CS 300 Gate Controls / rev. 04.06 - 1
MFZ
1. Contents 3. General safety instructions
1. Contents 2 Guarantee
2. Key to symbols 2 The function and safety of the equipment is only
3. General safety instructions 2 guaranteed if the warning and safety instructions
4. Overview of products 3 included in these operating instructions are adhered
5. Initial Operation 5 to.
6. Programming with the LED module 8 MFZ Antriebe GmbH + Co.KG is not liable for any
7. Programming with the LCD monitor 10 personal injury or damage to property that occurs as
8. Navigator (LCD monitor only) 12 a result of the warning and safety instructions being
9. Overview of functions 14 disregarded.
10. Error messages and rectification 18
11. Technical data 19
12. EU Declaration of Conformity 19 Using the equipment for its intended purpose
The CS 300 controls are designed only for controlling
gates and doors with digital end position systems.
It is only permitted to operate the equipment in dry
rooms.
Target group
Only qualified and trained electricians may connect,
programme and service the controls.
Qualified and trained electricians meet the following
requirements:
2. Key to symbols
- knowledge of the general and specific safety and
accident prevention regulations,
Danger of personal injury! - knowledge of the relevant electrical regulations,
The safety instructions must be - trained in the use and care of appropriate safety
observed! equipment,
- capable of recognising the dangers associated with
electricity.
Low voltage
- EN 60335-1 (Household and similar electrical
appliances - Safety)
- EN 60335-2-103 (Particular requirements for
drives for gates, doors and windows)
X9 Key:
X4
10 X1: terminal block
9 mains connection
X5 8
1 7
2 X8 6 X2 : terminal block
3 H4 5 motor
4 4
5 3
6 2 X3: terminal block
7 1 command devices
8
10 X4: terminal block
9
8 safety elements
X12
X11 7
X3 6 X5: terminal block
X6 5
X10 4 relay
3
X7 2 X6: sockets for internal
X2 1
ON-OFF switch
B2
B1
X7: sockets for internal
3-button input unit
W
end-position system
U V W B1 B2
M1
must be ensured:
M
- The gate or door is installed and ope T1
1 3 5
2 4 6
X2
rational.
K2
- The MFZ drive motor is installed and
L1 L2 L3 N
1 3 5
2 4 6
ready for operation.
- The command and safety devices are K1 X1
PE
PE
PE
- The control housing with the CS 300
control is installed.
Key:
1 - relay 1
1
sequence control 2
2
button or selector switch 3 - relay 2
3
effective in down direction 4
4
for external switching devices 5 - relay 3
(connection to terminals 1 and 2) 6
7 - relay 4
wt: white 8
gr: green
br: brown
10 - CLOSE button
9
8
7
6
5
- OPEN button
4
- STOP button
3
2
1
10 - CLOSE
9
8
7
6
5 - OPEN
4
3
2
1
Key:
LED off
LED illuminated
LED flashing
With the LED module, the controls have two modes of operation:
1. AUTOMATIC
2. ADJUSTMENT
Information:
The current mode of operation of the control is shown via the LEDs.
- In the AUTOMATIC mode, no LEDs flash.
- In the ADJUSTMENT mode, at least one LED flashes.
Pressing the P button toggles between the modes of operation.
LED displays:
H1 H2 Status
The door is open. The programmed OPEN end position has been reached.
The door is closed. The programmed CLOSED end position has been reached.
The door is between end positions. No end position has been reached.
The door has been moved beyond the CLOSED/OPEN end position.
Warning!
In the ADJUSTMENT mode of operation, the drive does not switch off when the end position is
reached. The door can be damaged if driven beyond the end position.
LED displays:
H1 H2 Status
The CLOSED and OPEN end positions are not programmed at this door position.
Key:
A: mode of operation /
diagnostic info
A AUTOMATIC O G
B: parameter /
B RESTING F diagnostic info
C: + button
D: - button
E: P button
F: value / status
C D E G: value / status
H: jumper
Display
Operating mode 1: AUTOMATIC - displays the check
In the AUTOMATIC operating mode the door system - displays the checking status
is operated.
Display:
- displays the function being carried out
- displays any error messages
Warning!
In the ADJUSTMENT mode of
operation, the drive does not switch off
when the end position is reached.
The door can be damaged if driven
beyond the end position.
Display:
- displays the end position value
P >1 Sec.
ADJUSTMENT
RESTING
Save door position:
- -> Position DOOR MANUAL
ADJUSTMENT DOWN P Hold P pressed and
CLOSED
P >1 Sec.
INPUT
+ and - > 2 Sec. GERMAN : Scroll up through menu:
INPUT + > 2 Sek
INPUT
Scroll down through menu:
RUNNING TIME : 60
- > 2 Sec.
INPUT Select value:
TIME OPEN : 0 P > 1 Sec.
INPUT Increase value:
FOREWARNING : 0 +
Save value:
INPUT
REL.1 - RESTING : Mod1 P
Return to
INPUT
QUICK CLOSE : OFF
INPUT:
+ and - > 1 Sec.
INPUT
RELAY 1 : Mod1
INPUT
RELAY 2 : Mod2
INPUT
RELAY 3 : Mod3
INPUT
RELAY 4 : Mod2
INPUT Pressure
sensor TEST : OFF
P >1 Sec.
INPUT
DELAY-OPEN : OFF
INPUT
FINE-OPEN : 4050
INPUT
FINE-CLOSE : 3950
INPUT
BES-OPEN : 4000
INPUT
BES-CLOSE : 4000
INPUT
ROT. FIELD : RE
INPUT
REVERSE OFF : 50
INPUT
POWER : 0
INPUT
AUTO LEVEL : OFF
INPUT
SELF LOCK : ON
INPUT
SU/WI : MOD1
IMPULS : OFF
TIMER : OFF
MFZ
P/E BARRIER : ON
STOP CIRCUIT : ON
Display Description
AUTOMATIC
The door is driven to the OPEN* end position
OPEN
AUTOMATIC
The door is driven to the CLOSED* end position
CLOSE
AUTOMATIC
The door stands between the end positions
RESTING
AUTOMATIC O
The door stands at the OPEN end position
RESTING
AUTOMATIC o
The door stands at the position PART OPEN („before-end position“ up)
RESTING
AUTOMATIC U
The door stands at the CLOSED end position
RESTING
AUTOMATIC u
The door stands at the position PART CLOSE („before-end position“ down)
RESTING
AUTOMATIC r
The door stands in the position where the reversing switches off
RESTING
*When the gate is being driven OPEN, the power currently being used is displayed
RUNNING Monitoring the max. running time for an open and close movement 1 – 250 Seconds 60 Seconds
TIME
OPEN After the door has opened, it runs in the CLOSE direction again after the 0 – 600 Seconds 0=
TIME set time has elapsed. Auto-close off
Open time > 0 = impulse functions only work in OPEN direction
ADVANCE The traffic light flashes before the door starts to move downwards. 0 - 120 Seconds 0 = Off
WARNING The programmed forewarning time is only active if the open time > 0 or if
TIME in radio-impulse operating mode
TURNA- Standing time at every change of direction 0,1 - 2,0 Seconds 0,3 Seconds
ROUND (in 1/10 Sec)
TIME
QUICK ON: The open time is cut short after the photoelectric barrier has ON OFF
CLOSE been passed (door closes immediately) OFF
OFF: The open time continues as usual
RELAY 1 MOD1: Relay 1 is permanently ON when the door is moving and MOD1 MOD1
flashes for forewarning MOD2
MOD2: Relay 1 flashes when the door is moving and as a forewarning MOD3
MOD3: Relay 1 is permanently ON when the door is moving and as a
forewarning
BES-OPEN Setting the before-end position switch point for the OPEN direction 0 – 8190 4000
(PART-OPEN)
BES- Setting the before-end position switch point for the CLOSE direction 0 – 8190 4000
CLOSE
This setting may only be altered in the case of a special customised drive
installation!
REVERSE The point where the reversing switch is activated before the CLOSE end 10 – 250 50
OFF position is reached.
System does not respond - No voltage supply - Check the voltage supply of the drive
and the controls
Door travels to the CLOSE end position - Rotating field is connected wrongly - Check the rotating field and establish
when the OPEN button is pressed clockwise rotating field if necessary
Door travels to the OPEN end position
when the CLOSE button is pressed
ERROR END POSITION - The door has travelled beyond one of - Check the programming of the end
the end positions positions and reset them if necessary
- The end positions have not been
programmed yet
ERROR RUN TIME - The programmed running time has - Check the path of the door
been exceeded - Re-programme the running time
ERROR SEP - The safety edge protection is faulty - Check the safety edge protection and
the spiral cable
- Safety edge protection was triggered - Remove obstruction from path of door
ERROR PRESSURE SENSOR TESTING - The PS switch is not activated at the - Check the PS switch, spiral cable and
CLOSE end position profile
- Check the setting for the CLOSE end
position
ERROR ROT. FIELD - An incorrect rotating field is connected - Ensure that a clockwise rotating field is
to terminal X1 connected
ERROR RS 485 - Communications fault between the end - Check the cable and socket
position switch and the controls connections
ERROR POWER - The power monitoring has been - Check that the door can move freely
triggered - Reset the power value
After rectifying the cause of the fault, the controls must be disconnected briefly from the mains!
Frequency 50 Hz
We hereby declare that, by virtue of their conceptual
development and design, as well as their
Current 10 A max.
manufacture as we have brought them onto the
market, the products cited below:
Protection grade IP 65
CS300 Door Controls
conform to the relevant basic health and safety
Operating -10˚ C to +60˚ C
regulations of the following EU guidelines and
temperature
standards:
Protection class I
Hans-Joachim Molterer
Position of signatory:
Manager
CS 300 Gate Controls / rev. 04.06 – 19