) PMU (2) PSU (R4850G2) (3) Filler panel (4) EPU05A-03 or EPU05A-05 Subrack
11A
Description
Module
Application Description
Type
Exteriors
Figure 1 and Figure 2 show the exteriors of the EPU05A-03 and EPU05A-05 subracks,
respectively.
Figure 1 Exterior of the EPU05A-03 subrack
(1) AC surge (2) PSU1/4 circuit breaker, PSU2/5 (3) AC (4) BAT circuit
protector circuit breaker, and PSU3 circuit OUTPUT breaker
breaker circuit
breaker
(5) Circuit breaker (6) Output terminal for storage (7) Output (8) Output terminals
for RFC 1 batteries terminal for for LOAD 0 to
RFC 1 LOAD 8
(9) Output (10) Spare fuse box (11) Short- (12) AC INPUT
terminals for RRU circuiting bara
0 to RRU 5
(13) AC OUTPUT - - -
NOTE:
a: When a short-circuiting bar is installed on the AC INPUT wiring terminal to connect the L1,
L2, and L3 terminals, the EPU subrack supports 220 V AC single-phase power. When the EPU
subrack supports 220 V AC three-phase power, the short-circuiting bar needs to be removed.
Function
An EPU05A-03 or EPU05A-05 distributes AC and DC power.
An EPU05A-03 or EPU05A-05 subrack performs the following AC power distribution
functions:
Provides two AC outputs. One is used for the service outlet unit (SOU). The other
one is connected to the junction box on the left side of the cabinet interior, and
divided into four AC power outputs, which are then provided to the heater or
heating film.
Reports AC input surge protection alarms.
An EPU05A-03 or EPU05A-05 subrack provides 17 DC outputs for a distributed base
station.
Terminals
The following figure shows the power input and output terminals on the EPU05A-03 or
EPU05A-05 subrack, as shown in Table 2, Table 3.
Figure 3 Power input and output terminals on the EPU05A-03 or EPU05A-05 subrack
LOAD 2 FAN
LOAD 3 TM_0a
LOAD 4 TM_1
LOAD 7 TMC
LOAD 8 IBBSb
NOTE:
a: TM is the customer transmission equipment. LOAD3, LOAD4, LOAD5, and LOAD6 are DC
output terminals for the transmission equipment, supporting four DC outputs.
b: When the IBBS200D is configured, LOAD8 is the DC output terminal connecting to the
IBBS200D fan power cable. When IBBS200T is configured, LOAD8 is the DC output terminal
connecting to the IBBS200T TEC power cable.
c: The spare fuse box can provide five 5 A fuses and three 30 A fuses, which can be used to
replace broken ones onsite.
Circuit Breakers
There are several circuit breakers on the EPU05A-03 or EPU05A-05 subrack panel to control the
DC outputs. The following figure shows the positions of the circuit breakers and the following
table describes the specifications of the circuit breakers.
Specifications
Component
PMU 11A
A power monitoring unit 11A (PMU 11A) manages the power system and battery, monitors
power distribution, and reports alarms. It can be used in BTS3900(Ver.D), BTS3900L(Ver.D),
BTS3900AL(Ver.A), OMB(Ver.C), BTS3900(Ver.D_A), BTS3900(Ver.D_B),
APM30H(Ver.D), APM30H(Ver.D_A1), APM30H(Ver.D_A2), APM30H(Ver.D_B),
BTS3012(Ver.D_Z), BTS3012AE(Ver.D_Z) cabinets and IMS06 subrack.
Exterior
The following figure shows the exterior of a PMU 11A.
Function
A PMU 11A performs the following functions:
Communicates with the upper-level device through an RS485 port.
Manages the power system and the charge and discharge of storage batteries.
Monitors the door status and the temperature of storage batteries.
Monitors power distribution and reports alarms.
Communicates with the battery cabinet through an RS485 port.
Port
The following figure shows the ports on a PMU 11A.
Indicator
The following table describes the indicators on a PMU 11A.
ALM Alarm Red Steady on Alarms are generated, and the module must
indicator be replaced.
DIP Switch
There is a DIP switch on the left panel of the PMU 11A. The DIP switch has eight bits, where
the four least significant bits 1, 2, 3, and 4 define the monitoring address of the PMU 11A, and
the four most significant bits 5, 6, 7, and 8 are not defined but reserved for future use.
ON is indicated by 1, and OFF is indicated by 0. The monitoring address of the PMU 11A is set
to 3 by default before delivery, as shown in the following figure.
NOTE:
At a site configured with two or more APM30Hs, if two PMU units are connected to one RS485
bus for the BBU, the monitoring address of the other PMU is set to 4. That is, the lower four bits
of the DIP switch are set to 0010.
PSU (R4850G2)
A power supply unit (PSU) (R4850G2) converts 110 V AC or 220 V AC power into -48 V DC.
It can be used in BTS3900(Ver.D), BTS3900L(Ver.D), BTS3900AL(Ver.A), OMB(Ver.C),
BTS3900(Ver.D_A), BTS3900(Ver.D_B), APM30H(Ver.D), APM30H(Ver.D_A1),
APM30H(Ver.D_A2), APM30H(Ver.D_B), BTS3012(Ver.D_Z), BTS3012AE(Ver.D_Z)
cabinets and IMS06 subrack.
Exterior
The following figure shows the exterior of a PSU (R4850G2).
Function
A PSU (R4850G2) performs the following functions:
Converts 110 V AC or 220 V AC power into -48 V DC and adjusts the output voltage.
Provides protection against overcurrent, overvoltage, and overtemperature for its DC
outputs.
Dissipates heat using its built-in fans.
Indicator
The following figure shows the indicators on a PSU (R4850G2).
The following table describes the indicators on a PSU (R4850G2).
Blinking (on for 1s and The communication between the module and
off for 1s) the PMU is interrupted.