Trelec S. A. ************************************************************************************************** * * * CAISSON - Pier Foundations Analysis and Design - Copyright Power Line Systems, Inc. 1993-2011 * * * **************************************************************************************************
Project Title: Poste 24 mts Clase 3000 Sondeo P4
Project Notes: Diseño Cimentacion Tipo Caisson LT 69 Kv Linea 6 Roosevelt
Calculation Method: Conservative 4CD
******* I N P U T D A T A
Pier Properties
Diameter Distance Concrete Steel
of Top of Pier Strength Yield above Ground Strength (ft) (ft) (ksi) (ksi) ------------------------------------------------ 4.26 0.00 3.00 60.00
Soil Properties
Layer Type Thickness Depth at Top Density CU KP PHI
Due To Due To End-Bearing Axial Load Weight Pressure (ft) (kips) (psf) (psf) (psf) --------------------------------------------------------------- 10.764 23.056 1778.7 1614.6 3393.3
Ultimate Resisting Forces Along Pier
Type Distance of Top of Layer Thickness Density CU KP Force Arm