Fire Extinguisher Design Procedure

I General Design Criteria


I.a Floor basis Minimum 2 extinguishers for
every 200 m2 area.
I.b Travel Basis Extinguishers should be Distance between 2 extinguishers
located at maximum 15m can be 15m to 30m.
radius from any location in
plant

m
15

15m

Sl.No. Area Description As per regulation Proposed System Remarks

1 Factory Warehouse/ As per Annex B, IS 2190:2010 Class B, MH


Workshop area/ Paint area
a Floor basis Two 9 litre foam extinguisher, 1 Foam type, 1 ABC dry powder Product Warehouse: 1285m2
mechanical type, or 5/6 kg dry type for every 200m2 floor area. 1285/200 * 2 = 14 No.s
powder extinguisher ( or one 7No.s Foam type, 7 No.s ABC type
of each type ) for every 200
m2 area with minimum of four
b Based on walking distance extinguisher per compartment. Extinguishers should be available Refer Reference Drawing "Sample
Extinguisher should be within 15m radius from any point in Fire Extinguishers Layout"
available within 15 m radius. plant.

2 Factory Machines area/ As per Annex B & Clause Class B, MH


Molding area 10.2, IS 2190:2010
a Floor basis 1) Two 9 litre foam extinguisher, 1 Foam type or CO2 type, 1 ABC dry Molding Room: 1485m2
mechanical type, or 5/6 kg dry powder
extinguisher ( or one of each type ) for powder type for every 200m2 floor 1485/200 * 2 = 16 No.s
every 200 m2 area with minimum of area. 4No.s Foam type, 4No.s CO2 type,
four extinguisher per compartment. 8 No.s ABC type
Extinguisher should be available
within 15 m radius.
2) Where energized electrical
b Based on walking distance equipment is involved Extinguishers should be available Refer Reference Drawing "Sample
in a fire, non-conductivity of the within 15m radius from any point in Fire Extinguishers Layout"
extinguishing media plant.
is of utmost importance, and only
extinguishers
CO2 extinguishers shall be located
expelling dry powder, carbon dioxide based on location of electrical
(without metal panels
horn) or clean agent should be used

3 Office Area As per Annex B, IS 2190:2010 Class A, SH

a Floor basis One 4.5 kg capacity carbon 1 CO2 type or 1 ABC dry powder All Office area: 727m2
dioxide or one 2/3 kg capacity type for every 100m2 floor area. 727/100 * 2 = 8 No.s
clean agent extinguisher for 4No.s CO2 type, 4 No.s ABC type
every 100 m2 of floor area or
part thereof with minimum of
b Based on walking distance two extinguishers so located Extinguishers should be available Refer Reference Drawing "Sample
as to be available within 10 m within 10m radius from any point in Fire Extinguishers Layout"
radius. plant.

1
Sl.No. Area Description As per regulation Proposed System Remarks

4 Canteens As per Annex B, IS 2190:2010 Class B, MH

a Floor basis Two 9 litre foam extinguisher, 1 Foam type, 1 ABC dry powder Canteen: 92m2
mechanical type, or 5/6 kg dry type for every 200m2 floor area, 92<200 = 2 No.s
powder extinguisher ( or one or minimum of 4 for each 1No. Foam type, 1 No. ABC type
of each type ) for every 200 compartment
m2 area with minimum of four
b Based on walking distance extinguisher per compartment. Extinguishers should be available Refer Reference Drawing "Sample
Extinguisher should be within 15m radius from any point in Fire Extinguishers Layout"
available within 15 m radius. plant.

5 DG shed As per Annex B, IS 2190:2010 Class B, MH As per Annex B, IS 2190:2010

a Floor basis Two 9 litre foam extinguisher, 1 Foam type, 1 ABC dry powder DG Shed: 74m2(74<200),
mechanical type, or 5/6 kg dry type for each DG No. of DG = 2,
powder extinguisher ( or one 2No. Foam type, 2 No. ABC type
of each type ) for every 200
m2 area with minimum of four
b Based on walking distance extinguisher per compartment. Extinguishers should be available Refer Reference Drawing "Sample
Extinguisher should be within 15m radius from any point in Fire Extinguishers Layout"
available within 15 m radius. plant.

6 HT/ LT Room, Transformer As per Clause 10.2, IS


2190:2010
a Floor basis Where energized electrical CO2 type & ABC dry powder type HT+LT Room area = 119m2
equipment is involved 1 No. CO2 type & 1 No. ABC type.
in a fire, non-conductivity of (1 No. sand bucket if required)
the extinguishing media
is of utmost importance, and
b Based on walking distance Extinguishers should be available Refer Reference Drawing "Sample
only extinguishers
expelling dry powder, carbon within 15m radius from any point in Fire Extinguishers Layout"
plant.
dioxide (without metal
horn) or clean agent should be
used

7 LPG Shed As per Annex B, IS 2190:2010 Class C, MH

a Floor basis One 10 kg dry powder 1 ABC dry powder type or 1CO2 type
extinguisher (stored pressure) for every 100m2 floor area,
or 6.5 kg carbon dioxide or minimum of 1 for each
extinguisher or 5 kg clean compartment.
agent for 100 m2 of floor area
or part thereof, with minimum
b Based on walking distance of one extinguishers of the Extinguishers should be available Refer Reference Drawing "Sample
same type for every within 15m radius from any point in Fire Extinguishers Layout"
compartment; extinguisher plant.
should be available within a
radius of 15 m.

2
Sl.No. Area Description As per regulation Proposed System Remarks

8 HSD Yard Class B, HH As per Annex B, IS 2190:2010

a Floor basis Two 9 litre foam extinguisher, 1 Foam type, 1 ABC dry powder
mechanical type, or 5/6 kg dry type for every 200m2 floor area plus
powder extinguisher ( or one One 50 litre foam type for every
of each type ) for every 200 100m2.
m2 area with minimum of four
extinguisher per compartment.
b Based on walking distance Extinguisher should be Extinguishers should be available Refer Reference Drawing "Sample
available within 15 m radius. within 15m radius from any point in Fire Extinguishers Layout"
plant.

12 Type of extinguishers

12.a ABC type A For all General fires like Organic


Material, Wood, Paper oil etc.
12.b DCP type D For fire due to flammable metals,
solids etc.
12.c Water CO2 type W For fire due to Liquid, Oil, Petrol
etc.
12.d Mechanical Foam type F For fire due to flammable solid,
liquid etc.
12.e CO2 type C For electrical fires.

12.f Sand Bucket The basic extinguisher for


flammable metal, liquid etc.

Note:
1 Generally ABC type and CO2 type fire extinguishers selected first and others are selected as per possible fire due to usage of the area.

2 The capacity of various types of extinguishers is based on the common practice in India.
3 For special areas like LPG facility, Electrical room, HSD Yard, Boiler area, Paint area appropriate requirement of various agencies and
Fire Officers also to be followed.