a Floor basis One 4.5 kg capacity carbon 1 CO2 type or 1 ABC dry powder All Office area: 727m2
dioxide or one 2/3 kg capacity type for every 100m2 floor area. 727/100 * 2 = 8 No.s
clean agent extinguisher for 4No.s CO2 type, 4 No.s ABC type
every 100 m2 of floor area or
part thereof with minimum of
b Based on walking distance two extinguishers so located Extinguishers should be available Refer Reference Drawing "Sample
as to be available within 10 m within 10m radius from any point in Fire Extinguishers Layout"
radius. plant.
1
Sl.No. Area Description As per regulation Proposed System Remarks
a Floor basis Two 9 litre foam extinguisher, 1 Foam type, 1 ABC dry powder Canteen: 92m2
mechanical type, or 5/6 kg dry type for every 200m2 floor area, 92<200 = 2 No.s
powder extinguisher ( or one or minimum of 4 for each 1No. Foam type, 1 No. ABC type
of each type ) for every 200 compartment
m2 area with minimum of four
b Based on walking distance extinguisher per compartment. Extinguishers should be available Refer Reference Drawing "Sample
Extinguisher should be within 15m radius from any point in Fire Extinguishers Layout"
available within 15 m radius. plant.
a Floor basis Two 9 litre foam extinguisher, 1 Foam type, 1 ABC dry powder DG Shed: 74m2(74<200),
mechanical type, or 5/6 kg dry type for each DG No. of DG = 2,
powder extinguisher ( or one 2No. Foam type, 2 No. ABC type
of each type ) for every 200
m2 area with minimum of four
b Based on walking distance extinguisher per compartment. Extinguishers should be available Refer Reference Drawing "Sample
Extinguisher should be within 15m radius from any point in Fire Extinguishers Layout"
available within 15 m radius. plant.
a Floor basis One 10 kg dry powder 1 ABC dry powder type or 1CO2 type
extinguisher (stored pressure) for every 100m2 floor area,
or 6.5 kg carbon dioxide or minimum of 1 for each
extinguisher or 5 kg clean compartment.
agent for 100 m2 of floor area
or part thereof, with minimum
b Based on walking distance of one extinguishers of the Extinguishers should be available Refer Reference Drawing "Sample
same type for every within 15m radius from any point in Fire Extinguishers Layout"
compartment; extinguisher plant.
should be available within a
radius of 15 m.
2
Sl.No. Area Description As per regulation Proposed System Remarks
a Floor basis Two 9 litre foam extinguisher, 1 Foam type, 1 ABC dry powder
mechanical type, or 5/6 kg dry type for every 200m2 floor area plus
powder extinguisher ( or one One 50 litre foam type for every
of each type ) for every 200 100m2.
m2 area with minimum of four
extinguisher per compartment.
b Based on walking distance Extinguisher should be Extinguishers should be available Refer Reference Drawing "Sample
available within 15 m radius. within 15m radius from any point in Fire Extinguishers Layout"
plant.
12 Type of extinguishers
Note:
1 Generally ABC type and CO2 type fire extinguishers selected first and others are selected as per possible fire due to usage of the area.
2 The capacity of various types of extinguishers is based on the common practice in India.
3 For special areas like LPG facility, Electrical room, HSD Yard, Boiler area, Paint area appropriate requirement of various agencies and
Fire Officers also to be followed.