ABSTRACT
A THEATER ENCOUNTERED THE PROBLEM OF
INCORRECT OPERATION OF POWER GENERATOR’S
EARTH FAULT PROTECTION SYSTEM WHICH TRIPPED
OUT CIRCUIT BREAKER WHEN DIMMER LOADS WERE
FULLY USED. THIS THEATER UTILIZED A LOT OF
DIMMERS AND INSTALLED A BACKUP POWER
GENERATOR WITH EARTH FAULT PROTECTION
SYSTEM. THE BACKUP GENERATOR WOULD SUPPLY
POWER TO A CRITICAL LOAD VIA AN AUTOMATIC
TRANSFER SWITCH (ATS) WHEN OUTAGE OCCURRED.
THE PROBLEM WAS CAUSED BY A HIGH DEGREE OF
THIRD HARMONIC CURRENT PRODUCED BY DIMMERS
AND INAPPROPRIATE INSTALLATION OF NEUTRAL AND
GROUND SYSTEM. CONSEQUENTLY, CURRENT
WOULD FLOW IN NEUTRAL AND GROUND SYSTEM
EVEN IN NORMAL LOAD CONDITION CAUSING ERRORS
TO CURRENT DETECTION OF EARTH FAULT
PROTECTION SYSTEM. TO RESOLVE THE SITUATION,
CHANGING EXISTING 3-POLE ATS TO 4-POLE TYPE
WAS NEEDED IN ORDER TO CONTROL CURRENT IN
NORMAL LOAD CONDITION (FUNDAMENTAL AND
THIRD HARMONIC CURRENT) TO FLOW IN ONLY
PHASE AND NEUTRAL CONDUCTOR AND NOT IN
GROUND CONDUCTOR WHICH WOULD LEAD TO
INCORRECT OPERATION OF EARTH FAULT
PROTECTION SYSTEM.
1. Introduction
A theater installs a lot of dimmers to control stage
lighting. These dimmers and other important loads are
connected to an Emergency Distribution Board (EDB) then
the Metropolitan Electricity Authority of Thailand (MEA)
feeder or an emergency generator selectable by an
Automatic Transfer Switch (ATS). See Figure 1, an
electrical line diagram for more details. In the Generator
Control Panel (GCP), an Earth Fault Relay is installed to
monitor a short circuit to ground condition and to protect the
generator. (Remark: Red line 3L represent 3 phase line,
white line represent neutral line, and green line represent
groung line).
Figure 1: An electrical line diagram of the theater.
3. Estimated loss
There is no equipment damage in this circumstance.
However, in each show, there are approximately 1,000
audiences and 1,000 Baht per ticket (20 Euro per ticket).
This theater may have to pay up to 1,000,000 Baht (20,000
Euro) for returned tickets. And also affect to the theater’s
reputation.
5. Problem analysis
Three scenarios is discussed here, one for normal load
circumstance, two for short circuit to ground circumstance,
and three for the third harmonic current from dimmers.
5.1 Normal load circumstance.
An unbalance load creates nonzero current flowing in
neutral and ground lines as shown in Figure 5. This current
can mislead the relay for the short circuit to ground.
Therefore, the relay is set to activate when 20 -30% of full
load current is detected. In this case, 600 A is set.
circumstance.
6. Solution
One way to solve the misinterpretation of the relay in
case of the third harmonic current in the ground line is to
change the ATS from three pole type to four pole type. This
change will control the harmonic current to flow only in the
neutral line between GCP and EDB only (and not get into the
ground line at the generator at GCP). This ATS type change
is to add one more switch for separating neutral circuits on
the MEA side from the generator side. Moreover, ground
line connection between GCP and EDB should be
disconnected. See Figure 8.
Figure 8: Electrical diagram shows 4-pole type ATS is
replaced 3-pole type ATS.
ATS can block the Earth Fault current that may flow thru
quicker.
Figure 10: Short circuit current flow during Earth Fault when
4-pole ATS is replaced.
7. Expenditure
Four pole ATS costs about 200,000 Baht (4,000 Euro),
which is 30,000 Baht (600 Euro) more expensive than the
three pole type. This cost does not include new wiring cost.
8. Conclusion
The third harmonic currents generated from dimmers
can make a generator’s Earth Fault Relay misinterpreting
situation and trip the generator’s circuit breaker. This is due
to the currents does not cancel each other at the neutral
point as in the normal load current. Additionally, improper
ground and neutral line wiring make current flow through
these lines significantly greater than it should be and again
make the Earth Fault Relay misinterpreting it as a short
circuit to ground and trip the generator breaker. Changing
the ATS from three pole type to four pole type can control
currents to flow only in phase and neutral lines.
Consequently, the Earth Fault Relay will not misinterpret
situation anymore.
----------------------------------------