Вы находитесь на странице: 1из 1

Project : Kelapa Gading Square

Subject : Estimated Electrical Load Calculation (Apartments in North City Walk)


Prepared by : PT. Arnan Pratama Consultants
Dated : 20 May 2003

APARTMENTS IN NORTH CITY WALK

 5 Tower Apartments
 1 Tower = 19 Floor Level = 190 unit Apartment
 Per floor level = 10 unit Apt.

Asumsi

A. PER UNIT APT. = 60 ~ 70 m2


- (2) R. Tidur
- Toilet
- R. Makan
- R. Keluarga
- Pantry

70 m2 x 65 VA/m = 4,550 VA
Power Supply per unit Apartment = 4,400 VA (20 A, 1ph)

Kebutuhan Daya Total untuk Apartment

 950 unit Apartment x 4400 VA = 4,180,000


VA
= 4,18 MVA

B. PER LEVEL PODIUM =  6,000 m2

Total Luas Podium 6,000 m2 x 5 level = 30,000 m2

Kebutuhan Daya untuk Podium

30,000 m2 x 100 VA/m2 = 3,000,000 VA


= 3,0 MVA

C. TOTAL DAYA LISTRIK YANG DIBUTUHKAN (POINT A + B)

4,18 MVA + 3,0 MVA = 7,18 MVA