STAAD INPUT
STRUCTURE DESIGN FOR 33kV SINGLE - RSJ POLE
1.GENERAL DATA:
1.1 Material Properties:
= 250 N/mm²
Steel use in Steel.str(fy) ---------------------------------------------------------
Unit weight of Steel -------------------------------------------------------------------------
= 78.5 KN/m³ Table 1-IS 875 (Part-1)-1987 _pg 17.
Factor of Safty (Normal Con) ---------------------------------------------------------
= 1.2
Factor of Safty (BW Con) ---------------------------------------------------------
= 1.2
1.2 Tower Details:
Transmission line ---------------------------------------------------------------------
= 33 kV
Tower --------------------------------------------------------------------------------------
= SINGLE - RSJ POLE
Lat. Dim. of Str. -------------------------------------------------------------------------
= UC 100 x 116 x 23
Height of the of Steel Structure (h) ---------------------------------------------------------
= 8.300 m
Height of the of Pedestal above GL (h) ---------------------------------------------------------
= 0.450 m
Height of Peak -------------------------------------------------------------------= 2.150 m
= 6.750 m
Height of tower from base to cross arms --------------------------------------------------------- , 0.000 m & 0.000 m
Height of the of Structure above GL (h) ---------------------------------------------------------
= 7.850 m
Basic/Ruling Span Right side -------------------------------------------------------------------
= 70.00 m
Basic/Ruling Span Left side -------------------------------------------------------------------
= 70.00 m
2.DESIGN DATA:
2.1 Normal Condition Span Details:
= 70.0 x 1.00
Wind Span --------------------------------------------------------------------- = 70.00 m
= 70.0 x 2.00
Weight Span (Max.) ---------------------------------------------------------------------
= 140.00 m
= 140.0 x 0.50
Weight Span (Min.) ---------------------------------------------------------------------
= 70.00 m
q1
Deviation Angle (Max.) ---------------------------------------------------------= 0° ( as per profile dwg.)
q = q1 / 2 = 0 °
Deviation Angle (Max.) ---------------------------------------------------------
****************************************************
* *
* STAAD.Pro V8i SELECTseries5 *
* Version 20.07.10.64 *
* Proprietary Program of *
* Bentley Systems, Inc. *
* Date= MAY 9, 2019 *
* Time= 15:22:54 *
* *
* USER ID: *
****************************************************
*** NOTE: If any floor diaphragm is present in the model Wind Load definition
should be defined after Floor Diaphragm definition. Otherwise wind
load generation may be unsuccessful during analysis.
P R O B L E M S T A T I S T I C S
-----------------------------------
STEEL TAKE-OFF
--------------
86. PARAMETER 1
87. CODE IS800 LSD
88. MAIN 250 MEMB 201 202 301 302
89. CHECK CODE MEMB 201 202 301 302
R0-33KV-RSJ POLE STR -- PAGE NO. 6
|----------------------------------------------------------------------------------|
| Member Number: 201 |
| Member Section: ST 100X116 (UPT) |
| Status: PASS Ratio: 0.991 Critical Load Case: 10 Location: 0.00 |
| Critical Condition: Slenderness |
|----------------------------------------------------------------------------------|
| Member Number: 202 |
| Member Section: ST 100X116 (UPT) |
| Status: PASS Ratio: 0.374 Critical Load Case: 10 Location: 0.00 |
| Critical Condition: Slenderness |
|----------------------------------------------------------------------------------|
| Member Number: 301 |
| Member Section: ST ISMC100 (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.268 Critical Load Case: 10 Location: 0.00 |
| Critical Condition: Slenderness |
|----------------------------------------------------------------------------------|
| Member Number: 302 |
| Member Section: ST ISMC100 (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.268 Critical Load Case: 10 Location: 0.00 |
| Critical Condition: Slenderness |
|----------------------------------------------------------------------------------|
R0-33KV-RSJ POLE STR -- PAGE NO. 7
90. FINISH
************************************************************
* For technical assistance on STAAD.Pro, please visit *
* http://selectservices.bentley.com/en-US/ *
* *
* Details about additional assistance from *
* Bentley and Partners can be found at program menu *
* Help->Technical Support *
* *
* Copyright (c) 1997-2014 Bentley Systems, Inc.