OBJECTIVE: For Safe & Smooth Operation of Turbine-generator lube oil system.
SCOPE: This SOP is applicable for Lube oil system for the steam turbine& generator Make DEC
China,Type. N600-16.7/538/538, of subcritical three cylinder/four flow, single shaft/single intermediate
reheat, condensing type.This procedure covers all the standard operating procedures related with lube
oil system of T.G.
INTRODUCTION: The lubricating oil system is provided to supply the lubricating oil for the
pedestal and thrust bearings of turbine-generator and for the turning gear. It also supplies the reserve
oil for the hydrogen seal oil system and the pressure oil for the mechanical overspeed trip device and
sufficient oil to the jacking oil pump
The lubricating oil system contains Main oil tank, MOP, BOP coupled with OIL TURBINE, TOP, EOP,
MSP, jacking oil pump(JOP), oil cooler and oil overflow valve etc. During the normal operation of the
unit, the inlet(suction) oil of MOP and the lubricating oil of the unit are supplied by the Booster oil
pump(BOP) which is installed inside the main oil tank. The pressure oil from the outlet of the main oil
pump is fed back to the BOP as its suction oil & this oil fed to oil-turbine mounted on the BOP shaft
which rotates the BOP. oil turbine on one hand utilizes the pressure of MOP discharge pressure for
rotating the booster oil pump(BOP) & after utilizing the pressure oil the oil gets depressurized & sent to
bearings as lube oil.When the unit is started and speeding up, or shut down, it is the TOP that feeds the
lubricating oil system. In the event of failure of the TOP, the EOP will take its place to maintain the
pressure of lubricating oil. The MSP supplies oil to the inlet of the main oil pump when the speed of the
turbine rotor is below 2850r/min. The jacking oil system is equipped with three pumps, comprising two
ACJOP and one DCJOP, which are started before the unit is turned by the turning gear to reduce the
start torque of the turning gear and prevent the shaft from rubbing against the bearing pad.
TECHNICAL DATA-
MAIN OIL TANK-
Main oil tank is an integrated oil tank with a lot of equipments of the system i.e.TOP,EOP,BOP,MSP,vapor
exhaust fan, oil level indicator, electric heaters etc. mounted on the oil tank.
Turbines Company
Oil- Type ISO VG-32 Capacity 41.6m3
MOP is a double suction single stage centrifugal pump coupled with T.G. main rotor & installed inside the
turbine front pedestal. During the normal running of turbine it runs along with turbine rotor & supplies oil
to Booster oil pump(BOP) from where oil gets depressurized & fed to T.G. Lube oil system.MOP takes
the suction oil from BOP discharge.
This pump supplies the oil for MOP suction during T.G. startup,shutdown or emergency conditions. MSP
supplies oil to the inlet of the main oil pump when the speed of the turbine rotor is below 2850r/min.
technology
This pump serves double purpose in the lube oil system.At one hand it utilizes MOP discharge pressure
oil as suction of OIL TURBINE mounted on shaft of BOP which rotates the BOP & after utilizing the
pressure of MOP discharge pressure oil BOP fed the oil to T.G. Lube oil system.Secondly this booster
pump supplies the oil to MOP suction.The throttle v/v, bypass v/v & overflow v/v of oil turbo should be
adjusted & throttled to maintain MOP suction pr. 0.098-0.147 Mpa & bearing lube oil pr. Between 0.137
-0.176 Mpa.
In the MOT 6 nos. of electric heaters are provided for initial heating of lube oil at start up time if the
temperature of lube oil in MOT is about 20 deg C.Use these heaters to raise the oil temperatures till 35
deg C & then stop.
The system is provided with oil fume separator device (vapor exhaust fans-2 nos.) which generates
slightly negative pressure inside the MOT causes the smooth flow of return oil in MOT & removes the oil
water vapors from the return oil & safely exhaust them in atmosphere.This improves turbine lube oil
quality & make system more reliable.
The system is provided with two nos. of oil filters installed on bearing lube oil supply circuit to maintain
the necessary lube oil cleanliness & quality in the system.
The lube oil system is equipped with 2 nos. of oil coolers (plate type heat exchangers)out of which one
will be in operation & other standby.it uses OCCW water as a cooling medium for taking heat of lube
oil.It generally keeps temperature of lube oil in the range 40-45 deg.C .
One oil purification device is incorporated with Lube oil system .the oil purification device seperatly
installed near MOT at 0 mtrs. Elevation.It took suction from MOT & after purification fresh oil fed back to
MOT.
cooler water line for any leakage,if any rectify the same.
10 Fire fighting system in respective area should be in
operating condition(Prechecking of all firefighting
nozzles, lines valves must done so that it may work
effectively during fire hazards.)
11 Check and make sure that lubricate oil temperature is
normal & there is no leakage in system.
START PERMISSIVE :
5 Check the lubricating oil system for leakage; ensure that the
lubricating oil pressure is not below 0.098MPa at the elevation of the √ √
front bearing housing.
6 Start the JOP. check the Discharge pressure & other parameters are
normal, check the individual bearings jacking oil pressure.JOP will be
√ √
in service till turbine attains 2500 RPM
7 Start the M.S.P. check the pressure & other parameters are normal.
MSP will be in service till turbine attains 2850 RPM √ √
8 Check & ensure the bearing lube oil return temperature is normal &
√ √
within limits
SHUTDOWN SEQUENCE:
PLANNED SHUTDOWN :
1 The Lube oil system can only be stopped if only the temperatures of √ √
Prepared by: Reviewed by: Approved by:
Signature: Signature: Signature:
Name: Saurabh Shrivastava Name: Name:
Designation: Asst. Manager Designation: Designation:
14
HPT inner casing comes below 120 Deg C & seal oil system is
working normally.
2 Jacking oil pump can stop(i.e. Barring gear) if only temp. of HPT √ √
Inner casing comes below 150 deg C.
3 After stopping the MSP & TOP from DCS,stop the water supply to oil
coolers,if and only temperatures of oil comes to 35 Deg C. Release √ √
the DC EOP from interlock.
4 Shut down the vapor exhaust Fan when all the pumps of lubricating
oil system has stopped & return lube oil temperatures comes below √ √
40 deg C
5 Pay attention to oil level rise of main oil tank, when oil level is too
high, it should overflow into oil storage tank out of turbine hall. √
INTRODUCTION: Turning Oil Pump (TOP) supplies oil to Turbo Generator bearings. There is one
AC motor driven TOP for supplying oil from bearing no.1 to 9 including thrust bearing. After TG attains a
speed of 3000 rpm, the shaft mounted Main Oil Pump (MOP) takes over and TOP is to be stopped. TOP
is to be kept select in ‘AUTO’ whenever the turbine is running. TOP is interlocked to start when the MOP
discharge pressure falls below 1.205MPa. TOP is rated to deliver 4685 Ltrs. meters per hour and is
driven by 415V, 3 phase, 75KW, 1480 rpm motor.
PRE CHECKS:
PLANNED SHUTDOWN :
1 The Turning oil pump(TOP) can only be stopped if only the turbine
rotor attains a speed of >2850 RPM or bearing temperatures of
Journal & thrust bearings comes below 50 deg C(lube oil system can √ √
stopped only When turbine HP inner casing temp. comes below 120
Deg C.)
2 Press the stop button on OIS and stop the TOP.
√
3 Check and confirm that emergency oil pump (EOP) can automatically
√ √
start and operate normally.
4 When the EOP starts the red lamp for operation indication on the OIS
turn on. When the TOP oil pump changes over to EOP oil pump, the
resultant sudden short time oil pressure drop will be detected by the
turning gear interlock device and therefore in this case the turning
√ √
gear will stop operation.
INTRODUCTION: Main startup pump(MSP) supplies oil to Main Oil pump (MOP) for suction head. At the
time of Turbine costing down, when turbine speed reduces to about 95%of rated speed(2850 RPM), the
discharge pressure of main oil pump is not high enough to drive booster pump, resulting in the shortage
of oil at main oil pump inlet. For safety sake MSP shall be started to feed oil to main oil pump inlet. There
is one AC motor driven MSP for supplying oil to MOP. During turbine rolling ,After TG attains a speed of
>2850 rpm, the shaft mounted Main Oil Pump (MOP) takes over and MSP is to be stopped. MSP is to be
kept select in ‘AUTO’ whenever the turbine is running. MSP is interlocked to start when the MOP suction
pressure falls below 0.07mpa.This is realized by electric interlock via pressure switch.
PRE CHECKS:
Sr. RESPONSIBILITY
Description
No. UCE DE FE EE
PRE- START CHECKS:
1 All permits and cross permits have been returned. √ √ √ √
SHUTDOWN SEQUENCE:
PLANNED SHUTDOWN :
1 Press the stop button on OIS and stop the MSP after turbine speed
√
reached >2850 rpm.
2 Check and confirm that suction (0.147MPa) as well discharge
√
pressure (1.55MPa) of MOP is normal after stopping MSP.
3 After stopping the pump put it on interlock. √
1) Turbine trip √
INTRODUCTION Emergency oil pump (EOP) comes into service in the event of an emergency. This
is driven by a DC motor.In the event of total plant power failure or, if the AC driven auxiliary oil
pump(TOP) fail to start due to any reason this pump comes to operation by interlock when lube oil
header pressure drops to 0.105 Mpa to supply the lube oil to TG bearings for its safe coasting down and
subsequent baring gear operation.
PRE CHECKS:
Sr. RESPONSIBILITY
Description
No. UCE DE FE EE
PRE- START CHECKS:
1 All permits and cross permits have been returned. √ √ √ √
2 DC power supply is available. √ √
3 Pressure switch interlock is properly incorporated √ √
4 Main oil tank is filled with suitable amount of qualified Oil and Oil
level is normal in Local & DCS. √ √
START PERMISSIVE :
1 TOP fails during start & lube oil pressure lower than 0.105 Mpa. √ √
START UP SEQUENCE :
1 DC EOP will start if the lube oil header pressure is lower than
0.105mpa. & MOP/TOP fails due to any reasons(power failture or √ √
any other reason)
2 If the interlock does not work the pump can be started from OIS. √ √
3 After starting the pump check discharge pressure and motor current. √ √
4 Check and make sure that vibration and sound is normal. √ √
5 Check the level of MOT is normal and oil level is indicated on OIS. √
SHUTDOWN SEQUENCE:
PLANNED SHUTDOWN :
Normally the Two AC driven JOP runs for barring gear. In the event of TG tripping due to total plant AC
failure or outage of Both AC JOP due to any reason, the DC driven JOP is to be run.
PRE CHECKS:
SAFTEY PRECAUTIONS:
Ensure no permit to work is pending on regarding this system by checking with EE/MRSE.
Sr. RESPONSIBILITY
Description
No. UCE DE FE EE
PRE- START CHECKS:
1 All permits and cross permits have been returned. √ √ √ √
2 Power and control supplies are available
√ √
3 TOP or EOP is running and oil temperature should be 35~40°C.
√ √
4 Oil extraction fan is in service √ √
5 Generator seal oil system must be in service prior to JOP start up. √ √
6 Suction and discharge valves of the JOP to be run are in open
√
condition and drain valves are close.
7 Both the micro filters at JOP discharge are in service.
√
START PERMISSIVE :
START UP SEQUENCE :
1 Start the JOP from OIS. √
2 After starting the pump check the discharge pressure of pump &
individual bearing supply line. √ √
PLANNED SHUTDOWN :
1 When the TG set is no longer on barring gear the JOP can put off.
√
1 Allow start jacking oil pump: Jacking oil pump inlet oil pressure not
low
2 jacking oil pump auto start:
Jacking oil pump inlet oil pressure is low and delay 5s.
INTRODUCTION During normal running of turbine , the lube oil supplied to various bearings comes
in to contact with condensate steam/water particles due to leakage through steam sealing rings& oil
catcher rings of journal & thrust bearings causing contamination of return oil. Further due to friction &
temperature rise in the system oil vapor will produce in the system.
Hence it is necessary to safely discharge the above oil & vapor fumes in to atmosphere for maintaining
the supply oil quality . for this purpose vapor exhaust fan (2 nos. )installed at the top of main oil tank
PRE CHECKS:
SAFTEY PRECAUTIONS:
Ensure no permit to work is pending on regarding this system by checking with EE/MRSE.
START UP SEQUENCE :
1 Start the Fan by giving Start command from DCS √
2 Check the normal current of mootor √ √
3 check for any abnormal sound or vibration. √ √
4 Check for MOT tank vacuum - it should be around 100-200 kpa. √ √
SHUTDOWN SEQUENCE:
PLANNED SHUTDOWN :
1 If all the pumps of lubricating oil system has stopped & temperature √
of return oil is below 40 Deg C. then vapor exhaust fan can be √
stopped
2
EMERGENCY SHUT DOWN
1
2
3
4
ABRIVIATIONS / NOTATIONS:-
o SOP: Standard Operating Procedure
o UCE: Unit Control Engineer
o DE: Desk Engineer
o FE: Field Engineer
o DCS: Distributed Control System
o EE: Electrical Shift Engineer
o MFT: Main Fuel Trip.