Diagram
50 pins
connector
Outputs
indicators
1
2 Spindle
3 Output
4 Terminals
5
X Axis 6
Terminals 7
1 XYZ home
2 sensor
3
indicators
4
Y Axis 1
Terminals 1 2 XYZ Home
2 sensors’
3
3 terminals
4 4
5
6
System
Z Axis 1 indicator
2
Terminals
3 1
4 2 C.A.D
3
4
terminals
C Axis 1
2
Terminals
3 1
4 2 Main
Power
terminals
5V positive
outputs fuse
Sensors
terminals 24V
fuse
No Terminal Pin Pin function Note
X 5v+ Positive power terminal of X axis Don’t supply any other voltage
Axis driver口DC5V output to this pin
Output
1 Terminals Pulse X axis pulse signal output terminal
Output Vol≧3V Current≦8mA
Y 5v+ Positive power terminal of Y axis Don’t supply any other voltage
Axis driver口DC5V output to this pin
Output
1 Terminals Pulse Y axis pulse signal output terminal
Output Vol≧3V Current≦8mA
Z 5v+ Positive power terminal of X axis Don’t supply any other voltage
Axis driver口DC5V output to this pin
1 Output
Terminals Pulse Z axis pulse signal output terminal
Output Vol≧3V Current≦8mA
DIR Z axis direction signal output
terminal
4
Voltage≧3V Current≦8mA
Shielding Z axis driver output shielding line Don’t use this pin as GND
terminal
C 5v+ Positive power terminal of X axis Don’t supply any other voltage
Axis driver口DC5V output to this pin
Output
1 Terminals Pulse C axis pulse signal output terminal
Output Vol≧3V Current≦8mA
DIR C axis direction signal output
terminal
4 Voltage≧3V Current≦8mA
Shielding C axis driver output shielding line Don’t use this pin as GND
terminal
Note: the square pin is the first pin and others No goes as the arrow direction
No Terminal Pin Pin Function Note
X、Y、Z X-Se Home sensor signal terminal of It works when this terminal get
1 home X axis short circuit with Sensor-
sensor
terminals Y-Se Home sensor signal terminal of It works when this terminal get
X axis short circuit with Sensor-
Z-Se Home sensor signal terminal of It works when this terminal get
X axis short circuit with Sensor-
Note: the connection lines’ diameter should be above 0.3 square mm.
The shielding line should be connect one end and cut down the other end.
No Terminal Pin Function Note
Definition
F2 fuse Pulse signal 5V output overload
protection
6
Sensor-
24V-
4 5
Sensor+
24V+
X signal
X_Se
3
Y axis sensor
NPN type Y signal
Y_Se
2
Z signal
Z_Se
1
J8
N0ote: the connection line diameter should be
above 0.3 square mm. Shielding line just connect
Z axis sensor
NPN type one end and cut down the other end.
Home Sensors Diagram
(Machinery sensor)
X axis Sensor
Shielding
Shield ling
6
Sensor-
24V-
4 5
Sensor+
24V+
X signal
X_Se
3
Y axis Sensor
Y signal
Y_Se
2
Z signal
Z_Se
1
Note: the connection line diameter should be above 0.3 square
mm. shielding line should connect one end.
J8
Z axis sensor
J9
Shield Spindle
1
motor
24v-
2
Cutter 3 Metal
24v+ 4 绝缘体
CAD Diagram 1 Double
layer CAD
Note: CAD signal lines’ diameter should be above 0.3 square mm. Shielding line just connect one end.
For CAD diagram 1, the 24V- (Sensor-) should be well connect to spindle motor cover. And do not
connect it to the machine fracture.
If you adopt precisive CAD sensor, please pay attention to the voltage it asks.
Note on Voltage: Because the internal power circuits of CAD, XYZ home sensors and spindle output
terminal are connected. If you have offered power to XYZ home sensor terminal, then you need not to
give power to CAD or Spindle output terminals.
J7
S0 1
S1 2
S2 3
S3 4
SP+ 5
SP- 6
Shield 7
注意事项:图纸标出的信号线均采用屏蔽线连接方式连接,主轴控
制信号屏蔽线内芯径应满足0.3平方毫米。对于屏蔽层起始端标出
连接位置,而末端未标出的剪断即可,但断面尽量靠近焊接点。主
要是为了防止屏蔽层断面离焊接点过长,致使屏蔽线的内芯暴露太 Inventor
长引来干扰。在不使用段速控制只使用主轴起停模式时,只连接S0
线和SP-两线既可。
严禁将主轴控制信号屏蔽层在接口板接地的同时将变频器一
端也接与变频器外壳地端。这样连接可能导致主轴电机失控。
24V+ L
Switch Filter
~220V
24V- N
Note:The output voltage should be 24V +/- 5%. The connecting line
diameter from the switch to the connection board should be above 0.8
square mm.
Don’t connect GND in connection board to any GND ports.