Вы находитесь на странице: 1из 2

UP16.

UP16.12
TEST/SIMULATIONS RESULTS:

UP16.3

Temp Element: Thermocouple Type K

Input Signal Display Reading DCS Alarm Indication

27 mV 653 deg. C none

28 mV 678 deg. C none

29 mV 704 deg. C TAH4666A

30 mV 735 deg. C TAH4666A

31 mV 769 deg. C TAHH4666A, TAH4666A

UP16.12

Temp Element: Thermocouple Type K

Input Signal Display Reading DCS Alarm Indication

27 mV 647 deg. C none

28 mV 672 deg. C none

29 mV 695 deg. C none

30 mV 727 deg. C TAH4666B

31 mV 755 deg. C TAHH4666B, TAH4666B

Additional remarks:

 Need to do simulation again when the MCC cell is reinstalled to verify tripping of the heater
supply at high and high-high temp.conditions

 Verify with DCS the HW bridge they’ve done as indicated on the info-tag on the cable
connected at UP16.12

Вам также может понравиться