Вы находитесь на странице: 1из 9

1058 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 17, NO.

6, NOVEMBER 2002

Mitigation of Saturation in Dynamic Voltage Restorer


Connection Transformers
Chris Fitzer, Atputharajah Arulampalam, Mike Barnes, and Rainer Zurowski

Abstract—During the transient period at the start of a voltage


sag, a DVR injection transformer can experience a flux-linkage
that is up to twice its nominal steady-state value. In order to
prevent the transformers from saturating it is normal to choose
a rating flux that is double that of the steady-state limit. An
alternative method is to limit the flux-linkage during the transient
switch-on period, thus preventing saturation. It is shown through
both simulation and experimental results that an adaptive form
factor can be applied to the DVR injected voltage, which mini-
mizes the disturbance seen by a sensitive load, while at the same Fig. 1. Equivalent electrical circuit diagram of the DVR.
time preventing saturation.
The proposed method removes the need for rating the series in-
jection transformers for the DVR transient switch-on period, and
therefore removes the redundancy normally associated with their
steady state operation. In economic terms, this may reduce the total
cost of a DVR system, thus making it a more attractive solution for
voltage sag mitigation.
Index Terms—Active power injection, DVR, sensitive loads,
space vector control, transformer saturation, voltage sags.

I. INTRODUCTION

V OLTAGE sags can be defined as momentary reductions in


supply voltage, lasting from a few milliseconds to a few
cycles. Due to the increased use of sensitive automated manu-
facturing and IT equipment, so-called sags or dips are becoming
an increasing problem.
When a sag causes an uncontrolled shutdown in an IT system
or industrial process the cost of the interruption may be dis- Fig. 2. Typical installation location of a dynamic voltage restorer.
proportionately large compared with the apparent severity of
the cause. This has been the fundamental reason for developing voltage and last for anything from a few milliseconds to a few
mitigation devices, which effectively buffer (completely or par- seconds [1]. It has been shown [1] that mitigation devices that
tially) the supply and a potentially sensitive load. A well-es- support rather than completely buffer the supply from a sen-
tablished device in the information technology industry is the sitive load need only be a fraction of the power rating of the
“un-interruptible power supply” or “UPS” for short. This typi- load and have much lower energy storage requirement com-
cally is a device connected between the load and supply, de-cou- pared with the traditional UPS. It has also been shown [1] that
pling both, thus offering protection for all types of supply fluc- series connected voltage support devices can have a lower rating
tuations, whether they be short duration sags, or longer term out- than the shunt connected variants. A series device or “Dynamic
ages. For industry, where loads are normally rated in the MW Voltage Restorer” (DVR) [1]–[6], [8], [9] as it is more com-
range, the UPS device is no-longer the most economic solu- monly known, injects a voltage in series with the supply to elim-
tion, as such a device would be required to have a power rating inate any voltage sags seen by a load (Fig. 1).
greater or equal to that of the load. The majority of voltage re- Fig. 2 highlights the problem a DVR is used to solve. Faults
ductions are typically to about 0.7 pu of a nominal 1.0 pu supply on adjacent feeders cause the receiving end voltage seen by a
load to reduce. A single-phase to ground short is a common
Manuscript received October 26, 2001; revised May 28, 2002. Recommended fault. The reduction seen by the DVR in such a case is a two-
by Associate Editor J. H. R. Enslin. phase dip with phase angle shift due to the “delta–wye” trans-
C. Fitzer, A. Arulampalam, and M. Barnes are with the Manchester Centre
for Electrical Energy (MCEE), Department of Electrical Engineering and former interconnection. Depending on the power factor of the
Electronics, University of Manchester Institute of Science and Technology load, the DVR is required to supply both real and reactive power
(UMIST), Manchester M60 1QD, U.K. (e-mail: mike.barnes@umist.ac.uk). so as to provide complete compensation for the dip.
R. Zurowski is with the System Planning Department, SIEMENS AG, EV SE
NC4, Erlangen D91050, Germany. A fast response feed-forward control system has already been
Digital Object Identifier 10.1109/TPEL.2002.805584 presented in [3]–[5] where a digital controller can quickly de-
0885-8993/02$17.00 © 2002 IEEE
FITZER et al.: MITIGATION OF SATURATION 1059

problems associated with this type of system, which still require


further investigation [8].
To correct for the effects of voltage sags, DVR’s are required
to inject both positive and negative sequence voltage vectors.
This unfortunately presents problems with unbalanced fluxes
if conventional three-limb injection transformers are used. To
avoid this, which mainly would be a result of a nonzero flux
in the center or common limb, three separate injection trans-
formers are utilized. This allows the flux-linkage in each to be
dealt with separately and remains true regardless of the external
configuration, star, or delta. The injection voltage across the pri-
mary coil (DVR side) of one of the three injection transformers
can be represented by

(2)

Fig. 3. Compensation strategy of the DVR for voltage sags with a phase jump.
If the voltage is injected ( ) at an angle , then the flux-
 : Angular position of synchronous frame. : Angle of supply vector. V : linkage in the transformer at a later angle is given by
Actual supply vector. V : “d” coordinate of the supply. V : “q ” coordinate of
the supply. V : “ ” coordinate of the supply. V : “ ” coordinate of the supply.
V : Compensation vector required to correct for fault. V : Reference
vector.

termine the injected voltage that is required to ride-though a


voltage sag. The control topology is based around a rotating ref- (3)
erence frame [ ] locked on to the fundamental positive se-
quence component of the supply voltage, which is represented If and , then
in a fixed [ ] frame [3]–[5], [7], [10]–[12]. and
are generated by
(4)

As illustrated by (4) and Fig. 4, if , or the start of a voltage sag,


occurs at (zero crossing), the flux-linkage during the
(1) first few cycles or more, depending on the transformer loading,
can be as much as double its steady-state value. This is due to
Fig. 3 illustrates a typical instantaneous snapshot of the con- an inherent dc offset that is created when the voltage applied, or
trol system vectors when a single-phase outage on a nearby injected, does not commence at a voltage maxima or minima. If
feeder causes both positive and negative sequence error infor- the injected voltage amplitude is close to the maximum voltage
mation to be generated. In the plane this is seen as a magni- rating of the injection transformer, then in the first few cy-
tude dip (positive sequence error) of the phasor , along with a cles can be as much as double the maximum rating and
100 Hz superimposed oscillation (negative sequence error). At this could result in the transformer saturating. The above re-
any instant a compensation vector (or phasor) can be calculated mains true provided that the interval between successive sags
by subtracting the actual vector from a reference vector, gen- is long enough to allow transformer fluxes to decay to zero.
erated by a phase-locked-loop (PLL). The error (or compensa- It is assumed in this paper that apart from the flux-linkage is-
tion) vector can then be used in various PWM schemes. In [3] sues there are no other transient delays in bringing the DVR on-
space-vector-pulse-width-modulation (SVPWM) was chosen as line. In practice this can be achieved by injecting a zero voltage
the DVR inverter control pattern. If a wye–wye interconnection during “normal” or “no-fault” conditions, rather than short-cir-
transformer is used in place of a delta–wye (Fig. 3), then the cuiting the DVR with an external crowbar. In the investigation
control and PWM scheme can be modified to so as to deal into transformer saturation a small voltage vector is injected
with any zero-sequence information generated [10]. during “no-fault” operation to correct for the slight fundamental
volt drop across the filter impedance.
A starting point in eliminating saturation would be to rate the
II. CONVENTIONAL METHODS TO LIMIT FLUX
injection transformers for the worst-case scenario, which would
The aim of this paper is to highlight and propose a possible be double the steady-state flux-linkage rating. For large loads
solution to one of the transient switch-on issues surrounding (in the MW range), doubling the transformer rating involves a
the use of series injection transformers as part of a dynamic significant increase in the cost, which may result in the DVR not
voltage restoration system. Transformer-less operation has been being cost effective. A more desirable option is to avoid the dou-
suggested as a possible remedy, however there are a number of bling of the flux-linkage during the first few cycles altogether.
1060 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 17, NO. 6, NOVEMBER 2002

subsequent angle radians later given by

(6)

where can be evaluated [Appendix (A16)–(A19)] to be

(7)

Referring back to (4), one method to prevent saturation is to


entirely remove or prevent a DC flux-linkage component .
This can be achieved by the solution of (7). Analytical methods
give one solution as

for
Fig. 4. Idealized representation of injected voltage and transformer flux for a
sag of 100 V (0.7 pu of a 230 Vrms nominal supply). This results in only half the required voltage being injected
for the first half-cycle. The solution correctly positions the
Apart from rating the transformer for the transient switch on flux-linkage of the injection transformer so that subsequent full
period, another qualitative method would be to only switch the voltage may be applied after the first half cycle, as has
transformers on at a voltage peak. Unfortunately this could lead been removed, Fig. 5.
to no voltage being injected by the DVR for up to half a cycle, This approach is a better solution than the previous quan-
which is undesirable. titative methods, as the dc offset and the need for rating the
transformers for the transient switch-on period is removed. This
method is, however, still far from ideal, as the load side volt-
III. NOVEL METHODS TO LIMIT FLUX ages are not fully compensated when the flux-linkage limiter
An effective method of preventing saturation can be achieved (form factor) is operational. Certain types of industrial drives
by applying a form factor to the injected voltage, which and process equipment may be intolerant of this effect [1], [13],
would have the effect of manipulating the injected voltage in [14].
a controlled manner, until the first zero crossing is detected.
This method can be compared to the gradual increase used B. Adaptive Form Factor
in some conventional transformer systems, but here a much Depending on the amplitude of a voltage applied to a trans-
faster ramp-up time is used, i.e., in milliseconds rather than former, in order to prevent it from saturating, it is not neces-
cycles. The rest of this paper focuses on the development and sary to completely remove the D.C offset. This means for sags
verification of such algorithms. less severe than the nominal rating of the DVR, a proportion-
ately larger voltage can be initially injected. From the above dis-
A. Constant Form Factor cussion, a DVR may inject up to half its nominal rated voltage
Consider a constant factor applied for a fixed time . If a in the first half cycle without exceeding the peak transformer
voltage sag occurs at an angle , the form function which flux-linkage rating. For lesser sags, the higher voltage may be
multiplies the injected voltage for a further angle , can be rep- used. This results in a residual flux-linkage offset but the peak
resented by the series flux is not exceeded. This result leads to the development of
more sophisticated form factors, which aim only to prevent the
maximum flux-linkage excursion from being exceeded. This
helps to reduce the voltage disturbance seen by a sensitive load
(5) during the initial stage of the voltage sag, while still maintaining
correct transformer operation.
This leads to a residual flux-linkage in the injection transformer The adaptive form factor developed in this paper predicts the
after the angle of , with the general flux-linkage at any amount the flux-linkage maximum will be exceeded during the
FITZER et al.: MITIGATION OF SATURATION 1061

Fig. 6. DVR injection voltage (one-of-three phases).

If then , setting and suitably rear-


ranging equation (10) to make “ ” the subject, will yield the
appropriate scaling factor by which the injected voltage must
be multiplied

(12)

Referring to Fig. 7, as it is the positive portion of the injected


voltage that may cause the start-up flux-linkage to exceed the
maximum value, only the positive portion of the waveform re-
quires scaling. Equation (10) is now changed to represent this
Fig. 5. Flux-linkage with the dc offset removed and corresponding load
voltages for a 0.7 pu balanced dip.

(13)
initial stage of the voltage sag, if at all. The basis of the adaptive
In order to determine the “ ” value, needs to be predicted
form factor is
(13). If then as previously “ ” requires
scaling
(8)

(14)
where can be evaluated as

(9) (15)

“ ” now replaces . Applied to Fig. 6 the formula be- In order to be able to use equations (8)–(15), one must determine
comes the injected voltage amplitude , and the point on wave that
the voltage sag commences with reference to a cosine wave “ ,”
as above. Also if the magnitude of a voltage sag may change
within the first cycle or so compared with its initial value, “ ”
(10)
must be adjusted if the correct transformer operation is to be
As it is the negative portion of the injected voltage that may
ensured.
cause the start-up flux-linkage to exceed the maximum value
in Fig. 6, only the negative portion of the waveform requires
scaling (10). The limit in the second integral (10) indicates IV. SIMULATION RESULTS
that after this angle ( ) in Fig. 6 the flux-linkage DC offset A model of the proposed DVR system has been implemented
will have reached its steady state value. In order to determine in the simulation package PSCAD/EMTDC. The overall circuit
“ ” value required, needs to be first predicted, or evaluated, layout and control topology, are illustrated in Fig. 8.
using The simulation is based around a nominal load line voltage of
415 Vrms, which allows for direct comparisons with the experi-
mental results, Figs. 17–23. The system voltage and load power
(11)
rating, although significantly lower than in a practical DVR
1062 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 17, NO. 6, NOVEMBER 2002

Fig. 10. Voltage required to be injected to fully compensate for the dip (phase
A, simulation).

Fig. 7. DVR injection voltage (one-of-three phases).

Fig. 11. The level of scaling required in order to prevent the injection
=
transformer (phase A, simulation) from saturating (1 no scaling required).

Fig. 8. PSCAD circuit and system control topology. To prevent a load from exposure to the sag, the DVR in Fig. 8
must inject a voltage of correct magnitude and phase, Fig. 10.
The voltage appears free of unwanted harmonics, as it is an
internal analog signal developed by the control system block
set, as opposed to the actual injected voltage, which is a fil-
tered PWM waveform. The small voltage that is injected during
the no-fault condition is required in order to compensate for
the slight volt-drop across the filter impedance, during normal
operating conditions. This action ensures that the transformer
flux-linkage at the sag onset and the control assumed value both
match, which is important, as the controller is purely feed-for-
ward.
The form factor to be applied to the injected voltage is cal-
culated by the flux-linkage-limiter algorithm. The form factor
Fig. 9. Supply voltage during a balanced dip (phase A, simulation).
calculated is effectively a continuously changing variable by
which the injected voltage is multiplied, Fig. 11. As the magni-
system, still allow for feasible results to be obtained, which are tude of the injected voltage varies slightly with time, the scaling
not overly damped. required to prevent transformer saturation must also change,
Fig. 11. Scaling is only required when the DVR is going from an
A. Summary of the Results off to on state. In the simulation this occurs twice. The second
The adaptive form factor operates on each of the three-phases fault occurs close to a zero crossing, hence the severe scaling
separately. Any type of sag, balanced or unbalanced, can be pre- as expected. The step appearance of Fig. 11 is due to the flux-
sented to the DVR system in order to verify the flux-limiting linkage-limiter algorithm only operating on the analog signal
process. The fault generator, Fig. 8, is set up to give a balanced Fig. 10 at a sampling rate of 1 ms.
three-phase dip to 70% of a nominal 230 V(rms) supply, Fig. 9. The modified injected voltage is shown in Fig. 12. This
The fault occurs, appears to clear, then re-occurs again. The produces a maximum flux-linkage excursion of not more than
flux-linkage limiter is programmed in such a way that when a 0.32 Wb-turns, Fig. 13. The peak flux-linkage limit varies
sag ends, it is assumed that the flux-linkage of the transformer depending on the magnitude of voltage dip a DVR is required
drops close to zero before another fault occurs. to compensate for. For this simulation a flux-maximum of 0.32
FITZER et al.: MITIGATION OF SATURATION 1063

Fig. 12. Injected voltage after scaling (phase A, simulation).

Fig. 13. Limited flux-linkage envelope magnitude (phase A, simulation).


Fig. 15. (a) Ideal and average 3-phase rms voltage. (b) Percentage deviation
from the ideal (simulation).

Fig. 14. Load voltage (phase A, simulation).

Wb-turns was specified which corresponds to a steady-state


Fig. 16. 10 KVA medium power hardware rig.
injected voltage of 100 V per phase.
The voltage (phase A) as seen by a sensitive load is shown in
It is important for a sensitive load that the supply be relatively
Fig. 14. Even with the flux-linkage-limiter operational, the DVR
free from any voltage fluctuations. It has been shown [1] that
still has sufficient compensation ability. When the second fault
some loads may trip or fail if the 3-phase rms supply reduces
occurs on phase A, the injected voltage required to compen-
excessively from a nominal 100% supply. Fig. 15 indicates that
sate has a magnitude that is equal to the maximum steady-state
the DVR can boost the receiving end voltage while and still
voltage rating of the transformer (100 v), but also commences
maintain correct transformer operation.
at a zero crossing. As explained in Section II this type of fault
produces the greatest flux dc offset. The only way in which to
V. EXPERIMENTAL RESULTS
prevent the transformers from saturating in this case is to halve
the injected voltage for a few milliseconds, Fig. 11. Due to this An experimental rig with potential rating of 10 kVA has
the load experiences a modest disturbance on phase “A” while been developed [3] to verify the control of the DVR in real
the flux-linkage-limiter is operational. The simulation results time. The control is realized via a pair of TMS320C4X DSP
however indicate this level of scaling is not required in all three processors.
phases at the same time, which results in the average 3-phase To introduce a fault, Fig. 16, a variable impedance is placed
rms voltage as seen by the load varying only slightly, Fig. 15. in series in-between the source and the delta–wye transformer.
1064 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 17, NO. 6, NOVEMBER 2002

Fig. 20. Injected voltage after scaling (phase A, experiment).


Fig. 17. Supply voltage during a balanced dip (phase A, experiment).

Fig. 18. Magnitude of the required injected voltage (phase A, experiment).


Fig. 21. Limited flux-linkage envelope magnitude (phase A, experiment).

Fig. 19. Level of scaling required in order to prevent the injection transformer
=
(phase A, experiment) from saturating (1 no scaling required).
Fig. 22. Load voltage (phase A, experiment).

This configuration gives fault types that are comparable with


those created by the fault generator in Fig. 8. As with the simu- pensate for the dip is shown in Fig. 18, where it is apparent
lation arrangement the load is connected to a nominal 415 V rms that there is a gradual rise in the voltage magnitude level.
3-phase supply. The load is rated at 3 kW, which is sufficient to This is due to the response of the digital control system,
test the DVR dynamic response. As with the simulation control, where the phase shifters and filters that are used to obtain
the DSP/Control coding for the adaptive form factor operates correct steady-state operation, degrade the dynamic response.
on each phase separately. The fault generator for the practical It is also noticeable that at no-fault conditions there is a
rig is set up only to give one fault, as opposed to the simulation small internal injected DVR voltage when the actual injected
where a fault occurs, appears to clear, then re-occurs again. The voltage across the transformers is approximately zero. This
following results illustrate the DVR’s ability to compensate for is for the same reason as in the simulation where the DVR is
a balanced three-phase fault. set to inject a small voltage, in order to compensate for the
A balanced three-phase fault occurs as illustrated in Fig. 17. volt drop across the transformer filter, which is created by
The magnitude of the ideal injected voltage required to com- the load curren This action is necessary to ensure that at a
FITZER et al.: MITIGATION OF SATURATION 1065

APPENDIX
Derivation of

(A16)

(A17)

(A18)

(A19)

Fig. 23. (a) Ideal and average 3-phase rms voltage. (b) Percentage deviation REFERENCES
from the ideal (experiment).
[1] M. H. J. Bollen, Understanding Power Quality Problems; Voltage Sags
and Interruptions. New York: IEEE Press.
sag on-set the actual transformer flux-linkage is sufficiently [2] Gyugyi, et al., “Apparatus and method for dynamic voltage restoration
of utility distribution networks,” U.S. Patent 5 329 222, July 12, 1994.
small that is can be considered approximately zero. [3] C. Zhan, V. K. Ramachandaramurthy, A. Arulampalam, C. Fitzer, S.
The other results Figs. 19–23, illustrate a control response Kromlidis, M. Barnes, and N. Jenkins, “Dynamic voltage restorer based
that matches that seen in the simulation results. The apparent on voltage space vector PWM control,” IEEE Trans. Ind. Applicat., vol.
37, pp. 1855–1863, Nov./Dec. 2001.
noise on some of the signals is due to harmonics on the supply [4] C. Zhan, C. Fitzer, V. K. Ramachandaramurthy, A. Arulampalam, M.
voltage, which are caused by a nearby computer cluster. The Barnes, and N. Jenkins, “Software phase-locked loop applied to Dy-
harmonics introduce small errors within the magnitude detec- namic Voltage Restorer (DVR),” in Proc. IEEE PES Winter Meeting,
2001, pp. 1033–1038.
tion algorithm, as the equations used have been developed only [5] K. Haddad, G. Joos, and S. Chen, “Control algorithms for series voltage
to deal with fundamental frequency information. regulators in faulted distribution systems,” in Proc. IEEE PESC’99
Conf., vol. 1, 1999, pp. 418–423.
[6] C. S. Chang, S. W. Yang, and Y. S. Ho, “Simulation and analysis of
VI. CONCLUSION Series Restorers (SVR) for voltage sag relief,” in Proc. IEEE PES Winter
Meeting, 2000.
This paper has proposed and verified a method that removes [7] V. Kaura and V. Blasko, “Operation of a phase locked loop system under
the need for rating the series injection transformers of the DVR distorted utility conditions,” IEEE Trans. Ind. Applicat., vol. 33, pp.
58–63, Jan./Feb. 1997.
for transient switch-on period, and therefore removes the redun- [8] B. H. Li, S. S. Choi, and D. M. Vilathgamuwa, “On some crucial tech-
dancy normally associated with their steady-state operation. In nologies for dynamic voltage restoration,” in Proc. 5th Int. Power Eng.
economic terms, this may reduce the total cost of a DVR system, Conf. (IPEC), 2001, pp. 426–431.
[9] R. S. Weissbach, G. G. Karady, and R. G. Farmer, “Dynamic voltage
thus making it a more attractive solution for voltage sag mitiga- compensation on distribution feeders using flywheel energy storage,”
tion. IEEE Trans. Power Delivery, vol. 14, pp. 465–471, Apr. 1999.
The simulation and experimental results illustrate that the av- [10] P. Verdelho and G. D. Marques, “Four wire current-regulated PWM
voltage converter,” IEEE Trans. Ind. Electron., vol. 45, pp. 761–770,
erage rms 3-phase voltage and the individual transformer flux- Oct. 1998.
linkages can be maintained within specified limits via a feed- [11] H. Fujita and H. Akagi, “The unified power quality conditioner: The
forward digital controller. integration of series and shunt active power filters,” IEEE Trans. Power
Electron., vol. 13, pp. 315–322, Mar. 1998.
It is possible for particular loads to be sensitive to the varia- [12] B. Singh, K. Al-Haddad, and A. Chandra, “A review of active filters for
tions in rms voltage caused by the adaptive form factor. The vari- power quality improvement,” IEEE Trans. Ind. Electron., vol. 46, pp.
ations can be made less severe by using transformers of higher 960–971, Oct. 1999.
[13] J. C. Smith, J. Lamoree, P. Vinett, T. Duffy, and M. Klein, “The impact of
flux ratings and adjusting the control such that it limits the in- voltage sags on industrial plant loads,” in Proc. Int. Conf. Power Qual/:
jected voltage proportionally less. End-Use Applicat. Perspectives (PQA-91), 2002, pp. 171–178.
1066 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 17, NO. 6, NOVEMBER 2002

[14] L. Conrad, K. Little, and C. Grigg, “Predicting and preventing problems Mike Barnes received the B.Eng. and Ph.D. degrees
associated with remote fault-clearing voltage dips,” IEEE Trans. Ind. from the University of Warwick, U.K., in 1993 and
Applicat., vol. 27, pp. 167–172, Jan. 1991. 1998, respectively.
He has worked as a Research Associate on a
DTI/LINK project on low cost switched reluctance
drives and as a Lecturer at Warwick. For the last
Chris Fitzer was born in Preston, U.K., in 1977. He five years he has been a Lecturer at the University
received the B.Sc. (with honors) degree in electronics of Manchester Institute of Science and Technology,
from the University of Central Lancashire, Preston, Manchester, U.K., where his research interests have
in 1999 and is currently pursuing the Ph.D. degree at covered power electronics applied to power systems,
the University of Manchester Institute of Science and machine drives, and photovoltaics.
Technology, Manchester, U.K.
His research interests are digital control of
power quality devices, dynamic voltage restorers,
transformer saturation prevention, digital signal
processing, and hybrid filters.

Atputharajah Arulampalam was born in Sri Lanka Rainer Zurowski (1965) received the Dipl.Ing.
in 1971. He received the B.Sc.Eng. (with honors) de- degree in electrical engineering from Friedrich
gree from the University of Peradeniya, Sri Lanka, Alexander University, Erlangen, Germany, in 1991
in 1997 and is currently pursuing the Ph.D. degree at and the Dr.Ing. degree from Ruhr University,
the University of Manchester Institute of Science and Bochum, Germany, in 2001.
Technology, Manchester, U.K. Since 1992, he has been with the System Planning
Since 1998, he has been a Lecturer with the De- Department, SIEMENS AG, Erlangen. His main
partment of Electrical and Electronic Engineering, activity is research and development of power
University of Peradeniya. His research interests are electronics based equipment for power quality
the applications of FACTS devices, power quality, improvement in transmission and distribution
and converter configurations. networks.

Вам также может понравиться