Вы находитесь на странице: 1из 1

NOTES -STEEL:-

1. ALL DIMENSION ARE IN MM


2. ALL WELDING SHALL BE 6MM FULL FILLET,BUT @ BASE PLATE
CONNECTION & KNEE JOINT 8M.M. FULL FILLET WELDING
3. ALL FEBRICATION AND ERECTION CONFIRM TO I.S.800
4. ALL WELDING SHALL BE CONFIRM TO I.S.816
5. ALL DIMENSIONS ARE SUBJECTED TO VERIFICATION ON SITE
6. ALL STEEL MEMBERS ARE FE 250
7. CAMBER FOR TIE RUNNER IS L\360

NOTES-CONCRETE
1. ALL DIMENSIONS ARE IN MILLIMETER
U.N.O.
2. BEARING CAPACITY TAKEN 12TON/SQM.
3. GRADE OF CONCRETE NOMINAL MIX
1:1.5:3 AND REINFORCEMENT Fe-415 OR
Fe-500 WHICH IS AVAILABLE.
4. OVERLAPPING LENGTH 50d OR AS PER IS
CODE.
5. CENTER TO CENTER DISTANCE MUST BE
VERIFIED BEFORE PLACING CONCRETE
AND ANCHOR BOLTS ARE TO BE CAST IN
SITU.
6. IN CASE OF FILLED SOIL, THE
FOUNDATION MUST BE KEPT 600mm IN
VIRGIN SOIL WITH APPROVAL FROM EIC.

SAFE BEARING CAPACITY OF SOIL 6.5T/M2

CLIENT PROJECT TITLE DRAWING TITLE DRAWING NO : KPC/15/2019-20 PROJECT ARCHITECT REV:

KPC MEDICAL COLLEGE & HOSPITAL PROPOSED TRANSFORMER AND DG TRANSFORMER & PANEL RELEASE FOR CONSTRUCTION N BISMI CONSTRUCTION

1F, RAJA SUBODH CHANDRA MULLICK ROAD, SHED STRUCTURE AT KPC MEDICAL ROOM BUILDING ( SINGLE
JADAVPUR, KOLKATA, WEST BENGAL 700 032 COLLEGE & HOSPITAL, JADAVPUR STORIED) DATE: 25.05.2019
SCALE - N.T.S
SHEET : 2 of 2