMITED TO LARSEN & TOUBRO LIMITED - DEDICATED FREIGHT CORRIDOR CORPORATION OF INDIA LIMITED, UNDER LICENSE FROM BSI, FOR INTERNAL USE BY THE LICENSEE.
The European Committee for Electrotechnical Standardization (CENELEC),
under whose supervision this European Standard was prepared, comprises the
national committees of the following countries:

Austria Italy
Belgium Luxembourg
Denmark Netherlands
Finland Norway
France Portugal
Germany Spain
Greece Sweden
Iceland Switzerland
Ireland United Kingdom

This British Standard, having


been prepared under the
direction of the Power
Electrical Engineering
Standards Policy Committee,
was published under the
authority of the
Standards Board and
comes into effect on Amendments issued since publication
15 May 1993

© BSI 02-1999 Amd. No. Date Comments

The following BSI references


relate to the work on this
standard:
Committee reference PEL/50
Draft for comment 92/17370 DC

ISBN 0 580 22131 8


BS EN 60146-1-3:1993

Contents

SUPPLIED BY BSB EDGE PRIVATE LIMITED TO LARSEN & TOUBRO LIMITED - DEDICATED FREIGHT CORRIDOR CORPORATION OF INDIA LIMITED, UNDER LICENSE FROM BSI, FOR INTERNAL USE BY THE LICENSEE.
Page
Cooperating organizations Inside front cover
National foreword ii
Foreword 2
Text of EN 60146-1-3 3
National annex NA (informative) Committees responsible Inside back cover
National annex NB (informative) Cross-references Inside back cover

© BSI 02-1999 i
BS EN 60146-1-3:1993

National foreword

SUPPLIED BY BSB EDGE PRIVATE LIMITED TO LARSEN & TOUBRO LIMITED - DEDICATED FREIGHT CORRIDOR CORPORATION OF INDIA LIMITED, UNDER LICENSE FROM BSI, FOR INTERNAL USE BY THE LICENSEE.
This British Standard has been prepared under the direction of the Power
Electrical Engineering Standards Policy Committee and is the English language
version of EN 60146-1-3:1993 Semiconductor convertors. General requirements
and line commutated convertors — Part 1-3: Transformers and reactors,
published by the European Committee for Electrotechnical Standardization
(CENELEC). It is identical with IEC 146-1-3:1991, published by the
International Electrotechnical Commission (IEC).
This British Standard, together with BS EN 60146-1-1, supersedes
BS 4417:1969, which is withdrawn.
A British Standard does not purport to include all the necessary provisions of a
contract. Users of British Standards are responsible for their correct application.
Compliance with a British Standard does not of itself confer immunity
from legal obligations.

Summary of pages
This document comprises a front cover, an inside front cover, pages i and ii,
the EN title page, pages 2 to 10, an inside back cover and a back cover.
This standard has been updated (see copyright date) and may have had
amendments incorporated. This will be indicated in the amendment table on
the inside front cover.

ii © BSI 02-1999
EUROPEAN STANDARD EN 60146-1-3
NORME EUROPÉENNE
February 1993
EUROPÄISCHE NORM

SUPPLIED BY BSB EDGE PRIVATE LIMITED TO LARSEN & TOUBRO LIMITED - DEDICATED FREIGHT CORRIDOR CORPORATION OF INDIA LIMITED, UNDER LICENSE FROM BSI, FOR INTERNAL USE BY THE LICENSEE.
UDC 621.314.21:621.315.59:621.318

Descriptors: Electronics, convertors, semiconductor convertors, tranformers, reactors, characteristics, specifications, test

English version

Semiconductor convertors
General requirements and line commutated convertors
Part 1-3: Transformers and reactors
(IEC 146-1-3:1991)

Convertisseurs à semiconducteurs Halbleiter-Stromrichter


Spécifications communes et convertisseurs Allgemeine Anforderungen und netzgeführte
commutés par le réseau Stromrichter
Partie 1-3: Transformateurs et bobines Teil 1-3: Transformatoren und Drosselspulen
d’inductance (IEC 146-1-3:1991)
(CEI 146-1-3:1991)

This European Standard was approved by CENELEC on 1992-12-09.


CENELEC members are bound to comply with the CEN/CENELEC Internal
Regulations which stipulate the conditions for giving this European Standard
the status of a national standard without any alteration.
Up-to-date lists and bibliographical references concerning such national
standards may be obtained on application to the Central Secretariat or to any
CENELEC member.
This European Standard exists in three official versions (English, French,
German). A version in any other language made by translation under the
responsibility of a CENELEC member into its own language and notified to the
Central Secretariat has the same status as the official versions.
CENELEC members are the national electrotechnical committees of Austria,
Belgium, Denmark, Finland, France, Germany, Greece, Iceland, Ireland, Italy,
Luxembourg, Netherlands, Norway, Portugal, Spain, Sweden, Switzerland and
United Kingdom.

CENELEC
European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung
Central Secretariat: rue de Stassart 35, B-1050 Brussels

© 1993 Copyright reserved to CENELEC members


Ref. No. EN 60146-1-3:1993 E
EN 60146-1-3:1993

SUPPLIED BY BSB EDGE PRIVATE LIMITED TO LARSEN & TOUBRO LIMITED - DEDICATED FREIGHT CORRIDOR CORPORATION OF INDIA LIMITED, UNDER LICENSE FROM BSI, FOR INTERNAL USE BY THE LICENSEE.
Foreword Contents
The CENELEC questionnaire procedure, performed Page
for finding out whether or not the International Foreword 2
Standard IEC 146-1-3:1991 could be accepted
1 Scope 3
without textual changes, has shown that no
common modifications were necessary for the 2 Normative references 3
acceptance as European Standard. 3 Rated values for convertor transformers 3
The reference document was submitted to the 3.1 Rated current values 3
CENELEC members for formal vote and was 3.2 Temperature limits of cooling media 3
approved by CENELEC as EN 60146-1-3
on 9 December 1992. 4 Losses and voltage drops in
transformers and reactors 4
The following dates were fixed.
4.1 Losses in the transformer windings 4
— latest date of publication 4.2 Losses in interphase transformers,
of an identical national
current balancing reactors,
standard (dop) 1993-12-01
series-smoothing reactors, transductors
— latest date of withdrawal and other current regulating accessories 4
of conflicting national 4.3 Voltage drops in transformers and
standards (dow) 1993-12-01 reactors 4
For products which have complied with the relevant 5 Tests for convertor transformers 4
national standard before 1993-12-01, as shown by 5.1 Measurement of commutating reactance
the manufacturer or by a certification body, this and determination of inductive voltage
previous standard may continue to apply for drop (type test) 5
production until 1998-12-01. 5.2 Short-circuit test (type test and
Annexes designated “normative” are part of the routine test) 5
body of the standard. In this standard, Annex A and 5.3 Temperature rise test (type test) 5
Annex ZA are normative.
Annex A (normative) Corrections to be
applied when cooling medium temperature
is higher than standard 9
Annex ZA (normative) Other international
publications quoted in this standard with
the references of the relevant
European publications 9
Table 1 — Temperature rise limits 6
Table 2 — Connections and calculation factors 7
Table A.1 — Reduction of limits of temperature
rise for cooling medium temperature higher
than standard in kelvins 9

2 © BSI 02-1999
EN 60146-1-3:1993

SUPPLIED BY BSB EDGE PRIVATE LIMITED TO LARSEN & TOUBRO LIMITED - DEDICATED FREIGHT CORRIDOR CORPORATION OF INDIA LIMITED, UNDER LICENSE FROM BSI, FOR INTERNAL USE BY THE LICENSEE.
1 Scope 3 Rated values for convertor
This Part 1-3 of the International Standard relates, transformers
in general, to those characteristics wherein 3.1 Rated current values
convertor transformers differ from ordinary power
3.1.1 Single convertor or double convertor
transformers. In all other respects, the rules
supplied from one common cell winding
specified in IEC 76 shall apply to convertor
transformers also, as far as they are not in The convertor transformer shall be capable of
contradiction with this standard. carrying current corresponding to rated direct
current of the convertor continuously, followed by
It should be borne in mind that a rectifier
overload current (where specified) for the specified
transformer operates with non-sinusoidal current
duration (See IEC 146-1-1, 3.10.3.5), at maximum
waveshape. In single-way connection, the current in
cooling temperatures without exceeding its thermal
each cell winding contains a d.c. component which
calls for special attention in design and testing. In limit.
some cases, a special design is necessary when 3.1.2 Double convertor where each thyristor
external short-circuits and cell failures would cause assembly has separate cell windings
abnormal stress. The convertor transformer shall be capable of
For certain types of transformers, the waveshape of carrying in each secondary group the appropriate
the normal operating voltage is non-sinusoidal. The current corresponding to rated direct current of the
core loss of such equipment is to be determined by convertor continuously, followed by overload
applying a sinusoidal voltage having the same current for the specified duration
half-cycle arithmetic mean value and the same (See IEC 146-1-1, 3.10.3.5), at maximum cooling
fundamental frequency as the voltage applied in temperatures without exceeding its thermal limit.
service. Where common line windings are used for the two
secondary windings, these should be rated as
2 Normative references in 3.1.1.
The following standards contain provisions which, 3.2 Temperature limits of cooling media
through reference in this text, constitute provisions
Temperature rise limits are specified in 5.3.
of this International Standard. At the time of
publication, the editions indicated were valid. All 3.2.1 Air cooled outdoor equipment
standards are subject to revision, and parties to The convertor transformer shall be designed to
agreements based on this International Standard operate at an ambient air temperature which does
are encouraged to investigate the possibility of not exceed + 40 °C, does not average more
applying the most recent editions of the standards than + 20 °C over a year and does not average more
listed below. Members of IEC and ISO maintain than + 30 °C for any 24 h period.
registers of currently valid International Standards.
3.2.2 Air cooled indoor equipment
IEC 76:1967, Power transformers.
The convertor transformer shall be designed to
IEC 146-1-1:1991, Semiconductor convertors — operate in an ambient air temperature of + 40 °C.
General requirements and line commutated
convertors — Part 1-1, IEC 146-1-1, Specifications of 3.2.3 Water cooled equipment
basic requirements. The convertor transformer shall be designed to
IEC 146-1-2:1991, Semiconductor convertors — operate with incoming cooling water temperature
General requirements and line commutated which does not exceed + 25 °C.
convertors — Part 1-2: Application guide.

© BSI 02-1999 3
EN 60146-1-3:1993

SUPPLIED BY BSB EDGE PRIVATE LIMITED TO LARSEN & TOUBRO LIMITED - DEDICATED FREIGHT CORRIDOR CORPORATION OF INDIA LIMITED, UNDER LICENSE FROM BSI, FOR INTERNAL USE BY THE LICENSEE.
4 Losses and voltage drops in 4.2.2 Current balancing reactors
transformers and reactors The iron losses in current balancing reactors are by
4.1 Losses in the transformer windings convention to be ignored.
The losses in the winding are either a part of the
The losses in the windings which appear under
convertor loss measurement or calculated as the
normal service conditions are composed of the losses
in the winding resistance as measured by d.c. and product of the d.c. measured resistance and the
the additional losses (depending on frequency) square of the r.m.s. current in the winding,
calculated on the basis of rectangular shaped
caused by eddy currents as well as the stray flux in
current waveform.
the windings and in the construction parts. Due to
the harmonics, the actual losses in the windings 4.2.3 Series-smoothing reactors
would require to be measured with the transformer The iron losses are, by convention, to be ignored.
in normal operation with the assembly.
The losses in the winding are either a part of the
This method of measurement cannot be convertor loss measurement or calculated as the
recommended because it is too complicated and product of the d.c. resistance and the square of the
inaccurate, unless total losses of transformer and direct current in the winding.
assembly are taken as one measurement. In such
cases and for units not exceeding a rated output 4.2.4 Transductors and other current
of 300 kW, the losses may be measured at normal regulating accessories
rated load operation. The iron losses shall be measured or calculated at
In all other cases, the losses in the windings are to magnetic flux conditions corresponding to operation
be calculated from the results of short-circuit of the convertor at rated current, rated line voltage
measurement carried out with sinusoidal currents. and specified direct voltage. Measurement is made
The method is based on the passage of sinusoidal at a frequency corrected to the available frequency
currents in the winding having the same r.m.s. nearest to the principal frequency nearest of the
values as those which would exist in operation with transductor core flux.
the assembly if the overlap was disregarded The losses in the power winding are to be calculated
(see Table 2). as the product of the d.c. measured resistance and
Owing to the fact that the r.m.s. values of the the square of the r.m.s. current in the winding,
currents during normal operation with the calculated on the basis of idealized current
assembly are somewhat smaller than those in the waveform (ignoring stray inductances). When the
test, a positive error is encountered. This positive power winding consists of heavy conductors, the
error is assumed to be compensated for by the eddy current losses should be estimated by
negative error resulting from the fact that the calculation and added.
additional stray losses caused by the harmonics in NOTE These losses are for use in efficiency calculations and not
for design.
operation with the assembly are disregarded.
4.3 Voltage drops in transformers and reactors
4.2 Losses in interphase transformers, current
balancing reactors, series-smoothing reactors, The voltage drops are calculated from the loss
transductors and other current regulating measurements by the formulae given in 3.5 of
accessories IEC 146-1-1.
4.2.1 Interphase transformers
5 Tests for convertor transformers
The supplier shall measure the iron losses at a
frequency and voltage calculated to provide the All tests specified for power transformers in IEC 76
magnetic flux corresponding to operation of the shall apply to convertor transformers if not in
convertor at rated current, voltage and specified contradiction with the tests specified in this clause.
phase control, corrected to the available frequency The tests specified below are to be regarded as
nearest to the principal frequency of the interphase additional or special tests applicable to convertor
transformer. transformers.
The losses in the winding are to be calculated as the
product of the d.c. resistance and the square of the
direct current in the winding.

4 © BSI 02-1999
EN 60146-1-3:1993

SUPPLIED BY BSB EDGE PRIVATE LIMITED TO LARSEN & TOUBRO LIMITED - DEDICATED FREIGHT CORRIDOR CORPORATION OF INDIA LIMITED, UNDER LICENSE FROM BSI, FOR INTERNAL USE BY THE LICENSEE.
5.1 Measurement of commutating reactance In this case, the inductive component of the input
and determination of inductive voltage drop voltage expressed in p.u. of the rated voltage
(type test) between terminals Uv0, represents the inductive
5.1.1 Commutating reactance voltage regulation dxt1.
To measure commutating reactance, the line-side For connections given in Table 2, the
inductive voltage regulation can be calculated
terminals of the transformer are short-circuited. An
from the results of secondary short-circuit tests
alternating current of rated frequency is passed
specified in column 17, with the exception of
through two consecutive phases of the same
connections Nos. 3, 4, 6, 9 and 12 for which the
commutating group of the cell winding and the
voltage between the terminals thus fed is measured. short-circuit test specified in 5.1.1 is
The commutating reactance 2 × Xt is equal to the recommended (see IEC 146-1-2, 1.5.4).
inductive component of the impedance calculated If the secondary currents are too high, this method
from this measurement. At least two tests should be cannot be applied; any other equivalent method
carried out with different pairs of phases in each comprising a winding short-circuit on the cell may
commutating group and the arithmetic mean value then be used.
of these measurements is taken. 5.2 Short-circuit test (type test and routine
The same line winding may feed a commutating test)
group assembly connected in parallel or in series The test is performed to obtain the total losses in the
and which commutates simultaneously. In this case, transformer windings.
the cell windings corresponding to these groups
The tests to be made and appropriate short-circuit
shall be connected phase by phase in parallel for the
connections for the most commonly used
above tests.
connections are indicated in Table 2. The currents in
5.1.2 Inductive voltage regulation the windings shall be sinusoidal with the
The inductive voltage regulation can be calculated same r.m.s. values in the line leads as would exist in
from the value of Xt by means of the following normal operation at rated direct current if the
formula: overlap is disregarded and at rated frequency.
I dN For each short-circuit test A, B and C respectively,
$ × q × s- × X × -------------
d xtN = ---------------------- the power inputs shall be measured. The power
2×;×g t U
di0 inputs are designated PA, PB and PC respectively
where and the total losses are calculated according to the
formulae given in Table 2.
g number of sets of commutating groups
between which IdN is divided; The measured losses in the windings are to be
corrected to a temperature of specified limit value
IdN rated direct current; (Table 1) plus 20 °C.
q commutation number; 5.3 Temperature rise test (type test)
s number of commutating groups in series; A temperature rise measurement of the transformer
windings shall be made after continuous application
Udi0 ideal no-load direct voltage;
of rated load. The temperature rise shall not exceed
$ number of commutating groups the values given in Table 1.
commutating simultaneously per The values in Table 1 are based on ambient and
primary. cooling medium temperatures specified in 3.2
and operation at an altitude not greater
It can also be obtained from the test described
than 1 000 metres. Corrections to be applied at
in 5.1.1 by passing during the test a current with an
higher cooling medium temperatures are given
r.m.s. value of:
in Annex A.
2 $
------- × --- × I dN
4 g

© BSI 02-1999 5
EN 60146-1-3:1993

SUPPLIED BY BSB EDGE PRIVATE LIMITED TO LARSEN & TOUBRO LIMITED - DEDICATED FREIGHT CORRIDOR CORPORATION OF INDIA LIMITED, UNDER LICENSE FROM BSI, FOR INTERNAL USE BY THE LICENSEE.
Table 1 — Temperature rise limits
Convertor duty class Transformer cooling Transformer Limit of winding temperature rise in K
a medium temperature class (measured by resistance)
1 2
Air A 60 55
B 80 80
I and II H 125 150
Oil A 65 55
A+ — 65
Air A 55 55
B 70 80
III H 110 150
Oil A 65 55
A+ — 65
Air A 50 50
B 65 80
IV H 100 150
Oil A 60 55
A+ — 65
Air A 45 45
B 60 75
V H 90 140
Oil A 50 50
A+ — 60
Air A 40 40
B 55 70
VI H 85 130
Oil A 50 50
A+ — 60
NOTE 1 Temperature rise limits given in columns 1 and 2 reflect two different practices and climatic conditions in different areas
of the world. Technical Committees dealing with transformers will be asked to study the problem with a view to reconciling the
differences if this is technically feasible.
NOTE 2 The temperature rise figures are based on a maximum ambient temperature of + 40 °C, with an average annual
temperature not exceeding + 20 °C and an average daily ambient temperature of + 30 °C.
NOTE 3 Other transformer temperature classes may be used. In such cases and when temperature rise figures are not shown in
the table, these are to be agreed upon by user and supplier.
NOTE 4 Temperature class A+ designates thermally upgraded paper with a permissible hot spot temperature of + 120 °C.
a Refer to IEC 146-1-1, Table 2.

6 © BSI 02-1999
PLIED BY BSB EDGE PRIVATE LIMITED TO LARSEN & TOUBRO LIMITED - DEDICATED FREIGHT CORRIDOR CORPORATION OF INDIA LIMITED, UNDER LICENSE FROM BSI, FOR INTERNAL USE BY THE LICENS
EN 60146-1-3:1993
Table 2 — Connections and calculation factors
© BSI 02-1999 7
PLIED BY BSB EDGE PRIVATE LIMITED TO LARSEN & TOUBRO LIMITED - DEDICATED FREIGHT CORRIDOR CORPORATION OF INDIA LIMITED, UNDER LICENSE FROM BSI, FOR INTERNAL USE BY THE LICENS
EN 60146-1-3:1993
Table 2 — Connections and calculation factors © BSI 02-1999
8
EN 60146-1-3:1993

SUPPLIED BY BSB EDGE PRIVATE LIMITED TO LARSEN & TOUBRO LIMITED - DEDICATED FREIGHT CORRIDOR CORPORATION OF INDIA LIMITED, UNDER LICENSE FROM BSI, FOR INTERNAL USE BY THE LICENSEE.
Annex A (normative)
Corrections to be applied when cooling medium temperature is higher than
standard
This appendix applies when the specified temperature of the cooling medium exceeds the standard values
given in 3.2 by not more than 15 K.
The temperature rise limits shall be reduced by the amounts given in the Table A.1.
Table A.1 — Reduction of limits of temperature rise for cooling medium temperature
higher than standard in kelvins
Duty classesa
Transformers and reactors I III V VI
II IV
Natural air-cooled and cooling by forced ventilation 1.0 0.7 0.6 0.5

Deduction from limit given in 5.3 per K excess in peak


cooling air temperature (insulation classes A or B)
Fluid-air cooling 1.0 0.8 0.8 0.8

Deduction from limit given in 5.3 per K excess in peak


annual average, or daily average cooling air
temperature, whichever excess is greater
(insulation class A)
Fluid-to-water cooling 1.0 0.8 0.8 0.8

Deduction from limit given in 5.3 per K excess in peak


annual average, or daily average cooling air
temperature, whichever excess is greater
(insulation class A)
a See IEC 146-1-1, 3.10.3.

Annex ZA (normative)
Other international publications quoted in this standard with the references of
the relevant European publications
When the international publication has been modified by CENELEC common modifications, indicated by
(mod), the relevant EN/HD applies.

IEC Publication Date Title EN/HD Date

76 series Power transformers HD 398 series


146-1-1 1991 Semiconductor convertors General requirements EN 60146-1-1 1993
and line commutated convertors —
Part 1-1: Specifications of basic requirements
146-1-2 1991 Part 1-2: Application guide — —

© BSI 02-1999 9
SUPPLIED BY BSB EDGE PRIVATE LIMITED TO LARSEN & TOUBRO LIMITED - DEDICATED FREIGHT CORRIDOR CORPORATION OF INDIA LIMITED, UNDER LICENSE FROM BSI, FOR INTERNAL USE BY THE LICENSEE.

blank
10
BS EN 60146-1-3:1993

National annex NA (informative)


Committees responsible
The United Kingdom participation in the preparation of this European Standard was entrusted by the
Power Electrical Engineering Standards Policy Committee (PEL/-) to Technical Committee PEL/50 upon

SUPPLIED BY BSB EDGE PRIVATE LIMITED TO LARSEN & TOUBRO LIMITED - DEDICATED FREIGHT CORRIDOR CORPORATION OF INDIA LIMITED, UNDER LICENSE FROM BSI, FOR INTERNAL USE BY THE LICENSEE.
which the following bodies were represented:

Association of Consulting Engineers


Electricity Association
Engineering Equipment and Materials Users’ Association
GAMBICA (BEAMA Ltd.)
Institution of Electrical Engineers
Institution of Incoporated Executive Engineers
Power Supply Manufacturers Association — PSMA (BEAMA Ltd.)
Railway Industry Association of Great Britain
Transmission and Distribution Association (BEAMA Ltd.)

National annex NB (informative)


Cross-references
Publication referred to Corresponding British Standard
IEC 76 BS 171 Power transformers
IEC 146-1-1:1991 BS EN 60146-1-1 Semiconductor convertors. General requirements and line
commutated convertors
Part 1-1:1993 Specification of basic requirements

© BSI 02-1999
|
|
|
|
|
|
|
|
|
BSI Ð British Standards Institution
|
|
|
|
|

SUPPLIED BY BSB EDGE PRIVATE LIMITED TO LARSEN & TOUBRO LIMITED - DEDICATED FREIGHT CORRIDOR CORPORATION OF INDIA LIMITED, UNDER LICENSE FROM BSI, FOR INTERNAL USE BY THE LICENSEE.
|
| BSI is the independent national body responsible for preparing British Standards. It
|
| presents the UK view on standards in Europe and at the international level. It is
| incorporated by Royal Charter.
|
|
| Revisions
|
|
| British Standards are updated by amendment or revision. Users of British Standards
|
| should make sure that they possess the latest amendments or editions.
|
|
| It is the constant aim of BSI to improve the quality of our products and services. We
|
| would be grateful if anyone finding an inaccuracy or ambiguity while using this
| British Standard would inform the Secretary of the technical committee responsible,
|
| the identity of which can be found on the inside front cover. Tel: 020 8996 9000.
|
| Fax: 020 8996 7400.
|
|
| BSI offers members an individual updating service called PLUS which ensures that
|
| subscribers automatically receive the latest editions of standards.
|
|
| Buying standards
|
| Orders for all BSI, international and foreign standards publications should be
|
| addressed to Customer Services. Tel: 020 8996 9001. Fax: 020 8996 7001.
|
|
| In response to orders for international standards, it is BSI policy to supply the BSI
|
| implementation of those that have been published as British Standards, unless
|
| otherwise requested.
|
|
| Information on standards
|
| BSI provides a wide range of information on national, European and international
|
| standards through its Library and its Technical Help to Exporters Service. Various
|
| BSI electronic information services are also available which give details on all its
|
| products and services. Contact the Information Centre. Tel: 020 8996 7111.
|
| Fax: 020 8996 7048.
|
|
| Subscribing members of BSI are kept up to date with standards developments and
| receive substantial discounts on the purchase price of standards. For details of
|
| these and other benefits contact Membership Administration. Tel: 020 8996 7002.
|
| Fax: 020 8996 7001.
|
|
| Copyright
|
|
| Copyright subsists in all BSI publications. BSI also holds the copyright, in the UK, of
|
| the publications of the international standardization bodies. Except as permitted
| under the Copyright, Designs and Patents Act 1988 no extract may be reproduced,
|
| stored in a retrieval system or transmitted in any form or by any means ± electronic,
|
| photocopying, recording or otherwise ± without prior written permission from BSI.
|
|
| This does not preclude the free use, in the course of implementing the standard, of
|
| necessary details such as symbols, and size, type or grade designations. If these
|
| details are to be used for any other purpose than implementation then the prior
| written permission of BSI must be obtained.
|
|
| If permission is granted, the terms may include royalty payments or a licensing
|
| agreement. Details and advice can be obtained from the Copyright Manager.
|
| Tel: 020 8996 7070.
|
|
|
|
|
|
|
|
|
BSI |
|
389 Chiswick High Road |
|
London |
|
W4 4AL |
|
|
|
|
|
|

Вам также может понравиться