Академический Документы
Профессиональный Документы
Культура Документы
Contents
1 Scope.............................................................. 2
2 Conflicts and Deviations................................. 2
3 References...................................................... 2
4 Definitions....................................................... 4
5 General Requirements.................................... 4
6 Indoor Cabinet Design.................................... 7
7 Outdoor Cabinet Design............................... 25
8 Testing and Inspection.................................. 29
9 Shipment....................................................... 29
1 Scope
This specification defines the requirements for instrument control panels in outdoor and
indoor areas. It also defines the requirements for control and marshalling cabinets for
location in electrically unclassified air-conditioned buildings as referenced in their
respective standards.
2.1 Any conflicts between this specification and their applicable Saudi Aramco
Materials System Specifications (SAMSS), Engineering Standards (SAESs),
Standard Drawings (SASDs), or industry standards, codes and forms shall be
resolved in writing by the Company or Buyer Representative through the
Manager, Process & Control Systems Department of Saudi Aramco, Dhahran.
2.2 Direct all requests to deviate from this specification in writing to the Company or
Buyer Representative, who shall follow internal company procedure SAEP-302
and forward such requests to the Manager, Process & Control Systems
Department of Saudi Aramco, Dhahran.
3 References
Page 2 of 33
Document Responsibility: Instrumentation Standards Committee 34-SAMSS-820
Issue Date: 13 July 2016
Next Planned Update: 13 July 2019 Instrument Control Cabinets
Page 3 of 33
Document Responsibility: Instrumentation Standards Committee 34-SAMSS-820
Issue Date: 13 July 2016
Next Planned Update: 13 July 2019 Instrument Control Cabinets
4 Definitions
Control Panel: A surface with cut-out(s) used to mount control devices and/or
instrument indicators (e.g., totalizers, pushbuttons, pullbuttons, indicating lights, meters,
annunciators, etc.).
Marshalling Cabinet: A cabinet containing wiring ducts, DIN rails, terminal strips
and/or wire terminations only. Cabinets: Generically used within this specification;
refers to all of the above.
5 General Requirements
5.2.1.3 Marshalling cabinets shall only contain wiring ducts, DIN rails,
terminal strips and/or wire terminations. The field homerun
Page 4 of 33
Document Responsibility: Instrumentation Standards Committee 34-SAMSS-820
Issue Date: 13 July 2016
Next Planned Update: 13 July 2019 Instrument Control Cabinets
The cabinet electronic equipment shall carry CE Mark for compliance with
EMC Directive 2004/108/EC and shall comply with immunity levels stated in
IEC 61000-6-2.
Alternatively, the vendor shall provide testing results to confirm that the
equipment will operate without disturbance when energized and subjected to an
electromagnetic field from a radiating source equivalent to a level 3 disturbance
as detailed in IEC 61000-4-3. In particular, RF source such as hand-held radio
transceivers operating at 5 Watts within the frequency ranges, 50-174 MHz,
406- 470 MHz, and 800-870 MHz and held at a distance of 1.0 meter from the
cabinet, with cabinet doors open shall not cause any malfunction, data
corruption, or damage to the equipment.
5.2.2.3 The cabinets and its integral parts shall be protected against
corrosion and operational failure due to wind-borne sea water
Page 5 of 33
Document Responsibility: Instrumentation Standards Committee 34-SAMSS-820
Issue Date: 13 July 2016
Next Planned Update: 13 July 2019 Instrument Control Cabinets
Page 6 of 33
Document Responsibility: Instrumentation Standards Committee 34-SAMSS-820
Issue Date: 13 July 2016
Next Planned Update: 13 July 2019 Instrument Control Cabinets
6.1 Style
The cabinets shall be rigid and self-supporting. Unless otherwise specified, the
cabinets shall be free standing, floor mounted type. Instruments and electronic
accessories shall be wired in accordance with this specification. Indoor cabinets
shall be made of metal. When multiple cabinets are provided, it is highly
recommended that they are identical in construction and external appearance.
6.2 Drawings
6.2.1 The cabinet fabricator shall supply detailed drawings for review and
approval.
6.2.4 All Vendor literature and drawings shall be of sufficient size and quality
to be clearly legible.
Page 7 of 33
Document Responsibility: Instrumentation Standards Committee 34-SAMSS-820
Issue Date: 13 July 2016
Next Planned Update: 13 July 2019 Instrument Control Cabinets
6.3 Construction
6.3.1 The cabinet shall be a NEMA Type 1 as a minimum per NEMA 250 and
NEMA ICS 6 or as specified in the functional specification document.
6.3.3 Fans with suitable filters and louvers may be used within control
cabinets to assist in heat removal. This can be achieved by installing a
filter fan at the air inlet (typically at the bottom of the cabinet door) to
blow cool air into the cabinet or by installing an exhaust filter fan at the
air outlet (typically at the upper section of the door) to draw hot air out
of the cabinet. The fan filter shall be easily accessible for maintenance
or replacement without dismantling the fan assembly.
6.3.4 All cabinets shall be designed to ensure the heat rise within the cabinet
does not exceed 10°C. Where circulation fans are required to meet the
maximum heat rise requirement, redundant air circulation fans shall be
provided. Heat load calculations may take credit for heat dissipation
from air circulation for one of the redundant fans.
Commentary Note:
The requirement for maximum heat rise within the cabinet of 10°C is to
ensure that the temperature within the cabinet does not exceed 35°C.
The normal ambient temperature within air conditioned buildings is 25°C.
6.3.5 Cabinet cooling fans shall be sized to handle 20% more air flow by
volume than the amount taken credit for in the heat dissipation calculation.
Commentary Note:
Page 8 of 33
Document Responsibility: Instrumentation Standards Committee 34-SAMSS-820
Issue Date: 13 July 2016
Next Planned Update: 13 July 2019 Instrument Control Cabinets
shroud to prevent dirt and debris from falling into the cabinet. In this
case, the cabinet shall be NEMA 12.
6.3.8 Where two or more front sections are required for a Control Panel, the
interior shall be an open-frame construction.
6.3.9 Cabinet support bracing shall not restrict maintenance access to chassis,
modules or components. Accessing any of the installed components or
wiring shall not require the removal of other components.
6.3.11 Cabinet doors shall be full-height. All doors shall be dust-tight and
reinforced against buckling. The maximum door width shall be
900 mm (36 inches) unless otherwise specified in the Purchase Order.
6.3.12 Cabinets intended for marshalling may have front and rear access and
shall be designed per paragraph 5.2. The distance from the front surface
to the surface of rear terminal blocks, shall not be more than 400 mm
deep to provide for safe access. The cable entry to the marshalling
cabinet shall be through the bottom.
6.3.14 Control and marshalling cabinets may be combined into a single cabinet
for systems where the entire control and marshalling fit into a single
cabinet. This is typical for systems such as VMS, RTU, PLC, CCS,
HIPS, etc. For these systems, it is preferable to segregate control
equipment from marshalling to the maximum extent possible. Front/rear
separation shall be considered.
Exception:
6.3.15 When front and rear accesses are provided for control cabinets, each
section shall have its own full size mounting plate. Cable routing shall
be tightly secured either on the sides and/or through properly dressed
holes. Wiring shall not be threaded through undressed access holes.
Glands or protective grommets shall be used.
6.3.16 All doors shall be provided with integral lockable door handles with the
same lock and key combination, unless otherwise specified on the ISS.
Page 9 of 33
Document Responsibility: Instrumentation Standards Committee 34-SAMSS-820
Issue Date: 13 July 2016
Next Planned Update: 13 July 2019 Instrument Control Cabinets
6.3.17 Equipment that are installed within cabinets or panels and are normally
used by the operator shall be readable and operable with the operator in a
standing position.
6.3.18 The inside of each door shall be equipped with a pocket suitable for
holding A4 documents and/or cabinet drawings.
6.3.19 Cabinets intended for bottom cable entry shall be provided with a gland
plate at the bottom of the cabinet.
6.4.1 The exterior and interior cabinet finish shall be the Cabinet Fabricator's
standard finish, unless otherwise specified in the Purchase Order.
A minimum of primer, undercoat and finishing coat of enamel or lacquer
is required. Electrostatic applied powder paint coatings which are then
baked (such as polyester urethane) is acceptable.
6.4.2 Interior cabinet color shall be white or of a light color such as light gray,
off-white, etc., or as specified in the purchase order.
6.5 Nameplates
6.5.1 Nameplates for cabinets and panels letter height and spacing shall follow
ISA RP60.6, Appendices A and C, unless otherwise specified in the
purchase order.
6.5.3 Control panel pushbuttons, switches, indicating lights and other through-
mounted devices shall be identified with the service description on the
front. The rear of the above devices shall be identified with the device
tag number. The nameplates shall be permanently attached. Adhesives
are allowed for indoor panels.
Page 10 of 33
Document Responsibility: Instrumentation Standards Committee 34-SAMSS-820
Issue Date: 13 July 2016
Next Planned Update: 13 July 2019 Instrument Control Cabinets
6.5.6 Each cabinet, front and rear, shall be identified with a nameplate located
above each door or pair of doors. The nameplate, as a minimum, shall
be the cabinet name/number as given in the cabinet drawings.
6.6.1 Unless otherwise specified in the Purchase Order, each cabinet shall be
provided with the following spare capacity to allow for future system
modifications:
a) 20% installed spare terminal blocks of each terminal block type
used for field home-run cables only. Spare terminal blocks are to be
distributed to match the layout of required spare I/O modules, field
termination assemblies, relays, etc.
Commentary Note:
b) 10% spare relay bases in cabinets where there are ten relays or
more. For less than ten relay installations, one spare base should be
installed.
Exception:
The above requirement does not apply on cabinets where only one
relay is installed for fan failure or alarm.
6.6.2 The Cabinet Fabricator shall supply a minimum of two (2) spare fuses or
10% (whichever is greater) for each type of general power and
termination strip fuses used within each cabinet. This requirement
includes supplying spares for fuses integral to installed electronics
(i.e., flow computers, field termination assemblies, etc.).
6.7 Electrical
Page 11 of 33
Document Responsibility: Instrumentation Standards Committee 34-SAMSS-820
Issue Date: 13 July 2016
Next Planned Update: 13 July 2019 Instrument Control Cabinets
Exception:
6.7.1.2 Power wiring for field instruments, all input and output points,
two-wire analog transmission loops, field switch contacts, etc.,
shall be individually fused and provided with a means of
disconnecting the power without disturbing terminated wiring
(e.g., knife-switch-type terminal blocks). Daisy chaining of
external loop power using wires or wire crimps is not
acceptable.
Exceptions:
Commentary Note:
Note: The basis for the upper DC voltage variations is due to installations where battery back-
up is used without voltage suppression and the batteries receive periodic charging.
Page 12 of 33
Document Responsibility: Instrumentation Standards Committee 34-SAMSS-820
Issue Date: 13 July 2016
Next Planned Update: 13 July 2019 Instrument Control Cabinets
6.7.2.2 Twist-on wire nut connectors shall not be used for making any
electrical instrumentation terminations.
Page 13 of 33
Document Responsibility: Instrumentation Standards Committee 34-SAMSS-820
Issue Date: 13 July 2016
Next Planned Update: 13 July 2019 Instrument Control Cabinets
Table 2
4-20 mA 24 VDC Copper
Signal Milli Volt
Analog Power/ 125 VDC 120 VAC Network
Category T/C RTD
24 VDC Digital Cable
Milli Volt 0 0 25 150 150 0
T/C RTD 0 0 25 75 75 0
0 0 0 75 75 0
4-20 mA
0 0 0 25 25 0
25 0 0 25 75 0
24 VDC
25 0 0 0 0 0
150 75 25 0 0 50
125 VDC
75 25 0 0 0 25
150 75 75 0 0 75
120 VAC
75 25 0 0 0 50
Copper
0 0 0 50 75 0
Network
0 0 0 25 50 0
Cable
Notes:
1) Upper Value Spacing is for wires in plastic ducts.
2) Lower Value Spacing is for wires separated by:
a) One metal conduit or
b) A 1/16-in. thick grounded steel divider.
3) Voltages shown are nominal.
Page 14 of 33
Document Responsibility: Instrumentation Standards Committee 34-SAMSS-820
Issue Date: 13 July 2016
Next Planned Update: 13 July 2019 Instrument Control Cabinets
Page 15 of 33
Document Responsibility: Instrumentation Standards Committee 34-SAMSS-820
Issue Date: 13 July 2016
Next Planned Update: 13 July 2019 Instrument Control Cabinets
Wiring for millivolt, microamp, pulse and frequency signals under 1 Volt
such as thermocouples, resistance temperature detectors (RTD),
vibration elements, analyzer elements, thermistor elements and
transmitters with pulse outputs may be directly connected to the I/O
unless otherwise specified in the Purchase Order.
6.7.7.2 Terminal strip spacing shall allow ample room for plastic wire
ducts and permit lacing of cables, and fanning of individual
wires to termination points. Each terminal strip shall be
labeled above or below with the terminal strip number, as
shown on wiring diagrams. Terminals for similar (AC or DC)
current service shall be grouped together and physically
separated from terminals for different service by means of
dividers, separate mounting rails or separate enclosures.
6.7.7.3 Standoffs for terminal strips are preferred to bring the terminal
blocks forward to be flush with the top of the plastic wire duct.
This wiring method assures that all wires can be accessed
without interference from other wires as the wire duct is filled.
Page 16 of 33
Document Responsibility: Instrumentation Standards Committee 34-SAMSS-820
Issue Date: 13 July 2016
Next Planned Update: 13 July 2019 Instrument Control Cabinets
6.7.8.1 No more than two bare wires shall be connected to each side of
a single terminal block.
Page 17 of 33
Document Responsibility: Instrumentation Standards Committee 34-SAMSS-820
Issue Date: 13 July 2016
Next Planned Update: 13 July 2019 Instrument Control Cabinets
6.7.8.9 Multiple-deck and spring type terminal blocks shall not be used.
Exception:
6.7.9.3 In addition to the above, the maximum plastic wire duct fill
(including spare capacity) shall not exceed 75% of its depth.
6.7.9.5 Where space limitations preclude the use of plastic wire ducts,
wiring shall be neatly loomed and secured with plastic spiral
wrapping or tie-wraps and anchors. Wiring between movable
parts such as doors shall be installed in flexible hoses.
6.7.9.8 Wire ducts for ESD wiring shall not contain any other types of
wiring.
Hot Black
AC Power Supply: Neutral White or gray
Ground Green or green with yellow tracer
Negative Black
DC Power Supply:
Positive Red
Negative White
Signal Pair
Positive Black
Page 18 of 33
Document Responsibility: Instrumentation Standards Committee 34-SAMSS-820
Issue Date: 13 July 2016
Next Planned Update: 13 July 2019 Instrument Control Cabinets
Positive Black
Signal Triad Negative White
Third Red
Negative Per ISA MC96.1
Thermocouple
Positive Per ISA MC96.1
Exceptions:
Page 19 of 33
Document Responsibility: Instrumentation Standards Committee 34-SAMSS-820
Issue Date: 13 July 2016
Next Planned Update: 13 July 2019 Instrument Control Cabinets
6.7.11.5 Wire tags shall be installed and oriented such that the tags are
easily read. (Upside down or covering of tag information by
plastic duct covers is not acceptable).
6.7.11.7 Per NEC 310-120, all conductors and cables shall be marked to
indicate the following information:
1) Maximum rated voltage for which the conductor was listed,
2) The letter designators for type of wire or cable,
3) Manufacture's name or trade mark,
4) The AWG size or circular mil area.
Page 20 of 33
Document Responsibility: Instrumentation Standards Committee 34-SAMSS-820
Issue Date: 13 July 2016
Next Planned Update: 13 July 2019 Instrument Control Cabinets
6.7.13 Relays
Page 21 of 33
Document Responsibility: Instrumentation Standards Committee 34-SAMSS-820
Issue Date: 13 July 2016
Next Planned Update: 13 July 2019 Instrument Control Cabinets
Push buttons and lights shall be industrial quality. Push buttons shall
have protective mechanisms to prevent accidental activation as required
by the detailed design specification. Long-life type lamps or LED
cluster lamps shall be used. It shall be possible to access the lamp bulbs
from the front for replacement. The color of the pushbuttons or lights
shall be green for “ON”/”OPEN” and red for “OFF/”CLOSE” positions.
Only screw terminals shall be provided on push buttons.
Exception:
Existing facilities that currently deviate from the above light color
specification may use other conventions in order to keep the lighting
philosophy consistent within the facility.
For all control panels with indicating lights, a lamp test button shall be
provided per panel.
Exceptions:
Page 22 of 33
Document Responsibility: Instrumentation Standards Committee 34-SAMSS-820
Issue Date: 13 July 2016
Next Planned Update: 13 July 2019 Instrument Control Cabinets
6.7.17.2 Shield drain wires shall not be daisy-chained using bare wires
or crimp connectors to the ground connection.
6.7.18 Grounding
6.7.18.3 All ground buses shall be made of a solid copper measuring the
following nominal dimensions 5mm x 40 mm x (y length),
suitably drilled, and tapped for screw terminals and wire lugs,
or fitted with screw-type compression lugs.
Commentary Note:
6.7.18.4 The preferred location of the ground bus bars is at the bottom
of the cabinet.
Page 23 of 33
Document Responsibility: Instrumentation Standards Committee 34-SAMSS-820
Issue Date: 13 July 2016
Next Planned Update: 13 July 2019 Instrument Control Cabinets
6.7.18.6 The ground bus bars shall be labeled and wired as follows:
6.7.19.3 Incandescent lamps shall have a guard to help protect the lamp
from accidental breakage. Fluorescent lamps shall have clear
plastic sleeve guards to help contain broken glass in case of an
accident.
Page 24 of 33
Document Responsibility: Instrumentation Standards Committee 34-SAMSS-820
Issue Date: 13 July 2016
Next Planned Update: 13 July 2019 Instrument Control Cabinets
6.7.19.6 A switch in the cabinet (in addition to the circuit breaker) shall
control each lamp where the lamp is installed. Automatic door
switches for lamps are allowed.
7.1 Enclosures
Enclosures shall meet the requirements of this section in addition to the indoor
requirements given under section 6 and all other general requirements of this
SAMSS.
7.1.2 In outdoor plant and other industrial areas located in severe corrosive
environments as defined in Paragraph 4.2, enclosures shall be
NEMA 250 / NEMA ICS 6 Type 4X or IEC 60529 Type IP66,
manufactured of 316L stainless steel. Door hinge, door stay, and door
lock shall be made of 316L stainless steel. Galvanized and/or painted or
coated carbon steel sheet metal enclosures are not permitted.
Commentary Note:
7.1.3 All cabinets intended for outdoor applications shall be certified by one of
the approved IECEx certifying bodies. Certification shall also include
Ingress Protection (IP rating) per IEC 60529.
Commentary Note:
Page 25 of 33
Document Responsibility: Instrumentation Standards Committee 34-SAMSS-820
Issue Date: 13 July 2016
Next Planned Update: 13 July 2019 Instrument Control Cabinets
7.2 Electrical
Cable ties used in outdoor cabinets shall be weather resistant nylon cable
ties with a stainless steel barb. The cable tie shall have a maximum
continuous use temperature rating of 85ºC or higher, e.g., Panduit Dome-
Top Barb Ty Cable Ties - Weather Resistant, or equivalent.
The panel/cabinet and all components within the panel shall be suitable
for the electrical area classification where the panel will be installed.
The cabinet and its equipment shall be certified by one of the approved
IECEx certifying bodies. The classification of the area in which the
panel will be used, shall be specified in the Purchase Order.
7.2.3.2 Elevated outdoor control cabinets shall have conduit entry from
the bottom.
7.2.4 Relays
Relays shall meet the area classification in which they are installed.
They shall also be weather-proof to meet any required environmental
conditions such as rain, dust, or corrosion.
The noise level from the panel shall not exceed 85 dB at 3 meters.
7.3 Nameplates
Page 26 of 33
Document Responsibility: Instrumentation Standards Committee 34-SAMSS-820
Issue Date: 13 July 2016
Next Planned Update: 13 July 2019 Instrument Control Cabinets
7.4 Piping
7.4.2.1 Tubing
7.4.2.2 Tube fittings shall be 316 stainless steel and shall be high
pressure and double compression type. Interchange of tube
fitting component parts from different manufacturers is not
allowed.
Page 27 of 33
Document Responsibility: Instrumentation Standards Committee 34-SAMSS-820
Issue Date: 13 July 2016
Next Planned Update: 13 July 2019 Instrument Control Cabinets
7.5 Documentation
7.5.2.1 Piping diagrams shall show the outline of the panels, relative
position of all instruments, and schematic of piping, including:
a. Piping connections on instruments
b. Interconnecting piping between instruments
c. Valving and test connections
d. Miscellaneous accessories such as pressure gages, snap
connectors, etc.
Page 28 of 33
Document Responsibility: Instrumentation Standards Committee 34-SAMSS-820
Issue Date: 13 July 2016
Next Planned Update: 13 July 2019 Instrument Control Cabinets
The Cabinet Fabricator shall verify the operation of all instrumentation and controls.
Documented test procedures shall be submitted to the proponent for approval not less
than thirty (30) days before commencement of test. Tests shall include, but shall not be
limited to:
a) Visual inspection to verify compliance with requirements of this specification.
b) Complete wiring check with verification that terminal and wiring code conforms to
cabinet design drawings.
The cabinet electronic equipment shall carry CE Mark for compliance with EMC
Directive 2004/108/EC and shall comply with immunity levels stated in IEC 61000-6-2.
Alternatively, the vendor shall provide testing results to confirm that the equipment will
operate without disturbance when energized and subjected to an electromagnetic field
from a radiating source equivalent to a level 3 disturbance as detailed in IEC 61000-4-3.
In particular, RF source such as hand-held radio transceivers operating at 5 Watts within
the frequency ranges, 50-174 MHz, 406- 470MHz, and 800-870 MHz and held at a
distance of 1.0 meter from the cabinet, with cabinet doors open shall not cause any
malfunction, data corruption, or damage to the equipment
For outdoor cabinet inspection, the above requirements shall apply. In addition, the
vendor shall perform functional tests on all non-electrical components such as tubing,
valves, fittings, gauges, and other mechanical components per the buyer’s requirements.
9 Shipment
Revision Summary
13 July 2016 Major revision to combine 34-SAMSS-821 in this document. Electromechanical relays
specifications have been modified.
Page 29 of 33
Document Responsibility: Instrumentation Standards Committee 34-SAMSS-820
Issue Date: 13 July 2016
Next Planned Update: 13 July 2019 Instrument Control Cabinets
Page 30 of 33
Document Responsibility: Instrumentation Standards Committee 34-SAMSS-820
Issue Date: 13 July 2016
Next Planned Update: 13 July 2019 Instrument Control Cabinets
Page 31 of 33
Document Responsibility: Instrumentation Standards Committee 34-SAMSS-820
Issue Date: 13 July 2016
Next Planned Update: 13 July 2019 Instrument Control Cabinets
Page 32 of 33
Document Responsibility: Instrumentation Standards Committee 34-SAMSS-820
Issue Date: 13 July 2016
Next Planned Update: 13 July 2019 Instrument Control Cabinets
Page 33 of 33