Академический Документы
Профессиональный Документы
Культура Документы
General Concepts
Syllabus:
Course Objectives:
1. Long- range with time horizons on the order of 15 or 20 years away, and
2. Short-range, with time horizons of up to 5 years distant.
1. Feeder limitations
2. Transmission Voltage
3. Tie Capacity
4. Load Forecast
5. Present capacity & Configurations
6. Projection limitations
7. Physical size and land availability
8. Economic factors
9. Power Losses
2. Sites that have some promise but are not selected for detailed
evaluation during the planning cycle, and
1.2.4 Total Cost: The substation planning must be within the cost limits
and distribution of power in the large amount with low losses.
1. Service Continuity
2. The maximum allowable peak-load v o l t a g e drop to the most
remote customer on the secondary.
3. The maximum allowable voltage dip occasioned by the starting of a
motor of specified starting current characteristics at the most remote
point on the secondary.
4. The maximum allowable peak load
5. Service reliability
6. Power losses
Fig .1.9
Importance: The daily load curves have attained a great importance in
generation as they supply the following information readily:
(i) The daily load curve shows the variations of load on the power station during
different hours of the day.
(ii) The area under the daily load curve gives the number of units generated in the
day.
(iii) The highest point on the daily load curve represents the maximum demand
on the station on that day.
(iv) The area under the daily load curve divided by the total number of hours
gives the average
load on the station in the day.
Average load =
(v) The ratio of the area under the load curve to the total area of rectangle in
which it is contained gives the load factor.
Load factor
(vi) The load curve helps in selecting the size and number of generating units.
(vii) The load curve helps in preparing the operation schedule of the station.
When the load elements of a load curve are arranged in the order of
descending magnitudes, the curve thus obtained is called a load duration curve.
The load duration curve is obtained from the same data as the load curve but the
ordinates are arranged in the order of descending magnitudes. In other words,
the maximum load is represented to the left and decreasing loads are represented
to the right in the descending order. Hence the area under the load duration
curve and the area under the load curve are equal. Fig.1.10 (i) shows the daily
load curve. The daily load duration curve can be readily obtained from it. It is
clear from daily load curve [See Fig. 1.10 (i)], that load elements in order of
descending magnitude are : 20 MW for 8 hours; 15 MW for 4 hours and 5 MW for
12 hours. Plotting these loads in order of descending magnitude, we get the daily
load duration curve as shown in Fig.1.10 (ii).
Fig 1.10
The following points may be noted about load duration curve:
(i) The load duration curve gives the data in a more presentable form. In other
words, it readily shows the number of hours during which the given load has
prevailed.
(ii) The area under the load duration curve is equal to that of the corresponding
load curve. Obviously, area under daily load duration curve (in kWh) will give the
units generated on that day.
(iii) The load duration curve can be extended to include any period of time. By
laying out the abscissa from 0 hour to 8760 hours, the variation and distribution
of demand for an entire year can be summarized in one curve. The curve thus
obtained is called the annual load duration curve.
1.5 Load Characteristics:
1. Demand: The demand of a system is the load at receiving end over a
specified time interval.
2. Maximum Demand: The maximum demand of a system is the greater of all
the demands within the time interval specified.
3. Diversified demand (or coincident demand): It is the demand of the
composite group, as a whole, of somewhat unrelated loads over a
specified period of time.
4. Demand factor: It is the "ratio o f the maximum demand of a system to
the total connected Load. It is dimension less.
Demand factor is usually less than 1.0.
Demand factor = Maximum demand/ Total connected demand
5. Non-coincident demand: I t i s “the sum of the demands of a group
of loads with no restrictions on the interval to which each demand
is applicable."
6. Connected load :It is "the sum of continuous ratings of the load-
consuming apparatus connected to the system”
7. Utilization factor: It is "the ratio of the maximum demand of a system to
the rated capacity of the system "
Load diversity: It is "the difference between the sum of the peaks of two or
more individual loads and the peak of the combined load"
Loss factor: It is '' the ratio o f the average power loss to the peak-load
power loss during a specified period of time"
Ex 1.Assume that annual peak load of a primary feeder is 2000 kW, at which
the power loss, that is, total copper, or F.PR loss, is 80 kW per three phase.
Assuming an annual loss factor of 0.15, determine: (a)The average annual
power loss (b) The total annual energy loss due to the copper losses of the
feeder circuits
Solution:
(a) From
Average power loss = power loss at peak load
=80kWx0 .1 5 = 12 kW.
= 105,120Kwh
Ex 2. Assume that there are two primary feeders supplied by one of the three
transformers located at the NL&NP's Riverside distribution substation, as shown
in Figure 1.11. One of the feeders supplies an industrial load which occurs
primarily between 8 A.M. and 11 P.M., with a peak of 2000 kW at 5 P.M. The
other one feeds residential loads which occur mainly between 6 A.M. and 12
P.M., with a peak of 2000 kW at 9 P.M., as shown in Figure 1.12. Determine the
following:
Fig. 1.11
Fig 1.12
Where PLS avg is the average power loss, P LSmax is the maximum power loss, is the
peak loss at peak load.
Substituting
Where PLS1, is the off-peak loss at off-peak load, t is the peak load duration, and
T - t i s the off-peak load duration.
The copper losses are the function of the associated loads. Therefore, the off-
peak and peak loads can be expressed, respectively, as
Where k is a constant. Thus, substituting above Equations In F LS, the loss factor
can be expressed as
Load factor can be related to loss factor for three different cases
That is, the load factor is equal to the loss factor and they are equal to the t/T
constant
That is, the value of the loss factor approaches the value of the load factor
squared
Case 3: Load is steady. Here,
That is, the difference between the peak load and the off-peak load is negligible.
For example, if the customer's load is a petrochemical plant, this would be the
case
That is, the value of the loss factor approaches the value of the load factor.
Therefore, in general, the value of the loss factor is
Therefore, the loss factor cannot be determined directly from the load factor.
The reason is that the loss factor is determined from losses as a function of
time, which, in turn, is proportional to the time function of the square load
Where FLS is the loss factor (pu) and FLD is the load factor (pu).
The above Equation gives a reasonably close result. Figure shown below
gives three different curves of loss factor as a function of load factor.
Relatively recently, the formula given before has been modified for rural
areas and expressed as
Fig 1.15
Ex.3 The average load factor of a substation is 0.65. Determine the average
loss factor of its feeders, if the substation services:
= 0.49.
0.84 F
(b) For the rural area, FLS = 0.16FLD + ( LD)2
= 0.16(0.65) + 0.84(0.65)2
= 0.53
A device which taps electrical energy from the electric power system is
called a load on the system. The load may be resistive (e.g., electric lamp),
inductive (e.g., induction motor), capacitive or some combination of them. The
various types of loads on the power system are:
(i) Domestic load: Domestic load consists of lights, fans, refrigerators, heaters,
television, small motors for pumping water etc. Most of the residential load
occurs only for some hours during the day (i.e., 24 hours) e.g., lighting load
occurs during night time and domestic appliance load occurs for only a few
hours. For this reason, the load factor is low (10% to 12%).
(ii) Commercial load: Commercial load consists of lighting for shops, fans and
electric appliances used in restaurants etc. This class of load occurs for more
hours during the day as compared to the domestic load. The commercial load has
seasonal variations due to the extensive use of air conditioners and space
heaters.
(iii) Industrial load: Industrial load consists of load demand by industries. The
magnitude of industrial load depends upon the type of industry. Thus small scale
industry requires load upto 25 kW, medium scale industry between 25kW and
100 kW and large-scale industry requires load above 500 kW. Industrial loads are
generally not weather dependent.
(iv)Municipal load: Municipal load consists of street lighting, power required for
water supply and drainage purposes. Street lighting load is practically constant
throughout the hours of the night. For water supply, water is pumped to
overhead tanks by pumps driven by electric motors. Pumping is carried out
during the off-peak period, usually occurring during the night. This helps to
improve the load factor of the power system.
(v) Irrigation load: This type of load is the electric power needed for pumps
driven by motors to supply water to fields. Generally this type of load is supplied
for 12 hours during night.
(vi) Traction load: This type of load includes tram cars, trolley buses, railways
etc. This class of load has wide variation. During the morning hour, it reaches
peak value because people have to go to their work place. After morning hours,
the load starts decreasing and again rises during evening since the people start
coming to their homes.
1.7 Load modeling:
A load model is a mathematical representation of the relation between the
active or reactive power (or the current injection) at a load bus / node and the
complex voltage of node.
Load modeling has been carried out based on two different approaches. The
first approach measures the voltage and frequency sensitivity of the active and
reactive powers at substations.
P=P(V) [1+ DP Δf]
Q=Q(V) [1+ DQ Δf]