Академический Документы
Профессиональный Документы
Культура Документы
6, NOVEMBER 2002
I. INTRODUCTION
(2)
Fig. 3. Compensation strategy of the DVR for voltage sags with a phase jump.
If the voltage is injected ( ) at an angle , then the flux-
: Angular position of synchronous frame.
: Angle of supply vector. V : linkage in the transformer at a later angle is given by
Actual supply vector. V : “d” coordinate of the supply. V : “q ” coordinate of
the supply. V : “” coordinate of the supply. V : “ ” coordinate of the supply.
V : Compensation vector required to correct for fault. V : Reference
vector.
(6)
(7)
for
Fig. 4. Idealized representation of injected voltage and transformer flux for a
sag of 100 V (0.7 pu of a 230 Vrms nominal supply). This results in only half the required voltage being injected
for the first half-cycle. The solution correctly positions the
Apart from rating the transformer for the transient switch on flux-linkage of the injection transformer so that subsequent full
period, another qualitative method would be to only switch the voltage may be applied after the first half cycle, as has
transformers on at a voltage peak. Unfortunately this could lead been removed, Fig. 5.
to no voltage being injected by the DVR for up to half a cycle, This approach is a better solution than the previous quan-
which is undesirable. titative methods, as the dc offset and the need for rating the
transformers for the transient switch-on period is removed. This
method is, however, still far from ideal, as the load side volt-
III. NOVEL METHODS TO LIMIT FLUX ages are not fully compensated when the flux-linkage limiter
An effective method of preventing saturation can be achieved (form factor) is operational. Certain types of industrial drives
by applying a form factor to the injected voltage, which and process equipment may be intolerant of this effect [1], [13],
would have the effect of manipulating the injected voltage in [14].
a controlled manner, until the first zero crossing is detected.
This method can be compared to the gradual increase used B. Adaptive Form Factor
in some conventional transformer systems, but here a much Depending on the amplitude of a voltage applied to a trans-
faster ramp-up time is used, i.e., in milliseconds rather than former, in order to prevent it from saturating, it is not neces-
cycles. The rest of this paper focuses on the development and sary to completely remove the D.C offset. This means for sags
verification of such algorithms. less severe than the nominal rating of the DVR, a proportion-
ately larger voltage can be initially injected. From the above dis-
A. Constant Form Factor cussion, a DVR may inject up to half its nominal rated voltage
Consider a constant factor applied for a fixed time . If a in the first half cycle without exceeding the peak transformer
voltage sag occurs at an angle , the form function which flux-linkage rating. For lesser sags, the higher voltage may be
multiplies the injected voltage for a further angle , can be rep- used. This results in a residual flux-linkage offset but the peak
resented by the series flux is not exceeded. This result leads to the development of
more sophisticated form factors, which aim only to prevent the
maximum flux-linkage excursion from being exceeded. This
helps to reduce the voltage disturbance seen by a sensitive load
(5) during the initial stage of the voltage sag, while still maintaining
correct transformer operation.
This leads to a residual flux-linkage in the injection transformer The adaptive form factor developed in this paper predicts the
after the angle of , with the general flux-linkage at any amount the flux-linkage maximum will be exceeded during the
FITZER et al.: MITIGATION OF SATURATION 1061
(12)
(13)
initial stage of the voltage sag, if at all. The basis of the adaptive
In order to determine the “ ” value, needs to be predicted
form factor is
(13). If then as previously “ ” requires
scaling
(8)
(14)
where can be evaluated as
(9) (15)
“ ” now replaces . Applied to Fig. 6 the formula be- In order to be able to use equations (8)–(15), one must determine
comes the injected voltage amplitude , and the point on wave that
the voltage sag commences with reference to a cosine wave “ ,”
as above. Also if the magnitude of a voltage sag may change
within the first cycle or so compared with its initial value, “ ”
(10)
must be adjusted if the correct transformer operation is to be
As it is the negative portion of the injected voltage that may
ensured.
cause the start-up flux-linkage to exceed the maximum value
in Fig. 6, only the negative portion of the waveform requires
scaling (10). The limit in the second integral (10) indicates IV. SIMULATION RESULTS
that after this angle ( ) in Fig. 6 the flux-linkage DC offset A model of the proposed DVR system has been implemented
will have reached its steady state value. In order to determine in the simulation package PSCAD/EMTDC. The overall circuit
“ ” value required, needs to be first predicted, or evaluated, layout and control topology, are illustrated in Fig. 8.
using The simulation is based around a nominal load line voltage of
415 Vrms, which allows for direct comparisons with the experi-
mental results, Figs. 17–23. The system voltage and load power
(11)
rating, although significantly lower than in a practical DVR
1062 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 17, NO. 6, NOVEMBER 2002
Fig. 10. Voltage required to be injected to fully compensate for the dip (phase
A, simulation).
Fig. 11. The level of scaling required in order to prevent the injection
=
transformer (phase A, simulation) from saturating (1 no scaling required).
Fig. 8. PSCAD circuit and system control topology. To prevent a load from exposure to the sag, the DVR in Fig. 8
must inject a voltage of correct magnitude and phase, Fig. 10.
The voltage appears free of unwanted harmonics, as it is an
internal analog signal developed by the control system block
set, as opposed to the actual injected voltage, which is a fil-
tered PWM waveform. The small voltage that is injected during
the no-fault condition is required in order to compensate for
the slight volt-drop across the filter impedance, during normal
operating conditions. This action ensures that the transformer
flux-linkage at the sag onset and the control assumed value both
match, which is important, as the controller is purely feed-for-
ward.
The form factor to be applied to the injected voltage is cal-
culated by the flux-linkage-limiter algorithm. The form factor
Fig. 9. Supply voltage during a balanced dip (phase A, simulation).
calculated is effectively a continuously changing variable by
which the injected voltage is multiplied, Fig. 11. As the magni-
system, still allow for feasible results to be obtained, which are tude of the injected voltage varies slightly with time, the scaling
not overly damped. required to prevent transformer saturation must also change,
Fig. 11. Scaling is only required when the DVR is going from an
A. Summary of the Results off to on state. In the simulation this occurs twice. The second
The adaptive form factor operates on each of the three-phases fault occurs close to a zero crossing, hence the severe scaling
separately. Any type of sag, balanced or unbalanced, can be pre- as expected. The step appearance of Fig. 11 is due to the flux-
sented to the DVR system in order to verify the flux-limiting linkage-limiter algorithm only operating on the analog signal
process. The fault generator, Fig. 8, is set up to give a balanced Fig. 10 at a sampling rate of 1 ms.
three-phase dip to 70% of a nominal 230 V(rms) supply, Fig. 9. The modified injected voltage is shown in Fig. 12. This
The fault occurs, appears to clear, then re-occurs again. The produces a maximum flux-linkage excursion of not more than
flux-linkage limiter is programmed in such a way that when a 0.32 Wb-turns, Fig. 13. The peak flux-linkage limit varies
sag ends, it is assumed that the flux-linkage of the transformer depending on the magnitude of voltage dip a DVR is required
drops close to zero before another fault occurs. to compensate for. For this simulation a flux-maximum of 0.32
FITZER et al.: MITIGATION OF SATURATION 1063
Fig. 19. Level of scaling required in order to prevent the injection transformer
=
(phase A, experiment) from saturating (1 no scaling required).
Fig. 22. Load voltage (phase A, experiment).
APPENDIX
Derivation of
(A16)
(A17)
(A18)
(A19)
Fig. 23. (a) Ideal and average 3-phase rms voltage. (b) Percentage deviation REFERENCES
from the ideal (experiment).
[1] M. H. J. Bollen, Understanding Power Quality Problems; Voltage Sags
and Interruptions. New York: IEEE Press.
sag on-set the actual transformer flux-linkage is sufficiently [2] Gyugyi, et al., “Apparatus and method for dynamic voltage restoration
of utility distribution networks,” U.S. Patent 5 329 222, July 12, 1994.
small that is can be considered approximately zero. [3] C. Zhan, V. K. Ramachandaramurthy, A. Arulampalam, C. Fitzer, S.
The other results Figs. 19–23, illustrate a control response Kromlidis, M. Barnes, and N. Jenkins, “Dynamic voltage restorer based
that matches that seen in the simulation results. The apparent on voltage space vector PWM control,” IEEE Trans. Ind. Applicat., vol.
37, pp. 1855–1863, Nov./Dec. 2001.
noise on some of the signals is due to harmonics on the supply [4] C. Zhan, C. Fitzer, V. K. Ramachandaramurthy, A. Arulampalam, M.
voltage, which are caused by a nearby computer cluster. The Barnes, and N. Jenkins, “Software phase-locked loop applied to Dy-
harmonics introduce small errors within the magnitude detec- namic Voltage Restorer (DVR),” in Proc. IEEE PES Winter Meeting,
2001, pp. 1033–1038.
tion algorithm, as the equations used have been developed only [5] K. Haddad, G. Joos, and S. Chen, “Control algorithms for series voltage
to deal with fundamental frequency information. regulators in faulted distribution systems,” in Proc. IEEE PESC’99
Conf., vol. 1, 1999, pp. 418–423.
[6] C. S. Chang, S. W. Yang, and Y. S. Ho, “Simulation and analysis of
VI. CONCLUSION Series Restorers (SVR) for voltage sag relief,” in Proc. IEEE PES Winter
Meeting, 2000.
This paper has proposed and verified a method that removes [7] V. Kaura and V. Blasko, “Operation of a phase locked loop system under
the need for rating the series injection transformers of the DVR distorted utility conditions,” IEEE Trans. Ind. Applicat., vol. 33, pp.
58–63, Jan./Feb. 1997.
for transient switch-on period, and therefore removes the redun- [8] B. H. Li, S. S. Choi, and D. M. Vilathgamuwa, “On some crucial tech-
dancy normally associated with their steady-state operation. In nologies for dynamic voltage restoration,” in Proc. 5th Int. Power Eng.
economic terms, this may reduce the total cost of a DVR system, Conf. (IPEC), 2001, pp. 426–431.
[9] R. S. Weissbach, G. G. Karady, and R. G. Farmer, “Dynamic voltage
thus making it a more attractive solution for voltage sag mitiga- compensation on distribution feeders using flywheel energy storage,”
tion. IEEE Trans. Power Delivery, vol. 14, pp. 465–471, Apr. 1999.
The simulation and experimental results illustrate that the av- [10] P. Verdelho and G. D. Marques, “Four wire current-regulated PWM
voltage converter,” IEEE Trans. Ind. Electron., vol. 45, pp. 761–770,
erage rms 3-phase voltage and the individual transformer flux- Oct. 1998.
linkages can be maintained within specified limits via a feed- [11] H. Fujita and H. Akagi, “The unified power quality conditioner: The
forward digital controller. integration of series and shunt active power filters,” IEEE Trans. Power
Electron., vol. 13, pp. 315–322, Mar. 1998.
It is possible for particular loads to be sensitive to the varia- [12] B. Singh, K. Al-Haddad, and A. Chandra, “A review of active filters for
tions in rms voltage caused by the adaptive form factor. The vari- power quality improvement,” IEEE Trans. Ind. Electron., vol. 46, pp.
ations can be made less severe by using transformers of higher 960–971, Oct. 1999.
[13] J. C. Smith, J. Lamoree, P. Vinett, T. Duffy, and M. Klein, “The impact of
flux ratings and adjusting the control such that it limits the in- voltage sags on industrial plant loads,” in Proc. Int. Conf. Power Qual/:
jected voltage proportionally less. End-Use Applicat. Perspectives (PQA-91), 2002, pp. 171–178.
1066 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 17, NO. 6, NOVEMBER 2002
[14] L. Conrad, K. Little, and C. Grigg, “Predicting and preventing problems Mike Barnes received the B.Eng. and Ph.D. degrees
associated with remote fault-clearing voltage dips,” IEEE Trans. Ind. from the University of Warwick, U.K., in 1993 and
Applicat., vol. 27, pp. 167–172, Jan. 1991. 1998, respectively.
He has worked as a Research Associate on a
DTI/LINK project on low cost switched reluctance
drives and as a Lecturer at Warwick. For the last
Chris Fitzer was born in Preston, U.K., in 1977. He five years he has been a Lecturer at the University
received the B.Sc. (with honors) degree in electronics of Manchester Institute of Science and Technology,
from the University of Central Lancashire, Preston, Manchester, U.K., where his research interests have
in 1999 and is currently pursuing the Ph.D. degree at covered power electronics applied to power systems,
the University of Manchester Institute of Science and machine drives, and photovoltaics.
Technology, Manchester, U.K.
His research interests are digital control of
power quality devices, dynamic voltage restorers,
transformer saturation prevention, digital signal
processing, and hybrid filters.
Atputharajah Arulampalam was born in Sri Lanka Rainer Zurowski (1965) received the Dipl.Ing.
in 1971. He received the B.Sc.Eng. (with honors) de- degree in electrical engineering from Friedrich
gree from the University of Peradeniya, Sri Lanka, Alexander University, Erlangen, Germany, in 1991
in 1997 and is currently pursuing the Ph.D. degree at and the Dr.Ing. degree from Ruhr University,
the University of Manchester Institute of Science and Bochum, Germany, in 2001.
Technology, Manchester, U.K. Since 1992, he has been with the System Planning
Since 1998, he has been a Lecturer with the De- Department, SIEMENS AG, Erlangen. His main
partment of Electrical and Electronic Engineering, activity is research and development of power
University of Peradeniya. His research interests are electronics based equipment for power quality
the applications of FACTS devices, power quality, improvement in transmission and distribution
and converter configurations. networks.