Вы находитесь на странице: 1из 3

CONTROL & INSTRUMENTATION

STATION : STANDARD CHECK LIST SHEET 1 OF 2

INSTRUMENT : PRESSURE TRANSMITER SCL REF 1.5.4

SUPPLIER __________________________________________________________________
MANUFACTUERER_____________________ TYPE _______________ S. NO.________
RANGE_________________ INPUT _______________ OUTPUT_____________
POWER SUPPLY ___________VOLTS _______ AMPS _________ HZ _______________
PLANT SYSTEM ________________________________ LOCATION __________________

NTPC TAG NO: UNIT:

NO. ACTIVITY REMARKS

1 Check that access is safe & easy, including associated valves.


Check mounting.
2 Check range, type, and output correct to schedule.
3 Check for correct tapping points.
4 Check that equipment location is correct in relation to tapping
point, correct pipework fall etc. see NTPC standards.
5 Check for correct mechanical & Electrical connections, cable
numbers, ferruling etc.
6 Check for correct labeling.
7 Check that electrical supplies are fed from correct source,
correctly transformer tappings.
8 Check that instrument earthing is correct.
9 Check calibration T.P.I.5.4 note: head correction.
10 Check that instrument works correctly during plant
operation.

Remarks:
WBSEDCL WBSEDCL Contractor
Erection Commissioning
Name
Designation
CONTROL & INSTRUMENTATION
STATION : STANDARD CHECK LIST SHEET 2 OF 2

INSTRUMENT: PRESSURE TRANSMITER SCL REF 1.5.4

NO. ACTIVITY REMARKS

1 TEST EQUIPMENT REQUIRED


1.1 Pressure souce with standard test gauge Accuracy 0.25%
1.2 multi range meter, MA & V, Accuracy 0.1%.
check calibration of test equipment.
Connect pressure source to transmitter and connet meter in the
output.
Check the output ant 20% intervals up & down by varying the
input pressure accordingly.
Record the results on standard calibration sheet I.15.1.
allow for head corrections if necessary.
Reconnect pressure & Electrical connections.
Check calibration of test equipment.
2
Head correction: should be applied at the rate of 0.1
kg/cm2/meter of height of transmitter above or below tapping
point where the process medium is water. In the case of
transmitters of range<50 kg/cm2 a more accurate head
correction should be calculated.
Acceptable errors.
3
Maximum error 0.5%Fsd. Unless otherwise stated in the
contract specification or manufacturers literature

Remarks:
WBSEDCL WBSEDCL Contractor
Erection Commissioning
Name
Designation
Signature
Date

Вам также может понравиться