Академический Документы
Профессиональный Документы
Культура Документы
R E G . N O . 8 1 / 0 1 9 2 8 / 0 7
P H O N E ( 0 2 1 ) 7 1 5 8 3 1 8 F A X ( 0 2 1 ) 7 1 5 8 5 4 1
Dear Jason
Thank you for your discussions re general heat pump selection and design. We’ve given a
general approach of how we would go about selection of the storage and heat pump
capacity for say a hotel of say 70 beds (100 people). This would include the kitchen and
laundry.
The peak 60C consumption including all facilities will be 125L/day/person in winter
(see attached hot water consumption table attached).
Hot water generation running costs should be based on an average consumption over the
year of 100L/day.
The average mains water temperature is 18C and falls as low as 12C in Gauteng.
For quick accurate calculations: 1 KWH = 20L water x 42dT
For hot water storage, assume that you need to store 50% of daily usage i.e.
62.5L/person. This assumption will permit lopsided consumptions of 67%/33%
morning and evening.
If you are comparing electrical element requirements vs heat pumps, you should follow
ASHRAE or IHVE recommendations of a 4hr recovery time, although we’re sure that a
6hr recovery is adequate for elements. Because heat pumps generate constant 60C water
as opposed to the mixed temperature from elements, the heat pumps need to generate the
60C hot water of 125 L/day/person on the coldest winter day.
In mid-winter your losses can be up to 30% of the daily generated 60C water i.e. you
need to design for generation of 1.4 x 125L/day/person. Average annual losses = 0.4 x
100L/day/person
From above, a full central plant system would be able to generate 100x1.4 x125 (=
17500L/day of 60C water). The required storage would be 62.5x100 (= 6250L storage).
Heat Pump running cost (Average annual COP 3.2 = Equiv. 30% Energy in)
Annual SAVINGS:
Investment PAYBACK:
NOTE: If it’s a new building, the council requires a capital payment for the intended
KVA connection. This is significant and the reduced KVA requirements with a heat
pump can sometimes almost be covered by this bulk factor charge.
We should probably give you a call when you have had a chance to read this.
We trust you will find this information clear and complete. Please do not to hesitate to
contact us if we can be of any further assistance.
Regards
Lawrence
HOT WATER CONSUMPTION DESIGN GUIDE
Retirement Village
General H3 100L/p/d 80L/p/d 5.7 4.6 142L/p/d 98L/p/d 8.1/p/d 4.9/p/d 50L/p 50L/p
Old Age Home
General H4 65L/p/d 52L/p/d 3.7 3.0 92L/p/d 63L/p/d 5.7/p/d 3.4/p/d 35L/p 35L/p
1
dependent on No. shifts
2
If restricted bathing
3
If HW consumption metered individually
4
If HW generated @constant 60C as per Fig.1
5
KW =Storage Liters*4.18*Winter dT/3600/4
EXAMPLE:
Calculate peak winter CONSUMPTION and SYSTEM energy requirements for 50 room
hotel in Bloemfontein AND the "Deemed to satisfy" requirement (assume Avg mains 18C) FIG.1
From Table 5 10252-1:2016 Peak for Med/Expensive Hotels 177L/p/d & mains water temp
Table I.5 column 14: 7.2C. Table 5 10400:2016 H1 Person density = 2
Peak mid-winter SYSTEM capacity required=2*50*(60-7.2)*177*4.18/3600=1085 KWH/d
Peak mid-winter CONSUMPTION capacity required=2*50*(60-7.2)*100*4.18/3600=766 KWH/d
NOTE: Energy to heat water = (60-Mains)*4.18/3600=KWH/L
NOTE:Annual AVG "Deemed to satisfy" (50% of annual CONSUMPTION energy @population density)
= 0.5*2*50*(60-18)*4.18/3600 = 2.44 KWH/day throught the year