ANSI/TIA-607-C Generic “Telecommunications Bonding and Grounding (Earthing) for Customer Do I Need an LP-Rated Cable?
Premises” was developed by the TIA TR-42.16 Grounding and Bonding Subcommittee and published in
November, 2015. This Standard provides basic principles, components, and design of telecommunications Bundling Recommendations for
bonding and grounding that shall be followed to ensure that the telecommunication bonding and gr ounding PoE Applications
systems within a building will have one electrical potential.
All News
Adoption of a minimum bend radius and angle requirements for bonding conductors Sign up for the Standards Informant E-
Expanded listing of insulated conductors required to be color-coded green Newsletter
New recommendation for a minimum 0.6m (2 ft) grid spacing for mesh bonding networks »Subscribe to RSS
ANSI/TIA-607-C Content
Regulatory
Overview of Telecommunication Grounding and Bonding Systems Google Translate
Telecommunications Bonding Componen ts
Design Requirements
External Grounding
Performance and Test Requirements
Annexes addressing Bonding Methods, Grounding Electrodes, Towers and Antennas,
Telecommunications Electrical Protection, Electrical Protection for Operator-Type Equipment Positions,
and Cross Reference of Terms
ANSI/TIA-607-C-1 Content
The inside bend radius of telecommunications bonding conduct ors terminated at the primary bonding busbar
(PBB) or secondary bonding busbar (SBB) shall have an inside bend radius of 200 mm (8 in). At other locations,
bends in the bonding conductors should be limited to the greatest practical inside bend radius with a minimum
bend radius of 10 times the bonding conductor diameter recommended. In all cases, the minimum bend r adius
angle shall be 90° or greater.
The grounding requirements for shielded cabling systems are identical to those specified for unshielded cabling
systems with the exception of the following additional step:
Patch panels for shielded cabling shall be bonded t o the telecommunications bonding system in
accordance with manufacturer instructions
Bonding of the shielded patch panel may be accomplished by connecting a 12 AWG stranded wire from the
ground point (or lug) provided on the patch panel to the rack , cabinet, or enclosure, bonding conductor.