DATA SHEET
GENERATOR SETS
101946-DS-0207
REV DATE DESCRIPTION AUTHOR MECH ENG PROCESS ENG ELEC ENG APPROVED
OFFERED/
DATA SHEET REQUIRED COMMENTS
GUARANTEED
DOCUMENT No: 101946-DS-0207 101946-DS-0207
EQUIPMENT NUMBER/S 4771-GE-001 4771-GE-001
EQUIPMENT NAME Generator Sets Generator Set
SUPPLIER/CONTRACTOR: By Supplier CUMMINS PERÚ
PLANT AREA: 4713 4713
MODEL No. / DESIGNATION Not Requiered C2000D6
1.00 General
1.01 Supplier By Supplier CUMMINS PERÚ
1.02 Manufacturer By Supplier CUMMINS POWER GENERATION
1.03 Location of assembly plant By Supplier UK
Refer to
101946-DC-0101
2.00 Site Condition
Site Conditions and General Project
Requirements Design Criteria
2.01 Altitude masl 825 825
2.02 Building Containerized Containerized
2.03 Electrical Room Containerized Containerized LV Switgear installed inside Enclosure
2.04 Ourdoors Requered Outdoor
2.05 Temperature Max °C 26.8 26.8
2.06 Temperature Min °C 6.7 6.7
2.07 Relative Humidity Max % 81.3 81.3
2.08 Relative Humidity Min % 70 70
2.09 Pollution Degree HIGH HIGH
3.00 Duty Description
3.01 Design life 20 Years 20 Years Standby operation
Emergency Standby (i.e. Average power output is
Emergency Standby (Average power output is
100% of the emergency standby power rating.
70% of the emergency standby power rating.
3.02 Duty Typical operation is 500 hours per year with
Typical operation is 200 hours per year or a
maximum expected usage of 1000 hours per
maximum of 400 hour in two years). According to ISO 8528-1
year).
3.03 Availability 99.9% 99.9%
3.04 Number of Equipment By Supplier 1
3.05 Type of Installation Stationary Stationary
3.06 Use Outdoor Outdoor
3.07 Operation Stand By Standby
3.08 Engine-generator set Containerized Containerized
3.09 Vibration isolators Required Included
4.00 Engine
4.01 Modelo By Supplier QSK60-G6
4.02 Cycles By Supplier 4
4.03 Cooling type Water cooled Water cooled
4.04 Fuel Diesel Diesel
4.05 Engine speed 1800 rpm 1800RPM
4.06 Electronic speed governor Required Included
4.07 Speed drop ≤ 1% Isochronous (+/-0.25%)
4.08 Cooled radiator Required Fan Cooled radiator Radiator mounted on engine skid
4.09 Controlled cooling system Thermostatically Thermostatically
4.10 Batteries and battery charger Required ( 24Vdc ≥ 200Ah) Included, 24Vdc 220Ah
4.11 Engine protection Required Included
4.12 Low oil pressure Required Included
4.13 High water temperature Required Included
4.14 Overspeed Required Included
4.15 Tank Diesel Capacity (Inside Skid) 12 Hours / day 1400 gal providing an autonomy of 12 hours
12 hours / day at full load (1.66MW).
5.00 Generator
5.01 Tipo SynchroNous (NEMA MG-1) Synchronous (NEMA MG-1)
5.02 Posición Horizontal Horizontal
5.03 Size (kW) 2000KW @ 825 masl 2000KW @ 825 masl
5.04 Switchgear for synchronization Required (See Drawing 101946-0000-K-053_B) Included, 480V, 3P, fixed type, motorized
5.05 Voltage 480 V 480 V
5.06 Power circuit breaker 4000 4000A
5.07 Power Rating circuit breaker 65kA 65kA
5.08 Phases Three Three
5.09 Grounding Required, 25 A - 18 Ohm Required, 25 A - 18 Ohm
5.10 Insulation Class H Class H
5.11 Generator Connection Wye Wye
5.12 Frequency 60 Hz 60 Hz
5.13 Power Factor 0.8 0.8 pf
5.14 Voltage Regulation, No Load to Full Load +/- 0.5% +/- 1.0%
5.15 Voltage Variation +/- 0.5% +/- 0.5%
5.16 Frequency Regulation Isochronous Isochronous
5.17 Frequency Variation +/- 0.2Hz +/- 1.5Hz (+/- 0.25%)
5.18 Efficiency at 100% load By Supplier 96.0%
5.19 Efficiency at 75% load By Supplier 96.5%
5.20 Efficiency at 50% load By Supplier 96.2%
5.21 Operating speed and full load capability 10 seconds after receiving a start signal 10 seconds after receiving a start signal
5.22 Overspeed Max. 1.25 1.25
5.23 Overspeed 1.1 1.1
5.24 Overload 10 % (1 hour minimum) 10 % (1 hour minimum) Each 12 hours
5.25 Space heaters Required (220 V, single phase and 60 Hz) Included (220 V, single phase and 60 Hz)
5.26 IP Rating 53 IP23
5.27 TIF (Telephone Influence Factor) < 50 < 50
5.28 RIS (Radio Interference Suppression) Required PMG included
5.29 Short circuit capacity and support 300% (10 Seg) 300% (10 Seg)
6.00 Local Engine Control Panel (Digital Controller ) and Protection
101946-DS-0207.xlsx 2 of 10
MARCOBRE S.A.C.
OFFERED/
DATA SHEET REQUIRED COMMENTS
GUARANTEED
DOCUMENT No: 101946-DS-0207 101946-DS-0207
EQUIPMENT NUMBER/S 4771-GE-001 4771-GE-001
EQUIPMENT NAME Generator Sets Generator Set
SUPPLIER/CONTRACTOR: By Supplier CUMMINS PERÚ
PLANT AREA: 4713 4713
MODEL No. / DESIGNATION Not Requiered C2000D6
Required
6.02 Remote panel Cummins DMC8000 with remote control and
monitoring of Gensets Updated Rev 01
Required
6.03 Synchronizer controllers Cummins DMC8000 with remote control and
monitoring of Gensets Updated Rev 01
6.04 Standard Generator Controls and Monitoring Required Cummins Powercommand 3201 Paralleling
System for Generator Control, Monitoring and
Protection Updated Rev 01
6.05 Digital ammeter, voltmeter, ammeter/voltmeter phase selector switch Required Included
6.06 Frequency meter Required Included
6.07 Voltage adjust rheostat Required Included Digital adjust
6.08 Standard Engine Controls and Monitoring
6.09 Three position engine control switch – Run/Auto/Stop Required Included
6.10 Cycle cranking Required Included
6.11 Cool down timer Required Included
6.12 Emergency stop pushbutton Required Included
6.13 Safety Shutdown Protection/Led Indications Included
6.14 High coolant temperature 107 ºC (225 F) Required Included
6.15 Low oil pressure Required Included
6.16 Emergency stop pushbutton Required Included
6.17 Overspeed Required Included
6.18 Overcrank Required Included
6.19 Spare alarm, spare shutdown Required Included
6.20 Digital Display (Woodward 3500 XT/P1)
6.21 Coolant temperature Required Included
6.22 Oil pressure Required Included
6.23 Service hours Required Included
6.24 Engine rpm Required Included
6.25 System DC volts Required Included
6.26 System diagnostic codes Required Included
6.27 Power Metering
6.28 3 phase power metering for kW, kVAR, PF, % kW, kW-hr, L-N voltages Required Included
6.29 Programmable Protective Relay Functions (87, 50, 51, 81, etc) with IEC 61850 GE Multilink G60 or Similar GE Multilin 889 with IEC 61850
Under voltage, over voltage, over frequency, under frequency, reverse power, over current
6.30 Required Included
(phase and total), (kW Level), 3 Spare LED’s (programmable) and 4 spare inputs.
6.31 Alarm Module NFPA 110
Provides flashing LEDs and Horn to annunciate: High Coolant Temperature Alarm, Low Coolant
Temperature Alarm, Low Oil Pressure Alarm, Low DC Volts Alarm, System not in Automatic; plus
6.32 Required Included
the following that require switches Malfunction, Engine Inlet Damper Closed.provided by others: Low
Fuel Level, Battery Charger Motorized dampers for air inlet is not provided
6.33 Communication
6.34 Communication Switches IEC 61850, Modbus TCP/ IP. Required (See Drawing 101946-0000-K-053_B)
Included
101946-DS-0207.xlsx 3 of 10
MARCOBRE S.A.C.
OFFERED/
DATA SHEET REQUIRED COMMENTS
GUARANTEED
DOCUMENT No: 101946-DS-0207 101946-DS-0207
EQUIPMENT NUMBER/S 4771-GE-001 4771-GE-001
EQUIPMENT NAME Generator Sets Generator Set
SUPPLIER/CONTRACTOR: By Supplier CUMMINS PERÚ
PLANT AREA: 4713 4713
MODEL No. / DESIGNATION Not Requiered C2000D6
8.19 Determination of efficiency at 100%, 75% and 50% of full load Required Included Fuel efficiency
8.20 Determination of power factor at 100%, 75% and 50% of full load Required Included Power factor is always 1.0 (resistive load)
8.21 Measure breakdown and starting Required Included Measure of time for starting (ready to load)
Sound measured at 7m eight points
8.22 Sound test per IEEE 85 Required
around genset surface
8.23 Bearing Temperature Required Included
Not included, full load current and
8.24 Full load current check - Equivalent circuit method F1, IEEE 112-2004 Required Reactances from protype test are available
101946-DS-0207.xlsx 4 of 10
MARCOBRE S.A.C.
OFFERED/
DATA SHEET REQUIRED COMMENTS
GUARANTEED
DOCUMENT No: 101946-DS-0207 101946-DS-0207
EQUIPMENT NUMBER/S 4771-GE-002 4771-GE-002
EQUIPMENT NAME Generator Sets Generator Set
SUPPLIER/CONTRACTOR: By Supplier CUMMINS PERÚ
PLANT AREA: 4713 4713
MODEL No. / DESIGNATION Not Requiered C2000D6
1.00 General
1.01 Supplier By Supplier CUMMINS PERÚ
1.02 Manufacturer By Supplier CUMMINS POWER GENERATION
1.03 Location of assembly plant By Supplier UK
Refer to
101946-DC-0101
2.00 Site Condition
Site Conditions and General Project
Requirements Design Criteria
2.01 Altitude masl 825 825
2.02 Building Containerized Containerized
2.03 Electrical Room Containerized Containerized LV Switgear installed inside Enclosure
2.04 Ourdoors Requered Outdoor
2.05 Temperature Max °C 26.8 26.8
2.06 Temperature Min °C 6.7 6.7
2.07 Relative Humidity Max % 81.3 81.3
2.08 Relative Humidity Min % 70 70
2.09 Pollution Degree HIGH HIGH
3.00 Duty Description
3.01 Design life 20 Years 20 Years Standby operation
Emergency Standby (i.e. Average power output is
Emergency Standby (Average power output is
100% of the emergency standby power rating.
70% of the emergency standby power rating.
3.02 Duty Typical operation is 500 hours per year with
Typical operation is 200 hours per year or a
maximum expected usage of 1000 hours per
maximum of 400 hour in two years).
year). According to ISO 8528-1
3.03 Availability 99.9% 99.9%
3.04 Number of Equipment By Supplier 1
3.05 Type of Installation Stationary Stationary
3.06 Use Outdoor Outdoor
3.07 Operation Stand By Standby
3.08 Engine-generator set Containerized Containerized
3.09 Vibration isolators Required Included
4.00 Engine
4.01 Modelo By Supplier QSK60-G6
4.02 Cycles By Supplier 4
4.03 Cooling type Water cooled Water cooled
4.04 Fuel Diesel Diesel
4.05 Engine speed 1800 rpm 1800RPM
4.06 Electronic speed governor Required Included
4.07 Speed drop ≤ 1% Isochronous (+/-0.25%)
4.08 Cooled radiator Required Fan Cooled radiator Radiator mounted on engine skid
4.09 Controlled cooling system Thermostatically Thermostatically
4.10 Batteries and battery charger Required ( 24Vdc ≥ 200Ah) Included, 24Vdc 220Ah
4.11 Engine protection Required Included
4.12 Low oil pressure Required Included
4.13 High water temperature Required Included
4.14 Overspeed Required Included
4.15 Tank Diesel Capacity (Inside Skid) 12 Hours / day 12 hours / day 1400 gal providing an autonomy of 12 hours at
full load (1.66MW).
5.00 Generator
5.01 Tipo SynchroNous (NEMA MG-1) Synchronous (NEMA MG-1)
5.02 Posición Horizontal Horizontal
5.03 Size (kW) 2000KW @ 825 masl 2000KW @ 825 masl
5.04 Switchgear for synchronization Required (See Drawing 101946-0000-K-053_B) Included, 480V, 3P, fixed type, motorized
5.05 Voltage 480 V 480 V
5.06 Power circuit breaker 4000 4000A
5.07 Power Rating circuit breaker 65kA 65kA
5.08 Phases Three Three
5.09 Grounding Required, 25 A - 18 Ohm Required, 25 A - 18 Ohm
5.10 Insulation Class H Class H
5.11 Generator Connection Wye Wye
5.12 Frequency 60 Hz 60 Hz
5.13 Power Factor 0.8 0.8 pf
5.14 Voltage Regulation, No Load to Full Load +/- 0.5% +/- 1.0%
5.15 Voltage Variation +/- 0.5% +/- 0.5%
5.16 Frequency Regulation Isochronous Isochronous
5.17 Frequency Variation +/- 0.2Hz +/- 1.5Hz (+/- 0.25%)
5.18 Efficiency at 100% load By Supplier 96.0%
5.19 Efficiency at 75% load By Supplier 96.5%
5.20 Efficiency at 50% load By Supplier 96.2%
5.21 Operating speed and full load capability 10 seconds after receiving a start signal 10 seconds after receiving a start signal
5.22 Overspeed Max. 1.25 1.25
5.23 Overspeed 1.1 1.1
5.24 Overload 10 % (1 hour minimum) 10 % (1 hour minimum) Each 12 hours
5.25 Space heaters Required (220 V, single phase and 60 Hz) Included (220 V, single phase and 60 Hz)
5.26 IP Rating 53 IP23
5.27 TIF (Telephone Influence Factor) < 50 < 50
5.28 RIS (Radio Interference Suppression) Required PMG included
5.29 Short circuit capacity and support 300% (10 Seg) 300% (10 Seg)
6.00 Local Engine Control Panel (Digital Controller ) and Protection
101946-DS-0207.xlsx 5 of 10
MARCOBRE S.A.C.
OFFERED/
DATA SHEET REQUIRED COMMENTS
GUARANTEED
DOCUMENT No: 101946-DS-0207 101946-DS-0207
EQUIPMENT NUMBER/S 4771-GE-002 4771-GE-002
EQUIPMENT NAME Generator Sets Generator Set
SUPPLIER/CONTRACTOR: By Supplier CUMMINS PERÚ
PLANT AREA: 4713 4713
MODEL No. / DESIGNATION Not Requiered C2000D6
Required
6.02 Remote panel Cummins DMC8000 with remote control and
monitoring of Gensets Updated Rev 01
Required
6.03 Synchronizer controllers Cummins DMC8000 with remote control and
monitoring of Gensets Updated Rev 01
6.04 Standard Generator Controls and Monitoring Required Cummins Powercommand 3201 Paralleling
System for Generator Control, Monitoring and
Protection Updated Rev 01
6.05 Digital ammeter, voltmeter, ammeter/voltmeter phase selector switch Required Included
6.06 Frequency meter Required Included
6.07 Voltage adjust rheostat Required Included Digital adjust
6.08 Standard Engine Controls and Monitoring
6.09 Three position engine control switch – Run/Auto/Stop Required Included
6.10 Cycle cranking Required Included
6.11 Cool down timer Required Included
6.12 Emergency stop pushbutton Required Included
6.13 Safety Shutdown Protection/Led Indications Included
6.14 High coolant temperature 107 ºC (225 F) Required Included
6.15 Low oil pressure Required Included
6.16 Emergency stop pushbutton Required Included
6.17 Overspeed Required Included
6.18 Overcrank Required Included
6.19 Spare alarm, spare shutdown Required Included
6.20 Digital Display (Woodward 3500 XT/P1)
6.21 Coolant temperature Required Included
6.22 Oil pressure Required Included
6.23 Service hours Required Included
6.24 Engine rpm Required Included
6.25 System DC volts Required Included
6.26 System diagnostic codes Required Included
6.27 Power Metering
6.28 3 phase power metering for kW, kVAR, PF, % kW, kW-hr, L-N voltages Required Included
6.29 Programmable Protective Relay Functions (87, 50, 51, 81, etc) with IEC 61850 GE Multilink G60 or Similar GE Multilin 889 with IEC 61850
Under voltage, over voltage, over frequency, under frequency, reverse power, over current
6.30 Required Included
(phase and total), (kW Level), 3 Spare LED’s (programmable) and 4 spare inputs.
6.31 Alarm Module NFPA 110
Provides flashing LEDs and Horn to annunciate: High Coolant Temperature Alarm, Low Coolant
Temperature Alarm, Low Oil Pressure Alarm, Low DC Volts Alarm, System not in Automatic; plus
6.32 Required Included
the following that require switches Malfunction, Engine Inlet Damper Closed.provided by others: Low
Fuel Level, Battery Charger Motorized dampers for air inlet is not provided
6.33 Communication
6.34 Communication Switches IEC 61850, Modbus TCP/ IP. Required (See Drawing 101946-0000-K-053_B) Included
101946-DS-0207.xlsx 6 of 10
MARCOBRE S.A.C.
OFFERED/
DATA SHEET REQUIRED COMMENTS
GUARANTEED
DOCUMENT No: 101946-DS-0207 101946-DS-0207
EQUIPMENT NUMBER/S 4771-GE-002 4771-GE-002
EQUIPMENT NAME Generator Sets Generator Set
SUPPLIER/CONTRACTOR: By Supplier CUMMINS PERÚ
PLANT AREA: 4713 4713
MODEL No. / DESIGNATION Not Requiered C2000D6
8.24 Full load current check - Equivalent circuit method F1, IEEE 112-2004 Required Not included, full load current and Reactances
from protype test are available
8.25 Rated rotor temperature vibration test Required Not included. Vibration test of all Genset is
included
9.00 SAT TESTING (Field)
9.01 Woodward Generators controller 3500XT/P1 Required Included
9.02 Woodward remote panel RP3000XT Required Included
9.03 Woodward synchronizer controllers LS-521 Required Included
9.04 Static Electrical Test
9.05 Resistance rolling test (Kelvin Method) Required Included
9.06 Insulation Resistance Required Included
9.07 Polarization index Required Included
9.08 High-potential test (Step Voltage) Required Included
9.09 Surge Test Required Not included
9.10 Insulation test Tangente delta Required Included
9.11 Dynamic electrical test
9.12 Power Quality analysis Required Included
9.13 Generator Performance with resistance load bank at 1.8MW x 5 hours Required Included
9.14 Current data Required Included
9.15 Connection diagram (fasors) Required Included
11.00 Shipping Data Units
11.01 Number of pieces to ship By Supplier 03 pieces
11.02 Overal Dimensions(L x W x H): mm By Supplier 12200 x 2950 x 3700 mm (Genset)
11.03 Largest shipping piece (L x W x H): mm By Supplier 12200 x 2950 x 3700mm
11.04 Heaviest component for shipping : kg By Supplier 30000 kg
11.05 Total shipping weight : kg By Supplier 31500 kg
11.06 F.O.B. Point By Supplier DCP-Callao
12.00 Notes
12.01 Diesel-Generator should be containerised suitable for outdoor installation.
101946-DS-0207.xlsx 7 of 10
MARCOBRE S.A.C.
OFFERED/
DATA SHEET REQUIRED COMMENTS
GUARANTEED
DOCUMENT No: 101946-DS-0207 101946-DS-0207
EQUIPMENT NUMBER/S 4771-GE-003 4771-GE-003
EQUIPMENT NAME Generator Sets Generator Set
SUPPLIER/CONTRACTOR: By Supplier CUMMINS PERÚ
PLANT AREA: 4713 4713
MODEL No. / DESIGNATION Not Requiered C2000D6
1.00 General
1.01 Supplier By Supplier CUMMINS PERÚ
1.02 Manufacturer By Supplier CUMMINS POWER GENERATION
1.03 Location of assembly plant By Supplier UK
Refer to
101946-DC-0101
2.00 Site Condition
Site Conditions and General Project
Requirements Design Criteria
2.01 Altitude masl 825 825
2.02 Building Containerized Containerized
2.03 Electrical Room Containerized Containerized LV Switgear installed inside Enclosure
2.04 Ourdoors Requered Outdoor
2.05 Temperature Max °C 26.8 26.8
2.06 Temperature Min °C 6.7 6.7
2.07 Relative Humidity Max % 81.3 81.3
2.08 Relative Humidity Min % 70 70
2.09 Pollution Degree HIGH HIGH
3.00 Duty Description
3.01 Design life 20 Years 20 Years Standby operation
Emergency Standby (i.e. Average power output is
Emergency Standby (Average power output is
100% of the emergency standby power rating.
70% of the emergency standby power rating.
3.02 Duty Typical operation is 500 hours per year with
Typical operation is 200 hours per year or a
maximum expected usage of 1000 hours per
maximum of 400 hour in two years). According to ISO 8528-1
year).
3.03 Availability 99.9% 99.9%
3.04 Number of Equipment By Supplier 1
3.05 Type of Installation Stationary Stationary
3.06 Use Outdoor Outdoor
3.07 Operation Stand By Standby
3.08 Engine-generator set Containerized Containerized
3.09 Vibration isolators Required Included
4.00 Engine
4.01 Modelo By Supplier QSK60-G6
4.02 Cycles By Supplier 4
4.03 Cooling type Water cooled Water cooled
4.04 Fuel Diesel Diesel
4.05 Engine speed 1800 rpm 1800RPM
4.06 Electronic speed governor Required Included
4.07 Speed drop ≤ 1% Isochronous (+/-0.25%)
4.08 Cooled radiator Required Fan Cooled radiator Radiator mounted on engine skid
4.09 Controlled cooling system Thermostatically Thermostatically
4.10 Batteries and battery charger Required ( 24Vdc ≥ 200Ah) Included, 24Vdc 220Ah
4.11 Engine protection Required Included
4.12 Low oil pressure Required Included
4.13 High water temperature Required Included
4.14 Overspeed Required Included
4.15 Tank Diesel Capacity (Inside Skid) 12 Hours / day 12 hours / day 1400 gal providing an autonomy of 12 hours at
full load (1.66MW).
5.00 Generator
5.01 Tipo SynchroNous (NEMA MG-1) Synchronous (NEMA MG-1)
5.02 Posición Horizontal Horizontal
5.03 Size (kW) 2000KW @ 825 masl 2000KW @ 825 masl
5.04 Switchgear for synchronization Required (See Drawing 101946-0000-K-053_B) Included, 480V, 3P, fixed type, motorized
101946-DS-0207.xlsx 8 of 10
MARCOBRE S.A.C.
OFFERED/
DATA SHEET REQUIRED COMMENTS
GUARANTEED
DOCUMENT No: 101946-DS-0207 101946-DS-0207
EQUIPMENT NUMBER/S 4771-GE-003 4771-GE-003
EQUIPMENT NAME Generator Sets Generator Set
SUPPLIER/CONTRACTOR: By Supplier CUMMINS PERÚ
PLANT AREA: 4713 4713
MODEL No. / DESIGNATION Not Requiered C2000D6
Required
6.02 Remote panel Cummins DMC8000 with remote control and
monitoring of Gensets Updated Rev 01
Required
6.03 Synchronizer controllers Cummins DMC8000 with remote control and
monitoring of Gensets Updated Rev 01
6.04 Standard Generator Controls and Monitoring Required Cummins Powercommand 3201 Paralleling
System for Generator Control, Monitoring and
Protection Updated Rev 01
6.05 Digital ammeter, voltmeter, ammeter/voltmeter phase selector switch Required Included
6.06 Frequency meter Required Included
6.07 Voltage adjust rheostat Required Included Digital adjust
6.08 Standard Engine Controls and Monitoring
6.09 Three position engine control switch – Run/Auto/Stop Required Included
6.10 Cycle cranking Required Included
6.11 Cool down timer Required Included
6.12 Emergency stop pushbutton Required Included
6.13 Safety Shutdown Protection/Led Indications Included
6.14 High coolant temperature 107 ºC (225 F) Required Included
6.15 Low oil pressure Required Included
6.16 Emergency stop pushbutton Required Included
6.17 Overspeed Required Included
6.18 Overcrank Required Included
6.19 Spare alarm, spare shutdown Required Included
6.20 Digital Display (Woodward 3500 XT/P1)
6.21 Coolant temperature Required Included
6.22 Oil pressure Required Included
6.23 Service hours Required Included
6.24 Engine rpm Required Included
6.25 System DC volts Required Included
6.26 System diagnostic codes Required Included
6.27 Power Metering
6.28 3 phase power metering for kW, kVAR, PF, % kW, kW-hr, L-N voltages Required Included
6.29 Programmable Protective Relay Functions (87, 50, 51, 81, etc) with IEC 61850 GE Multilink G60 or Similar GE Multilin 889 with IEC 61850
Under voltage, over voltage, over frequency, under frequency, reverse power, over current
6.30 Required Included
(phase and total), (kW Level), 3 Spare LED’s (programmable) and 4 spare inputs.
6.31 Alarm Module NFPA 110
Provides flashing LEDs and Horn to annunciate: High Coolant Temperature Alarm, Low Coolant
Temperature Alarm, Low Oil Pressure Alarm, Low DC Volts Alarm, System not in Automatic; plus
6.32 Required Included
the following that require switches Malfunction, Engine Inlet Damper Closed.provided by others: Low
Fuel Level, Battery Charger Motorized dampers for air inlet is not provided
6.33 Communication
6.34 Communication Switches IEC 61850, Modbus TCP/ IP. Required (See Drawing 101946-0000-K-053_B) Included
101946-DS-0207.xlsx 9 of 10
MARCOBRE S.A.C.
OFFERED/
DATA SHEET REQUIRED COMMENTS
GUARANTEED
DOCUMENT No: 101946-DS-0207 101946-DS-0207
EQUIPMENT NUMBER/S 4771-GE-003 4771-GE-003
EQUIPMENT NAME Generator Sets Generator Set
SUPPLIER/CONTRACTOR: By Supplier CUMMINS PERÚ
PLANT AREA: 4713 4713
MODEL No. / DESIGNATION Not Requiered C2000D6
8.23 Bearing Temperature Required Included
8.24 Full load current check - Equivalent circuit method F1, IEEE 112-2004 Required Not included, full load current and Reactances
from protype test are available
8.25 Rated rotor temperature vibration test Required Not included. Vibration test of all Genset is
included
9.00 SAT TESTING (Field)
9.01 Woodward Generators controller 3500XT/P1 Required Included
9.02 Woodward remote panel RP3000XT Required Included
9.03 Woodward synchronizer controllers LS-521 Required Included
9.04 Static Electrical Test
9.05 Resistance rolling test (Kelvin Method) Required Included
9.06 Insulation Resistance Required Included
9.07 Polarization index Required Included
9.08 High-potential test (Step Voltage) Required Included
9.09 Surge Test Required Not included
9.10 Insulation test Tangente delta Required Included
9.11 Dynamic electrical test
9.12 Power Quality analysis Required Included
9.13 Generator Performance with resistance load bank at 1.8MW x 5 hours Required Included
9.14 Current data Required Included
9.15 Connection diagram (fasors) Required Included
11.00 Shipping Data Units
11.01 Number of pieces to ship By Supplier 03 pieces
11.02 Overal Dimensions(L x W x H): mm By Supplier 12200 x 2950 x 3700 mm (Genset)
11.03 Largest shipping piece (L x W x H): mm By Supplier 12200 x 2950 x 3700mm
11.04 Heaviest component for shipping : kg By Supplier 30000 kg
11.05 Total shipping weight : kg By Supplier 31500 kg
11.06 F.O.B. Point By Supplier DCP-Callao
12.00 Notes
12.01 Diesel-Generator should be containerised suitable for outdoor installation.