ffiffi ffiffi On-Site Test

ffiffiffi$$ Protocols for Commissioning

Gas density relay


Measuring instrument type. tr DILO SK 509
tr
Inventory no.: H437022664
SFo pressure (measured actual value):-__..-_..__._-_--_. see table 1

SFo filling pressure (default value):-.....-.. .___.- see appendix B

Table 1: SF6 pressures


SFs- filling pressures
Contact / Tu Default Actual
Bay Gas density relay Remarks
signal level
at ambient temperature
oc kPa (100 kPa = 1 bar)

=C21 GO 11-13 20 620 634 s/N 602495081


21-23 20 600 614
31-33 20 600 615
G1 11-13 20 540 551 s/N 606806{11
21-23 20 520 533
G2 11-13 20 540 551 s/N 606806426
21-23 20 520 532
G4 11-13 20 540 549 s/N 606806417
21-23 20 520 531

=C23 GO 1 1-13 20 620 631 s/N 602495{54


21-23 20 600 612
31-33 20 600 613
G2 1 1-13 20 540 549 s/N 606806{16
2',1-23 20 520 533
G4 11-13 20 540 550 s/N 606806004
2',1-23 20 520 532

Tu = Ambient temperature (indoor design), temperature of housing (outdoor design)

Note The oressure levels as well as the formula for calculation of the required pressure can
be found in appendix B.

Tested: Mourad REMILI xrr,rlrn(P:


07.06.2017 10.06.2017

Date, Consultant