Вы находитесь на странице: 1из 62

OPERATION &

MAINTENANCE
MANUAL
with
FILLING INSTRUCTIONS

Bladder Tank Proportioning System

06/18 MANUAL P/N: 1298-9944-5(A)


BLADDER TANK PROPORTIONING SYSTEM TABLE OF CONTENTS

TABLE OF CONTENTS

Section Page

Table of Contents ...................................................................................................................................................... i - iii

CHAPTER 1 - INTRODUCTION
Angus Fire Emergency Foam Service .........................................................................................................................1-1
1-1. Safety Information .......................................................................................................................................................1-2
1-2. General Description .....................................................................................................................................................1-3
1-3. General Notes ..............................................................................................................................................................1-4

CHAPTER 2 - INSTALLATION
Warning - System Inspection After Installation .........................................................................................................2-1
Caution - System Installation .....................................................................................................................................2-1
Caution - Customer Modification of Equipment ........................................................................................................2-1
Note - Read Operating Instructions .............................................................................................................................2-1
2-1. Recommended Materials of Construction ...................................................................................................................2-1
2-2. Bladder Tank Site Selection.........................................................................................................................................2-2
2-3. Badder Tank Off Loading ............................................................................................................................................2-2
2-4. Bladder Tank Installation.............................................................................................................................................2-2
2-5. Sight Glass Installation ................................................................................................................................................2-4
2-6. Start-Up Procedures.....................................................................................................................................................2-5
2-7. Testing After Installation .............................................................................................................................................2-5
Figure 2-1 General Arrangement-Horizontal Bladder Tank w/Fill Piping & Optional Sight Glass........................2-6
Horizontal Bladder Tank Capacity, Dimensions & Weight Chart .........................................................2-7
Figure 2-2 General Arrangement-Vertical Bladder Tank w/Fill Piping & Optional Sight Glass ............................2-8
Vertical Bladder Tank Capacity, Dimensions & Weight Chart ..............................................................2-9

CHAPTER 3 - CONCENTRATE FILLING PROCEDURE FOR BLADDER TANKS


Warning - Damage from Incorrect Filling Procedures ...............................................................................................3-1
Note - Recommendation to Keep Bladder Full and Filling Methods .........................................................................3-1
3-1. Introduction .................................................................................................................................................................3-1
Bladder Tank Fill Manifold .........................................................................................................................................3-2
3-2. Horizontal Bladder Tank Filling Instructions ..............................................................................................................3-3
A. Initial Fill or Empty Bladder Tank Fill .................................................................................................................3-3
Figure 3-1 Bladder Filled With Air ..................................................................................................................3-3
Figure 3-2 Bladder Filling With Foam Concentrate .........................................................................................3-4
B. Refilling or Topping Off Using Motor Driven Foam Concentrate Pump .............................................................3-5
Figure 3-3 Refilling or Topping-Off .................................................................................................................3-5
C. Topping Off Using Hand Pouring Method ...........................................................................................................3-6
Figure 3-4 Topping-Off Using Hand Pouring Method .....................................................................................3-6
D. Topping-Off Using Hand Pumping Method .........................................................................................................3-7

06/18 -i-
TABLE OF CONTENTS BLADDER TANK PROPORTIONING SYSTEM

Figure 3-5 Topping-Off Using Hand Pumping Method ...................................................................................3-7


3-3. Vertical Bladder Tank Filling Instructions...................................................................................................................3-8
A. Initial Fill or Empty Bladder Tank Fill .................................................................................................................3-8
Figure 3-6 Tank Shell Filled With Water ..........................................................................................................3-8
Figure 3-7 Bladder Being Filled With Air ........................................................................................................3-9
Figure 3-8 Bladder Filling With Foam Concentrate .......................................................................................3-10
B. Refilling or Topping-Off Using Motor Driven Foam Concentrate Pump .......................................................... 3-11
Figure 3-9 Bladder Filling With Foam Concentrate ....................................................................................... 3-11
C. Topping-Off Using Hand Pouring Method .........................................................................................................3-12
D. Topping-Off Using Hand Pumping Method .......................................................................................................3-12
3-4. Procedures for Checking Foam Concentrate Level ...................................................................................................3-12

CHAPTER 4 - OPERATING PROCEDURES


4-1. Operation of System ....................................................................................................................................................4-1
1. Manual Operation .................................................................................................................................................4-1
2. Automatic Operation ............................................................................................................................................4-1
4-2. Shutdown of System ....................................................................................................................................................4-1
1. Manual Operation .................................................................................................................................................4-1
2. Automatic Operation ............................................................................................................................................4-2
4-3. Automatic System Flushing ........................................................................................................................................4-2
Figure 4-1 System Operating Drawing - Horizontal Bladder Tank - Valve Description & Position Chart .............4-3
Figure 4-2 System Operating Drawing - Vertical Bladder Tank - Valve Description & Position Chart .................4-4
Figure 4-3 Ratio Controller Flow Range and Piping Size Chart .............................................................................4-5
Figure 4-4 Ratio Controller Minimum Inlet Pressure vs Solution Flow Chart .......................................................4-5

CHAPTER 5 - INSPECTION, MAINTENANCE & REPAIR


5-1. Inspection and Maintenance ........................................................................................................................................5-1
5-2. Testing After System Maintenance ..............................................................................................................................5-1
5-3. Annual Testing .............................................................................................................................................................5-1
Table 5-1 - Recommended Inspection & Maintenance Schedule ...............................................................................5-2
5-4. Total System ................................................................................................................................................................5-2
5-5. Strainers .......................................................................................................................................................................5-3
5-6. Electrically Actuated Valves ........................................................................................................................................5-3
5-7. Water Powered Ball Valves .........................................................................................................................................5-3
5-8. Foam Concentrate Storage Tank..................................................................................................................................5-4
5-9. Foam Concentrate ........................................................................................................................................................5-4
5-10. Control System ............................................................................................................................................................5-4

CHAPTER 6 - FOAM CONCENTRATES


6-1. Proper Storage & Maintenance ...................................................................................................................................6-1
6-2. Basic Guidelines for Improving Foam Concentrate Storage Life ...............................................................................6-1
6-3. Foam Concentrate Testing ...........................................................................................................................................6-2
6-4. Control Measures.........................................................................................................................................................6-2
6-5. Safe Handling of AF Foam Products ...........................................................................................................................6-2

- ii - 06/18
BLADDER TANK PROPORTIONING SYSTEM TABLE OF CONTENTS

Warning - Foam is a Conductor .................................................................................................................................6-2


Warning - Fires Where Foams are not Suitable Extinguishing Agents ......................................................................6-2
Warning - Judgment in Applying Foams ...................................................................................................................6-2
6-6. Sampling Procedures ...................................................................................................................................................6-3
6-7. Documentation ............................................................................................................................................................6-3
Sample Request for Analysis of Foam Concentrates Form .........................................................................................6-4

CHAPTER 7 - TROUBLESHOOTING
7-1. Troubleshooting Recommendations ............................................................................................................................7-1
Table 7-1 - Troubleshooting ........................................................................................................................................7-1
7-2. No Proportioning .........................................................................................................................................................7-1
7-3. Low Percent of Proportioning .....................................................................................................................................7-2
7-4. High Percent of Proportioning.....................................................................................................................................7-3
7-5. No Flow at Discharge ..................................................................................................................................................7-3
7-6. Low Flow at Discharge................................................................................................................................................7-3
7-7. No Operation ...............................................................................................................................................................7-3

CHAPTER 8 - RATIO CONTROLLER STORAGE AND INSTALLATION INSTRUCTIONS


- RATIO CONTROLLER SUPPLIED AS LOOSE COMPONENT -

8-1. 2″ RCT (Threaded) Thru 8″ RCF (Flanged) Units ......................................................................................................8-1


A. Storage ..................................................................................................................................................................8-1
B. Installation ............................................................................................................................................................8-1
Figure 8-1 RCF (RCT) Installation Illustration .......................................................................................................8-2
8-2. 3″ Thru 8″ RCW (Between the Flange Type) Units ....................................................................................................8-3
A. Storage ..................................................................................................................................................................8-3
B. Installation ............................................................................................................................................................8-3
Figure 8-2 RCW Installation Illustration .................................................................................................................8-3

CHAPTER 9 - WATER POWERED BALL VALVE INSTALLATION INSTRUCTIONS


MODEL WPBV-M2 : STANDARD AND SOLENOID RELEASE
- WPBV SUPPLIED AS LOOSE COMPONENT -

9-1. Standard Models - Description ....................................................................................................................................9-1


9-2. Solenoid Release Models - Description ......................................................................................................................9-1
9-3. General Installation .....................................................................................................................................................9-2
• Solenoid Release Installation ...............................................................................................................................9-2
Figure 9-1 WPBV-M2 Water Powered Ball Valve Installation Illustration .............................................................9-3

CHAPTER 10 - TANK BLADDER INTEGRITY TEST


10-1. Purpose ......................................................................................................................................................................10-1
10-2. Required Equipment ..................................................................................................................................................10-1
10-3. Bladder Integrity Testing Procedures ........................................................................................................................10-1
Figure 10-1 Bladder Integrity Test Setup ................................................................................................................10-2

06/18 - iii -
BLADDER TANK PROPORTIONING SYSTEM INTRODUCTION

CHAPTER 1 - INTRODUCTION

Emergency Foam Service

Angus Fire’s Emergency Foam Service is a system set up to respond to the emergency situation.
Fire, hazardous material spill, or any other emergency service Angus Fire can provide is available 24 hours a day, 365
days a year. An Emergency Foam Service will be handled by a qualified Angus Fire professional who will respond to your
call and satisfy your requirements for emergency foam, equipment or service, and work with you until your emergency
is under control.
Call the “Emergency Hotline” telephone number anytime, anywhere in the world for Angus Fire emergency foam service
or products.
EMERGENCY HOTLINE NUMBER: +44 (0) 15242 61166
Angus Fire and our representatives are always ready to assist you in the event of an emergency.

06/18 1-1
INTRODUCTION BLADDER TANK PROPORTIONING SYSTEM

1-1. Safety Information

WARNING
This manual has been prepared as an aid and guide for personnel involved in the installation, operation, and
maintenance of an Angus Fire Bladder Tank Proportioning System. All instructions must be read and understood
thoroughly before attempting any installation, operation, or maintenance to this system. Failure to follow these
instructions could result in personal injury and/or damage to the system.

The various Danger, Warning, Caution, and Note signal words that appear in this manual must be observed for safe
system personnel and equipment operation. Signal word selection is based upon hazard classification.

The International Safety Alert Symbol - - is used with the signal word to gain and direct operating personnel's attention
to the signal word.
The following explains each signal word. Personnel operating and maintaining the system must familiarize themselves
with each signal word's intent.

DANGER signal words indicate an extremely hazardous situation which, if not avoided, will result in death or
serious injury to the operator.

WARNING signal words indicate a potentially hazardous situation which, if not avoided, could result in serious
injury or death to the operator.

CAUTION signal words indicate the following:


A potentially hazardous situation which, if not avoided, may result in minor or moderate injury.
A potentially hazardous situation which, if not avoided, may damage or destroy equipment or cause a loss of
operating effectiveness.
Alert operating personnel to unsafe practices.
NOTE signal words indicate statements which must be observed for essential and effective operating procedures,
conditions, and as a statement to be highlighted.
It is the responsibility and duty of all personnel involved in the installation, operation, and maintenance of this system
to fully understand the DANGER, WARNING, CAUTION and NOTE procedures by which hazards are to be reduced
or eliminated. Personnel must become thoroughly familiar with all aspects of safety and equipment prior to installation,
operation, or maintenance of the equipment.
Operation and Maintenance Instructions and layouts shall be posted at control equipment with a second copy on file.
All persons who may be expected to inspect, test, maintain, or operate the system shall be thoroughly trained and kept
thoroughly trained in the functions they are expected to perform.

1-2 06/18
BLADDER TANK PROPORTIONING SYSTEM INTRODUCTION

1-2. General Description

The Bladder Tank Proportioning System is designed to The main components of the AF Bladder Tank Proportioning
inject foam concentrate into the water supply at the correct System are:
percentage. This system will automatically and accurately
1. An ASME constructed carbon steel pressure vessel
proportion over a wide range of flows and pressures.
ASME Code construction is standard for all AF Bladder
The Bladder Tank Proportioning System employs water Tanks.
pressure and a bladder equipped tank in conjunction with a
2. A flexible thermoplastic vulcanized rubber bladder
ratio controller to make foam solution. The proportioning is
which holds the foam concentrate. The bladder provides
accomplished by using a water orifice and a foam concentrate
a physical barrier which prevents the foam concentrate
orifice both discharging into a common reduced pressure
from coming into contact with water or the inside of
area (Ratio Controller).
the tank shell.
The water supply simultaneously feeds the ratio controller
3. Perforated PVC Schedule 80 center discharge piping,
(venturi-type proportioner) and pressurizes the foam
located within the bladder, terminating at the flanged
concentrate. A portion of the water supply is diverted
concentrate connection points on the tank. The purpose
upstream of the proportioner and is used to pressurize the
of the center discharge piping is to insure that the foam
foam concentrate through an elastomeric bladder in the tank
concentrate can be channelled to the outlet connection
separating the foam concentrate from the water.
points regardless of the manner in which the bladder
The water flowing through the controller jet creates a collapses.
differential pressure common to both the downstream water
4. Internally installed section of 1ʺ rubber hose between
and foam concentrate. This pressure difference between the
the bladder and the tank shell, extending from the water
tank and controller concentrate inlet forces foam concentrate
vent to the water drain connection. This hose prevents
from the tank through the foam concentrate orifice and into
the bladder from sealing off the water vent and drain
the controller. Here it mixes with water to produce a constant
openings during filling operation.
predetermined percent solution at various flow rates. The
units have a low pressure drop and connect directly to the 5. All necessary drain and vent valves, concentrate fill
solution discharge valve. piping and fill cup and carbon steel tank supports.
During foam operation, the water outside the bladder 6. Optional Sight Gauge Assembly with 1-1/2″ O.D.
gradually displaces the foam concentrate inside the bladder polycarbonate sight glass, a ball shutoff valve to stop
causing the bladder to collapse until the supply is exhausted, leakage of concentrate in case of accidental sight glass
at which time, the system must be shut down, the tank breakage and compression nut and washer to mount
drained and the bladder refilled with foam concentrate. sight glass to shutoff valve.
Replenishment of the foam concentrate during system
operation is not possible. The customer connections for water pressurization and
foam concentrate outlet are NPT. All AF Bladder Tanks are
A separate section of this manual is devoted to tank filling. designed for 175 psi (12 bar) maximum operating pressure
It is very important to follow this procedure in order to and are UL Listed.
prevent damage to the tank bladder.
Bladder Tank Proportioning Systems used with AR-AFFF
The bladder tank is the main component in the AF Bladder foam concentrate require special attention due to flow range
Tank Proportioning System. The AF Bladder Tank limitations of the ratio controllers. Contact AF Engineering
Proportioning System is available in either horizontal or Department for further information.
vertical configurations.

06/18 1-3
INTRODUCTION BLADDER TANK PROPORTIONING SYSTEM

1-3. General Notes

1. All correspondence relating to this system should refer area(s) of coverage. The design requirements may or
to the Sales Order Number, file number and user name may not have been provided to Angus Fire. Any changes
and location. to the area(s) of coverage or additions of other products
could exceed the design parameters of the system.
2. Before installation is begun, the final plans and design
Contact AF Engineering Dept. for questions regarding
data should be presented to the authorities having
changes to design.
jurisdiction.
6. At least annually, all foam systems shall be inspected
3. Angus Fire recommends that those individuals
and checked for proper operation.
charged with designing, installing, operating, testing
and maintaining a foam fire protection system, or the 7. In accordance with the requirements of NFPA 11,
replacement of equipment and/or components of an Angus Fire recommends that the system be inspected
existing system, refer to the appropriate authority having and tested by qualified personnel. Testing shall meet
jurisdiction for compliance with applicable standard(s), the approval of the authority having jurisdiction, and as
code(s) and regulation(s) for that particular type of a minimum, shall be as outlined in NFPA 11 to insure
system and its components. that the system has been properly installed and will
function as intended.
4. Angus Fire concentrates must be maintained and stored
within certain specified temperatures, containers and 8. Before filling the bladder tank, carefully read the
conditions. Failure to follow Angus Fire’s guidelines concentrate filling instructions to prevent damaging
regarding these concentrates can compromise their the bladder.
effectiveness. Refer to Chapter 6 - Foam Concentrates,
9. All electrical installations and equipment must conform
Sections 6-1 and 6-2 for AF recommendations.
to the provisions of the National Electric Code and all
5. The foam system provided is based on specific design local codes.
requirements, that is, products(s) being protected and

1-4 06/18
BLADDER TANK PROPORTIONING SYSTEM INSTALLATION

CHAPTER 2 - INSTALLATION

WARNING:
Angus Fire recommends the system be inspected and tested in accordance with applicable NFPA
standards.
CAUTION:
Install the bladder tank and piping in accordance with instructions in this manual. Variations may
affect system performance or cause system failure.
Customer modification or alteration of this equipment, or the use of replacement parts other than
those as specified by AF may affect the performance of this equipment and may void the warranty.

NOTE: READ ALL OPERATING INSTRUCTIONS BEFORE USING EQUIPMENT. It is the


responsibility and duty of all personnel involved in the installation, operation, inspection, maintenance
and refilling of this system to read and understand this entire manual before using the equipment.

2-1. Recommended Materials of Construction


NOTE: The following recommendations are for materials which will be in contact with the foam concentrates.

CAUTION:
Galvanized steel or other internal coatings must never be used in piping which will contain any foam concentrates.

1. Used With Synthetic Based Polar Solvent/AFFF and 2. Used With Protein-Based Foam Concentrates.
Conventional AFFF Foam Concentrates.
a. Piping:
a. Piping:
• Brass or Bronze
• Brass or Bronze
• Same materials as Synthetic Based Polar
• Stainless Steel Type 304 or 316 Solvent/AFFF and Conventional AFFF Foam
• High Density Polyethylene Concentrate with the exception of welded
stainless steel.
• PVC
b. Valves:
• Fiberglass with isophthalic based polyester and
an internal layer (50-100 mils min.) of vinyl • Brass or Bronze. Cast brass valves fitted with
ester resin in contact with foam concentrate. stainless steel (304 or 316 grades) or brass
trim are acceptable. Teflon seats and packing
b. Valves: are preferable for foam concentrate service.
• Brass or Bronze. Cast brass valves fitted with EPT (EPDM), Buna-N or Viton are also
stainless steel (304 or 316 grades) or brass acceptable seal materials for use with AF foam
trim are acceptable. Teflon seats and packing concentrates.
are preferable for foam concentrate service.
EPT (EPDM), Buna-N or Viton are also
acceptable seal materials for use with AF foam NOTE: 304 and 316 grades also include “L” grades.
concentrates.
• Stainless Steel Type 304 or 316

06/18 2-1
INSTALLATION BLADDER TANK PROPORTIONING SYSTEM

2-2. Bladder Tank Site Selection


NOTE: For Bladder Tank dimensions, refer to the General 3. The tank must be securely bolted in place using the bolt
Arrangement Drawing for your particular system. holes provided on the tank tie-down pads.
1. The Bladder Tank must be located on a suitably supported 4. If applicable, the bladder tank must be placed in
flat and level surface. Shims and/or grout may be used a temperature controlled location. Since water is
to obtain proper level. used to operate the proportioning system and is also
proportioned with foam concentrate, the system must
2. The recommended base is concrete.
be protected from freezing temperatures.

2-3. Bladder Tank Off Loading


1. Do not allow the tank to be rolled over the fittings.
CAUTION:
2. Do not allow lifting forks, crane attachments or other This vessel is fitted with a bladder, and therefore, no
lifting devices to contact the ratio controller(s), fittings welding shall be done on the pressure vessel. Welding
or valves during a moving operation. could damage the bladder and will void the ASME Code
certification.

2-4. Bladder Tank Installation

NOTE: Refer to System Operating Drawing Fig. 4-1 for 6. When designing a building to house bladder tanks,
horizontal tanks or Fig. 4-2 for vertical tanks for Normal provisions should be made to remove the internal pipes
Stand-By Valve position chart and valve location. and bladder, which are the full length and/or height of
the tank.
WARNING:
NOTE: Bladder tanks have flanges on both ends of the
Angus Fire has not provided an over pressure relief device
tank. Horizontal tanks always use the larger flanged end
with this pressure vessel. ASME Code may require over
and Vertical tanks always use the top end flange for internal
pressure protection before placing a pressure vessel into
piping and bladder removal. The tank must be located and
sevice. It shall be the owner’s responsibility to provide
positioned in the building to allow sufficient room for
over pressure protection for this vessel in accordance
removal of the internal piping and bladder.
with ASME Code .
7. Check the flange bolts on both ends of the tank for
1. Remove the Bladder Tank from crate. Remove all
proper tightness before placing the tank into service.
wrapping, banding and/or support blocks. Inspect
Follow the appropriate torque rating below to insure that
the entire system and components for damage before
the bolts are fixed securely in place and have not been
securing in place.
loosened during shipment. If tightening is required, a
2. Vibration during transportation may affect fittings. criss-cross pattern technique is recommended to insure
Check all fittings and the nuts on all bolted fittings that the flange is secured completely and correctly (see
before the tank is placed in service. illustration for recommended tightening sequence).
Tighten the bolts in 1/3 increments - tighten in steps of
3. All interconnecting piping must be self-supported. 1/3 tight, 2/3 tight and finally, fully tightened. Do not
4. Sufficient space above the tank must be allowed to fully tighten bolts in one step/pass. Also, follow the
permit filling of the tank with foam concentrate. recommended torque ratings when relacing an internal
bladder.
5. Remove the appropriate foam concentrate contents label
- with type and percentage - from the sheet of contents 4 in. flange ----------------50 ft. lbs.
labels provided. Attach the label to the bladder tank 6 and 8 in. flange --------60 ft. lbs.
following the instructions provided with the contents 10 in. flange ------------ 120 ft. lbs.
labels pack.

2-2 06/18
BLADDER TANK PROPORTIONING SYSTEM INSTALLATION

12. If applicable, install the water powered ball valve. Refer


1
to Chapter 9 - Water Powered Ball Valve Installation
1 5 11 6
Instructions for the proper installation of standard and
7 10
8 3 solenoid release models.
3 4
13. A check valve must be installed on the foam concentrate
4 7 9 8 supply line to prevent backflow of water into the foam
6 2 5 12 concentrate supply line.
2

WARNING:
4, 6, & 8 In. Flange 12 In. Flange
If a customer supplied ball check valve will be
8. If applicable, install the ratio controller. Refer to Chapter installed on the foam concentrate supply line, the ball
8 - Ratio Controller Storage and Installation Instructions check valve spring must be removed before placing
(ratio controller supplied as a loose component) for the bladder tank into service. Failure to remove the
the proper installation of flanged or wafer style ratio spring will result in improper proportioning.
controllers.
AF recommends the appropriately sized Conbraco
NOTE: A minimum of 5 pipe diameters of straight and 61-100 Series Ball Check Valve, or equal, with “spring
unobstructed pipe is required upstream and downstream removed” for use with AF bladder tanks. Contact AF
of each ratio controller. Engineering Department for questions or problems.
NOTE: Refer to Fig. 4-3 Ratio Controller Flow Range For proper operation, the ball check valve must be
and Piping Size Chart on page 4-5 for standard water installed in the vertical position.
and foam concentrate line sizes.
14. A check valve is required in each water pressure feed
CAUTION: line if more than one ratio controller is installed.
For Accurate Proportioning: When AR-AFF 15. If applicable, install foam concentrate supply piping
is utilized in the bladder tank system, the foam and valves from the Bladder Tank to the ratio controller.
concentrate piping to the ratio controller must be Install water supply piping and valves to Bladder Tank
one(1) pipe size larger than standard concentrate and foam solution piping and valves from Bladder Tank
pipe size. Refer to Fig. 4-3 Ratio Controller Flow to the discharge devices.
Range and Piping Size Chart on page 4-5 for AR-
AFFF foam concentrate line sizes. CAUTION:
If installing strainers, flow meters or other
9. Install optional sight glass, if provided. See Sect. 2-5
components not described on the System Operating
for Sight Glass Installation procedures.
Drawing, friction loss allowances must be made for
these components when designing foam concentrate
CAUTION:
and water supply piping.
Alcohol type AFFF foam levels will not be accurately
indicated in the sight glass there-fore it is necessary to 16. Regarding only tanks with customer mounted ratio
determine a full condition by noting foam concentrate controller(s): The end user shall supply an isolation valve
flow from the Bladder Foam Concentrate Vent Valve at connection point “M”, Figure 2-1, for horizontal or
5, as descibed in the filling instructions in this manual. connection point “J”, Figure 2-2, for vertical bladder
It may be necessary to remove and clean the sight tanks.
glass and then re-install after checking the level.
17. Perform a Tank Bladder Integrity Test before filling the
10. If an automated Foam Concentrate Supply Valve No. bladder tank with foam concentrate. Refer to Chapter
1A will be used on the system, it must be installed along 10 for AF recommended procedures.
with a manual Foam Concentrate Supply Valve No. 1,
and it will normally be closed. 18. Test the Bladder Tank System before putting it into
service. See Sect. 2-7, Testing After Installation, for
11. Because of the various types and brands of automatic
proper installation testing procedures.
valves and actuators which may be used in a bladder
tank system, refer to the manufacturer’s installation
instructions when installing on the proportioning system.

06/18 2-3
INSTALLATION BLADDER TANK PROPORTIONING SYSTEM

2-5. Sight Glass Installation

NOTE: See Sight Glass Installation Illustration below. of split pipe clamp allows proper seating of sight glass
in Valve 8. Centerline of sight glass and Valve 8 is 4ʺ
1. Remove sight glass, split pipe clamp, threaded rod and
from Bladder Tank side.
(2) nuts from packaging, taking care not to damage the
glass or lose the mounting pieces. 4. Loosen closure screw and open split pipe clamp.
2. Mount threaded rod to split pipe clamp. Thread one nut 5. Apply a thread sealer to the sight glass connection.
onto threaded rod. Install the sight glass securely into Valve 8 and position
it in the split pipe clamps.
3. Mount threaded rod and split pipe clamp to channel
hanger on tank and thread second nut on threaded rod 6. Close split pipe clamp and tighten closure screw.
as shown on illustration.
7. Adjust mounting nuts so sight glass is in correct vertical
NOTE: Adjust mounting nuts so vertical alignment alignment.

SIGHT GLASS (OPTIONAL)

SIGHT
GLASS CHANNEL
SIGHT GLASS VALVE NO. 8 HANGER
(NORMAL POSITION-CLOSED)

THREADED ROD

CLOSURE
SCREW
SIGHT GLASS SUPPLY
VALVE NO. 9
(NORMAL POSITION-OPEN)
SPLIT
CONCENTRATE DRAIN/FILL PIPE MOUNTING NUTS
VALVE NO. 7 CLAMP
(NORMAL POSITION-CLOSED)

2-4 06/18
BLADDER TANK PROPORTIONING SYSTEM INSTALLATION

2-6. Start-Up Procedures

WARNING:
The customer shall be responsible to insure that the sprinklers or nozzles.
water supply pressure does not exceed the maximum
3. After flushing, remove all strainer baskets and clean.
rated working pressure of the pressure vessel (foam
Then reinstall the baskets.
concentrate tank). Refer to Fig. 2-1 Notes, Item 4 or to
the appropriate general arrangement drawing for your 4. Fill the Bladder Tank and foam concentrate piping with
particular tank(s) for the maximum working pressure foam concentrate using the concentrate filling procedure
of the pressure vessel. outlined in Chapter 3, Sect. 3-2 for Horizontal Tanks
and Sect. 3-3 for Vertical Tanks.
1. Hydrostatically test the water and foam solution piping
before placing the bladder tank into service. CAUTION:
Filling Instructions described in Chapter 3 must be
CAUTION: followed to prevent damage to the bladder.
The bladder tank must be completely isolated from
the water/foam solution piping (Close Valves 1 and 2) 5. Place all valves in their stand-by position. Refer to Fig.
during all hydrostatic testing to prevent damage to the 4-1 for Horizontal tanks or Fig. 4-2 for Vertical tanks,
System Operating Drawings with valve position chart.
internal bladder.
6. Proceed with full scale test as described in Sect. 2-7,
2. Flush the water lines and all foam solution lines. This
Testing After Installation.
should be done prior to installing any foam makers,

2-7. Testing After Installation


1. Before acceptance, all operating devices and equipment *Angus Fire Ranges of Acceptability
shall be tested for proper function. for
Foam Solution Strength
2. A full scale test should be run after the system is
installed and prior to acceptance of the system. The • Values for Proportioning Devices Manufactured
test run should include running water to each discharge Prior to July 1, 1995:
device to insure that proper pressures and flow rates
can be achieved and to insure there is no blockage. Foam Solution Concentration AF Standards
Then foam solution shall be run (1) - to the devices 3% 3.0 to 4.0%
protecting the greatest single hazard and (2) - to the 6% 5.0 to 7.0%
device with the lowest flow rate. The foam test(s) shall • Values for Proportioning Devices Manufactured
last a minimum of 1 minute (actual injection time) to After to July 1, 1995:
insure the proportioning system has stabilized before
taking samples. At this time, the quality of the foam Foam Solution Concentration AF Standards
shall be observed and the foam solution concentration 2% 2.0 to 2.6%
should be checked by refractive index or conductivity 3% 3.0 to 3.9%
method*. See NFPA 11 for detailed procedures. 6% 6.0 to 7.0%
3. After completion of acceptance tests, the system shall NOTE: AF standards conform to both NFPA and UL
be flushed and restored to operational condition. standards.

06/18 2-5
INSTALLATION BLADDER TANK PROPORTIONING SYSTEM

NOTE: CONC. VENT WILL ALSO BE USED


"K" FNPT WATER TO TOP OFF THE CONC. LEVEL. A FILL CUP
CONCENTRATE LEVEL INLET CONNECTION WILL BE PROVIDED WITH EACH TANK.
4 CHECK LABEL (CONTRACTOR P.O.C.)
AF LOGO 5
SIGHT GLASS
(OPTIONAL)
INSTALLATION
C INSTRUCTION EMERGENCY FOAM "H"
LABEL SERVICE LABEL

"D" BLADDER
REMOVAL
FLANGE
AF 1X3 LABEL CONTENTS LABEL
EQUIPMENT ID
C (TO BE APPLIED
8 IN FIELD) B "G"

A A

6
"J" B CL OF TANK TO
"P" "Q" FOAM CONC. SUPPLY
"L" CONTRACTOR P.O.C.
UL LABEL
"M" FNPT FOAM CONCENTRATE
SUPPLY CONNECTION OPERATING INSTRUCTIONS "A" "C"
(CONTRACTOR P.O.C.) 9
SEE NOTE 15 1" FNPT FOAM
7 CONCENTRATE DRAIN/FILL
"B"
SIGHT GLASS SIGHT GLASS "E" "B" "C"
(OPTIONAL) 7 (OPTIONAL)
TANK SHELL "F" DIA. HOLES
TYP. (8) PLACES
8
SIGHT
GLASS
(OPTIONAL) 7-3/4

9 9 7
8
DETAIL "A-A" DETAIL "B-B" 8-3/4

4
VALVE DESCRIPTION (102)
TYP. FILL FUNNEL
Valve No Description Normal Position
DETAIL "C-C" (TO BE SCREWED INTO VALVE NO. 5)
4 ............Tank Water Vent ........................... Closed
5 ............Concentrate Vent/Fill .................... Closed
6 ............Water Drain/Fill............................. Closed • Ball shutoff valve
7 ............Concentrate Drain/Fill .................. Closed • Split pipe clamp w/threaded rod
8 ............Sight Glass (Optional) .................. Closed 10. Fill Funnel and Optional Sight Glass Tube will be packed and
9 ............Sight Glass Supply (Optional) .........Open shipped separately.
11. Optional Sight Glass level check can not be performed with alcohol
NOTES FOR HORIZONTAL AND VERTICAL TANKS: type AFFF concentrates. Refer to the Operating & Maintenance
Manual for further instructions.
1. All weights and dimensions are approximate and may vary slightly.
12. Contents label will be supplied to customer by AF and applied by
2. Weights listed apply to empty tanks. customer to area provided.
3. Carbon steel ASME Code Section VIII tanks supplied as standard. 13. When designing a building to house bladder tanks, provisions must
4. All tanks are designed for 175 psi (12 Bar) working pressure. be made to remove the internal piping and bladder. These items
5. All tanks are finish painted OSHA Safety Red per AF Specification are the full length and height of tank.
ASI-06-008. 14. For non-standard or special tanks, refer to the specific general
6. All tanks supplied in accordance with AF Specification ASI-09-084. arrangement drawing for that tank for details.
7. Contractor P.O.C. refers to Contractor Point of Connection. 15. Horizontal Tanks: End user shall supply isolation valve at connection
8. All tank and valve openings will be plugged for shipping. point “M”. Vertical Tanks: End user shall supply isolation valve at
9. Optional Sight Glass Assembly includes: connection point “J”

• Polycarbonate sight glass tube, 1-1/2ʺ (38) O.D. open to 16. Refer to page 2-7 (Horizontal) or page 2-9 (Vertical) for Tank
atmosphere (vented cap) Dimension Chart.

FIGURE 2-1
General Arrangement - Horizontal Bladder Tank
with Fill Piping and Optional Sight Glass

2-6 06/18
Capacity Empty Weight

06/18
gal. (liters) ʺAʺ ʺBʺ ʺCʺ ʺDʺ ʺEʺ ʺFʺ ʺGʺ ʺHʺ ʺJʺ ʺKʺ ʺLʺ ʺMʺ ʺPʺ ʺQʺ lb (kg)
50 (189) 20 (508) 7 (178) 7/8 (22) 20 (508) 3 (76) 9/16 (14) 22 (559) 41-1/2 (1054) 14 (356) 2 (51) 55-1/2 (1410) 2 (51) 4 (103) 16-1/2 (419) 360 (163)
100 (379) 24 (610) 9 (229) 7/8 (22) 24 (610) 3 (76) 9/16 (14) 24 (610) 45-1/2 (1054) 22 (559) 2 (51) 72 (1828) 2 (51) 4 (103) 18-1/2 (470) 651 (295)
150 (568) 30 (762) 11 (279) 1-1/8 (29) 30 (762) 4 (102) 9/16 (14) 27 (686) 51-1/2 (1308) 36 (914) 2 (51) 71 (1803) 2 (51) 4 (103) 21-1/2 (546) 940 (426)
200 (757) 30 (762) 11 (279) 1-1/8 (29) 30 (762) 4 (102) 9/16 (14) 27 (686) 51-1/2 (1308) 34 (864) 2 (51) 89 (2261) 2 (51) 4 (103) 21-1/2 (546) 1137 (516)
300 (1136) 34 (864) 13 (330) 1-1/8 (29) 36 (914) 4 (102) 9/16 (14) 30 (762) 57-1/2 (1460) 36 (914) 2 (51) 93 (2362) 2 (51) 4 (103) 24-1/2 (622) 1554 (705)
400 (1514) 40 (1016) 15 (381) 1-3/8 (35) 42 (1067) 5 (127) 11/16 (17) 33 (838) 63-1/2 (1613) 50 (1270) 2 (51) 93 (2362) 2 (51) 4 (103) 27-1/2 (699) 1870 (848)
500 (1893) 40 (1016) 15 (381) 1-3/8 (35) 42 (1067) 5 (127) 11/16 (17) 33 (838) 63-1/2 (1613) 48 (1219) 2 (51) 112 (2845) 3 (76) 4 (103) 27-1/2 (699) 2130 (966)
600 (2271) 40 (1016) 15 (381) 1-3/8 (35) 42 (1067) 5 (127) 11/16 (17) 33 (838) 63-1/2 (1613) 60 (1524) 3 (76) 131 (3327) 3 (76) 4 (103) 27-1/2 (699) 2237 (1015)
HORIZONTAL BLADDER TANK

700 (2650) 44 (1118) 17 (432) 1-3/8 (35) 48 (1219) 5 (127) 11/16 (17) 40 (1016) 73-1/2 (1867) 50 (1270) 3 (76) 119 (3023) 3 (76) 8 (203) 30-1/2 (775) 2644 (1199)
800 (3028) 44 (1118) 17 (432) 1-3/8 (35) 48 (1219) 5 (127) 11/16 (17) 40 (1016) 73-1/2 (1867) 60 (1524) 3 (76) 134 (3404) 3 (76) 8 (203) 30-1/2 (775) 3298 (1496)
900 (3407) 44 (1118) 17 (432) 1-3/8 (35) 48 (1219) 5 (127) 11/16 (17) 40 (1016) 73-1/2 (1867) 70 (1778) 3 (76) 148 (3759) 3 (76) 8 (203) 30-1/2 (775) 3655 (1658)
1000 (3785) 44 (1118) 17 (432) 1-3/8 (35) 48 (1219) 5 (127) 11/16 (17) 40 (1016) 73-1/2 (1867) 94 (2388) 3 (76) 163 (4140) 3 (76) 8 (203) 30-1/2 (775) 3872 (1756)
1100 (4164) 44 (1118) 17 (432) 1-3/8 (35) 48 (1219) 5 (127) 11/16 (17) 40 (1016) 73-1/2 (1867) 100 (2540) 3 (76) 177 (4496) 3 (76) 8 (203) 30-1/2 (775) 4256 (1930)
1200 (4542) 54 (1372) 22 (559) 1-3/4 (44) 60 (1524) 6 (152) 11/16 (17) 46 (1168) 85-1/2 (2172) 58 (1473) 3 (76) 131 (3327) 3 (76) 8 (203) 36-1/2 (927) 4323 (1961)
1300 (4921) 54 (1372) 22 (559) 1-3/4 (44) 60 (1524) 6 (152) 11/16 (17) 46 (1168) 85-1/2 (2172) 60 (1524) 3 (76) 141 (3581) 3 (76) 8 (203) 36-1/2 (927) 4626 (2098)
1400 (5300) 54 (1372) 22 (559) 1-3/4 (44) 60 (1524) 6 (152) 11/16 (17) 46 (1168) 85-1/2 (2172) 76 (1930) 3 (76) 151 (3835) 3 (76) 8 (203) 36-1/2 (927) 4913 (2228)
1500 (5678) 54 (1372) 22 (559) 1-3/4 (44) 60 (1524) 6 (152) 11/16 (17) 46 (1168) 85-1/2 (2172) 80 (2032) 3 (76) 159 (4039) 3 (76) 6 (152) 36-1/2 (927) 5294 (2401)
1600 (6057) 64 (1626) 28 (711) 2-3/4 (70) 72 (1829) 8 (203) 1-1/16 (27) 50 (1270) 95-1/2 (2426) 44 (1118) 3 (76) 125 (3175) 3 (76) 6 (152) 42-1/2 (1080) 4691 (2128)
1700 (6435) 64 (1626) 28 (711) 2-3/4 (70) 72 (1829) 8 (203) 1-1/16 (27) 50 (1270) 95-1/2 (2426) 50 (1270) 3 (76) 131 (3327) 3 (76) 6 (152) 42-1/2 (1080) 4873 (2210)
1800 (6814) 64 (1626) 28 (711) 2-3/4 (70) 72 (1829) 8 (203) 1-1/16 (27) 50 (1270) 95-1/2 (2426) 56 (1422) 3 (76) 138 (3505) 3 (76) 6 (152) 42-1/2 (1080) 5054 (2292)
1900 (7192) 64 (1626) 28 (711) 2-3/4 (70) 72 (1829) 8 (203) 1-1/16 (27) 50 (1270) 95-1/2 (2426) 60 (1524) 3 (76) 144 (3658) 3 (76) 6 (152) 42-1/2 (1080) 5279 (2395)
2000 (7571) 64 (1626) 28 (711) 2-3/4 (70) 72 (1829) 8 (203) 1-1/16 (27) 50 (1270) 95-1/2 (2426) 70 (1778) 3 (76) 151 (3835) 3 (76) 6 (152) 42-1/2 (1080) 5504 (2497)
2100 (7949) 64 (1626) 28 (711) 2-3/4 (70) 72 (1829) 8 (203) 1-1/16 (27) 50 (1270) 95-1/2 (2426) 76 (1930) 3 (76) 157 (3988) 3 (76) 6 (152) 42-1/2 (1080) 5696 (3584)
2200 (8328) 64 (1626) 28 (711) 2-3/4 (70) 72 (1829) 8 (203) 1-1/16 (27) 50 (1270) 95-1/2 (2426) 80 (2032) 3 (76) 164 (4166) 3 (76) 6 (152) 42-1/2 (1080) 5887 (2670)
2300 (8706) 64 (1626) 28 (711) 2-3/4 (70) 72 (1829) 8 (203) 1-1/16 (27) 50 (1270) 95-1/2 (2426) 80 (2032) 3 (76) 170 (4318) 3 (76) 6 (152) 42-1/2 (1080) 6093 (2764)
2400 (9085) 64 (1626) 28 (711) 2-3/4 (70) 72 (1829) 8 (203) 1-1/16 (27) 50 (1270) 95-1/2 (2426) 80 (2032) 3 (76) 177 (4496) 3 (76) 6 (152) 42-1/2 (1080) 6299 (2857)
2500 (9464) 64 (1626) 28 (711) 2-3/4 (70) 72 (1829) 8 (203) 1-1/16 (27) 50 (1270) 95-1/2 (2426) 100 (2540) 3 (76) 183 (4648) 3 (76) 6 (152) 42-1/2 (1080) 6499 (2948)
2600 (9842) 64 (1626) 28 (711) 2-3/4 (70) 72 (1829) 8 (203) 1-1/16 (27) 50 (1270) 95-1/2 (2426) 100 (2540) 3 (76) 189 (4801) 3 (76) 6 (152) 42-1/2 (1080) 6699 (3039)
2700 (10221) 64 (1626) 28 (711) 2-3/4 (70) 72 (1829) 8 (203) 1-1/16 (27) 50 (1270) 95-1/2 (2426) 100 (2540) 3 (76) 196 (4978) 3 (76) 6 (152) 42-1/2 (1080) 6889 (3125)
2800 (10599) 64 (1626) 28 (711) 2-3/4 (70) 72 (1829) 8 (203) 1-1/16 (27) 50 (1270) 95-1/2 (2426) 100 (2540) 3 (76) 202 (5131) 3 (76) 6 (152) 42-1/2 (1080) 7078 (3211)
2900 (10978) 64 (1626) 28 (711) 2-3/4 (70) 72 (1829) 8 (203) 1-1/16 (27) 50 (1270) 95-1/2 (2426) 100 (2540) 3 (76) 209 (5309) 3 (76) 6 (152) 42-1/2 (1080) 7278 (3301)
3000 (11356) 64 (1626) 28 (711) 2-3/4 (70) 72 (1829) 8 (203) 1-1/16 (27) 50 (1270) 95-1/2 (2426) 120 (3048) 3 (76) 215 (5461) 3 (76) 6 (152) 42-1/2 (1080) 7478 (3392)
3100 (11735) 64 (1626) 28 (711) 2-3/4 (70) 72 (1829) 8 (203) 1-1/16 (27) 50 (1270) 95-1/2 (2426) 120 (3048) 3 (76) 222 (5639) 3 (76) 6 (152) 42-1/2 (1080) 7679 (3483)
3200 (12113) 64 (1626) 28 (711) 2-3/4 (70) 72 (1829) 8 (203) 1-1/16 (27) 50 (1270) 95-1/2 (2426) 120 (3048) 3 (76) 228 (5791) 3 (76) 6 (152) 42-1/2 (1080) 7880 (3574)
3300 (12492) 64 (1626) 28 (711) 2-3/4 (70) 72 (1829) 8 (203) 1-1/16 (27) 50 (1270) 95-1/2 (2426) 120 (3048) 3 (76) 234 (5944) 3 (76) 6 (152) 42-1/2 (1080) 8100 (3674)
3400 (12870) 64 (1626) 28 (711) 2-3/4 (70) 72 (1829) 8 (203) 1-1/16 (27) 50 (1270) 95-1/2 (2426) 120 (3048) 3 (76) 241 (6121) 3 (76) 6 (152) 42-1/2 (1080) 8300 (3765)
3500 (13249) 64 (1626) 28 (711) 2-3/4 (70) 72 (1829) 8 (203) 1-1/16 (27) 50 (1270) 95-1/2 (2426) 120 (3048) 3 (76) 247 (6274) 3 (76) 6 (152) 42-1/2 (1080) 8500 (3856)
3600 (13627) 64 (1626) 28 (711) 2-3/4 (70) 72 (1829) 8 (203) 1-1/16 (27) 50 (1270) 95-1/2 (2426) 120 (3048) 3 (76) 254 (6452) 3 (76) 6 (152) 42-1/2 (1080) 8700 (3946)
3700 (14006) 64 (1626) 28 (711) 2-3/4 (70) 72 (1829) 8 (203) 1-1/16 (27) 50 (1270) 95-1/2 (2426) 120 (3048) 3 (76) 260 (6604) 3 (76) 6 (152) 42-1/2 (1080) 8900 (4037)
3800 (14385) 64 (1626) 28 (711) 2-3/4 (70) 72 (1829) 8 (203) 1-1/16 (27) 50 (1270) 95-1/2 (2426) 120 (3048) 3 (76) 267 (6782) 3 (76) 6 (152) 42-1/2 (1080) 9100 (4128)
3900 (14763) 64 (1626) 28 (711) 2-3/4 (70) 72 (1829) 8 (203) 1-1/16 (27) 50 (1270) 95-1/2 (2426) 120 (3048) 3 (76) 273 (6934) 3 (76) 6 (152) 42-1/2 (1080) 9300 (4218)
4000 (15142) 64 (1626) 28 (711) 2-3/4 (70) 72 (1829) 8 (203) 1-1/16 (27) 50 (1270) 95-1/2 (2426) 120 (3048) 3 (76) 280 (7112) 3 (76) 6 (152) 42-1/2 (1080) 9500 (4309)

HORIZONTAL BLADDER TANK NOTE: All dimensions are in inches (millimeters).


CAPACITY, DIMENSIONS & WEIGHT CHART

2-7
CAPACITY, DIMENSIONS & WEIGHT CHART
INSTALLATION BLADDER TANK PROPORTIONING SYSTEM

"A" NOTE: VENT VALVE WILL ALSO BE USED TO ‫ފ‬66


5 TOP OFF THE CONCENTRATE LEVEL. A FILL VALVE
CUPWILL BE PROVIDED WITH EACH TANK
4
LIFTING
LUG
"F" FNPT WATER
INLET CONNECTION C
(CONTRACTOR P.O.C.) INSTALLATION CONTENTS LABEL
INSTRUCTION (TO BE APPLIED IN
C FIELD)
LABEL
AF LOGO OPERATING
INSTRUCTIONS
CONCENTRATE LEVEL
CHECK LABEL
UL LABEL
"K"
EMERGENCY AF 1X3 LABEL
FOAM SERVICE "B" EQUIPMENT ID
LABEL
SIGHT GLASS
ASSEMBLY
"C"
(OPTIONAL)

6 8
A A
D D
1" FNPT FOAM B "G"
"J" FNPT CONCENTRATE "H"
FOAM CONCENTRATE 9 7 DRAIN/FILL CONTRACTOR
SUPPLY CONNECTION P.O.C.
(CONTRACTOR P.O.C.)
SEE NOTE 15
90°
TYP.
SIGHT GLASS
(OPTIONAL) 7
45°
TYP.

‫ (ފ‬DIA. HOLE
4" TYP. TYP. 4 PLACES

9 DETAIL "C-C" ‫ 'ފ‬DIA.


8 BOLT CIRCLE
DETAIL "A-A"
6(&7,21‫ފ''ފ‬
SIGHT GLASS FLOOR ANCHORING DETAIL
7-3/4
(OPTIONAL)

8
8-3/4 VALVE DESCRIPTION
Valve No Description Normal Position
4 ............Tank Water Vent ........................... Closed
5 ............Concentrate Vent/Fill .................... Closed
9 7 FILL FUNNEL
6 ............Water Drain/Fill............................. Closed
DETAIL "B-B" (TO BE SCREWED INTO VALVE NO. 5)
7 ............Concentrate Drain/Fill .................. Closed
SEE NOTE 10
8 ............Sight Glass (Optional) .................. Closed
9 ............Sight Glass Supply (Optional) .........Open

FIGURE 2-2
General Arrangement - Vertical Bladder Tank
with Fill Piping and Optional Sight Glass

2-8 06/18
Empty

06/18
Capacity Weight
gal. (liters) ʺAʺ ʺBʺ ʺCʺ ʺDʺ ʺEʺ ʺFʺ ʺGʺ ʺHʺ ʺJʺ ʺKʺ lb (kg)
25 (95) 20 (508) 49 (1245) 29 (737) 22-3/4 (578) 9/16 (14) 2 (51) 15-1/4 (387) 4 (102) 2 (51) 36 (914) 150 (68)
36 (136) 24 (610) 50 (1270) 25 (635) 22-3/4 (578) 9/16 (14) 2 (51) 17-1/4 (438) 4 (102) 2 (51) 37 (940) 220 (100)
50 (189) 24 (610) 58 (1473) 33 (838) 22-3/4 (578) 9/16 (14) 2 (51) 17-1/4 (438) 4 (102) 2 (51) 45 (1143) 307 (139)
100 (379) 24 (610) 87 (2210) 62 (1575) 22-3/4 (578) 9/16 (14) 2 (51) 17-1/4 (438) 4 (102) 2 (51) 74 (1880) 465 (211)
150 (568) 30 (762) 86 (2184) 59 (1499) 27-3/4 (705) 9/16 (14) 2 (51) 20-1/4 (514) 4 (102) 2 (51) 73 (1854) 620 (281)
VERTICAL BLADDER TANK

200 (757) 30 (762) 104 (2642) 77 (1956) 27-3/4 (705) 9/16 (14) 2 (51) 20-1/4 (514) 4 (102) 2 (51) 91 (2311) 757 (343)
300 (1136) 36 (914) 108 (2743) 80 (2032) 32-3/4 (832) 9/16 (14) 2 (51) 23-1/4 (591) 4 (102) 2 (51) 95 (2413) 1101 (499)
400 (1514) 48 (1219) 91 (2311) 59-1/2 (1511) 41-1/2 (1054) 11/16 (17) 2 (51) 29-1/4 (743) 4 (102) 2 (51) 78 (1981) 1504 (682)
500 (1892) 48 (1219) 105 (2667) 73-1/2 (1867) 41-1/2 (1054) 11/16 (17) 2 (51) 29-1/4 (743) 4 (102) 2 (51) 92 (2337) 1560 (709)
600 (2271) 48 (1219) 120 (3048) 88-1/2 (2248) 41-1/2 (1054) 11/16 (17) 3 (76) 29-1/4 (743) 4 (102) 2 (51) 107 (2718) 1669 (757)
700 (2649) 48 (1219) 134 (3404) 102-1/2 (2604) 41-1/2 (1054) 11/16 (17) 3 (76) 29-1/4 (743) 4 (102) 3 (76) 121 (3073) 1799 (816)
750 (2839) 48 (1219) 142 (3607) 110-1/2 (2807) 51-1/2 (1308) 11/16 (17) 3 (76) 29-1/4 (743) 8 (203) 3 (76) 125 (3175) 1900 (862)
800 (3028) 60 (1524) 113 (2870) 78-1/2 (1994) 51-1/2 (1308) 11/16 (17) 3 (76) 35-3/4 (908) 8 (203) 3 (76) 96 (2438) 2004 (909)
900 (3407) 60 (1524) 122 (3099) 87-1/2 (2223) 51-1/2 (1308) 11/16 (17) 3 (76) 35-3/4 (908) 8 (203) 3 (76) 105 (2667) 2334 (1059)
1000 (3785) 60 (1524) 132 (3353) 97-1/2 (2477) 51-1/2 (1308) 13/16 (21) 3 (76) 35-3/4 (908) 8 (203) 3 (76) 115 (2921) 2730 (1238)
1100 (4164) 60 (1524) 141 (3581) 106-1/2 (2705) 51-1/2 (1308) 13/16 (21) 3 (76) 35-3/4 (908) 8 (203) 3 (76) 124 (3150) 3823 (1734)
1200 (4542) 60 (1524) 150 (3810) 115-1/2 (2934) 51-1/2 (1308) 13/16 (21) 3 (76) 35-3/4 (908) 8 (203) 3 (76) 133 (3378) 3221 (1461)
1300 (4921) 60 (1524) 160 (4064) 125-1/2 (3188) 51-1/2 (1308) 13/16 (21) 3 (76) 35-3/4 (908) 8 (203) 3 (76) 143 (3632) 3340 (1515)
1400 (5300) 60 (1524) 169 (4293) 134-1/2 (3416) 51-1/2 (1308) 13/16 (21) 3 (76) 35-3/4 (908) 8 (203) 3 (76) 152 (3861) 3459 (1569)
1500 (5678) 60 (1524) 178 (4521) 143-1/2 (3645) 51-1/2 (1308) 13/16 (21) 3 (76) 35-3/4 (908) 8 (203) 3 (76) 161 (4089) 3510 (1592)
1600 (6057) 72 (1829) 144 (3658) 109-1/2 (2781) 57-1/2 (1461) 13/16 (21) 3 (76) 41-3/4 (1060) 8 (203) 3 (76) 127 (3226) 3600 (1633)
1700 (6425) 72 (1829) 150 (3810) 115-1/2 (2934) 57-1/2 (1461) 13/16 (21) 3 (76) 41-3/4 (1060) 8 (203) 3 (76) 133 (3378) 3725 (1690)
1800 (6814) 72 (1829) 157 (3988) 122-1/2 (3112) 57-1/2 (1461) 13/16 (21) 3 (76) 41-3/4 (1060) 8 (203) 3 (76) 140 (3556) 3850 (1746)
1900 (7192) 72 (1829) 163 (4140) 128-1/2 (3264) 57-1/2 (1461) 13/16 (21) 3 (76) 41-3/4 (1060) 8 (203) 3 (76) 146 (3708) 3975 (1803)
2000 (7571) 72 (1829) 170 (4318) 135-1/2 (3442) 57-1/2 (1461) 13/16 (21) 3 (76) 41-3/4 (1060) 8 (203) 3 (76) 153 (3886) 4100 (1860)
2100 (7949) 72 (1829) 176 (4470) 141-1/2 (3594) 57-1/2 (1461) 13/16 (21) 3 (76) 41-3/4 (1060) 8 (203) 3 (76) 159 (4039) 4225 (1916)
2200 (8328) 72 (1829) 183 (4648) 148-1/2 (3772) 57-1/2 (1461) 13/16 (21) 3 (76) 41-3/4 (1060) 8 (203) 3 (76) 166 (4216) 4350 (1973)
2300 (8706) 72 (1829) 189 (4801) 154-1/2 (3924) 57-1/2 (1461) 13/16 (21) 3 (76) 41-3/4 (1060) 8 (203) 3 (76) 172 (4369) 4475 (2030)
2400 (9085) 72 (1829) 196 (4978) 161-1/2 (4102) 57-1/2 (1461) 13/16 (21) 3 (76) 41-3/4 (1060) 8 (203) 3 (76) 179 (4547) 4600 (2087)

VERTICAL BLADDER TANK NOTE: All dimensions are in inches (millimeters).


CAPACITY, DIMENSIONS & WEIGHT CHART
CAPACITY, DIMENSIONS & WEIGHT CHART

2-9
BLADDER TANK PROPORTIONING SYSTEM FILLING PROCEDURES

CHAPTER 3
CONCENTRATEFILLINGPROCEDUREFORBLADDERTANKS

WARNING:
Incorrect filling procedures can damage the internal bladder. Angus Fire products have a limited warranty
for one year from date of purchase.
NOTE: AF recommends the bladder tank be kept completely full at all times to insure maximum fire fighting
capability of the system. The bladder tank should be refilled or topped off any time the system has been activated
and foam concentrate has been discharged from the tank.
AF recommends that the bladder tank be filled using a motor driven fill pump, however, as an alternative, a hand
operated fill pump can be used in place of the motor driven type. Initial fill and empty bladder tank fill procedures
are identical for both motor driven and hand pumping methods. The motor driven pump fill/refill method only is
to be used when filling the bladder tank with AR-AFFF foam concentrates.

3-1. Introduction
The following describes the recommended method for filling 1. An open top 55 gallon drum (208 L), or appropriate
bladder tanks. To assure that the bladder is positioned so as sized container (approx. 3 ft. high x 2 ft. dia.), to be
to be fully supported by the tank shell, it is imperative that completely filled with clean fresh water.
this procedure be followed.
2. An appropriate length (20 ft.) of 1ʺ clear air/foam
The fill procedure is divided into two sections: The first concentrate vent hose with a male NPT swivel for
section (3-2.) covers Horizontal Bladder Tanks and the connection to Foam Concentrate Vent Valve 5, and a
second section (3-3.) covers Vertical Bladder Tanks. weighted end piece to hold and maintain the clear hose
at the bottom of the 55 gal. drum. This length of clear
Each fill section is further divided into:
hose connects Valve 5 to the 55 gallon drum allowing
A. Initial Fill or Empty Bladder Tank Fill. bladder air discharge thru the water in the drum, and
also allows foam concentrate discharge indicating that
B. Refilling or Topping-Off using motor driven foam the bladder is completely filled.
concentrate pump because of: (1) the type of foam
concentrate, i.e., an AR-AFFF, or (2) the volume to be 3.* A Bladder Tank Fill Manifold which includes the
replenished. required valves, fittings and pressure gauge. See Fill
Manifold Illustration, page 3-2, for parts and description.
C. Topping-Off by hand pouring foam concentrate from
containers directly into the fill funnel. NOTE: AF recommends a pressure gauge in the
manifold type setup as an additional safeguard when
CAUTION: filling. If unreasonably high pressure is indicated on the
The method described in Section C can be used only when gauge (10 psi or higher), shutdown the fill operation and
less than 30% of tank volume needs to be replenished check the setup to see that it conforms to AF instructions,
and must not be used when topping-off with AR-AFFF and to insure that all valves are in the correct position
foam concentrates due to the viscosity characteristics at that point in the procedure.
of alcohol type AFFF agents. 4.* A clean air or nitrogen supply (25 psi to 35 psi
D. Topping-Off by using the hand pumping method. capacity) along with approximately 25 ft. of heavy duty
compressor hose and fittings required for connection to
The following equipment is required for proper bladder tank the 1/4ʺ NPT valve on the Bladder Tank Fill Manifold.
fill in cases of initial fill/empty tank or large volume refill:

06/18 3-1
FILLING PROCEDURES BLADDER TANK PROPORTIONING SYSTEM

5. A foam concentrate fill pump. Also, the hose and NOTE: * indicates a complete Bladder Tank Electric Fill
adapters needed to connect the pump with the fill Pump Kit available from AF. Kit includes all necessary
manifold and hose, adapters and dip tube needed to hose, tubing, fittings, fill manifold, electric fill pump and
transfer the foam concentrate from its container to the air compressor (optional item).
pump. (* All equipment in item 5, including a motor
• Complete kit w/compressor (Items 3, 4, 5 & 6) - Part
driven foam concentrate pump, positive displacement,
number: 1221-0100-2.
rated 20 gpm @ 20 psi., is available in an AF Electric
Fill Pump Kit, NF part number:1221-0100-4) • Complete kit w/o compressor (Items 3, 5 & 6) - Part
number: 1221-0100-3.
6.* 2 lengths of rubber garden hose (3/4ʺ x 25 ft.) which:
• Electric Fill Pump Kit only (Item 5) - Part number:
a. Are used to add water, when required, to the shell
1221-0100-4.
side of the bladder thru the Water Drain/Fill Valve
No. 6. Contact AF Sales Department for further information.
b. Allows water discharged from the Tank Water Vent
Valve 4 to be directed to a drain. CAUTION:
Before starting the Bladder Tank Fill Procedure, carefully
Refer to Valve Description and Position Chart, Fig. 4-1 for review the valve description chart and diagrams. Read
Horizontal Tanks or Fig. 4-2 for Vertical Tanks for valve all fill instructions before attempting Bladder Tank fill.
numbers, description and normal valve stand-by position. Failure to follow these filling instructions may result in
a ruptured internal bladder.

Bladder Tank Fill Manifold

Pressure Gauge
0 - 60 PSI

7
6 4
3 1 3
Connection
To Concentrate/Water
Foam Concentrate Drain/Fill Shutoff ValveI
&
Water Drain/Fill Valve

3 6
2 8

9 5

Air Supply
Shutoff Valve

Item No. Description Quantity


1 ...........................Pipe Cross, Std MI, 1ʺ............................................................... 1
2 ...........................Pipe Union, Std. MI, 1ʺ ............................................................. 1
3 ...........................Pipe Nipple, Std Stl, 1ʺ x 2ʺ ...................................................... 3
4 ...........................Ball Valve, 1ʺ Brass Full Port ................................................... 1
5 ...........................Ball Valve, 1/4ʺ Brass Full Port ................................................ 1
6 ...........................Pipe Bushing, Hex Std MI, 1/4 x 1 ........................................... 2
7 ...........................Pressure Gauge, 2ʺ 0-60 psi, 1/4ʺ MNPT Bot. Conn. ............... 1
8 ...........................Pipe Nipple, X-Hvy Stl, 1/4 x 1 Close ...................................... 1
9 ...........................Pipe Plug, Std MI, 1/4ʺ ............................................................. 1

3-2 06/18
BLADDER TANK PROPORTIONING SYSTEM HORIZONTAL BLADDER TANK FILLING PROCEDURES

3-2. Horizontal Bladder Tank Filling Instructions


A. Initial Fill or Empty Bladder Tank Fill

CAUTION: Be sure all valves are in their normal stand-by position. Refer
A Bladder Integrity Test must be performed prior to to System Operating Drawing Fig. 4-1, Horizontal Bladder
initial fill or empty tank fill. See Chapter 10 for Bladder Tanks, for Normal Stand-By Valve Position Chart and valve
Integrity instructions. location. See Figures 3-1 and 3-2 for set-up illustrations.

AIR/FOAM CONCENTRATE VENT HOSE

5 2
4
BLADDER SIGHT GLASS
AIR DISCHARGE (OPTIONAL)
55 GAL. DRUM
THRU WATER
FILLED WITH
IN DRUM
WATER AIR

1A

9 7
1

OVERFLOW TUBE 6
TO DRAIN
(OPTIONAL) 8

0 - 60 PSI
PRESSURE GAUGE
BLADDER FILLED CONCENTRATE/WATER
WITH AIR SHUTOFF VALVE
(CLOSED)
AIR
AIR SUPPLY SHUTOFF VALVE (OPEN)

NITROGEN
OR
COMPRESSED AIR
SUPPLY FILL MANIFOLD
END VIEW

FIGURE 3-1 BLADDER FILLED WITH AIR


1. Close Valve 2. Be sure Valve 1, or 1A if appropriate, is is closed. Connect the air supply to the fill manifold.
closed. Connect the air/foam concentrate vent hose to Open Valve 5. Open the Air Supply Shutoff Valve.
the Bladder Foam Concentrate Vent Valve 5. Fill the 55 Start the air source, at a pressure between 5-10 psi, and
gallon drum completely with water and place the vent slowly open Valve 7. The bladder will begin to fill with
hose discharge end at the bottom of the drum. The vent air. See Figure 3-1.
hose must be positioned and maintained at the bottom
4. The bladder is filled with air when air bubbles are
of the drum using a weighted device. Attach one end
expelled from the vent hose at the bottom of the drum.
of overflow hose to Valve 4 and place the other end of
Let the vent hose expel air for approximately 30 seconds
the hose into a drain or container.
to insure complete inflation of the bladder.
2. If desired, attach a drain hose to Valve 6 and run it to
5. Close the manifold Air Supply Shutoff Valve and Valve
a drain or drain area. Open the Water Drain/Fill Valve
7. Shutdown and disconnect air supply from the fill
6 and the Tank Water Vent Valve 4.
manifold.
3. Attach the fill manifold to Foam Concentrate Drain/ Fill
Valve 7. Make sure the Concentrate/Water Shutoff Valve

06/18 3-3
HORIZONTAL BLADDER TANK FILLING PROCEDURES BLADDER TANK PROPORTIONING SYSTEM

6. Connect the foam concentrate fill pump to the fill indicate a full bladder. Continue filling until liquid
manifold Concentrate/Water Shutoff Valve. Connect foam concentrate is detected.
the pump to the foam concentrate source.
CAUTION:
7. Open the Concentrate/Water Shutoff Valve. Start
Normally the actual capacity of a bladder tank
pumping foam concentrate and slowly open Valve 7.
will exceed the nominal capacity listed on the tank.
Be sure to start pumping then open Valve 7. Fill bladder
Therefore, it is recommended to continue filling until
at a pressure between 5-10 psi. See Figure 3-2.
foam concentrate is detected coming from Valve 5
and not until nominal capacity is reached. If the
CAUTION:
tank is not filled to capacity with foam concentrate,
Make certain that vent hose remains securely the remaining area of the tank shall be filled with
positioned at bottom of 55 gallon drum. water until all air has been vented from the tank.
NOTE: Air bubbles will be expelled thru the vent 9. Close Valve 7. Remove the fill manifold.
hose and drum as foam concentrate displaces the air
and fills the bladder. NOTE: Flush the fill manifold and foam concentrate
fill pump (following manufacturer’s instructions) after
NOTE: If appropriate, when the bladder is almost full filling bladder tank.
reduce the foam concentrate fill rate.
10. If the system is not equipped with a sight glass level
8. Continue filling until foam concentrate is seen in the indicator, return all valves to normal stand-by positions
clear vent hose or is detected coming from the hose as shown on the System Operating Drawing Fig. 4-1.
discharge end. Record date of refill/top-off and notify appropriate
personnel that system is back in service.
CAUTION:
Foam concentrate bubbles may be detected in the 11. If the system is equipped with a sight glass level indicator,
vent hose or at the discharge end of the hose when refer to Section 3-4, Procedures for Checking Foam
nearing bladder capacity. These bubbles do not Concentrate Level.

AIR/FOAM CONCENTRATE VENT HOSE

AIR BUBBLES
THEN LIQUID 5 2
4
FOAM CONCENTRATE SIGHT GLASS
DISCHARGE (OPTIONAL)
55 GAL. DRUM THRU WATER
FILLED WITH
WATER
IN DRUM AIR

FOAM 1A
CONCENTRATE
9 7
1

OVERFLOW TUBE 6
TO DRAIN
(OPTIONAL) 8
0 - 60 PSI
BLADDER FILLING PRESSURE GAUGE
WITH CONCENTRATE/WATER SHUTOFF VALVE
FOAM CONCENTRATE. (OPEN)
AIR BLADDER AIR VENTED
FOAM CONCENTRATE SUPPLY
THRU VALVE 5
FOAM TO FILL PUMP

CONCENTRATE
AIR SUPPLY SHUTOFF VALVE
(CLOSED) FILL MANIFOLD

END VIEW FIGURE 3-2 BLADDER FILLING WITH


FOAM CONCENTRATE
3-4 06/18
BLADDER TANK PROPORTIONING SYSTEM HORIZONTAL BLADDER TANK FILLING PROCEDURES

B. Refilling or Topping Off Using Motor Driven Foam Concentrate Pump

NOTE: The following procedure assumes that the system 4. Open the Concentrate/Water Shutoff Valve. Start the
has been operated, and there is some foam concentrate in foam concentrate fill pump and slowly open Valve 7.
the bladder and water occupies the remaining area in the Be sure to start the pump then open Valve 7.
tank shell. It is also assumed that the bladder is leak free
and in good condition. If the system is equipped with a sight 5. Fill the bladder until foam concentrate is discharged from
glass level indicator, refer to Section 3-4, Procedures for Valve 5 and no water is being discharged from Valve
Checking Foam Concentrate Level. 4. At this time, open Valve 6 and drain any remaining
water from the tank shell.
CAUTION:
6. Close the Concentrate/Water Shutoff Valve and shut
When topping off, make sure foam concentrate fill pump
down the foam concentrate fill pump.
does not exceed the water venting (discharge) capability of
Valve 4. Throttle thru Valve 7, or if using a fill manifold, 7. Return all tank valves to their normal stand-by position.
use the Concentrate/Water Shutoff Valve. Refer to System Operating Drawing Fig. 4-1, Horizontal
Bladder Tanks, for Normal Stand-By Valve Position
NOTE: Be sure all valves are in their normal standby
Chart and valve location.
position. Refer to System Operating Drawing Fig. 4-1,
Horizontal Bladder Tanks, for Normal Stand-By Valve 8. Disconnect foam concentrate fill pump at the fill
Position Chart and valve location. manifold and flush the pump following manufacturer’s
instructions. Remove the fill manifold from Valve 7.
1. Close Valve 1, 1A and 2. Attach the fill manifold to the
Thoroughly flush fill manifold.
Foam Concentrate Drain/Fill Valve. Make sure that the
Air Supply Shutoff Valve is closed. Attach one end of 9. If the system is not equipped with a sight glass level
overflow tubing to Valve 4 and place other end of hose indicator, return all valves to normal stand-by positions
into a drain or container. See Figure 3-3 below. as shown on the System Operating Drawing Fig. 4-1.
Record date of refill/top-off and notify appropriate
2. Connect the foam concentrate fill pump to the fill
personnel that system is back in service.
manifold Concentrate/Water Shutoff Valve. Connect
the pump to the foam concentrate source. 10. If the system is equipped with a sight glass level indicator,
refer to Section 3-4, Procedures for Checking Foam
3. If desired, attach a drain hose to Valve 6 and run it to
Concentrate Level.
a drain or drain area. Open Water Vent Valve 4. Open
Bladder Foam Concentrate Vent Valve 5.

NOTE: 4 5 2
Quantity of foam concentrate and water shown
are for illustration purposes only. Actual amount SIGHT GLASS
of foam concentrate/water will vary depending (OPTIONAL)
on individual system circumstances.
WATER
SHELL WATER
OVERFLOW TUBE
TO DRAIN FOAM
1A
CONCENTRATE
9 7
1

WATER IN SHELL- (OPTIONAL) 8


A QUANTITY OF
UNDISCHARGED 0 - 60 PSI
FOAM CONCENTRATE PRESSURE GAUGE
IN BLADDER CONCENTRATE/WATER SHUTOFF VALVE
(OPEN)
FOAM
FOAM CONCENTRATE SUPPLY
CONCENTRATE TO FILL PUMP

AIR SUPPLY SHUTOFF VALVE


(CLOSED)
FILL MANIFOLD

FIGURE 3-3 REFILLING OR TOPPING-OFF


06/18 3-5
HORIZONTAL BLADDER TANK FILLING PROCEDURES BLADDER TANK PROPORTIONING SYSTEM

C. Topping-Off Using Hand Pouring Method

CAUTION: WARNING:
To be used only when less than 30% of tank volume needs The Bladder Tank may be under pressure when
to be replenished. Do not use this method for empty tanks opening Valves 4 and 5. Do not put face or body in
or when topping-off with AR-AFFF foam concentrate. front of valves until pressure has been vented.
NOTE: Be sure all valves are in their normal stand-by 5. Hand pour foam concentrate into fill funnel. Fill tank
position. Refer to System Operating Drawing, Fig. 4-1 to capacity.
for Horizontal Bladder Tanks or Fig. 4-2, Vertical Bladder
NOTE: Foam concentrate must be poured into the fill
Tanks, for Normal Stand-By Valve Position Chart and valve
funnel slowly. The fill funnel must be kept full at all
location.
times to prevent air from entering fill connection and
1. See Figure 3-4. Attach fill funnel to Valve 5. causing frothing of the foam concentrate.
2. If desired, attach a drain hose to Valve 6 and run it to a 6. If the system is not equipped with a sight glass level
drain or drain area. Open Valve 6 and slowly remove indicator, return all valves to normal stand-by positions
water from the shell until pressure inside the bladder as shown on the System Operating Drawing Fig. 4-1,
drops enough to allow foam concentrate to be added Horizontal Tanks or Fig. 4-2, Vertical Tanks. Record
thru the fill funnel. date of refill/top-off and notify appropriate personnel
that system is back in service.
3. Attach one end of overflow tubing to Valve 4 and place
other end of hose into a drain or container. 7. If the system is equipped with a sight glass level indicator,
refer to Section 3-4, Procedures for Checking Foam
4. Close Valve 2. Make sure Valve 1 is closed. Slowly
Concentrate Level.
open Valves 4 and 5.

HAND POURING
METHOD
SHELL WATER
OVERFLOW TUBE 4
TO DRAIN 5 2
BLADDER
SIGHT GLASS
(OPTIONAL)
WATER DRAINED FROM SHELL

FOAM VALVE 7
1A
CONCENTRATE CLOSED
FOR HAND POUR
1 9 7

BLADDER 6

(OPTIONAL) 8

FOAM
CONCENTRATE FIGURE 3-4 TOPPING-OFF
USING HAND POURING
END VIEW

3-6 06/18
BLADDER TANK PROPORTIONING SYSTEM HORIZONTAL BLADDER TANK FILLING PROCEDURES

D. Topping-Off Using Hand Pumping Method

CAUTION:
To be used only when less than 30% of tank volume trate/water shutoff valve and start hand pumping foam
needs to be replenished. concentrate into the bladder.
NOTE: Be sure all valves are in their normal standby 5. Open Valve 5. If required, use the concentrate/water
position. Refer to System Operating Drawing, Fig. 4-1 shutoff valve for throttling the pressure to the bladder.
for Horizontal Bladder Tanks or Fig. 4-2, Vertical Bladder Water may still flow from the shell thru Valve 6 as
Tanks, for Normal Stand-By Valve Position Chart and valve concentrate is added.
location.
6. Continue pumping concentrate until foam concentrate
1. See Figure 3-5. Close Valve 2. Make sure Valve 1 is is detected coming from Valve 5. Close the concentrate/
closed. water shutoff valve and then close Valves 4, 5, 6 and 7.
2. If desired, attach a drain hose to Valve 6 and run it to 7. If the system is not equipped with a sight glass level
a drain or drain area. Attach one end of overflow hose indicator, return all valves to normal stand-by positions
to Valve 4 and place the other end of the hose into a as shown on the System Operating Drawing Fig.
drain or container. Slowly open Valve 6 and Valve 4 4-1,Horizontal Tanks or Fig. 4-2, Vertical Tanks. Record
and remove water from the shell. date of refill/top-off and notify appropriate personnel
that system is back in service.
3. Attach the fill manifold to Valve 7. Connect the hand
pump/foam concentrate supply to the fill manifold 8. If the system is equipped with a sight glass level indicator,
concentrate/water shutoff valve. refer to Section 3-4, Procedures for Checking Foam
Concentrate Level.
4. Open Valve 7. Slowly open the fill manifold concen -

SHELL WATER
OVERFLOW TUBE 4
TO DRAIN 5 2
BLADDER
SIGHT GLASS
(OPTIONAL)
WATER DRAINED FROM SHELL

FOAM VALVE 7
1A
CONCENTRATE OPEN
FOR HAND PUMPING
1 9 7

BLADDER 6
(OPTIONAL) 8
0 - 60 PSI

FIGURE 3-5
PRESSURE GAUGE
CONCENTRATE/WATER
SHUTOFF VALVE

TOPPING-OFF
(OPEN)
FOAM
CONCENTRATE
USING HAND PUMPING
METHOD HAND
PUMPING AIR SUPPLY
FILL MANIFOLD
END VIEW METHOD SHUTOFF VALVE
(CLOSED)

06/18 3-7
VERTICAL BLADDER TANK FILLING PROCEDURES BLADDER TANK PROPORTIONING SYSTEM

3-3. VERTICAL BLADDER TANK FILLING INSTRUCTIONS

A. Initial Fill or Empty Bladder Tank Fill

CAUTION:
A Bladder Integrity Test must be performed prior to
initial fill or empty tank fill. See Chapter 10 for Bladder
BLADDER
Integrity instructions. AIR DISCHARGE
THRU WATER
Be sure all valves are in their normal stand-by position. AIR/FOAM CONCENTRATE VENT HOSE IN DRUM

Refer to System Operating Drawing Fig. 4-2, Vertical


Bladder Tanks, for Normal Stand-By Valve Position Chart
and valve location. See Figures 3-6, 3-7 and 3-8 for set-up
SHELL WATER
illustrations. OVERFLOW TUBE
TO DRAIN
1. See Figure 3-6. Close Valve
2. Be sure Valve 1, or 1A if 5

appropriate, and Valve 6 are SYSTEM FLOW 55 GAL. DRUM


FILLED WITH
closed. Open Valves 4 and 5. WATER
4
2. Attach the fill manifold to
Valve 6. Attach one end of
STEPS 1 - 3
overflow hose to Valve 4 and place the
WATER
other end of the hose into a drain or 2
container. Connect a water source to the
concentrate/water shutoff valve. Be sure SIGHT GLASS
(OPTIONAL)
the concentrate/water shutoff valve is
closed before pressurizing the water line. 1A WATER
Open Valve 6 and then slowly open the
fill manifold Concentrate/Water Shutoff
Valve, and fill the tank shell until all air
is vented from the bladder and a steady
flow of water comes thru Valve 4. 1

3. Connect the air/foam concentrate vent 7


9
hose to the Bladder Foam Concentrate
Vent Valve 5. Fill the 55 gallon drum
completely with water and place the vent
6
hose discharge end at the bottom of the (OPTIONAL) 8

drum. The vent hose must be positioned


and maintained at the bottom of the drum
using weighted device. 0 - 60 PSI PRESSURE GAUGE

CONCENTRATE/WATER
SHUTOFF VALVE
(OPEN)

FILL MANIFOLD
WATER SUPPLY
TO SHELL
AIR SUPPLY SHUTOFF VALVE (CLOSED)

FIGURE 3-6 TANK SHELL FILLED WITH WATER

3-8 06/18
BLADDER TANK PROPORTIONING SYSTEM VERTICAL BLADDER TANK FILLING PROCEDURES

4. Close Valve 6 (Valve 4 remains open). Attach BLADDER AIR DISCHARGE


the fill manifold to Foam Concentrate Drain/ AIR/FOAM CONCENTRATE VENT HOSE
THRU WATER
IN DRUM
Fill Valve 7. Make sure the Concentrate/
Water Shutoff Valve is closed. Connect the
air supply to the fill manifold. Open the Air
Supply Shutoff Valve. Start the air source, SHELL WATER
at a pressure between 5-10 psi, and slowly OVERFLOW TUBE
TO DRAIN
open Valve 7.
The bladder 5
will begin to SYSTEM FLOW 55 GAL. DRUM
FILLED WITH
fill with air. WATER
Completely fill 4
bladder with
air. See Figure AIR AIR STEPS 4 - 6
3-7. 2
5. The bladder is filled with
air when air bubbles are SIGHT GLASS
(OPTIONAL)
expelled from the vent
hose at the bottom of WATER
1A
the drum, and water no
WATER
longer flows from Valve
4. Let the vent hose expel
air for approximately 30
seconds to insure complete 1
inflation. Open Valve 6 to
drain any remaining water 9 7
from the shell.
6. Close Valves 6 and 7 and
the manifold Air Supply 6 (OPTIONAL) 8
Shutoff Valve. Shutdown
and disconnect air supply 0 - 60 PSI PRESSURE GAUGE
from the manifold.
CONCENTRATE/WATER
SHUTOFF VALVE
(CLOSED)

AIR SUPPLY SHUTOFF VALVE (OPEN)

NITROGEN FILL MANIFOLD


OR
COMPRESSED AIR
SUPPLY

FIGURE 3-7 BLADDER BEING FILLED WITH AIR

06/18 3-9
VERTICAL BLADDER TANK FILLING PROCEDURES BLADDER TANK PROPORTIONING SYSTEM

7. Connect the foam concentrate fill pump to the fill NOTE: Flush the fill manifold and foam concentrate
manifold Concentrate/Water Shutoff Valve. Connect fill pump (following manufacturer’s instructions) after
the pump to the foam concentrate source. See Figure filling bladder tank.
3-8.
11. If the system is not equipped with a sight glass level
8. Open the Concentrate/Water Shutoff Valve. Start indicator, return all valves to normal stand-by positions
pumping foam concentrate and slowly open Valve 7. as shown on the System Operating Drawing Fig. 4-2.
Be sure to start pumping then open Valve 7. Record date of refill/top-off and notify appropriate
personnel that system is back in service.
CAUTION:
12. If the system is equipped with a sight glass level indicator,
Make certain that vent hose remains securely
refer to Section 3-4, Procedures for Checking Foam
positioned at bottom of 55 gallon drum.
Concentrate Level.
NOTE: Air bubbles will be expelled thru the vent AIR BUBBLES THEN LIQUID
hose and drum as foam concentrate displaces the air AIR/FOAM CONCENTRATE FOAM CONCENTRATE
VENT HOSE DISCHARGE THRU WATER
and fills the bladder. IN DRUM

9. Continue filling until SHELL WATER


foam concentrate is seen OVERFLOW TUBE
TO DRAIN
in the clear vent hose or
is detected coming from 5
SYSTEM
the hose discharge end. FLOW

CAUTION: 4 55 GAL. DRUM


FILLED WITH
Foam concentrate bubbles may WATER
be detected in the vent hose or AIR AIR
at the discharge end of the hose STEPS 7 - 9
2
when nearing bladder capacity.
These bubbles do not indicate SIGHT GLASS
a full bladder. Continue filling (OPTIONAL)
until liquid foam concentrate
is detected. 1A

Normally the actual capacity


of a bladder tank will exceed
the nominal capacity listed FOAM
on the tank. Therefore, it is 1 CONCENTRATE
recommended to continue
filling until foam concentrate is 9 7
detected coming from Valve 5
and not until nominal capacity
is reached. If the tank is not (OPTIONAL) 8
filled to capacity with foam
6
concentrate, the remaining 0 - 60 PSI PRESSURE GAUGE
area of the tank shall be filled CONCENTRATE/WATER
SHUTOFF VALVE
with water until all air has been (OPEN)
vented from the tank.
FOAM CONCENTRATE
10. Close Valve 7. Remove the SUPPLY
fill manifold. TO FILL PUMP FILL MANIFOLD
AIR SUPPLY SHUTOFF VALVE (CLOSED)

FIGURE 3-8
BLADDER FILLING WITH FOAM CONCENTRATE
3-10 06/18
BLADDER TANK PROPORTIONING SYSTEM VERTICAL BLADDER TANK FILLING PROCEDURES

B. Refilling or Topping-Off Using Motor Driven Foam Concentrate Pump

NOTE: The following procedures assume the system has 6. Close the Concentrate/Water Shutoff Valve and shut
been operated; and therefore, the tank shell is filled with down the foam concentrate fill pump.
water. It is also assumed that the bladder is leak free and
in good condition. If not, water must be added to the tank 7. Return all tank valves to their normal stand-by position.
thru Valve 6 or Valve 2 until it flows from Valve 4. Refer to System Operating Drawing Fig. 4-2, Vertical
Bladder Tanks, for Normal Stand-By Valve Position
CAUTION: Chart and valve location.
When topping-off, make sure foam concentrate fill
pump does not exceed the water venting (discharge) 8. Disconnect foam concentrate fill pump at the fill
capability of Valve 4. Throttle thru Valve 7, or if using a manifold and flush the pump following manufacturer’s
fill manifold, use the Concentrate/Water Shutoff Valve. instructions. Remove the fill manifold from Valve 7.
Thoroughly flush fill manifold.
NOTE: Be sure all valves are in their normal stand-by
position. Refer to System Operating Drawing Fig. 4-2, 9. If the system is not equipped with a sight glass level
Vertical Bladder Tanks, for Normal Stand-By Valve Position indicator, return all valves to normal stand-by positions
Chart and valve location. as shown on the System Operating Drawing Fig. 4-2.
Record date of refill/top-off and notify
1. Close Valve 1, 1A SHELL WATER appropriate personnel that
and 2. Attach the fill OVERFLOW TUBE
system is back in service.
TO DRAIN
manifold to the Foam
Concentrate Drain/Fill SYSTEM 5 10. If the system is equipped
Valve. Make sure that FLOW with a sight glass level
the Air Supply Shutoff indicator, refer to
Valve is closed. Attach 4 Section 3-4, Procedures
one end of overflow tubing to for Checking Foam
Valve 4 and place other end of Concentrate Level.
hose into a drain or container. WATER WATER
See Figure 3-9 for setup. 2

2. Connect the foam concentrate SIGHT GLASS


fill pump to the fill manifold (OPTIONAL)
Concentrate/ Water Shutoff
Valve. Connect the pump to 1A
the foam concentrate source.
3. If desired, attach a drain hose
to Valve 6 and run it to a drain FOAM
or drain area. Open Water Vent 1
CONCENTRATE
Valve 4. Open Bladder Foam
Concentrate Vent Valve 5. 7
9
4. Open the Concentrate/Water
Shutoff Valve. Start the foam
concentrate fill pump and slowly (OPTIONAL) 8

open Valve 7. Be sure to start the 6


0 - 60 PSI PRESSURE GAUGE
pump then open Valve 7. CONCENTRATE/WATER
SHUTOFF VALVE
5. Fill the bladder until foam concentrate (OPEN)
is discharged from Valve 5 and no
water is being discharged from Valve FOAM CONCENTRATE
4. At this time, open Valve 6 and SUPPLY
FILL
TO FILL PUMP
drain any remaining water from the AIR SUPPLY SHUTOFF VALVE (CLOSED) MANIFOLD
tank shell.
FIGURE 3-9
BLADDER FILLING WITH FOAM CONCENTRATE
06/18 3-11
VERTICAL BLADDER TANK FILLING PROCEDURES BLADDER TANK PROPORTIONING SYSTEM

C. Topping-Off Using Hand Pouring Method

CAUTION:
To be used only when less than 30% of tank volume
needs to be replenished. Do not use this method for empty
tanks or when filling with AR-AFFF foam concentrates.
1. Follow procedures as described for Horizontal Bladder
Tanks, Sect. 3-2.C.
D. Topping-Off Using Hand Pumping Method
1. Follow procedures as described for Horizontal Bladder
Tanks, Sect. 3-2.D.

3-4. Procedures for Checking Foam Concentrate Level

NOTE: Be sure all valves are in their normal stand-by Vent Valve, Valve 5, to measure the foam concentrate
position. Refer to System Operating Drawing Fig. 4-1 for level.
Horizontal Bladder Tanks or Fig. 4-2 for Vertical Bladder
4. To drain the sight glass, close Valve 9 and open Valve
Tanks, for Normal Stand-By Valve Position Chart and valve
7. Make sure Valve 9 is closed. Return all valves to
location.
their normal stand-by position as shown on the System
Operating Drawing Fig. 4-1, Horizontal Tanks, or Fig.
CAUTION:
4-2, Vertical Tanks.
Alcohol type AFFF foam levels will not be accurately
indicated in the sight glass, therefore it is necessary to 5. If the bladder tank has been completely filled with
determine a full condition by noting foam concentrate foam concentrate, no water has to be replaced in the
flow from the Bladder Foam Concentrate Vent Valve 5, tank shell to return the tank to full stand-by condition.
as descibed in the filling instructions in this manual. It
may be necessary to remove and clean the sight glass However, if the system has been operated and there is
and then re-install after checking the level. foam concentrate in the bladder and water occupied the
remaining area in the tank shell before checking the
The foam concentrate level cannot be checked while the foam level, water must be replaced in the tank shell to
tank is pressurized. To determine the concentrate level, return the tank to full stand-by condition:
follow the procedures below:
a. Attach a water supply to Valve 6.
1. Depressurize tank.
b. Open Valves 5 and 6. Slowly add water thru Valve 6.
a. Close Valve 2. Make sure Valves 1 and 7 are closed.
c. When foam concentrate is discharged from Valve
b. Slowly open the following valves: Valve 4 (allow 5, shut off the water supply and close Valve 5.
pressure to vent before opening remaining valves),
5, 6, 8 and 9 (Valve 9 normally open). d. Open Valve 4 and slowly add water thru Valve 6
until water flows from Valve 4. Close Valves 4 & 6.
CAUTION: e. Return all valves to their normal stand-by position
The tank will still contain some residual pressure as shown on the System Operating Drawing, Fig.
which will be released. 4-1 or Fig. 4-2. The tank is now in its stand-by
condition.
2. When water stops flowing from Water Drain/Fill Valve
6, observe the concentrate level in the sight glass. 6. If appropriate, record date of fill and notify appropriate
personnel that system is back in service.
3. For tanks with an alcohol type AFFF foam concentrate:
Use a dipstick or ruler through the Foam Concentrate

3-12 06/18
BLADDER TANK PROPORTIONING SYSTEM OPERATING PROCEDURES

CHAPTER 4 - OPERATING PROCEDURES

4-1. Operation of System


NOTE: Before operation, verify that all valves on the proportioning system are in their normal stand-by position. Refer
to System Operating Drawing Fig. 4-1 for Horizontal Bladder Tanks or Fig. 4-2 for Vertical Bladder Tanks, for Normal
Stand-By Valve Position Chart and valve location.

1. Manual Operation (No Automated Valves): a. The appropriate foam solution discharge valve(s) to the
discharge device(s) in the required hazard area(s) will
a. Open the appropriate foam solution discharge
open.
valve(s) to the discharge device(s) in the required
hazard area(s). b. Water flow through the ratio controller(s) will start.
b. Start water flow through the ratio controller(s). c. The appropriate automatic Foam Concentrate Supply
Valve(s) No. 1A for the required hazard area(s) will
c. Open the appropriate Foam Concentrate Supply
open.
Valve(s) No. 1 for the required hazard area(s).
NOTE: The above is representative of a fully
2. Automatic Operation (Automated Systems Only):
automated system. Since certain systems have both
Upon initiation of the automatic start sequence, the manually and automatic actuated valves, personnel
following should occur: operating the system must actuate only manual valves
in conjunction with the automatic sequence above.

4-2. Shutdown of System


1. Manual Operation (No Automated Valves):
a. Close Foam Concentrate Supply Valve(s) No. 1 e. Return all valves to their normal stand-by position.
for the appropriate hazard area(s). Refer to Fig. 4-1 for Horizontal Tanks or Fig. 4-2 for
Vertical Tanks for valve position.
WARNING: f. Replenish supply of foam concentrate. Refer to Bladder
Only after the fire is out and the danger of Tank Filling Instructions, Chapter 3.
reignition has passed, shall consideration be
given to flushing and draining the system. CAUTION:
b. Flush the system by allowing the water to flow until Only foam concentrate of the type listed on the
clear water issues from devices being operated. tank nameplate should be used to replenish the
tank. Mixing of different types or brands of foam
c. Stop the water flow to the ratio controller(s). concentrate could cause deterioration of foam
concentrates or failure of the system.
d. Close the appropriate Foam Solution Discharge
Valve(s) to the hazard area(s). g. Replace all breakable components such as glass
diaphragms, rupture discs, etc. in foam lines or foam
making devices.

06/18 4-1
OPERATING PROCEDURES BLADDER TANK PROPORTIONING SYSTEM

2. Automatic Operation (Automated Systems Only):

Reset automatic system. Upon system shutdown and d. Replenish supply of foam concentrate. Refer to Bladder
system reset, the following sequence should occur: Tank FIlling Instructions, Chapter 3.
a. The appropriate foam solution discharge valve(s) e. Return all valves to their normal stand-by position.
to the discharge device(s) in the hazard area(s) will Refer to Fig. 4-1 for Horizontal Tanks or Fig. 4-2 for
close. Vertical Tanks for valve position.
b. Water flow to the ratio controller(s) will stop.
CAUTION:
c. The appropriate automatic Foam Concentrate Only foam concentrate of the type listed on the
Supply Valve(s) No. 1A for the required hazard tank nameplate should be used to replenish the
area(s) will close. tank. Mixing of different types or brands of foam
concentrate could cause deterioration of foam
NOTE: Water Powered Foam Concentrate Supply concentrates or failure of the system.
Valve(s) 1A do not reset automatically and must be
reset manually. Filling Instructions described in Chapter 3 must be
followed to prevent damage to the bladder.
NOTE: The above is representative of a fully
automated system. Since certain systems have both f. Replace all breakable components such as glass
manually and automatic actuated valves, personnel diaphragms, rupture discs, etc., in foam lines or foam
operating the system must close only manual valves making devices.
in conjunction with the automatic sequence above.

4-3. Automatic System Flushing


NOTE: If system has a water powered foam concentrate manual override on automated valve(s) or a combination of
valve, the cylinder water pressure supply valve in the water the two. Allow clear water to flow until clear water issues
line supplying pressure to the water powered ball valve from devices operated. Reset automatic system and return
operating cylinder must be closed before any flushing all valves to their normal stand-by position. Refer to System
operation. Operating Drawing Fig. 4-1 for Horizontal Bladder Tanks
or Fig. 4-2 for Vertical Bladder Tanks, for Normal Stand-By
The proportioning system must be flushed and drained
Valve Position Chart and valve location.
after operation. Flushing may be done by control system or

4-2 06/18
BLADDER TANK PROPORTIONING SYSTEM FIGURE 4-1 - HORIZONTAL SYSTEM OPERATING DRAWING

VALVE DESCRIPTION
Normal Valve Position
Valve No. Description Manual System Automatic System
1 Foam Concentrate Supply (Manual) N.C. N.O.
1A Foam Concentrate Supply (Automatic) -- N.C.
2 Water Pressure Supply N.O. N.O.
4 Tank Water Vent N.C. N.C.
5 Bladder Foam Concentrate Vent N.C. N.C.
6 Water Drain/Fill N.C. N.C.
7 Foam Concentrate Drain/Fill N.C. N.C.
8 Sight Glass N.C. N.C.
9 Sight Glass Supply N.O. N.O.

NOTE:
1. N.O. - Normally Open; N.C. - Normally Closed.
2. Valve numbers are labeled on tank.
3. Larger flanged end used for bladder removal.

C
F
4 G H
J 5

D
2
E
1A

1 8
9 7
B A
6

COMPONENT DESCRIPTION
A - Storage Tank E - Sight Glass
B - Bladder F - Fill Cup (For Top Off Only)
C - Ratio Controller G - Water Supply Piping
D - Check Valve H - Foam Solution Delivery Piping
J - Over Pressure Relief Device (By others if required)

FIGURE 4-1
System Operating Drawing
Horizontal Bladder Tank - Valve Description & Position Chart

06/18 4-3
FIGURE 4-2 - VERTICAL SYSTEM OPERATING DRAWING BLADDER TANK PROPORTIONING SYSTEM

VALVE DESCRIPTION
Normal Valve Position
Valve No. Description Manual System Automatic System
1 Foam Concentrate Supply (Manual) N.C. N.O.
1A Foam Concentrate Supply (Automatic) -- N.C.
2 Water Pressure Supply N.O. N.O.
4 Tank Water Vent N.C. N.C.
5 Bladder Foam Concentrate Vent N.C. N.C.
6 Water Drain/Fill N.C. N.C.
7 Foam Concentrate Drain/Fill N.C. N.C.
8 Sight Glass N.C. N.C.
9 Sight Glass Supply N.O. N.O.

NOTE:
1. N.O. - Normally Open; N.C. - Normally Closed.
2. Valve numbers are labeled on tank.
3. Top end flange used for bladder removal.
F
C J
4 5
H G

2
COMPONENT DESCRIPTION
A - Storage Tank
E
B - Bladder D
C - Ratio Controller
D - Check Valve
E - Sight Glass A
F - Fill Cup (For Top Off Only)
G - Water Supply Piping
H - Foam Solution Delivery Piping
1A
J - Over Pressure Relief Device
(By others if required)
B
1
8
6
9 7

FIGURE 4-2
System Operating Drawing
Vertical Bladder Tank - Valve Description & Position Chart

4-4 06/18
BLADDER TANK PROPORTIONING SYSTEM RATIO CONTROLLER CHARTS

RATIO CONTROLLER FLOW RANGE STANDARD


SPECIAL FLOW WATER
PROTEIN, WITH AR-AFFF & AR-AFFF
R.C. FLUOROPROTEIN AFFF FOAM CONCENTRATES CONCENTRATE CONCENTRATE
SIZE GPM (LPM) GPM (LPM) LINE SIZES LINE SIZES
2 30 - 180 (114 - 681) 60 - 180 (228 - 681) 1ʺ 1-1/4ʺ
3 70 - 450 (284 - 1703) 170 - 450 (644 - 1703) 1-1/4ʺ 1-1/2ʺ
4 150 - 1200 (568 - 4542) 320 - 1200 (1211 - 4542) 1-1/2ʺ 2ʺ
6 300 - 2500 ( 1136 - 11356) 700 - 2500 (2650 - 11356) 2ʺ 2-1/2ʺ
8 850 - 5000 (3218 - 18927) 1400 - 5000 (5300 - 18925) 2-1/2ʺ 3ʺ

FIGURE 4-3
Ratio Controller Flow Range and Piping Size Chart

%$536, Ǝ5&7 Ǝ5&)5&: Ǝ5&)5&: Ǝ5&)5&: Ǝ5&)5&:


6.9/100
6.2/90
WATER INLET PRESSURE (PSI/BAR)

5.5/80
4.8/70
4.1/60

3.4/50

2.7/40

2.06/30

1.3/20
*30 60 80 100 200 400 600 800 1000 2000 4000
/30 227 303 379 757 1514 2271 3028 3785 7571 15141

SOLUTION FLOW (GPM/LPM)

NOTE:
The curves in Figure 4-4 indicate the minimum inlet pressure required relative to the anticipated flow rate of the
system. These curves apply to all proportioning systems which utilize Model RCT, RCF or RCW ratio controllers.

FIGURE 4-4
Ratio Controller Minimum Inlet Pressure vs. Solution Flow Chart

06/18 4-5
BLADDER TANK PROPORTIONING SYSTEM INSPECTION, MAINTENANCE & REPAIR

CHAPTER 5 - INSPECTION, MAINTENANCE & REPAIR

5-1. Inspection and Maintenance becomes necessary to replace, repair or modify system
components, component parts, operating devices or
See Table 5-1 for Recommended Inspection and Maintenance equipment, the system must be tested to insure proper
Procedures. These procedures and recommended intervals operation before being placed back into service.
are based on normal operating conditions and may have to
be modified to meet the existing conditions.
5-3. Annual Testing
CAUTION:
When cycling automated valves, make sure that the At least annually, all foam systems shall be thoroughly
Water Pressure Supply Valve 2 and Foam Concentrate inspected and checked for proper operation. This shall
Manual Supply Valve 1 are closed. After cycling, return include performance evaluation of the foam concentrate
all valves to their normal stand-by position. or premix solution quality or both. Deviation of results
exceeding 10 percent from those recorded in acceptance
WARNING: testing shall be discussed immediately with the
manufacturer. Regular service contracts are recommended.
The intervals in this chapter are a general
recommendation; some environmental conditions The goal of this inspection and testing shall be to ensure
may dictate such inspections be performed at more that the system is in full operating condition, and that it
frequent intervals. will remain in that condition until the next inspection.
The inspection report, with recommendations, shall be
filed with the owner. Between the regular service contract
5-2. Testing After System Maintenance inspections or tests, the system shall be inspected by
competent personnel following an approved schedule.
If during the course of normal system maintenance it

06/18 5-1
INSPECTION, MAINTENANCE & REPAIR BLADDER TANK PROPORTIONING SYSTEM

TABLE 5-1 - RECOMMENDED INSPECTION & MAINTENANCE SCHEDULE

NOTE: The following recommendations are based on normal operating conditions. Due to environmental or
other conditions unique to your system, the frequency of some inspecton and maintenance procedures
may need to be adjusted. Additional inspection and maintenance procedures may also be required.
NOTE: When performing inspection and maintence procedures which:
a require operation of the system or parts of the system,
b. cause the system to be non-operational during the procedure,
c. cause a trouble indication,
the system shall be taken out of service and the proper authorities should be notified.

Semi-Annual
Operation

Monthly
Start-up

Annual
Weekly
Post-
Description Other
5-4. Total System
After
1. Check all valves to insure that they are in the normal stand-by condition. See All
System Operating Drawing Fig. 4-1 or 4-2. ● ● Maint.
Procedures

2. Inspect system for physical damage and repair. ● ●


3. Check the complete system, all valves, fittings & connections for leakage. ● ●
4. Perform normal maintenance and inspection of the fire water supply system to
insure that it will be operational when required. ●
5. Perform the After Installation test as prescribed in Chapter 2, Sect. 2-7 of this manual. ●
6. Perform annual system test as prescribed in the Chapter 5, Sect. 5-3 of this manual. ●
7. Flush proportioning system. See flushing instructions Sect. 4-2.1, Shutdown
of System (Manual Operation) or Sect. 4-3 Automatic System Flushing. ●
8. Cycle automated valve(s). Cycling of valves can be done manually or by control
system.
After
CAUTION: Maint.
● To
When cycling automated valves, make sure that the Water Pressure Supply Piping
Valve 2 and Manual Concentrate Supply Valve 1 are closed. After cycling
return all valves to their normal standby position.

9. Cycle manual valves to insure freedom of movement.


CAUTION: ●
Make sure that cycling of valves does not take the bladder system out of
the in-service status.

10. Check flange bolts for tightness. ● ●


11. Check system for any external damage to the paint surfaces. ● ●

5-2 06/18
BLADDER TANK PROPORTIONING SYSTEM INSPECTION, MAINTENANCE & REPAIR

TABLE 5-1: RECOMMENDED INSPECTION AND MAINTENANCE SCHEDULE (CONT’D)

Semi-Annual
Operation

Monthly
Start-up

Annual
Weekly
Post-
Description Other
NOTE: Recommended inspection & maintenance items 12 & 13 shall all be
performed at the specified interval as a single procedure with various components
requiring particular procedures.
Every
12. The bladder tank shall be drained of foam concentrate. Thoroughly clean Ten (10)
the inside of the tank. Scrape any rust or sediment which may be present. If Years
(Per NFPA)
necessary, scrub with a detergent solution. Thoroughly flush with clean water.
(Foam concentrate shall be permitted to be salvaged and reused. If concentrate
is to be reused, before returning it to tank, make sure to run it through a strainer
or screen to remove any solid particles present.)
13. Inspect for internal and external corrosion while the bladder tank is drained of Every
foam concentrate. After verifying that the tank and components are suitable Ten (10)
for return to service, fill the tank with clean water and hydrostatically test the Years
(Per NFPA)
pressure vessel to the specified working pressure.
5-5. Strainers
Total System:
1. Remove screens, check, clean and reinstall. ● ●
5-6. Electrically Actuated Valves
1. Cycle valve(s) - Valve(s) may be cycled from control panel or by manual
override at valve.
CAUTION: ● ●
When cycling automated valves, make sure that the Water Pressure Supply
Valve 2 and Manual Concentrate Supply Valve 1 are closed. After cycling
return all valves to their normal standby position.
2. Cycle valve(s) from the control panel to insure proper operation from control. ● ●
3. Check supervision of circuit. ● ●
4. Check for leakage past valve seat. ● ● ●
5-7. Water Powered Ball Valves

CAUTION:
When cycling automated valves, make sure that the Water Pressure Supply
Valve 2 and Manual Concentrate Supply Valve 1 are closed. After cycling
return all valves to their normal standby position.
1. Cycle the valve(s) either manually or through control panel. ● ●
2. Cycle the valve(s) using the solenoid release (if applicable). ● ●
3. Check supervision of circuit if solenoid release is provided. ● ●
4. Make sute that the quick release pin is securely positioned thru the clevis. ● ●
5. Make sure the bleeder/vent valve is properly tightened. ● ●

06/18 5-3
INSPECTION, MAINTENANCE & REPAIR BLADDER TANK PROPORTIONING SYSTEM

TABLE 5-1: RECOMMENDED INSPECTION AND MAINTENANCE SCHEDULE (CONT’D)

Semi-Annual
Operation

Monthly
Start-up

Annual
Weekly
Post-
Description Other
5-8. Foam Concentrate Storage Tank
Perform
1. Check the level of concentrate in the tank. Refer to Chap. 3, Sect. 3-4. for Check

procedures to check foam concentrate level.


● ● ● During
Annual
Testing

2. Check water side of tank for traces of foam concentrate.


NOTE: Open Valve 6 and observe the water drained. If traces of foam concentrate ●
are found in the water that is drained, contact AF Engineering Department.
3. Check for rust, corrosion, leakage, and weak spots or other physical damage. ●
At
Installation
4. Check flange bolts on both ends of the tank for proper tightness. Refer to Section or When
2-4., item 7, Bladder Tank Installation, for further details. Replacing
Internal
Bladder

5-9. Foam Concentrate


1. Check that storage temperature is within acceptable limits. Refer to Section
6-1. for recommended temperatures. ●
2. Sample foam concentrate and submit sample to foam manufacturer to be tested
for sedimentation, corrosion, dilution or contamination. See Chapter 6, Section ●
6-6. & 6-7. for foam concentrate sampling instructions.
5-10. Control System
1. Check that proper indicators are present. See control panel data. ● ●
2. Check supervision of all circuits. ● ●
3. Check alarm operation. ● ●
4. Check system operation. See control panel data. ● ●
5. Check that all indicators illuminate. ● ●

5-4 06/18
BLADDER TANK PROPORTIONING SYSTEM FOAM CONCENTRATES

CHAPTER 6 - FOAM CONCENTRATES

6-1. Proper Storage and Maintenance


Angus Fire concentrates are designed to provide years of Excessive temperatures either above or below storage
service and reliability when properly stored and maintained. limits may cause deterioration in any foam concentrate.
Properly constructed large capacity tanks offer the optimum
Storage in shipping containers is acceptable, but care shall
conditions for prolonged storage.
be exercised with metal pails and 55 gallon drums to protect
Maximum and minimum recommended storage them from external corrosion. Properly constructed large
temperatures for Angus Fire concentrates shall not be capacity tanks offer the optimum conditions for prolonged
exceeded. Consult product data sheets for additional storage.
information.

6-2. Basic Guidelines for Improving Foam Concentrate Storage Life

1. Avoid long-term storage at temperatures above the 5. Valves, couplings or piping that will be in continual
maximum recommended. contact with the foam concentrate shall not be
constructed of dissimilar metals. The use of dissimilar
2. Never mix different foam concentrates in common metals may cause galvanic corrosion.
storage tanks.
6. Annual inspection of foam concentrates is recommended.
3. Avoid dilution of foam concentrates with water. This inspection should include a sample of the foam
4. Avoid contamination with foreign ingredients, concentrate being submitted to Angus Fire’s Technical
chemicals or oils. Service Department for analysis. Refer to Sect. 6-3 for
additional information.

6-3. Foam Concentrate Testing


At least annual inspection shall be made of foam One pint samples shall be drawn from the top and bottom
concentrates and their tanks or storage containers for of the tank annually and sent to AF laboratories for testing.
evidence of excessive sludging or deterioration. Samples These samples will be examined for contamination, dilution
of concentrates shall be referred to the manufacturer or and suitability for use. See Sections 6-6 and 6-7 for the
qualified laboratory for quality condition testing. Quantity correct procedure in obtaining and submitting the samples.
of concentrate in storage shall meet design requirements,
and tanks or containers shall normally be kept full with
adequate space allowed for expansion.

06/18 6-1
FOAM CONCENTRATES BLADDER TANK PROPORTIONING SYSTEM

6-4. Control Measures


A. Concentrate: B. Foam Solution:
1. Collect all spilled concentrate with absorbent 1. Do not flush to waterways.
material.
2. Dispose of diluted material according to Local,
2. Flush area with water until it no longer foams. State, and Federal regulations.
3. Disposal shall be made in accordance with Local, 3. Small quantities of foam solution may be absorbed
State, and Federal regulations. High temperature onto absorbents which can then be disposed of by
incineration is recommended for foam concentrates incineration or in accordance with Local, State,
containing fluorosurfactants. or Federal regulations.
Please consult Angus Fire for additional Please consult Angus Fire for additional
information regarding the disposal of foam information regarding the disposal of foam
concentrates and foam solutions. concentrates and foam solutions.

6-5. Safe Handling of AF Foam Products


Angus Fire’s Safety Data Sheets, which cover our foam products, have been designed in accordance with OSHA’s Toxic
and Hazardous Substances Hazard Communication Standard (CFR-29, Section 1910.1200).
A specific AF foam product may or may not have been tested as a whole for acute oral and inhalation toxicity, primary eye
irritation or primary skin irritation, and may or may not be considered toxic. For specific information, consult the Safety
Data Sheet of the applicable AF foam product.

WARNING:
Foam is a conductor and shall not be used on energized electrical equipment fires.
Foams are not suitable extinguishing agents for fires involving gases, liquefied gases with boiling
points below ambient temperatures such as butane, butadiene, propane, etc., or cryogenic liquids.
Judgement must be used in applying foams to hot oils, burning asphalts or burning liquids which
are above the boiling point of water. Intermittent foam operation shall be used to prevent violent
frothing and “slop-over” of the tank contents.

6-2 06/18
BLADDER TANK PROPORTIONING SYSTEM FOAM CONCENTRATES

6-6. Foam Concentrate Sampling Procedures

1. To obtain a representative sample, if the system NOTE: Drain lines may contain materials that are not
design permits, the foam should be re-circulated for representative of the contents of the storage tank. If a
approximately 30 minutes prior to sampling. drain connection is used for sampling, draw off and
discard two gallons of concentrate before re-circulating
If circulation is not possible for any reason, then take
the foam and taking the sample.
samples from the following:
2. The sample must be one litre in volume and shipped in
a) Top of the tank
a clean, tightly sealed container made of polyethylene.
b) Middle of the tank
If new unused containers are unavailable, ensure the
c) Bottom of the tank
containers are washed properly beforehand. Do not use
containers which have previously contained detergent
If it is not possible to take three samples, due to the or oil materials.
construction of the vessel or other reason, then take
3. Sample containers must be packaged to avoid damage
one sample from the top of the tank and a second
during shipment. The container label (do not use
sample from the bottom.
gummed labels) or container must be marked with a
NOTE: SUBMIT ONE COMPOSITE SAMPLE waterproof pen showing the following information:
ONLY, made by mixing together the samples taken
• Name of company
from the tank.
• Samples should be clearly labeled with origin,
If it is only possible to take one sample from a storage
foam type, and recommended induction rate
vessel which has not been circulated, it should be
understood that this may not be truly representative • Source of sample (1500 gallon foam storage tank
of the complete contents of the storage tank. located in B5 Foam Room - Tank #1.)

6-7. Documentation
1. Fill in ALL the information required on the Foam 3. Note any special conditions or problems.
Testing Service Application Form provided or make
4. Be specific in storage container identification. For
a clean, clear copy of sample form provided on the
example, 500 gallon foam storage tank located in
next page of this manual.
North Tank Farm.
2. If the sample is an AF concentrate, indicate origin,
foam type, and recommended induction rate. If the
sample is from another manufacturer, indicate the
manufacturer, type of foam and lot number.

NOTE: See next page for sample Foam Testing Service Application Form

06/18 6-3
FOAM CONCENTRATES BLADDER TANK PROPORTIONING SYSTEM

Foam Testing Service - Application Form

Company: ______________________________ Order Number:


Customer Name: ________________________
Address: _______________________________
______________________________________ Email: ________________________________
______________________________________ Phone:________________________________
Country: _______________________________ Fax: __________________________________

Sample Information:
 1 Litre Sample
 Clean Bottle
 One Form Per Sample

Concentration: 1% 3% 6% Don’t Know _____

1-3% 3-3% 3-6% 6-6%

Storage Type: Original Containers Bulk Tank Other __________

Container Volume: 20/25 Ltr 200 Ltr 1000 Ltr Other __________

Sample Location: Top Middle Bottom Other __________

Sample Age (Yrs): Under 2 2-5 Over 5 Estimate _______

Comments: ______________________________________________________________________

Internal Use Only Return Address

Foam Testing Department


RC SA SS Angus Fire Ltd
Station Road
Bentham, Lancaster
TD RS SO LA2 7NA
United Kingdom

6-4 06/18
BLADDER TANK PROPORTIONING SYSTEM TROUBLESHOOTING

CHAPTER 7 - TROUBLESHOOTING

7-1. Troubleshooting Recommendations


See Table 7-1 for troubleshooting problems, possible causes and corrective actions.
These procedures cover problems that may be experienced during normal operations. Although these recommendations cover
most problems that are experienced, there are some situations that may occur which are not covered in these instructions.
Please contact Angus Fire’s Engineering Department for problems that cannot be resolved through the use of this manual.
NOTE: Refer to individual instruction manuals for additional information on system components and discharge devices.

TABLE 7-1
Troubleshooting
Problem Possible Cause Corrective Action
7-2. No Water Pressure Supply Valve 2 not open. Check valve position. Fully open valve(s) if closed.
Proportioning
Manual Foam Concentrate Supply Valve 1 not Fully open valve.
open.
Automatic Foam Concentrate Supply Valve 1A Refer to manufacturer’s data.
not functioning properly.
Automatic Foam Concentrate Supply Valve 1A Check that wiring is installed to actuator.
closed. (Electrically actuated)
Check that signal from control system is available
at valve actuator. If voltage is not present, check
control system.

If signal is present at actuator, use manual override


to cycle valve. If valve cycles manually, then valve
actuator is probably bad.

Remove actuator, check operation. If bad, repair or


replace. If valve does not open using manual override
on actuator, then the valve is jammed. Remove
valve, determine and correct reason for jam. See
actuator data.
Automatic Foam Concentrate Supply Valve 1A Check that cylinder water pressure supply valve is
closed or not functioning properly. Water Powered fully open.
Ball Valve)
Check that quick release pull pin is not removed from
clevis. Reinsert pin thru clevis and valve handle.

Check 1/4″ Bleeder/Vent Valve on stariner for


clogging which shuts off water supply to cylinder.
Open Bleeder/Vent Valve on strainer, vent and flush
any debris blocking water supply.

06/18 7-1
TROUBLESHOOTING BLADDER TANK PROPORTIONING SYSTEM

TABLE 7-1 - Troubleshooting


Problem Possible Cause Corrective Action
7-2. No Valve or valves not in proper stand-by position. Place valve(s) in normal stand-by position as shown
Proportioning on System Operating Dwg. Figure 4-1 for Horizontal
(continued) Tanks or Figure 4-2 for Vertical Tanks.
Blockage in piping between tank and ratio Determine location of blockage, drain concentrate
controller or the water feed line. from tank, remove appropriate run of piping and
remove blockage.
System operating below minimum proportioner Refer to Fig. 4-4 Ratio Controller Minimum Inlet
inlet pressure. Pressure versus Solution Flow Chart for proper inlet
pressures.
Ratio controller flow below minimum flow range Refer to Fig. 4-3 Ratio Controller Flow Range
of proportioners. and Piping Size Chart for proper flow range of
proportioners.
Control system not functioning properly. Check wiring for correct interconnection and proper
connections. See control system manual.
Foam concentrate incompatible with the system Drain and clean tank before filling with new
design. concentrate. Fill with correct concentrate for system
design.
Bladder tank empty. Refer to Chapter 3 Sect. 3-4., Procedures for Checking
Foam Concentrate Level. If empty, follow appropriate
fill procedures in Chapter 3.
Strainer(if installed) blocked. Remove all strainer screens and clean. Reinstall after
cleaning. Check for strainer screen perforation size
- Strainer mesh shall have 1/8″ openings for all AF
foam concentrates.
7-3. Low Water Pressure Supply Valve 2 partially open. Check valve position. Fully open valve.
Percent of
Manual Foam Concentrate Supply Valve(s) 1 Fully open valve. If system has dual proportioners,
Proportioning
partially open. be sure second supply valve for proportioner not
being used, is closed.
Automatic Foam Concentrate Supply Valve(s) 1A Valve blocked from fully opening or control system
not fully open. problem. Determine cause and correct.
Automatic Foam Concentrate Supply Valve 1A Cylinder water pressure supply valve partially open.
opens slowly. (Water Powered Ball Valve) Fully open valve.

Tighten 1/4″ Bleeder/Vent Valve on cylinder strainer.


Snug with wrench to insure closure to rated pressure.

1/4″ Bleeder/Vent Valve strainer clogged, obstructing


water supply to cylinder. Open 1/4″ Bleeder/Vent
valve on strainer and vent. Flush any debris blocking
water supply.
Flow rate below minimum rate of ratio controller. Refer to Fig. 4-3 Ratio Controller Flow Range
and Piping Size Chart for proper flow range of
proportioners.
Reduced port valve(s) being used instead of full Replace reduced port valve(s) with full port valve(s).
port type.

7-2 06/18
BLADDER TANK PROPORTIONING SYSTEM TROUBLESHOOTING

TABLE 7-1 - Troubleshooting


Problem Possible Cause Corrective Action
7-3. Low Piping too small or excessive run between tank The total friction loss in the water and foam
Percent of and ratio controller causing excessive friction loss concentrate lines between the tank and ratio controller
Proportioning in water and/or foam concentrate piping. shall not exceed 2 psi. Redesign piping accordingly.
(continued)
Refer to Figure 4-3.
Water pressure too high causing excessive flow, Adjust pressure to proportioner to be within the flow
exceeding the design limits of the system. and pressure limits of the system.
Drain valve(s) or vent valve(s) open or partially Fully close all drain or vent valve(s).
open.
Incorrect orifice diameter or adjustment. Contact AF Engineering Dept. for instructions on
checking orifice and adjustment settings.
Control system not functioning properly. See control system manual. Check wiring for correct
interconnection and proper connections.
Strainer(if installed) blocked. Remove all strainer screens and clean. Reinstall
after cleaning.
System operating below minimum proportioner Refer to Fig. 4-4 Ratio Controller Minimum Inlet
inlet pressure. Pressure versus Solution Flow Chart for proper inlet
pressures.
Foam concentrate incompatible with system Drain and clean tank. Fill with correct concentrate.
design.
7-4. High Incorrect orifice diameter or adjustment. Contact AF Engineering Dept. for instructions on
Percent of checking orifice and adjustment settings.
Proportioning
Water pressure source to tank, other than water Contact AF Engineering Dept. for instructions on
main supplying ratio controller, which supplies locating water pressure source properly on water
higher water pressure to tank than does water main.
7-5. No Flow Zone discharge valve closed or will not open. Open valve. If automated, find problem and correct.
at Discharge
Blockage in the foam solution discharge line or Find the cause of the blockage and correct.
discharge device.
7-6. Low Flow System pressure too low. Check inlet pressure and correct for proper operation.
at Discharge
Partial blockage in water or foam solution line.

Zone valve did not open completely. Valve jammed,


determine reason and correct.
7-7. No Water supply source failure. Check source and correct problem.
Operation
Control system not functioning properly. Check wiring for correct interconnection and proper
(Automated system) connections. See control system manual.
Foam tank empty. Fill tank with proper type foam concentrate.

06/18 7-3
BLADDER TANK PROPORTIONING SYSTEM RATIO CONTROLLER STORAGE & INSTALLATION

CHAPTER 8 - RATIO CONTROLLER


STORAGE AND INSTALLATION INSTRUCTIONS
- RATIO CONTROLLER SUPPLIED AS LOOSE COMPONENT -

8-1. 2ʺ RCT (Threaded) Thru 8ʺ RCF (Flanged) Units

A. Storage:
1. Ratio Controllers are machined brass castings and 2. For protection against physical damage, a ratio
contain no moving parts. They are shipped with plastic controller should be kept in its shipping crate until
protectors on the water inlet, foam concentrate inlet time of installation. The plastic protectors should not
and foam solution outlet. be removed until just preceding installation in the
piping line.

B. Installation:
WARNING:
1. Remove ratio controller from shipping crate and remove If a customer supplied ball check valve will be
plastic protectors. installed on the foam concentrate supply line, the
2. Observe flow arrow on body for proper flow direction. ball check valve spring must be removed before
Ratio controller and water inlet spool piece (if provided) placing the bladder tank into service. Failure
can be installed in the pipe line in any orientation. to remove the spring will result in improper
proportioning.
3. A minimum of 5 pipe diameters of straight unobstructed
pipe is required upstream and downstream of each AF recommends the appropriately sized Conbraco
ratio controller. 61-100 Series Ball Check Valve, or equal, with
“spring removed” for use with AF bladder tanks.
4. Water supply and foam concentrate piping between the Contact AF Engineering Department for questions
ratio controller and the bladder tank must be designed or problems.
and installed so that the total pressure differential
between the ratio controller water inlet and the foam For proper operation, the ball check valve must be
concentrate inlet does not exceed 2 psi. Refer to page installed in the vertical position.
8-2, Fig. 8-1, RCF (RCT) Installation Illustration. 8. A water pressure shutoff valve is recommended on
5. Piping connected to the ratio controller must be self- the water pressure supply line.
supporting so that no strain is imposed on the ratio 9. A check valve is required on the water pressure supply
controller body. line of each ratio controller when 2 or more ratio
6. A concentrate shutoff valve must be installed on the controllers are supplied from a common bladder tank.
foam concentrate supply line. 10. Install Ratio Controller in system piping as shown in
7. A check valve must be installed on the foam concentrate Fig. 8-1, RCF (RCT) Installation Illustration.
supply line to prevent backflow of water into the foam 11. Install a 150# non-asbestos full face flange gasket on
concentrate supply line. the water inlet side and the foam solution side of the
ratio controller.
NOTE: When multiple ratio controllers (more than 1) are
used in the proportioning system, the above installation
instructions apply to each ratio controller on the system.

06/18 8-1
RATIO CONTROLLER STORAGE & INSTALLATION BLADDER TANK PROPORTIONING SYSTEM

CHECK VALVE WATER PRESSURE SUPPLY


(Needed only if 2 or more TO BLADDER TANK
Ratio Controllers are installed)

WATER PRESSURE
SUPPLY VALVE

RATIO
SPOOL PIECE CONTROLLER
(If Provided)

WATER FOAM
SUPPLY SOLUTION

WATER SUPPLY A A
PRESSURE DIFFERENTIAL
VALVE
BETWEEN THESE TWO POINTS
SHALL NOT EXCEED 2 PSI

FOAM
CONCENTRATE
SUPPLY
FROM
BLADDER
FOAM CONCENTRATE
TANK CHECK VALVE
SUPPLY VALVE
WATER
SENSING PORT
(PLUGGED)

FOAM CONCENTRATE
SUPPLY INLET

PROPORTIONING
ADJUSTMENT SCREW
(SEE NOTE)
VIEW A - A

CAUTION: CAUTION:
Proportioning adjustment screw is shown for Failure to follow these installation instructions will
recognition only. The proportioning adjustment prevent proper operation and/or cause failure of
screw allows the factory to adjust the calibration the foam system.
of the proportioner to compensate for the type of
concentrate and manufacturing tolerances. This is
a factory adjustment and it is not to be adjusted in
the field. Tampering with this adjustment will effect
the percentage of injection of foam concentrate and
may cause failure of the system.

FIGURE 8-1
RCF/RCT Installation Illustration

8-2 06/18
BLADDER TANK PROPORTIONING SYSTEM RATIO CONTROLLER STORAGE & INSTALLATION

8-2. 3ʺ Thru 8ʺ RCW (Between the Flange Type) Units

A. Storage: 7. A check valve must be installed on the foam concentrate


supply line to prevent backflow of water into the foam
1. Ratio Controllers are machined brass castings and concentrate supply line.
contain no moving parts.
WARNING:
2. For protection against physical damage, a ratio If a customer supplied ball check valve will be
controller should be kept in its shipping crate until installed on the foam concentrate supply line, the ball
time of installation. Protective wrapping or packing check valve spring must be removed before placing
materials should not be removed until just preceding the bladder tank into service. Failure to remove the
RCW installation in the piping line. spring will result in improper proportioning.
B. Installation: AF recommends the appropriately sized Conbraco
1. Remove ratio controller from shipping crate and remove 61-100 Series Ball Check Valve, or equal, with “spring
plastic protectors. removed” for use with AF bladder tanks. Contact AF
Engineering Department for questions or problems.
2. Observe flow arrow on body for proper flow direction.
Ratio controller and water inlet spool piece (if provided) For proper operation, the ball check valve must be
can be installed in the pipe line in any orientation. installed in the vertical position with the flow arrow
pointing to the ratio controller.
3. A minimum of 5 pipe diameters of straight unobstructed
pipe is required upstream and downstream of each ratio 8. A water pressure shutoff valve is recommended on the
controller. water pressure supply line.

4. Water supply and foam concentrate piping between the 9. A check valve is required on the water pressure supply
ratio controller and the bladder tank must be designed line of each ratio controller when 2 or more ratio
and installed so that the total pressure differential controllers are supplied from a common bladder tank.
between the ratio controller water inlet and the foam 10. Install Ratio Controller in system piping as shown in
concentrate inlet does not exceed 2 psi. Refer to Fig. Fig. 8-2, RCW Installation Illustration below.
8-2, RCW Installation Illustration below.
11. Install a 150# non-asbestos ring gasket on the water inlet
5. Piping connected to the ratio controller must be self- side and the foam solution side of the ratio controller.
supporting so that no strain is imposed on the ratio
controller body. NOTE: When multiple ratio controllers (more than 1)
are used in the proportioning system, the above installation
6. A concentrate shutoff valve must be installed on the instructions apply to each ratio controller on the system.
foam concentrate supply line.

WATER PRESSURE SUPPLY


TO BLADDER TANK
CHECK VALVE
(Needed only if 2 or more
Ratio Controllers are installed)

SPOOL PIECE WATER PRESSURE


RATIO
(If Provided) SUPPLY VALVE
CONTROLLER

WATER FOAM
SUPPLY SOLUTION

WATER SUPPLY
VALVE PRESSURE DIFFERENTIAL
BETWEEN THESE TWO POINTS
SHALL NOT EXCEED 2 PSI CHECK VALVE

FOAM CONCENTRATE
FOAM CONCENTRATE SUPPLY SUPPLY VALVE
FROM BLADDER TANK

FIGURE 8-2
RCW Installation Illustration

06/18 8-3
BLADDER TANK PROPORTIONING SYSTEM WATER POWERED BALL VALVE INSTALLATION

CHAPTER 9
WPBV-M2 WATER POWERED BALL VALVE INSTALLATION
- SUPPLIED AS LOOSE COMPONENT -

9-1. Standard Models - Description


Angus Fire Water Powered Ball Valves are designed for carbon steel brackets and mounting hardware.
use when automatic valve actuation is required. Actuation • stainless steel actuating cylinder with clevis and quick
is accomplished by using a pressurized water supply as release pull pin.
the actuating agent. • 1/4ʺ FNPT bronze wye strainer with flush out valve.
The pressurized water supply enters the water powered ball The water powered ball valve assembly is capable of
valve assembly thru a 1/4ʺ FNPT inlet, passes through a manual override by disengaging the cylinder from the
wye strainer and is directed through a run of hose to the ball valve handle. Simply remove the quick release pull
valve actuating cylinder. As the pressurized water energizes pin from the rod clevis and the valve is ready for manual
the cylinder, a piston and rod assembly are forced the full operation or resetting.
internal travel of the cylinder body. The piston and rod
assembly in turn operate a rod clevis that is connected to CAUTION:
the ball valve operating handle by a quick release pull pin. Be sure to replace the quick release pull pin after
When the cylinder piston and rod assembly have reached resetting the ball valve.
the end of their stroke the ball valve will be fully open. The Water Powered Ball Valve Assembly is installed in
The Water Powered Ball Valve Assembly consists of the the normally closed stand-by valve position. The operating
following major components: pressure range is 30 psi(2.0 Bar) minimum to 250 psi(17.0
Bar) maximum water supply pressure. The assembly is
• a brass body ball valve with chrome plated ball. capable of operating in a horizontal or vertical mounting
• stainless steel valve handle. position.
• brass inlet pipe with stainless steel, brass or plated

9-2. Solenoid Release Models - Description


Angus Fire Solenoid Release Water Powered Ball Valves • stainless steel valve handle.
are designed for use when automatic valve actuation by • brass inlet pipe with stainless steel, brass or plated
electric current is required. Automatic actuation occurs carbon steel brackets and mounting hardware.
when an electric current energizes(opens) the solenoid • a two way solenoid valve(normally closed).
valve, allowing a pressurized water supply to be used as • stainless steel actuating cylinder with clevis and quick
the valve actuating agent.The solenoid valve(normally release pull pin.
closed) is energized by either a 120 VAC or 24 VDC • 1/4ʺ FNPT bronze wye strainer with flush out valve.
electric current. • 1/4ʺ FNPT brass cylinder drain valve.
• 1/4ʺ FNPT brass water supply inlet valve.
The pressurized water supply enters the water powered ball
valve assembly thru a 1/4ʺ FNPT cylinder water pressure The water powered ball valve assembly is capable of manual
supply valve(normally open), passes through a wye strainer, override by disengaging the cylinder from the ball valve
across the solenoid valve and a cylinder drain valve and handle. Simply remove the quick release pull pin from
is directed through a run of hose to the valve actuating the rod clevis and the valve is ready for manual operation
cylinder. As the pressurized water energizes the cylinder, or resetting.
a piston and rod assembly are forced the full internal travel
of the cylinder body. The piston and rod assembly in turn CAUTION:
operate a rod clevis that is connected to the ball valve Be sure to replace the quick release pull pin after
operating handle by a quick release pull pin. When the resetting the ball valve.
cylinder piston and rod assembly have reached the end of The Water Powered Ball Valve Assembly is installed in the
their stroke the ball valve will be fully open. normally closed stand-by valve position and opens when the
The Solenoid Release Water Powered Ball Valve Assembly solenoid valve is energized(opened). The operating pressure
consists of the following major components: range is 30 psi(2.0 Bar) minimum to 250 psi(17.0 Bar)
maximum water supply pressure. The assembly is capable
• a brass body ball valve with chrome plated ball. of operating in a horizontal or vertical mounting position.

06/18 9-1
WATER POWERED BALL VALVE INSTALLATION BLADDER TANK PROPORTIONING SYSTEM

9-3. General Installation


1. The valve assembly can be mounted in any orientation.
However, the strainer must be mounted in the horizontal
or vertical position as illustrated. If Water Flow
necessary, remove the strainer/drain
valve and repipe to provide the proper Water Flow
To Cylinder
orientation.
NOTE: Refer to page 9-3, Figure 9-1, Strainer
Water Powered Balll Valve Installation Strainer
Illustration for typical installation.
2. Valve assembly must be mounted to allow Drain Valve
full range of motion of the operating handle. To Cylinder
3. When a Water Powered Ball Valve is installed as the Drain Valve
Automated Foam Concentrate Supply Valve No. 1A,
normally open valve must be installed in the water supply line downstream of the water powered ball
pressure supply line to the cylinder actuator. This valve valve.
allows system flushing or a water system test without
actuating the water powered ball valve. NOTE: Close WARNING:
valve during system flushing or testing water system. If a customer supplied ball check valve will be
installed on the foam concentrate supply line, the
CAUTION: ball check valve spring must be removed before
Provision should be made to ensure the cylinder placing the bladder tank into service. Failure
water pressure shut-off valve is always in the open to remove the spring will result in improper
position when the system is in the stand-by mode. proportioning.
To prevent accidental closure of the shut-off valve,
use a nylon wire tie or safety wire to secure it in AF recommends the appropriately sized Conbraco
the open position. 61-100 Series Ball Check Valve, or equal, with
“spring removed” for use with AF bladder tanks.
4. Cylinder water pressure source (dry system piping): Contact AF Engineering Department for questions
a. Tap off deluge valve alarm pressure switch or or problems.
water motor alarm line. For proper operation, the ball check valve must be
b. Tap off main water supply line downstream of installed in the vertical position.
water supply valve to ratio controller. 7. Working pressure:
c. Tap off water sensing port on ratio controller. Minimum - 30 PSI (2 Bar)
NOTE: If using other than this water pressure Maximum - 250 PSI (17 Bar)
source, the water sensing port on the ratio
controller must be plugged (1/4ʺ NPT). 8. After installation, test the water powered ball valve
for proper operation.
CAUTION:
When using cylinder water pressure source b or Installation for Water Powered Ball Valves
c, an interval of time may elapse between system with Solenoid Release:
initiation and actuation of the water powered
ball valve. The time lapse will depend on the time 1. Follow the preceding instructions for standard model
required to fill the piping and increase pressure to WPBV installation.
the minimum required to actuate the valve. 2. Provide the correct voltage (120VAC or 24 VDC) to
NOTE: The strainer / drain valve remains stationary the WPBV. Conduit connection - 1/2” FNPT.
during operation; therefore, water pressure supply line 3. All wiring, electrical installations and equipment must
piping can be rigid. conform to the provisions of the National Electric Code
5. When a Water Powered Ball Valve is used on the system and also all local codes.
as the Automatic Foam Concentrate Supply Valve No. 4. The solenoid valve control circuit must be supervised.
1A, it must be installed along with a manual Foam
Concentrate Supply Valve No. 1. The Automatic Foam 5. Refer to page 6 for typical installation illustration.
Concentrate Supply Valve No. 1A is normally closed
and the Manual Foam Concentrate Supply Valve No. WARNING:
1 is normally open in the stand-by mode. Keep face and body away from drain valve when
venting water powered ball valve.
6. A check valve must be mounted in the foam concentrate

9-2 06/18
BLADDER TANK PROPORTIONING SYSTEM WATER POWERED BALL VALVE INSTALLATION

WATER PRESSURE SUPPLY


CHECK VALVE
TO BLADDER TANK
(Needed only if 2 or more
Ratio Controllers are installed)

WATER PRESSURE
SUPPLY VALVE
(Valve No. 2)

RATIO
SPOOL PIECE CONTROLLER
(If Provided)

FOAM
SOLUTION

PRESSURE DIFFERENTIAL A A
WATER SUPPLY
BETWEEN THESE TWO POINTS
VALVE
SHALL NOT EXCEED 2 PSI
CHECK VALVE

AUTOMATIC FOAM CONCENTRATE


CYLINDER WATER
SUPPLY VALVE NO. 1A
PRESSURE SUPPLY
(WATER POWERED BALL VALVE)
SHUT-OFF VALVE
(WITH DRAIN)AND
/,1( ‫ފ‬2'
OPERATING CYLINDER 78%(25‫ފ‬3,3(

MANUAL
FOAM CONCENTRATE
SUPPLY VALVE NO. 1

FOAM CONCENTRATE SUPPLY


FROM WATER
BLADDER TANK SENSING PORT
(PLUGGED)
FOAM CONCENTRATE
SUPPLY INLET

CAUTION:
Proportioning adjustment screw is shown for PROPORTIONING
recognition only. The proportioning adjustment ADJUSTMENT SCREW
screw allows the factory to adjust the calibration VIEW A - A (SEE NOTE)

of the proportioner to compensate for the type of


concentrate and manufacturing tolerances. This is
a factory adjustment and it is not to be adjusted in CAUTION:
the field. Tampering with this adjustment will effect Failure to follow these installation instructions will
the percentage of injection of foam concentrate and prevent proper operation and/or cause failure of
may cause failure of the system. the foam system.

FIGURE 9-1
WPBV-M2 Water Powered Ball Valve Installation Illustration

06/18 9-3
BLADDER TANK PROPORTIONING SYSTEM TANK BLADDER INTEGRITY TEST

CHAPTER 10 - TANK BLADDER INTEGRITY TEST

10-1. Purpose
The purpose of the bladder integrity test is to insure that the bladder integrity procedure on their particular tank(s)
there are no holes or tears in the bladder prior to filling the to check for possible damage that may have occured to the
tank with foam concentrate. bladder during shipping, handling or installation.
Although each Angus Fire tank bladder is tested before CAUTION:
it leaves our factory, AF recommends that the customer, Failure to perform this procedure could result in loss
before filling and placing the tank into service, perform of foam concentrate and delay in placing the bladder
tank proportioning system into service.
10-2. Required Equipment
The following equipment is required to properly test vent hose, with a male NPT swivel, for connection to
the integrity of a Angus Fire tank bladder: Foam Concentrate Vent Valve 5, a pail or water tight
container, large enough to hold at least 6ʺ of water and
1. An open top 55 gallon drum completely filled with a weighted end piece to hold and maintain the hose at
clean fresh water. The 55 gallon drum described in the bottom of the pail. This arrangement allows any
the bladder tank filling procedures page 3-1, Sect. 3-1, air inside the bladder to be discharged to the water
Item 1 will be appropriate for this requirement. pail/container. The hose described in the bladder tank
2. A length of 3/4ʺ rubber garden hose which allows filling procedures Sect. 3-1., page 3-1, Item 2 will be
the air used to compress the bladder and discharged appropriate for this requirement.
through the Tank Water Vent Valve 4, to be directed 4. A clean air or nitrogen supply and heavy duty
to the 55 gallon drum. A weighted end piece to hold compressor hose. The air supply/hose arrangement
and maintain the hose at the bottom of the drum is attaches to the Water Drain/Fill Valve 6 and provides
required. The rubber hose described in the bladder air, used to compress the bladder, to the inside of the
tank filling procedures Sect. 3-1., page 3-2, Item 6 tank shell. The hose and air supply as described in the
will be appropriate for this requirement. bladder tank filling procedures Sect. 3-1., page 3-1,
3. An appropriate length of 1ʺ clear air/foam concentrate Item 4 will be appropriate for this requirement.

10-3. Bladder Integrity Testing Procedures


1. Set up the tank and testing equipment as described As the tank shell fills with air and the bladder is fully
in Sect. 10-2 and as shown in the illustration on page collapsed, the air bubbles through Valve 5 will slow
10-2. Ensure that there is no water in the shell and down and bubbles will start to escape through Valve 4.
that there is no foam concentrate in the bladder before This decrease of air bubbles from Valve 5 and an increase
proceding to step 2. from Valve 4 will continue for a period of time and should
develope into a steady stream of air bubbles escaping from
2. Open valves 4, 5 & 6. Make sure that all other valves
Valve 4. Air bubbles from Valve 5 should stop completely at
on the bladder tank are closed.
this point. If no air bubbles are noted from Valve 5 into the
CAUTION: pail of water, then positive bladder integrity is indicated and
Valves 4, 5 & 6 must be opened to avoid damage to the you may proceed with the bladder tank filling procedures
bladder and assure a proper bladder integrity test. as described in this manual in Chapter 3.
3. Add air to the tank through Valve 6. A steady stream of CAUTION:
air will start to escape through Valve 5 as the bladder If a steady stream of bubbles continue to escape
is collapsed. This air will show itself as bubbles in the through Valve 5, then a hole or tear in the bladder is
pail of water. indicated. Contact the Angus Fire Parts Department
for information on tank bladder replacement or for
NOTE: The amount of time it takes before air escape questions or problems regarding the bladder integrity
through Valves 4 & 5 is in relation to the air supply
testing procedures.
pressure and the size of the tank.

06/18 10-1
TANK BLADDER INTEGRITY TEST BLADDER TANK PROPORTIONING SYSTEM

IF NO AIR BUBBLES NOTED: NOTE:


POSITIVE BLADDER INTEGRITY • Open Valves 4, 5, & 6. Make sure that all other valves
on the bladder tank are closed.
• Drain any residual water from the shell before
conducting integrity test.
• Drain all foam concentrate from the bladder before
conducting integrity test.

IF STEADY STREAM OF AIR BUBBLES NOTED:


HOLE OR TEAR IS INDICATED

4 5 2

55 GAL. DRUM
FILLED WITH
WATER AIR AIR

1A
8
1 7

AIR USED TO 9
COMPRESS THE
BLADDER
DISCHARGED
THRU WATER
IN DRUM FILL MANIFOLD (SEE PAGE 3-2)

AIR SUPPLY SHUTOFF VALVE


TANK SHELL
FILLED WITH AIR
NITROGEN
OR
COMPRESSED AIR
AIR SUPPLY

BLADDER
COMPRESSED

END VIEW

FIGURE 10-1
Bladder Integrity Test Setup

10-2 06/18
Station Road, Bentham
Lancaster, LA2 7NA UK
Tele +44 (0) 1844 265000
Tel +44 (0) 15242 61166
www.angusfire.co.uk

Вам также может понравиться