Вы находитесь на странице: 1из 1

VEDANTA LIMITED

CAIRN OIL AND GAS

Report No: 2018/Apr/06 Calibration Date: 22.02.2018


Project: Rajasthan Southern Area Devolopment
Unit: RGF
Description: Filsep filter
Tag No: 1320-PSV-0001-A Details of Test gauge
Make: FAINGER LESER Make : Crystal
Sr.No: 11120516 Sr.No : 473231
Type Conventional/ Belows/ Pilot Accuracy : 0.01kg/cm2
Set point: 9500 kPag Certificate No : 7115877
CDSP: 96.87 kg/cm2(g) Range : (0 - 300)kg/cm2
Back Pressure: Nil Valid up to : 26.05.18
Size: 1"600# X 1"150#
Orifice:
COLD DIFFERENTIAL TEST (kg/cm2(g))
SPECIFIED OBSEREVED REMARKS
TEST PRESSURE 96.87 INSTRUMENT FOUND SATISFIED
SEAT LEAKAGE TEST 90 % OF CDSP AS PER API 527
SPECIFIED OBSEREVED REMARKS
. 87.18 63.90 INSTRUMENT FOUND SATISFIED
BACK PRESSURE TEST
SPECIFIED OBSEREVED REMARKS
TEST PRESSURE NIL NIL
OTHER INSPECTION & INFORMATION
SERVICE : PG
VALVE SEALED WITH SEAL WIRE YES/ NO No
DATA SHEET NO: -
LINE NO:
AFTER TESTING CALIBRATION TAG PROVIDED YES/ NO YES
P& ID NO: DECO-RP01-P-PID-4001-04
Calibrated by : Hemant Inspected by : Checked by :
Mechanical Engineer QA/QC Mechanical Supt

Approved by: Maintenance Manager C. Prabhu


THE CERTIFICATE IS VALID FOR 12M FROM THE MONTH OF ISSUE April