Вы находитесь на странице: 1из 4

HOT WATER SYSTEM ESTIMATION

Ref. DESCRIPTION UNIT QTY

1 HOT WATER SYSTEM


INSTALL ONLY the following as described and as shown on the drawings
1.1 and specification: Unit 3
Hot water plant (Heat Pumps) - WH-101.A&B
- Location : Level - Roof
- Ambient water temp. : 28 deg C
- Hot water storage temp. : 60 deg C
- Recovery rate : 8 HR
- Req. hot water production : 5,000 Ltr
- Air on max. temp. : 33 DB deg C
- Air on min. temp. : 26 DB deg C
- Air on max. temp. : 28 WB deg C
- No. operating of units : 2
- No. standby of units : 1
- COP of units : 4
- Heating rating per units : 25 KW
- Including spring mounting and all accessories as spesified.
- Including circulation pump

1.2 Hot water tank ST101 ( Supply & Intall ) Unit 2


- Req. cap. storage tank : 7000 Ltr
- Total cap. : 14000 Ltr
- Including : insulation, automatic air realese valve (AARV), pressure
gauge (PG), drain valve and all accessories as specified.

Supply and Install the following as described and as shown on the


drawings and specification:
Circulation pump primary HW-SIRC-101, SS Vertical Multi Stage type, 100
L/M capacity, 1 bar head and all necessary accessories as indicated on
1.3 drawing and spesification, 0.4 kW/220/1P/50 Hz Unit 3
Circulation pump primary HW-SIRC-101, SS Vertical Multi Stage type, 100
L/M capacity, 1 bar head and all necessary accessories as indicated on
1.4 drawing and spesification, 0.4 kW/220/1P/50 Hz Unit 3
Circulation pump primary HW-SIRC-101, SS Vertical Multi Stage type, 100
L/M capacity, 1 bar head and all necessary accessories as indicated on
1.5 drawing and spesification, 0.4 kW/220/1P/50 Hz

2 Riser shaft installation


Polypropylene (PPR) class PN 20, fittings and valves, including insulation,
hangers, brackets, clamps and all necessary accessories as indicated on
drawing and spesification
2.1 32 mm pipe m 60
2.2 50 mm pipe m 40
2.3 80 mm pipe m 40
150 mm pipe m 60
2.4 Extra over PPR for the following fittings:
2.5 80 mm bend
2.6 Valve and accessories
2.7 Gate Valve 80 mm Unit 3
2.8 Gate Valve 32 mm Unit 7
2.9 Gate Valve 150 mm unit 2

80 mm pressure reduction valve (PRV) set (c/w gate valve and


2.9 accessories) Unit 3

Panel distribution including electronic meter c/w the following minimum


function : Volts P to P and P to N (kWs), Amps-each phase (A), Frequency
3 (kWhs) Unit 1
Circulation pump primary HW-SIRC 4 ea c/w M.O.A and 2
3.1 Thermocontrols Sequences Unit 1
Circulation pump primary PU.101 3 ea c/w M.O.A and pressure control
3.2 with sequences Unit 1

** Harga Jasa Instalasi


MATION

UNIT RATE TOTAL

3,500,000 10,500,000

4,500,000 9,000,000

1,500,000 4,500,000

1,500,000 4,500,000

32,000 1,920,000
50,000 2,000,000
80,000 3,200,000
150,000 9,000,000

800,000 2,400,000
320,000 2,240,000
1,500,000 3,000,000

800,000 2,400,000

1,500,000 1,500,000

1,500,000 1,500,000

1,500,000 1,500,000

Total : Rp. 59,160,000