Ref: FAMC-MPC-TS-GA-IPS-001

Date: 14/09/2019
Reply To Comments
No Comments Al Sanabel Reply

DBP UPS.IPS01-B1-PO (TYPICAL)- Attached GA As per IEC 60364-7-710/ IEC 61558-2-15,


drawings showing two Nos. 6.3 KVA transformer with The maximum permitted rating is 10 KVA. For larger
80A isolators instead of 12.6 KVA /100A as per ratings, two or three transformers are used. Copy of
1 approved load schedule (12.6 KVA transformer is split relevant regulation is attached. Revised load schedules
in two 6.3 KVA transformers), Provide manufacturer
are also attached.
clarification letter prior material delivery.

2 Updated AS-Built as per actual panel construction Material is delivered on site. Updated As-Built Drawings
should be provided prior material delivery. are provided along with the panels.

3 ERB/Connection details should be reflected on the ERB/Connection details highlighted in attached sheet of
drawings. wiring schematic (Typical).

4 Alarm Monitoring Panel is not shown on drawings. Connections to remote alarm unit highlighted in the
attached sheet of wiring schematic.

5 Comments reply sheet should be submitted prior Complied.


material delivery.