SCHEDULE OF TECHNICAL DATA FOR DISTRIBUTION


TRANSFORMERS , 11/0.415KV 400 KVA RATING.
WAPDA SPECIFICATIONS DDS-84:2007 (A-5)

Transfopower
Industries (pvt) Ltd.
1 Name & address of the manufacturer.
2 Km Katar Bund Road,
Thokar Niaz Baig, Off
Multan Road, Lahore
2 Experience of transformer ‘s manufacturing. 22 Years
3 Type/Model. TTO 400/11
4 Rated voltage at no load.
a) Higher voltage side. 11 KV
b) Lower voltage side. 0.415 KV
5 Conforming standard (WAPDA Specs: DDS-84 (A-5) ) , IEC - 60076
6 Rated current.
a) Higher voltage side. 20.99 A
b) Lower voltage side. 556.48 A
7 Rated capacity. 400 PMT KVA
8 No. of phases. 3
9 Impedance voltage. 1.12 4 %
10 Percentage reactance. 3.84 %
11 Type of cooling. ONAN
12 Regulating taps(%). 2.5, 0 , -2.5 , -5.0,- 7.5 %
(Tappings being located on HV winding.) Yes
13 Insulation material & points of application . Class - A
14 Insulating oil ,
Whether it meets the requirement of IEC-296 class -I oil Yes
15 Insulation level. (BIL) LI 95
16 Power frequency test voltage. 34 KV
17 Impulse test voltage.
a) Full wave. 95 KV
a) Chopped wave 110 KV
18 Induced voltage with frequency.
a) HT winding. 22 KV , 200 Hz
b) LT winding. 830 V , 200 Hz
19 Limits of temperature rise for prototype
a) Winding. 50°C
b) Core. < 50°C
c) Oil. 40 °C
20 Limits of temperature rise for mass production
a) Winding. 50°C
b) Core. < 50°C
c) Oil. 40°C
21 Short circuit withstand standard. IEC - 60076(5)

22 Reference ambient temperature.


a) Max. ambient air temperature. 45°C
b) Max. daily average ambient temperature. 40°C
c) Max. yearly average ambient temperature. 30°C
d) Altitude. 1000 m above sea level
23 a) Oil weight. 417 Kg Approx
b) Core weight. 640 Kg Approx
c) HT winding.
I ) Weight. 206 Kg Approx.
II ) Dia of wire/P.I.Cu Strip.
With Insulation. 2.0 x 4.6
Without Insulation. 1.4 x 4.0
III ) Outer diameter of coil / packet Round/Straight. 335 mm Approx
IV ) Height of Coil 415 mm Approx
V ) No. of HT winding packets. Disc Winding

Page 1 of 3
400 kVA

d) LT winding.
I ) Weight 109 Kg Approx
II) Dia of wire . 3.5 x 9.0 / 4.1 x 9.6
III) Outer diameter of coil / packet Round/Straight. 233 mm Approx
IV) Height of coil / packet. 405 mm Approx
V) No. of winding packets. 1 No
e) Liftable weight including weight of winding , 1085 Kg Approx
weight of core , top cover , bushing & hardware.
f) Weight of empty tank without top cover. 448 Kg Approx
g) Weight complete transformer. 2721 Kg Approx Including Panel
24 Vector group. Dyn-11
25 Type of test certificate , if any.
a) Issuing authority. HV & SC Lab. Rawat
b) WAPDA approval letter No.& date (Copy attached) Attached

26 TIPL Guaranteed Losses.


a) Total copper losses at 100% rated load. 4480 Watts
b) Total iron losses at 100% voltage. 740 Watts
c) Total losses Minimum 5220 Watts

27 Efficiencies.
1. For unit power factor.
a) At 100% rated load. 98.71 %
b) At 75% rated load. 98.93 %
c) At 50% rated load. 99.08 %
2. For 0.8 power factor.
a) At 100% rated load. 98.39 %
b) At 75% rated load. 98.66 %
c) At 50% rated load. 98.85 %

28 Voltage regulation.
a) Voltage regulation in % of the load voltage at full load &
at unity power factor. 1.19 %
b) Voltage regulation in % of the load voltage at full load &
at 0.9 lagging power factor. 2.73 %
29 Provision of fittings.
Whether the following fittings for transfomers have been provided.
a) Rating plate. Yes
b) Terminal marking . Yes
c) Lifting lugs. Yes
d) Earthing terminals for tanks. Yes
e) Oil filling hole & plug with sealing arrangement. Yes
f) Oil level indicator. Yes
g) Support lug. No
h) Channels. Yes
i) HT & LT bushings , Name & year of manufacture. Yes
j) Minimum creepage distance of HT bushing. 355 mm
k) Whether bushing manufacturer has provided a certificate that the bushing
have been tested fully according to applicable clauses of IEC-233. If yes
please attach a copy of certificate. Non submission of certificate will render
the bid non responsive. Yes

Page 2 of 3
400 kVA

30 Tank
a) Whether transformer is of tube type tank construction
Tubular Type
or Corrugated type?
b) Whether conservator with breather have been fitted with transformer. Yes
c) Whether transformers are effectively sealed from atmosphere for a
top oil temperature range of 0 to 110°C. Yes
d) Whether completely assembled transformer is designed & tested to
withstand without deformation or leakage pressure of 15lbs/sq.in. Yes
in casse of tubular tank and 5 lb/sq.in in case of corrugated type tank
construction.
e) Whether tank is marked outside & inside with white enameled
to show minimum & maximum oil levels at 30°C. Yes
f) To prevent flashovers caused by large birds , whether transformer
top covers are effectively coated with a weather proof permanent
insulating material having a dielectric & withstand voltage at not less Yes
than 8KV. If yes,name the isolating material. Araldite / Paint
g) The tank paint is highly resistant in the effects of strong sun light &
high temperature & shall have a long life under such priming coat &
Yes
two finish coats , Which are applied after the rough cleaning of the tank.
Whether thickness of the paint coating is greater than 0.12mm.
h) Whether bushing & connectors have been provided on transformers
Yes
as per WAPDA drawings.
i) Whether all nuts & bolts used for the construction of the tank are
HOT DIP Galvanized. Yes
31 No. of cooling Fins & size. 45 Nos , (42/19 mm)
(Attached dimensional drawing).
32 Overall dimensions of transformers with panel. LxWxH
(Attached dimensional drawing). 2350 x 1635 x 1527 Approx

33 Tank dimensions.
Height 1260 mm Approx
Width 885 mm Approx
Length 1916 mm Approx
34 Whether rollers have been fitted with tank as per WAPDA specs. Yes
35 Thickness of tank Frame. 6 mm
36 Thickness of top cover sheet. 6 mm
37 Thickness of bottom sheet. 4 mm
38 Total No. of pressure blocks & material. 40 Nos
39 Total No. of tie rods, size & No.of nuts. - 8 Nos. M20 , 16 nuts M20
40 Total No. of hanging studs, size & No. of nuts. 4 Nos. M20 , 8 nuts M20
41 Total No. of core bolts, size & No. of nuts. 8 Nos. M16, 16 nuts M16
42 Whether the end rings provided. If yes, indicate 10 mm
quantity, dimensions & material.
43 Whether tie rods have been covered with insulating sleeves. Yes
44 Any other important information. NA
45 Whether all the points for non entry of moisture have been
achieved as per clause 16.3 of WAPDA specs. DDS-84 Yes

NOTE:
Non submission of drawing/data as mentioned above will render the bid non-responsive.
The columns which are not applicable shall be filled N.A.