Академический Документы
Профессиональный Документы
Культура Документы
O
ne of the fundamental design elements that every Is a Water Booster Pump Needed?
plumbing engineer faces is the design of domestic To determine whether a water booster pump is required,
water systems. Water is used in just about every the following information is used:
building of every type, and it is necessary for the plumbing • The minimum required water pressure typically is 20
engineer to be able to design and lay out a water system to pounds per square inch gauge (psig) if flush valves are
be as efficient as possible in these days of lower fees and used and 10 psig otherwise. For healthcare, laboratory,
more demand from clients. or industrial projects, you may have equipment that has
This article outlines a methodology plumbing engineers higher minimum pressure requirements.
can use to design an efficient domestic water system. It walks • The elevation difference between the elevation of the
through the design process for a relatively large, multistory water supply flow test and the highest fixture in the
building, which will allow readers to look at all elements of building must be determined. You typically do not have
the design of a domestic water system with the knowledge to worry about hose bibbs in mechanical penthouses.
that smaller projects will not need to address every issue. It is The elevation difference in feet multiplied by 0.454 gives
up to the designer to audit the steps presented for each spe- the pressure drop in psi.
cific type of project. Please note that the scope of this article • The longest run of piping in the building, including fit-
does not allow great depth on the design of water-heating tings, must be determined. This typically is figured at
systems or water booster pump systems. Designers should this stage in the design process by adding the height,
review ASPE design manuals, such as Domestic Water Heat- width, and length of the building and multiplying by 1.5.
ing Design Manual II or the Plumbing Engineering Design • Assume a pressure drop of 1.5 feet per 100 feet (approxi-
Handbooks, for further information on those topics. mately 0.7 psi per 100 feet).
To summarize the process, the specific steps used for flow rate, you don’t need to worry about whether they are
sizing piping are as follows: using hot or cold water.
1. Using the amount of piping in the longest run and the
water supply flow information, the maximum allow- Backflow Preventers
able pressure drop can be determined. This value will Unless you have a break tank in your system, the local util-
be based on the difference between the water supply ity may insist on a reduced-pressure backflow preventer
pressure and the minimum pressure at the fixtures. If (RPBP) on the water service to the building. Even if you are
a water booster pump is used, the available pressure on a campus area that provides a master RPBP to protect
is set at 55 psi, assuming a 75-psig discharge from the the utility, you still should have a building-level RPBP so
booster pump and a minimum of 20 psig at the fixture. that one building does not compromise the campus system.
(Refer to Table 1.) Further, if at all possible, the RPBP should be installed out-
2. For DHW systems, the maximum flow rate is set at 6 feet side or at least in a mechanical room that is above grade.
per second (fps) for most pipe materials, and the flow RPBP vent sections are designed to flow full under some
information for systems with flush tanks is used. (As types of failure conditions. Figure 2 indicates how much
an aside, it is recognized that according to the Copper water can flow from this vent. As you can see, a 6-inch RPBP
Development Association, velocities for hot water installed in a basement level mechanical room with a 50-gpm
piping should not exceed 5 fps. However, based on the sump pump will not work. I speak from personal observation!
DHW system not being a steady flow system and the
actual flow rates based on Hunter’s curve being high Type of Building
with low-flow fixtures, I never have had a problem with Most buildings can be sized safely based on the fixture
erosion in a DHW system sized for 6-fps maximum units and Hunter’s curve flow rates in the plumbing codes.
velocity.) If the maximum allowable pressure drop does However, especially for buildings with large assembly
not allow for a velocity of 6 fps, the limit based on pres- occupancies, you will have to increase the pipe sizes to
sure drop is used. (Refer to Table 4.) get everything to work. For example, when the Tennessee
3. For DCW systems serving group toilets, the volume of Titans opened their new stadium in Nashville, the DCW
water is based on only the maximum flow rate limit of system was designed for all the flush valves in the facility to
8 fps. For the most part, you are not worried about the be actuated at the same time. If there was enough system
pressure drop in the short runs of pipe that make up a pressure to close the diaphragms, the system would work.
toilet room. (Refer to Table 2.) They even brought in the local Boy Scouts and other volun-
4. For the main DCW distribution system, the maxi- teers to test the system. The same can be true for theaters,
mum flow rate is set at 8 fps, and the resultant flow conference centers, and large auditoriums. On the other
is compared to the flow rate based on the maximum end of the scale are building such as hospitals where most
allowable pressure drop. Usually, the maximum pres- rooms have a bathroom. In that case, using Hunter’s curve
sure drop will be the limiting factor in the smaller will drastically oversize the piping system unless you figure
pipe sizes, while the maximum flow rate will be the everything as “private” use.
limiting factor in the larger pipe sizes. The breakpoint
is determined by the actual allowable pressure drop. Temperature Maintenance
(Refer to Table 3.) If a recirculation system is used, the layout of the hot
5. You should walk through the entire building and cal- water system must include circulation legs for any branch
culate the number of fixture units on each section of that exceeds 100 feet in length. In reality, especially for
piping. Refer to Figure 1 for a sample of this method. In branches that serve only public lavatories, the minimum
Figure 1, the blue numbers represent the DCW system branch lengths really need to be evaluated.
fixture units, and the red numbers are the fixture units Further, I recommend using a minimum pipe size of ⅜
for the DHW system. inch in lieu of ½ inch as is normally used. The reasoning for
6. This fixture unit value then is compared to the appro- this change is apparent by looking at the velocity of water in
priate Table (2, 3, or 4) to determine the size of that the various pipe sizes. Table 5 provides some comparison
section of piping. information for ⅜-inch and ½-inch piping.
It is advised to keep your markup drawing as part of your For a lavatory with a maximum flow rate of 0.5 gpm, this
project notebook just in case you have to verify or defend results in a velocity of 44 feet per minute in ½-inch pipe and
your sizing in the future. 76 feet per minute in ⅜-inch pipe. Thus, if you want water
to get to the fixture in a reasonable time, the smaller pipe
Things to Think About is the better choice. Further, using a maximum of 6 fps for
Water Service Sizing hot water systems, a ⅜-inch pipe can carry 3.2 gpm while
The water service should be sized using the total water a ½-inch pipe can carry 5.6 gpm. This means that without
column indicated in Table 1. This value accommodates the diversity, a ⅜-inch pipe could serve seven lavatories while a
fact that while faucets and shower valves have a maximum ½-inch pipe could serve 11 lavatories.
Table 1 Tabulation of fixture units (FU) for a sample project Table 4 DHW sizing
Available Pressure (psi) Maximum Water Velocities (fps) Pipe Flow at
Pipe ID Maximum Maximum FU,
Static 73 Cold water 8 Size Maximum
(in.) Velocity (fps) Flush Tank
Residual 67 Hot water 6 (in.) Velocity (gpm)
Flow rate 1,574 /8
3
0.43 6.00 2.72 1
½ 0.527 6.00 4.08 4
Required pressure: 25 psi Highest elevation: 37 feet ¾ 0.785 6.00 9.05 12
1 1.025 6.00 15.43 21
Hot Water Cold Water Total Water 1¼ 1.265 6.00 23.50 36
Description Number FU Total FU Total FU Total 1½ 1.505 6.00 33.27 60
EWC 5 0 0 0.25 1.25 0.25 1.25 2 1.985 6.00 57.87 160
Lavatory, public 35 1.5 52.5 1.5 52.5 2 70 2½ 2.465 6.00 89.24 321
Sink 11 1.5 16.5 1.5 16.5 2 22 3 2.945 6.00 127.38 517
Shower, public 44 3 132 3 132 4 176 4 3.905 6.00 223.96 1,116
Service receptor 4 2.25 9 2.25 9 3 12
Water closet, valve, public 39 0 0 10 390 10 390 Table 5 Piping comparison
Floor totals (FU) 210 601.25 671.25 3
/8-inch Pipe ½-inch Pipe
Flow rate (gpm) 67 155 165 Inside diameter (inches) 0.402 0.529
Supply pressure @ flow 72.90
Volume of 1 foot of pipe (gallons) 0.0066 0.0114
Length of pipe for 0.5 gallon (feet) 75.8 43.8
Corrections
Elevation 17 Capacity of pipe at 6 fps (gpm) 3.2 5.6
Site piping (ft) 150 0.13 Number of public lavatories at 0.5
6 11
Inside diameter (in.) 6 gpm, undiversified
C value 150
Water meter 6
Backflow preventer 11
Fixture minimum 20
Available pressure 18.77
Longest pipe run – Pipe + Fittings (equivalent length) 100 ft
Pipe Size Pipe ID Maximum Flow at Maximum Maximum FU, Maximum FU,
(in.) (in.) Velocity (fps) Velocity (gpm) Flush Valve Flush Tank
/8 3
0.43 8.00 3.62 0 3
½ 0.545 8.00 5.82 0 6
¾ 0.785 8.00 12.07 0 16
1 1.025 8.00 20.57 0 30
1¼ 1.265 8.00 31.34 14 56
1½ 1.505 8.00 44.36 35 103
2 1.985 8.00 77.16 136 259
2½ 2.465 8.00 118.99 351 470
3 2.945 8.00 169.84 694 743
4 3.905 8.00 298.62 1,738 1,738
Pipe Size Pipe ID Allowable Allowable Velocity Maximum Flow at Maximum Maximum FU, Maximum FU,
(in.) (in.) Loss (psi) Flow (gpm) (fps) Velocity (fps) Velocity (gpm) Flush Valve Flush Tank
/8
3
0.43 0.188 2.91 6.44 8.00 3.62 0 1
½ 0.545 0.188 5.44 7.48 8.00 5.82 0 6
¾ 0.785 0.188 14.20 9.42 8.00 12.07 0 16
1 1.025 0.188 28.66 11.14 8.00 20.57 0 30
1¼ 1.265 0.188 49.87 12.73 8.00 31.34 14 56
1½ 1.505 0.188 78.78 14.21 8.00 44.36 35 103
2 1.985 0.188 163.25 16.93 8.00 77.16 136 259
2½ 2.465 0.188 288.69 19.41 8.00 118.99 351 470
3 2.945 0.188 461.12 21.72 8.00 169.84 694 743
4 3.905 0.188 969.08 25.96 8.00 298.62 1,738 1,738