Вы находитесь на странице: 1из 116

Bulletin 1492 I/O Wiring Conversion Systems

PLC-5 1771 to ControlLogix 1756


Selection Guide
Bulletin 1492
I/O Wiring Conversion Systems - PLC-5 1771 to ControlLogix 1756
Product Overview

Bulletin 1492 Table of Contents


I/O Wiring Conversion System - 1771 to 1756 Conversion
I/O Conversion Modules provide a fast and efficient method for Modules and
converting Bul. 1771 I/O to Bul. 1756 I/O. The I/O conversion is Cables page 4
accomplished without removing any field wires from the existing
Bul. 1771 Swing Arm, virtually eliminating the risk of wiring errors.
Product
The existing Bul. 1771 Swing Arms fit directly onto the edge
Selection page 5
connector of the Bul. 1492 Conversion Modules.
The Bulletin 1492 Cables are pre-wired and have a connector for the Specifications page 10
Bul. 1492 Conversion Module on one end and a Bul. 1756 RTB
(Removable Terminal Block) on the other end. The I/O signals are Approximate
routed through the Bul. 1492 Conversion Module and the Bul. 1492 Dimensions page 11
Cable to the appropriate terminals on the Bul. 1756 I/O module.
Wiring
Diagrams page 19
The I/O Conversion System includes:
 Conversion Modules (Ex: Cat No: 1492-CM1771-LD001)
 Cables (Ex: Cat No: 1492-CONACAB005X)
 Conversion Mounting Assembly
(Ex: Cat No: 1492-MUA4-A13-A17)

Visit our website: www.ab.com


Publication 1492-SG121D-EN-P 3
Bulletin 1492
I/O Wiring Conversion Systems - Bulletin 1771 to ControlLogix 1756
Product Overview

Conversion Modules and Cables


The Bulletin 1492 I/O Wiring Conversion System virtually eliminates the time and risk associated with the normal “rip and replace” rewiring
0 process by using Conversion Modules instead. The Conversion Modules provide the mating connections (edge connectors) to the specific
1771 I/O Swing Arms. This allows the field wires to remain attached to the 1771 Swing Arm, eliminating the time and risk normally
associated with converting from one I/O system to another. The I/O signals are routed through to a connector on the 1492 Conversion
Module and through the 1492 pre-wired Cable to the appropriate terminals on the 1756 I/O module via the 1756 RTB (Removable Terminal
Block) on the other end of the 1492 pre-wired Cable.
1

4
Conversion Modules Bulletin 1492 Pre-wired Cables, 25-pin

5 Conversion Mounting Assembly

Conversion Assembly Base-Plate Conversion Assembly Cover-Plate


8
The Conversion Modules are housed in a Conversion Mounting The Conversion Mounting Assembly Cover Plate covers and protects
Assembly Base Plate. This Base Plate has the same mounting the Conversion Modules while providing a place to mount the new
footprint and mounting holes as the 1771 chassis that it replaces. 1756 chassis. The Cover Plate has pre-drilled and tapped mounting
This eliminates the need to drill and tap new mounting holes in the holes allowing the new 1756 chassis to be mounted in several
9 control cabinet. locations – centered, right-justified or left-justified. This eliminates
the need to drill and tap new mounting holes in the control cabinet.

10

11

Visit our website: www.ab.com


4 Publication 1492-SG121D-EN-P
Bulletin 1492
I/O Wiring Conversion Systems - PLC-5 1771 to ControlLogix 1756
Product Selection

Bulletin 1492 Conversion Mounting Assembly


The Bulletin 1492 Conversion Modules must be installed in a Bulletin 1492 Conversion Mounting Assembly (see Table 1
below). A complete System Installation Manual ships with the Bulletin 1492 Conversion Mounting Assembly.

Step 1:
Determine the quantity of each type of Bul. 1771 I/O modules used in the Bul. 1771 I/O chassis to be converted
Step 2:
Select the applicable Bul. 1492 conversion modules from Table 2, Section III
Step 3:
Review the Max Slots for I/O and Chassis Width data from the Table 1 below
Step 4:
Select a Bul. 1756 I/O chassis which has enough I/O slots
NOTE: (2) I/O slots are required in the Bul. 1756 chassis for conversions where (1) Bul. 1771 I/O module converts to (2)Bul. 1756 I/O
modules
Step 5: Select the Bul. 1492 conversion mounting assembly which has enough conversion module slots.
NOTE: (2) conversion module slots are required in the Bul. 1492 conversion mounting assembly for conversions where (2) Bul. 1771
I/O module convert to (1) Bul. 1756 I/O modules.
Step 6: The combined depth of the Bul. 1492 conversion mounting assembly with the Bul. 1756 chassis mounted on top is 10.25 inches
(controller w/key) or 10.0 inches (controller w/o key).
Step 7: Dimension drawings are included in the System Installation Manual that ships with the 1492 Conversion Mounting Assembly.

Bulletin 1771 Chassis Bulletin 1756 Chassis Bulletin 1492 Conversion Mounting Assembly

Max Chassis Width‡ Max Max Slots


Slots in. (mm) Slots for
for Without Power With Power for Chassis Width Conversion Chasis Width
Cat. No. I/O Supply Supply Cat. No. I/O in. (mm) Cat. No. Modules in. (mm)
10.35
1756-A4 3
9.01 12.61 (263) 9.01
1771-A1B 4 1492-MUA1B-A4-A7 4
(229) (320) 14.49 (229)
1756-A7 6
(368)

14.49
1756-A7 6
14.01 17.61 (368) 14.01
1771-A2B 8 1492-MUA2B-A7-A10 8
(356) (447) 19.02 (356)
1756-A10 9
(483)

19.02
1756-A10 9
19.01 (483) 19.01
1771-A3B1  12 1492-MUA3-A10-A13 12
(483) 23.15 (483)
1756-A13 12
(588)

23.15
1756-A13 12
24.01 (588) 24.01
1771-A4B 16 1492-MUA4-A13-A17 16
(610) 29.06 (610)
1756-A17 16
(738)
 1771-A3B is not listed as it is used for 19 inch wide instrumentation panels.
 Notice that the 1756 Chassis Width sometimes exceeds the 1771 Chassis Width, with or without the Power Supply. The Cover-Plate of the 1492 Conversion
Mounting Assembly allows the 1756 Chassis to be Left justified, Right justified or Centered. A complete System Installation Manual ships with the 1492
Conversion Mounting Assembly.

Visit our website: www.ab.com


Publication 1492-SG121D-EN-P 5
Bulletin 1492
I/O Wiring Conversion Systems - PLC-5 1771 to ControlLogix 1756
Product Selection

Table 2A - Digital Inputs

0 Step 1: In Column 1, find the Catalog Number of the 1771 Digital I/O module.
Step 2: In column 2, find the Catalog Number of the compatible 1756 Digital I/O module. In some cases more than one module exists.
Review the matrix carefully and review the I/O module Installation Manuals to determine full compatibility.
Step 3: In column 3, find the Catalog Number of the 1492 Conversion Module.
1 Step 4: In column 4, find the Catalog Number of the 1492 Cable.

1 2 3 4
Bulletin 1492 Conversion Module Bulletin 1492 Cable 1
2 Bulletin 1771
Digital I/O Module ® Qty.
Bulletin 1756
Digital I/O Module ® Qty.
Cat. No.
Order
Qty.
Cat. No.
Order
Qty.
1771-IA 2 1756-IA16 1 1492-CM1771-LD007 2 1492-C005005XE 1
1771-IA2 2 1756-IA16 1 1492-CM1771-LD007 2 1492-C005005XE 1
1771-IAD 1 1756-IA16 1 1492-CM1771-LD001 1 1492-CONCAB005X 1
3 1771-IAD 1 1756-IH16I 1 1492-CM1771-LD002 1 1492-CONCAB005Y 1
1771-IAN 1 1756-IA32 1 1492-CM1771-LD003 1 1492-CONCAB005Z 1
1771-IB 2 1756-IB16 1 1492-CM1771-LD007 2 1492-C005005XE 1
1771-IBD 1 1756-IB16 1 1492-CM1771-LD001 1 1492-CONCAB005X 1
4 1771-IBN 1 1756-IB32 1 1492-CM1771-LD003 1 1492-CONCAB005Z 1
1771-IC 2 1756-IC16 1 1492-CM1771-LD007 2 1492-C005005XE 1
1771-ICD 1 1756-IC16 1 1492-CM1771-LD001 1 1492-CONCAB005X 1
1771-ID 2 1756-IA16I 1 1492-CM1771-LD012 2 1492-C005005XL 1

5 1771-ID01
1771-ID16
2
1
1756-IM16I
1756-IA16I
1
1
1492-CM1771-LD012
1492-CM1771-LD004
2
1
1492-C005005XL
1492-CONCAB005Y
1
1
1771-ID16 1 1756-IH16I 1 1492-CM1771-LD004 1 1492-CONCAB005Y 1
1771-IG 2 1756-IG16 1  1492-CM1771-LA003 2 1492-C005005XS 1
1771-IGD 1 1756-IG16 1 1492-CM1771-LD006 1 1492-CONCAB005X 1
6 1771-IH 2 1756-IC16 1 1492-CM1771-LD007 2 1492-C005005XE 1
1771-IM 2 1756-IM16I 1 1492-CM1771-LD007 2 1492-C005005XH 1
1771-IMD 1 1756-IM16I 1 1492-CM1771-LD002 1 1492-CONCAB005Y 1
1771-IN 2 1756-IN16 1 1492-CM1771-LD007 2 1492-C005005XE 1
7 1771-IND 1 1756-IN16 1 1492-CM1771-LD001 1 1492-CONCAB005X 1
1771-IND1 1 1756-IN16 1 1492-CM1771-LD001 1 1492-CONCAB005X 1
1771-IQ 2 1756-IB16I 1 1492-CM1771-LD007 2 Sink 1492-C005005XK 1
1771-IQ 2 1756-IB16I 1 1492-CM1771-LD014 2 Source 1492-C005005XJ 1
1771-IQ16 1 1756-IB16I 1 1492-CM1771-LD004 1 1492-CONCAB005Y 1
8 1771-IT 2 1756-IB16 1 1492-CM1771-LD007 2 1492-C005005XE 1
1771-IV 2 1756-IV16 1 1492-CM1771-LD014 2 1492-C005005XG 1
1771-IVN 1 1756-IV32 1 1492-CM1771-LD005 1 1492-CONCAB005Z 1
1 The 005 in the Cat. No. indicates cable length of the Bulletin 1492 cable. The recommended length of 0.5 M is listed, additional lengths are listed below.
9 1.0M Cable = 1492-CONCAB010_
1.0M/1.0M Cable= 1492-C010010X_
0.5M/1.0M Cable = 1492-C005010X_
1.0M/0.5M Cable = 1492-C010005X_
® To understand any issues concerning I/O module compatibility refer to the conversion module wiring diagrams and the Installation Manuals for the specific I/O

10 modules involved (with particular attention to the specification and wiring instructions).
 These 1771 Digital I/O Modules use a Swing Arm that only mounts to these Analog I/O Conversion Modules, which will therefore be used to provide for these
1771 Digital I/O conversions.

11

Visit our website: www.ab.com


6 Publication 1492-SG121D-EN-P
Bulletin 1492
I/O Wiring Conversion Systems - PLC-5 1771 to ControlLogix 1756
Product Selection

Table 2B - Digital Outputs


Step 1: In Column 1, find the Catalog Number of the 1771 Digital I/O module.
Step 2: In column 2, find the Catalog Number of the compatible 1756 Digital I/O module. In some cases more than one module exists.
Review the matrix carefully and review the I/O module Installation Manuals to determine full compatibility.
Step 3: In column 3, find the Catalog Number of the 1492 Conversion Module.
Step 4: In column 4, find the Catalog Number of the 1492 Cable.

1 2 3 4
Bulletin 1771 Digital I/O Module ® Bulletin 1756 Digital I/O Module ® Bulletin 1492 Conversion Module Bulletin 1492 Cable 1
Order Order
Cat. No. Qty. Cat. No. Qty. Cat. No. Cat. No.
Qty. Qty.
1771-OA 1 1756-OA8E 1 1492-CM1771-LD014 1 1492-CONCAB005U 1
1771-OAD 1 1756-OA16 1 1492-CM1771-LD006 1 1492-CONCAB005X 1
1771-OAN 1 § 1756-OA16 2 1492-CM1771-LD013 1 1492-CONCAB005S3 1
1771-OB 2 1756-OB16D 1 1492-CM1771-LD014 2 1492-C005005XF 1
1771-OBD 1 1756-OB16E 1 1492-CM1771-LD006 1 1492-CONCAB005X 1
1771-OBD 1 § 1756-OC8 2 ♣ 1492-CM1771-LD008F 1 1492-CONCAB005S1 1
1771-OBDS 1 1756-OB16E 1 1492-CM1771-LD006 1 1492-CONCAB005X 1
1771-OBN 1 1756-OB32 1 ♣ 1492-CM1771-LD009F 1 1492-CONCAB005Z 1
1771-OC 1 1756-OC8 1 1492-CM1771-LD014 1 1492-CONCAB005V 1
1771-OD 2 1756-OA16I 1 1492-CM1771-LD012 2 1492-C005005XM 1
1771-OD16 1 1756-OA16I 1 ♣ 1492-CM1771-LD010F 1 1492-CONCAB005Y 1
1771-ODD 1 1756-OA16I 1 ♣ 1492-CM1771-LD010F 1 1492-CONCAB005Y 1
1771-ODZ 2 1756-OA16I 1 1492-CM1771-LD012 2 1492-C005005XP 1
1771-OG 2 1756-OG16 1  1492-CM1771-LA003 1 1492-C005005XS 1
1771-OGD 1 1756-OG16 1 1492-CM1771-LD006 1 1492-CONCAB005X 1
1771-OM 2 1756-OA16 1 1492-CM1771-LD014 2 1492-C005005XG 1
1771-OMD 1 1756-OA16 1 1492-CM1771-LD006 1 1492-CONCAB005X 1
1771-ON 1 1756-ON8 1 1492-CM1771-LD014 1 1492-CONCAB005W 1
1771-OND 1 § 1756-ON8 2 1492-CM1771-LD006 1 1492-CONCAB005S2 1
1771-OQ 2 1756-OB16I 1  1492-CM1771-LA004 2 1492-C005005XT 1
1771-OQ16 1 1756-OB16I 1 ♣ 1492-CM1771-LD010F 1 1492-CONCAB005Y 1
1771-OR 2 1756-OA16I 1 1492-CM1771-LD012 2 1492-C005005XR 1
1771-OVN 1 § 1756-OV16E 2 1492-CM1771-LD013 1 1492-CONCAB005S3 1
1771-OW 1 1756-OX8I 1 1492-CM1771-LD012 1 1492-CONCAB005Y 1
1771-OW16 1 1756-OW16I 1 1492-CM1771-LD011 1 1492-CONCAB005Y 1
1771-OWNA 1 § 1756-OW16I 2 1492-CM1771-LD013 1 1492-CONCAB005S4 1
1771-OY 1 1756-OX8I 1 1492-CM1771-LD012 1 1492-CONCAB005Y 1
1771-OYL 1 1756-OX8I 1 1492-CM1771-LD012 1 1492-CONCAB005Y 1
1771-OZ 1 1756-OX8I 1 1492-CM1771-LD012 1 1492-CONCAB005Y 1
1771-OZL 1 1756-OX8I 1 1492-CM1771-LD012 1 1492-CONCAB005Y 1
1 The 005 in the Cat. No. indicates cable length of the Bulletin 1492 cable. The recommended length of 0.5 M is listed, additional lengths are listed below.
1.0M Cable = 1492-CONCAB010_
1.0M/1.0M Cable= 1492-C010010X_
0.5M/1.0M Cable = 1492-C005010X_
1.0M/0.5M Cable = 1492-C010005X_

§ The two 1756 modules must be located directly next to each other in the 1756 chassis.
♣ The "F" at the end of the 1492 I/O Conversion Module Catalog Number indicates it is fused to match the functionality of the 1771 module being replaced.
® To understand any issues concerning I/O module compatibility refer to the conversion module wiring diagrams and the Installation Manuals for the specific I/O
modules involved (with particular attention to the specification and wiring instructions).
 These 1771 Digital I/O Modules use a Swing Arm that only mounts to these Analog I/O Conversion Modules, which will therefore be used to provide for these
1771 Digital I/O conversions.

Visit our website: www.ab.com


Publication 1492-SG121D-EN-P 7
Bulletin 1492
I/O Wiring Conversion Systems - PLC-5 1771 to ControlLogix 1756
Product Selection

Table 3 - Analog Inputs and Outputs

0
Step 1: In Column 1, find the Catalog Number of the 1771 Analog I/O module.
Step 2: In column 2, find the Catalog Number of the compatible 1756 Analog I/O module. In some cases more than one module exists.
Review the matrix carefully and review the I/O module Installation Manuals to determine full compatibility.
1 Step 3: In column 3, find the Catalog Number of the 1492 Conversion Module.
Step 4: In column 4, find the Catalog Number of the 1492 Cable.

1 2 3 4
2 Bulletin 1771 Bulletin 1756 Bulletin 1492 Bulletin 1492
Analog I/O Module1 Analog I/O Module1 Conversion Module Cable 
Order Order
Cat. No. Qty. Cat. No. Description Qty. Cat. No. Qty. Cat. No. Qty.
Diff Current 1 1492-CM1771-LA002 1 1492-CONACAB005D 1
3 1771-IFE 1 1756-IF16
Diff Voltage 1 1492-CM1771-LA002 1 1492-CONACAB005C 1
Sgl End Current 1 1492-CM1771-LA001 1 1492-CONACAB005B 1
Sgl End Voltage 1 1492-CM1771-LA001 1 1492-CONACAB005A 1
Diff Current 1 1492-CM1771-LA002 1 1492-CONACAB005D 1
4 1771-IFF 1 1756-IF16
Diff Voltage 1 1492-CM1771-LA002 1 1492-CONACAB005C 1
Sgl End Current 1 1492-CM1771-LA001 1 1492-CONACAB005B 1
Sgl End Voltage 1 1492-CM1771-LA001 1 1492-CONACAB005A 1
1756-IF8I Current 1 1492-CM1771-LA004 1 1492-CONACAB005K8 1
(8-ch)
5 1771-IL 1756-IF6I
Voltage
Current
1
1
1492-CM1771-LA004
1492-CM1771-LA004
1
1
1492-CONACAB005L8
1492-CONACAB005K
1
1
(8-ch) (6-ch) Voltage 1 1492-CM1771-LA004 1 1492-CONACAB005L 1
1
1756-IF6I Current 2 1492-CM1771-LA004 1 1492-CONACAB005T1 1
(2 x 4ch) Voltage 2 1492-CM1771-LA004 1 1492-CONACAB005T2 1
6 1771-IR 1 1756-IR6I — 1 1492-CM1771-LA005 1 1492-CONACAB005F 1
1 1756-IT6I2 — 1 1492-CM1771-LA005 1 1492-CONACAB005G 1
1771-IXE
1 1756-IRT8I — 1 1492-CM1771-LA005 1 1492-CONACAB005G8 1
1 1756-IT6I2 — 1 1492-CM1771-LA005 1 1492-CONACAB005G 1
1771-IXHR
7 1771-OFE1
1
1
1756-IRT8I
1756-OF6VI


1
1
1492-CM1771-LA005
1492-CM1771-LA003
1
1
1492-CONACAB005G8
1492-CONACAB005E
1
1
1771-OFE2 1 1756-OF6CI — 1 1492-CM1771-LA003 1 1492-CONACAB005E 1
1 To understand any issues concerning I/O module compatibility refer to the conversion module wiring diagrams and the Installation Manuals for the specific I/O
modules involved (with particular attention to the specification and wiring instructions).
8  The 005 in the Cat. No. indicates cable length of the Bulletin 1492 cable. The recommended length of 0.5 M is listed, additional lengths are listed below.
1.0M Cable = Cat. No. 1492-CONCAB010_
Series B

10

11

13
Visit our website: www.ab.com
8 Publication 1492-SG121D-EN-P
Bulletin 1492
I/O Wiring Conversion Systems - PLC-5 1771 to ControlLogix 1756
Product Selection

Bulletin 1771-N High Resolution Isolated Analog I/O Modules


 The Bulletin 1771-N High Resolution Analog I/O modules were designed to be
used with Bulletin 1771-RTPs (Remote Termination Panels) and connected by a
6ft or 15ft cable (Cat. No. 1771-NC6 or 1771-NC15).
 The conversion of the Bul. 1771-N Series I/O to a Bul. 1756 ControlLogix I/O can
be accomplished without the removal of any field wires from the existing
Bul. 1771-RTPs.
 Simply replace the (2) existing Bul. 1771 cables with (2) of the following
Bul. 1492 cables in the tables below.
 Each of these new Bul. 1492 cables has a connector on one end that attaches
directly to the existing Bul. 1771-RTP and a Bul. 1756 RTB (Removable Terminal
Block) on the other end for connection to the Bul. 1756 ControlLogix I/O module.

Step 1: In Column 1, find the Catalog Number of the Bul.1771 Digital I/O module.
Step 2: In column 2, find the Catalog Number of the compatible Bul.1756 Digital I/O
module. In some cases more than one module is required. Review the matrix carefully
and review the I/O module Installation Manuals to determine full compatibility. Please Note: These conversions do not require the
use of the Conversion Mounting Assemblies or
Step 3: In column 3, find the Catalog Numbers and descriptions of the Bul. 1492 Cables Conversion Modules.
required.

Table 4 - Conversion Cables for Bulletin 1771-N Series I/O


1 2 3
Bulletin 1771 Bulletin 1756 Bulletin 1492
Analog I/O Module1 Analog I/O Module1 Cable §♣
Order
Cat. No. Qty. Cat. No. Qty. Description Cat. No. Replaces Cables
Qty.
1771-NOC 1 1756-OF6CI 2 Current, Isolated 1492-CONACAB020N1 A and B 2
 1771-NOC 1 1756-OF8 1 Current, Non-Isolated 1492-CONACAB020N8 A and B 1
1771-NIS 1 1756-IF6CIS 2 Current 1492-CONACAB020N2 A and B 2
1756-IF6I 2 Current 1492-CONACAB020N3 A and B 2
1756-IF6I 2 Voltage 1492-CONACAB020N7 A and B 2
‡ 1771-NIV 1
Current 1492-CONACAB020N3 A or B 1
1756-IF6I 2
Voltage 1492-CONACAB020N7 A or B 1
1771-NR 1 1756-IR6I 2 RTD 1492-CONACAB020N4 A and B 2
1771-NT1 1 1756-IT6I 2 Thermocouple 1492-CONACAB020N5 A and B 2
1771-NOV 1 1756-OF6VI 2 Voltage 1492-CONACAB020N1 A and B 2
1771-NIV1 1 1756-IF6I 2 Voltage 1492-CONACAB020N7 A and B 2
1771-NT2 1 1756-IT6I2 2 Thermocouple 1492-CONACAB020N6 A and B 2
1 To understand any issues concerning I/O module compatibility refer to the Installation Manuals for the specific I/O modules involved.
 Cat. No. 1492-CONACAB020N8 has (2) connectors on one end for the RTP, so only (1) Cable is required.
‡ Three conversions are possible using these two cables - (8 Voltage) or (8 Current) or (4 Voltage & 4 Current)
§ These catalog numbers are for a 2.0M cable length. A 5.0M cable is also available. Change the 3 numerals in the middle of the catalog number from "020" to
"050" (Example: Cat. No. 1492-CONACAB020N1 becomes Cat. No.1492-CONACAB050N1).
♣ Only 2 cables can be used at one time. Each cable attaches to 1 of the 2 connectors on the existing RTP module. Each cable converts 4 of the Bul. 1771
channels to 4 of the 1756 channels. The other end of the cable attaches to 1 of the 2 new Bul. 1756 modules.
Table 5- Conversion Cables for Bulletin 1771-N Series I/O Combination Modules
1 2 3
Bulletin 1771 Bulletin 1756 Bulletin 1492
Analog I/O Module1 Analog I/O Module1 Cables§♣
Replaces Order
Cat. No. Qty. Cat. No. Qty. Description Cat. No.
Cable Qty.
1756-IR6I 1 RTD 1492-CONACAB020N4 B 1
® 1771-NIVR 1
1756-IF6I 1 Voltage 1492-CONACAB020N7 A 1
1756-IR6I 1 RTD 1492-CONACAB020N4 B 1
® 1771-NIVR 1
1756-IF6I 1 Current 1492-CONACAB020N3 A 1
1756-IT6I 1 Thermocouple 1492-CONACAB020N5 B 1
 1771-NIVT 1
1756-IF6I 1 Voltage 1492-CONACAB020N7 A 1
1756-IT6I 1 Thermocouple 1492-CONACAB020N5 B 1
 1771-NIVT 1
1756-IF6I 1 Current 1492-CONACAB020N3 A 1
1 To understand any issues concerning I/O module compatibility refer to the Installation Manuals for the specific I/O modules involved.
® Two conversions are possible using these two cables - (4 Voltage & 4 RTD) or (4 Current & 4 RTD)
 Two conversions are possible using these two cables - (4 Voltage & 4 Thermocouple) or (4 Current & 4 Thermocouple)
§ These catalog numbers are for a 2.0M cable length. A 5.0M cable is also available. Change the 3 numerals in the middle of the catalog number from "020" to
"050" (Example: Cat. No. 1492-CONACAB020N1 becomes Cat. No. 1492-CONACAB050N1).
♣ Only 2 cables can be used at one time. Each cable attaches to 1 of the 2 connectors on the existing RTP module. Each cable converts 4 of the Bul. 1771
channels to 4 of the 1756 channels. The other end of the cable attaches to 1 of the 2 new Bul. 1756 modules.
Visit our website: www.ab.com
Publication 1492-SG121D-EN-P 9
Bulletin 1492
I/O Wiring Conversion Systems - PLC-5 1771 to ControlLogix 1756
Specifications

Conversion Module Specifications

0 Specifications  Value
Dimensions (H x D x W) 300 x 111.25 x 38.1 mm (11.81 x 4.38 x 1.5 in.)
Approximate Shipping Weight (module dependant, refer to installation manual) 260g (0.57 lb)
Storage Temperature -40...+85 °C (-40...+185 °F)
Operating Temperature 0...+60 °C (+32...+140 °F)
1 Operating Humidity 5...95% at +55 °C (+131 °F)
Non-operating 50 g
Shock
Operating 30 g
Operational Vibration 2 g at 10...500 Hz
2 Agency Certifications UL Classified (UL File No. E113724)
CE Certifications Compliant for all applicable directives
Pollution Degree 2
Environmental Rating IP20
3  Operating specifications are when installed in the conversion system base and cover plate assembly.
 1492-CABLE connection pins are limited to 2 A per pin. Note: Refer to the wiring diagrams for current limits for a specific configuration.

10

11

13
Visit our website: www.ab.com
10 Publication 1492-SG121D-EN-P
Bulletin 1492
I/O Wiring Conversion Systems - PLC-5 1771 to ControlLogix 1756
Approximate Dimensions

Cat No. MUA1B-A4-A7 used with Cat No. 1756-A4

Left Justified

10.4
[263.6 ]
9.0 9.9
[229.6 ] [251.9 ]
2.4
[60.2 ]

5.4
[137 ] 12.5
[317.2 ]

11.1
[281.7 ]

6.1
[154 ]
Right Justified

10.4
[264.1 ]
9.1
2.4 [230.7 ]
[60.1 ]

5.4
[137 ] 11.1 12.5
[281.7 ] [317.2 ]

Visit our website: www.ab.com


Publication 1492-SG121D-EN-P 11
Bulletin 1492
I/O Wiring Conversion Systems - PLC-5 1771 to ControlLogix 1756
Approximate Dimensions

Cat No. MUA1B-A4-A7 used with Cat No. 1756-A7

Left Justified 14.6


[370.6 ]
9.9
2.4 9.0
[251.9 ]
[60.2 ] [229.6 ]

2.4 6.1
[60.2 ] [154 ]

5.4
[136.5 ]
12.5
[317.2 ]
11.1
[281.7 ]

14.6
[370.1 ]
Centered 4.1 9.0
[104.5 ] [229.6 ]
2.4
[60.2 ]

5.4
[137.3 ] 12.5
[317.2 ]

14.6
[370.1 ]

Right2.4Justified 9.1
[231.9 ]
[60.2 ]

5.4
[137.3 ] 12.5
[317.2 ]
11.1
[281.7 ]

Visit our website: www.ab.com


12 Publication 1492-SG121D-EN-P
Bulletin 1492
I/O Wiring Conversion Systems - PLC-5 1771 to ControlLogix 1756
Approximate Dimensions

Cat No. MUA2B-A7-A10 used with Cat No. 1756-A7

Centered
14.6
[370.1 ]
.2 14.0 .3
[5.7 ] [356.6 ] [7.8 ]

2.4
[59.7 ]

5.4 12.5
[136 ] [317.3 ]
11.1
[281.7 ]

9.9
[251.9 ]

6.1
[154 ]

Visit our website: www.ab.com


Publication 1492-SG121D-EN-P 13
Bulletin 1492
I/O Wiring Conversion Systems - PLC-5 1771 to ControlLogix 1756
Approximate Dimensions

Cat No. MUA2B-A7-A10 used with Cat No. 1756-A10


Left Justified
19.1
[485 ]
.2 14.0 9.9
2.4 [5.5 ] [356.6 ] [252.3 ]
[60.2 ]

5.4
[137 ]
12.5
[317.3 ]
11.1 6.1
[281.7 ] [154.4 ]

Centered
19.1
[485 ]
2.5 14.0
[63.5 ] [356.6 ]
2.4
[60.2 ]

5.4
[137.3 ]
12.5
11.1 [317.3 ]
[281.7 ]

SCALE 0.300

Right Justified
19.1
[485 ]
5.1 14.0
2.4 [130 ] [356.6 ]
[60.2 ]

5.4
[136 ] 12.5
11.1 [317.3 ]
[281.7 ]

Visit our website: www.ab.com


14 Publication 1492-SG121D-EN-P
Bulletin 1492
I/O Wiring Conversion Systems - PLC-5 1771 to ControlLogix 1756
Approximate Dimensions

Cat No. MUA3-A10-A13 used with Cat No. 1756-A10

Centered

19.2
[486.9 ]
19.0
[483.6 ]
2.4
[60.2 ]

5.4
[137 ]
12.5
[317.3 ]
11.1
[281.7 ]

9.9
[252.3 ]

6.1
[154.4 ]

Visit our website: www.ab.com


Publication 1492-SG121D-EN-P 15
Bulletin 1492
I/O Wiring Conversion Systems - PLC-5 1771 to ControlLogix 1756
Approximate Dimensions

Cat No. MUA3-A10-A13 used with Cat No. 1756-A13

Left Justified

.7 19.0 9.6
[18 ] [483.6 ] [243.9 ]
2.4
[60.2 ]

5.4
[137 ] 11.1 12.5
[281.7 ] [317.3 ]

5.7
[146 ]
23.2
[588 ]
Centered
2.4
[59.9 ]

2.2 1.9
[56.8 ] [47.4 ]

5.4
[137 ] 11.2
[285.6 ]

19.0
[483.6 ]
23.2
[588 ]
Right Justified
2.4
[60.2 ] 23.2
[588 ]

4.1
[103.1 ]

5.4
[137 ] 11.1
[281.7 ]

Visit our website: www.ab.com


16 Publication 1492-SG121D-EN-P
Bulletin 1492
I/O Wiring Conversion Systems - PLC-5 1771 to ControlLogix 1756
Approximate Dimensions

Cat No. MUA4-A13-A17 used with Cat No. 1756-A13


Centered

24.0
[610.6 ]
23.2
2.4
[588 ]
[60.2 ]

5.4
[137 ]
12.5
[316.7 ]
11.1
[281.7 ]

9.6
[243.7 ]

5.7
[145.9 ]

Visit our website: www.ab.com


Publication 1492-SG121D-EN-P 17
Bulletin 1492
I/O Wiring Conversion Systems - PLC-5 1771 to ControlLogix 1756
Approximate Dimensions

Dimensions are shown in incles (millimeters). Dimensions are not intended for manufacturing purposes.

Cat No. MUA4-A13-A17 used with Cat No. 1756-A17

Left
Justified 29.1
[737.9 ]
.2 24.0 4.8
[6.2 ] [610.6 ] [121 ]

2.4 9.9
[60.1 ] [251.9 ]
12.5
[316.7 ]
6.1
[154 ]
11.1
[281.7 ]

Centered 29.1
[737.9 ]
3.6 24.0 1.4
2.4 [91.7 ] [610.6 ] [35.6 ]
[60.1 ]

11.1
[281.7 ]
5.4
[137 ]
12.5
[316.7 ]

Right
Justified 29.1
[737.9 ]
5.1 24.0
2.4 [130 ] [610.6 ]
[60.1 ]

5.4
[137 ]
11.1
12.5
[281.7 ]
[316.7 ]

Visit our website: www.ab.com


18 Publication 1492-SG121D-EN-P
Bulletin 1492
I/O Wiring Conversion Systems - PLC-5 1771 to ControlLogix 1756
Wiring Diagrams - Digital

Cat No. 1771-IA (Qty. 2) to 1756-IA16

WARNING There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module Cable


1492-CM1771-LD007 1492-C005005XE 1756-IA16
1 Black CABLE “A” 10
L2-0
Not used A 2 White 9
L2-0
Input 0 0 3 Red 1
IN-0
Input 1 1 4 Green 2
IN-1
Input 2 2 5 Orange 3
IN-2
L1 Input 3 3 6 Blue 4
IN-3
Input 4 4 7 White/Black 5
IN-4
Input 5 5 8 Red/Black 6
L2 IN-5
Input 6 6 9 Green/Black 7
IN-6
Input 7 7 10 Orange/Black 8
IN-7
L2 B 11
12
13 CABLE “B” 11
14 IN-8
12
15 IN-9
13
16 IN-10
14
17 IN-11
15
18 IN-12
16
19 IN-13
17
20 IN-14
18
IN-15
1771-WA Swing Arm 21 20
L2-1
From 1771-IA , -IA2 22 19
L2-1
23
24
25

Conversion Module
1492-CM1771-LD007
1 Black
Not used A 2 White
Input 8 0 3 Red
Input 9 1 4 Green
Input 10 2 5 Orange
L1 Input 11 3 6 Blue
Input 12 4 7 White/Black
Input 13 5 8 Red/Black
L2 Input 14 6 9 Green/Black

Input 15 7 10 Orange/Black

L2 B 11
12
13
14
15
16
17
18
19
20
1771-WA Swing Arm 21
22
From 1771-IA , -IA2 23
24
25

Conversion Module Installation and Application Considerations


 This Bul. 1492 cable consists of 2 separate cables (cable “A” and cable “B”) wired to one 1756-IA16 RTB. Recommended cable
lengths of 0.5 M / 0.5 M are shown. See table 2 for other lengths.
 The input delay times for the 1771-IA, -IA2 module versus the 1756-IA16 module are as follows:
1771-IA, -IA2 1756-IA16 w/ 1492-C005005XE
a) Off-to-On Delay 24ms (+/-10ms) 10ms max (plus selectable filter)
b) On-to-Off Delay 24ms (+/-10ms) 8ms max (plus selectable filter)
 The 1771-IA, -IA2 module is rated 87V to 138V AC and 97V to 138V DC. The 1756-IA16 module is rated 79V to 132V AC only.
 Refer to your 1771-IA, -IA2 and 1756-IA16 Installation Manual wiring schematics and diagrams for more details.
[Reference Doc: 41170-952 (Version 02)]

Visit our website: www.ab.com


Publication 1492-SG121D-EN-P 19
Bulletin 1492
I/O Wiring Conversion Systems - PLC-5 1771 to ControlLogix 1756
Wiring Diagrams - Digital

Cat No. 1771-IA2 (Qty. 2) to 1756-IA16

WARNING There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module Cable


1492-CM1771-LD007 1492-C005005XE 1756-IA16
1 Black CABLE “A” 10
L2-0
Not used A 2 White 9
L2-0
Input 0 0 3 Red 1
IN-0
Input 1 1 4 Green 2
IN-1
Input 2 2 5 Orange 3
IN-2
L1 Input 3 3 6 Blue 4
IN-3
Input 4 4 7 White/Black 5
IN-4
Input 5 5 8 Red/Black 6
L2 IN-5
Input 6 6 9 Green/Black 7
IN-6
Input 7 7 10 Orange/Black 8
IN-7
L2 B 11
12
13 CABLE “B” 11
14 IN-8
12
15 IN-9
13
16 IN-10
14
17 IN-11
15
18 IN-12
16
19 IN-13
17
20 IN-14
18
IN-15
1771-WA Swing Arm 21 20
L2-1
From 1771-IA , -IA2 22 19
L2-1
23
24
25

Conversion Module
1492-CM1771-LD007
1 Black
Not used A 2 White
Input 8 0 3 Red
Input 9 1 4 Green
Input 10 2 5 Orange
L1 Input 11 3 6 Blue
Input 12 4 7 White/Black
Input 13 5 8 Red/Black
L2 Input 14 6 9 Green/Black

Input 15 7 10 Orange/Black

L2 B 11
12
13
14
15
16
17
18
19
20
1771-WA Swing Arm 21
22
From 1771-IA , -IA2 23
24
25

Conversion Module Installation and Application Considerations


 This Bul. 1492 cable consists of 2 separate cables (cable “A” and cable “B”) wired to one 1756-IA16 RTB. Recommended cable
lengths of 0.5 M / 0.5 M are shown. See table 2 for other lengths.
 The input delay times for the 1771-IA, -IA2 module versus the 1756-IA16 module are as follows:
1771-IA, -IA2 1756-IA16 w/ 1492-C005005XE
a) Off-to-On Delay 24ms (+/-10ms) 10ms max (plus selectable filter)
b) On-to-Off Delay 24ms (+/-10ms) 8ms max (plus selectable filter)
 The 1771-IA, -IA2 module is rated 87V to 138V AC and 97V to 138V DC. The 1756-IA16 module is rated 79V to 132V AC only.
 Refer to your 1771-IA, -IA2 and 1756-IA16 Installation Manual wiring schematics and diagrams for more details.
[Reference Doc: 41170-952 (Version 02)]

Visit our website: www.ab.com


20 Publication 1492-SG121D-EN-P
Bulletin 1492
I/O Wiring Conversion Systems - PLC-5 1771 to ControlLogix 1756
Wiring Diagrams - Digital

Cat No. 1771-IAD to 1756-IA16

WARNING There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module
1492-CM1771-LD001
Cable
Terminal A A 1492-CONCAB005X 1756-IA16
Terminal B B
Terminal C C 1 Black 10
L2-0
Terminal D D 2 White 9
L2-0
Input 00 00 3 Red 1
IN-0
Input 01 01 4 Green 2
IN-1
Input 02 02 5 Orange 3
IN-2
Input 03 03 6 Blue 4
IN-3
Input 04 04 7 White/Black 5
IN-4
Input 05 05 8 Red/Black 6
IN-5
Input 06 06 9 Green/Black 7
IN-6
Input 07 07 10 Orange/Black 8
IN-7
Input 10 10 11 Blue/Black 11
IN-8
Input 11 11 12 Black/White 12
IN-9
Input 12 12 13 Red/White 13
L1 IN-10
Input 13 13 14 Green/White 14
IN-11
Input 14 14 15 Blue/White 15
IN-12
Input 15 15 16 Black/Red 16
L2 IN-13
Input 16 16 17 White/Red 17
IN-14
Input 17 17 18 Orange/Red 18
IN-15
Terminal E E 19 Blue/Red 20
L2-1
20 Red/Green 19
L2-1
21
22
23
24
25

1771-WH Swing Arm


From 1771-IAD

Conversion Module Installation and Application Considerations


 This Bul. 1492 cable consists of a cable wired to one 1756-IA16 RTB. Recommended cable lengths of 0.5M or 1.0M
(005=0.5M, 010=1.0M). See table 2 for other lengths.
 The input delay times for the 1771-IAD module versus the 1756-IA16 module are as follows:
1771-IAD 1756-IA16 w/ 1492-CONCAB005X
a) Off-to-On Delay 5ms (+/-3ms) @120VAC 10ms max (plus selectable filter)
b) On-to-Off Delay 25ms (+/-5ms) 8ms max (plus selectable filter)
 The 1771-IAD module is rated 79V to 138V AC or DC. The 1756-IA16 module is rated 74V to 132V AC. If the input
source voltage is DC use a 1756-IH16l and 1492-CM1771-LD002 conversion module.
 Refer to your 1771-IAD and 1756-IA16 Installation Manual wiring schematics and diagrams for more details.
[Reference Doc: 41170-925 (Version 02)]

Visit our website: www.ab.com


Publication 1492-SG121D-EN-P 21
Bulletin 1492
I/O Wiring Conversion Systems - PLC-5 1771 to ControlLogix 1756
Wiring Diagrams - Digital

Cat No. 1771-IAD to 1756-IH16I

WARNING There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module
1492-CM1771-LD002
1
Terminal A A 2 Cable
Terminal B B 3 1492-CONCAB005Y 1756-IH16I
Terminal C C 4
Terminal D D 5 Orange 2
GND-0
Input 00 00 6 Blue 1
IN-0
7 White/Black 4
GND-1
Input 01 01 8 Red/Black 3
IN-1
9 Green/Black 6
GND-2
Input 02 02 10 Orange/Black 5
IN-2
11 Blue/Black 8
GND-3
Input 03 03 12 Black/White 7
IN-3
13 Red/White 10
GND-4
Input 04 04 14 Green/White 9
IN-4
15 Blue/White 12
GND-5
Input 05 05 16 Black/Red 11
IN-5
17 White/Red 14
GND-6
Input 06 06 18 Orange/Red 13
IN-6
19 Blue/Red 16
GND-7
Input 07 07 20 Red/Green 15
IN-7
21 Orange/Green 18
GND-8
Input 10 10 22 Black/White/Red 17
IN-8
23 White/Black/Red 20
GND-9
Input 11 11 24 Red/Black/White 19
IN-9
25 Green/Black/White 22
GND-10
Input 12 12 26 Orange/Black/White 21
IN-10
27 Blue/Black/White 24
GND-11
Input 13 13 28 Black/Red/Green 23
IN-11
29 White/Red/Green 26
GND-12
Input 14 14 30 Red/Black/Green 25
IN-12
31 Green/Black/Orange 28
GND-13
Input 15 15 32 Orange/Black/Green 27
IN-13
33 Blue/White/Orange 30
GND-14
Input 16 16 34 Black/White/Orange 29
IN-14
35 White/Red/Orange 32
GND-15
Input 17 17 36 Orange/White/Blue 31
+ IN-15
37
- Terminal E E

1771-WH Swing Arm


From 1771-IAD

Conversion Module Installation and Application Considerations


 The input delay times for the 1771-IAD module versus 1756-IH16I module are as follows:
1771-IAD 1756-IH16I
a) Off-to-On Delay 3ms @120V DC 2ms (plus selectable filter)
b) On-to-Off Delay 25ms (+/-5ms) 6ms (plus selectable filter)
 The 1771-IAD module is rated 79V to 138V AC or DC. The 1756-IH16I module is rated 90V to 146V DC. If the input
spurce voltage is AC use a 1756-IA16 and 1492-CM1771-LD002 conversion module.
 Refer to your 1771-IAD and 1756-IH16I Installation Manual wiring schematics and diagrams for more details.
[Reference Doc: 41170-927 (Version 02)]

Visit our website: www.ab.com


22 Publication 1492-SG121D-EN-P
Bulletin 1492
I/O Wiring Conversion Systems - PLC-5 1771 to ControlLogix 1756
Wiring Diagrams - Digital

Cat No. 1771-IAN to 1756-IA32

WARNING There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module Cable


1492-CM1771-LD003 1492-CONCAB005Z 1756-IA32
Common 0 10 1 Black 18
L2-0
Common 2 30 2 White 36
L2-1
3 Red
Input 00 1 4 Green 1
IN-0
Input 00 21 5 Orange 19
IN-16
Input 01 2 6 Blue 2
IN-1
Input 01 22 7 White/Black 20
IN-17
Input 02 3 8 Red/Black 3
IN-2
Input 02 23 9 Green/Black 21
IN-18
Input 03 4 10 Orange/Black 4
IN-3
Input 03 24 11 Blue/Black 22
IN-19
Input 04 5 12 Black/White 5
IN-4
Input 04 25 13 Red/White 23
IN-20
Input 05 6 14 Green/White 6
IN-5
Input 05 26 15 Blue/White 24
IN-21
Input 06 7 16 Black/Red 7
IN-6
Input 06 27 17 White/Red 25
IN-22
Input 07 8 18 Orange/Red 8
IN-7
Input 07 28 19 Blue/Red 26
IN-23
Input 10 11 20 Red/Green 9
IN-8
Input 10 31 21 Orange/Green 27
IN-24
Input 11 12 22 Black/White/Red 10
IN-9
L1 Input 11 32 23 White/Black/Red 28
IN-25
Input 12 13 24 Red/Black/White 11
IN-10
Input 12 33 25 Green/Black/White 29
IN-26
L2 Input 13 14 26 Orange/Black/White 12
IN-11
Input 13 34 27 Blue/Black/White 30
IN-27
Input 14 15 28 Black/Red/Green 13
IN-12
Input 14 35 29 White/Red/Green 31
IN-28
Input 15 16 30 Red/Black/Green 14
IN-13
Input 15 36 31 Green/Black/Orange 32
IN-29
Input 16 17 32 Orange/Black/Green 15
IN-14
Input 16 37 33 Blue/White/Orange 33
IN-30
Input 17 18 34 Black/White/Orange 16
IN-15
Input 17 38 35 White/Red/Orange 34
IN-31
Common 0 9 36 Orange/White/Blue 17
Common 1 L2-0
19 37 White/Red/Blue 35
L2-1
Common 1 20
Common 2 29
Common 3 39
Common 3 40

1771-WN Swing Arm


From 1771-IAN

Conversion Module Installation and Application Considerations


 The input delay times for the 1771-IAN module versus 1756-IA32 module are as follows:
1771-IAN 1756-IA32
a) Off-to-On Delay 10ms (+/-7ms) 10ms max (plus selectable filter)
b) On-to-Off Delay 20ms (+/-15ms) 8ms max (plus selectable filter)
 The 1771-IAN has 4 groups(allowing 4 seperate power supplies) and the 1756-IA32 has 2 groups.
This module/cable combination ties Groups 0 & 1 from the 1771-IAN to Group 0 on the 1756-IA32 and it ties Groups 2 & 3
from the 1771-IAN to Group 1 on the 1756-IA32. Field wiring modification must be made to accommodate this if multiple
supplies were used. If 4 supplies were used, 2 must be removed.
 Refer to your 1771-IAN and 1756-IA32 Installation Manual wiring schematics and diagrams for more details.

[Reference Doc: 41170-930 (Version 02)]

Visit our website: www.ab.com


Publication 1492-SG121D-EN-P 23
Bulletin 1492
I/O Wiring Conversion Systems - PLC-5 1771 to ControlLogix 1756
Wiring Diagrams - Digital

Cat No. 1771-IB (Qty. 2) to 1756-IB16

WARNING There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module Cable


1492-CM1771-LD007 1492-C005005XE 1756-IB16
1 Black 10
GND-0
Not used A 2 White 9
GND-0
Input 0 0 3 Red 1
IN-0
Input 1 1 4 Green 2
IN-1
Input 2 2 5 Orange 3
IN-2
+ Input 3 3 6 Blue 4
IN-3
Input 4 4 7 White/Black 5
- IN-4
Input 5 5 8 Red/Black 6
IN-5
Input 6 6 9 Green/Black 7
IN-6
Input 7 7 10 Orange/Black 8
IN-7
GND-1 B 11 CABLE “A”
12
13 CABLE “B” 11
14 IN-8
12
15 IN-9
13
16 IN-10
14
17 IN-11
15
18 IN-12
16
19 IN-13
17
20 IN-14
18
IN-15
1771-WA Swing Arm 21 20
GND-1
22 19
From 1771-IB 23
GND-1
24
25

Conversion Module
1492-CM1771-LD007
1 Black
Not used A 2 White
Input 0 0 3 Red
Input 1 1 4 Green
Input 2 2 5 Orange
+ Input 3 3 6 Blue
Input 4 4 7 White/Black
- Input 5 5 8 Red/Black
Input 6 6 9 Green/Black

Input 7 7 10 Orange/Black

GND-1 B 11
12
13
14
15
16
17
18
19
20
1771-WA Swing Arm 21
22
From 1771-IB 23
24
25

Conversion Module Installation and Application Considerations


 This Bul. 1492 cable consists of 2 separate cables (cable “A” and cable “B”) wired to one 1756-IB16 RTB. Recommended cable
lengths of 0.5 M / 0.5 M are shown. See table 2 for other lengths.
 The input delay times for the 1771-IB module versus the 1756-IB16 module are as follows:
1771-IB 1756-IB16 w/ 1492-C005005XE
a) Off-to-On Delay 24ms (+/-10ms) 1ms max (plus selectable filter)
b) On-to-Off Delay 24ms (+/-10ms) 2ms max (plus selectable filter)
 The 1771-IB module is rated 24V DC. The 1756-IB16 module is rated 10 - 31V DC only.
 Refer to your 1771-IB and 1756-IB16 Installation Manual wiring schematics and diagrams for more details.
[Reference Doc: 41170-995 (Version 00)]

Visit our website: www.ab.com


24 Publication 1492-SG121D-EN-P
Bulletin 1492
I/O Wiring Conversion Systems - PLC-5 1771 to ControlLogix 1756
Wiring Diagrams - Digital

Cat No. 1771-IBD to 1756-IB16

WARNING There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module
1492-CM1771-LD001
Cable
Terminal A A 1492-CONCAB005X 1756-IB16
Terminal B B
Terminal C C 1 Black 10
GND-0
Terminal D D 2 White 9
GND-0
Input 00 00 3 Red 1
IN-0
Input 01 01 4 Green 2
IN-1
Input 02 02 5 Orange 3
IN-2
Input 03 03 6 Blue 4
IN-3
Input 04 04 7 White/Black 5
IN-4
Input 05 05 8 Red/Black 6
IN-5
Input 06 06 9 Green/Black 7
IN-6
Input 07 07 10 Orange/Black 8
IN-7
Input 10 10 11 Blue/Black 11
IN-8
Input 11 11 12 Black/White 12
IN-9
Input 12 12 13 Red/White 13
+ IN-10
Input 13 13 14 Green/White 14
IN-11
Input 14 14 15 Blue/White 15
- IN-12
Input 15 15 16 Black/Red 16
IN-13
Input 16 16 17 White/Red 17
IN-14
Input 17 17 18 Orange/Red 18
IN-15
Terminal E E 19 Blue/Red 20
GND-1
20 Red/Green 19
GND-1
21
22
23
24
25

1771-WH Swing Arm


From 1771-IBD

Conversion Module Installation and Application Considerations


 This Bul. 1492 cable consists of a cable wired to one 1756-IB16 RTB. Recommended cable lengths of 0.5M or
1.0M (005=0.5M, 010=1.0M). See table 2 for other lengths.
 The input delay times for the 1771-IBD module versus the 1756-IB16 module are as follows:
1771-IBD 1756-IB16 w/ 1492-CONCAB005X
a) Off-to-On Delay 1ms 1ms (plus selectable filter)
b) On-to-Off Delay 1ms 2ms (plus selectable filter)
 Refer to your 1771-IBD and 1756-IB16 Installation Manual wiring Schematics and diagrams for more details.
[Reference Doc: 41170-926 (Version 02)]

Visit our website: www.ab.com


Publication 1492-SG121D-EN-P 25
Bulletin 1492
I/O Wiring Conversion Systems - PLC-5 1771 to ControlLogix 1756
Wiring Diagrams - Digital

Cat No. 1771-IBN to 1756-IB32

WARNING There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module Cable


1492-CM1771-LD003 1492-CONCAB005Z 1756-IB32
dc Common 0 10 1 Black 18
GND-0
dc Common 2 30 2 White 36
GND-1
3 Red
Input 00 1 4 Green 1
IN-0
Input 00 21 5 Orange 19
IN-16
Input 01 2 6 Blue 2
IN-1
Input 01 22 7 White/Black 20
IN-17
Input 02 3 8 Red/Black 3
IN-2
Input 02 23 9 Green/Black 21
IN-18
Input 03 4 10 Orange/Black 4
IN-3
Input 03 24 11 Blue/Black 22
IN-19
Input 04 5 12 Black/White 5
IN-4
Input 04 25 13 Red/White 23
IN-20
Input 05 6 14 Green/White 6
IN-5
Input 05 26 15 Blue/White 24
IN-21
Input 06 7 16 Black/Red 7
IN-6
Input 06 27 17 White/Red 25
IN-22
Input 07 8 18 Orange/Red 8
IN-7
Input 07 28 19 Blue/Red 26
IN-23
Input 10 11 20 Red/Green 9
IN-8
Input 10 31 21 Orange/Green 27
IN-24
Input 11 12 22 Black/White/Red 10
IN-9
Input 11 32 23 White/Black/Red 28
+ IN-25
Input 12 13 24 Red/Black/White 11
IN-10
Input 12 33 25 Green/Black/White 29
- IN-26
Input 13 14 26 Orange/Black/White 12
IN-11
Input 13 34 27 Blue/Black/White 30
IN-27
Input 14 15 28 Black/Red/Green 13
IN-12
Input 14 35 29 White/Red/Green 31
IN-28
Input 15 16 30 Red/Black/Green 14
IN-13
Input 15 36 31 Green/Black/Orange 32
IN-29
Input 16 17 32 Orange/Black/Green 15
IN-14
Input 16 37 33 Blue/White/Orange 33
IN-30
Input 17 18 34 Black/White/Orange 16
IN-15
Input 17 38 35 White/Red/Orange 34
IN-31
dc Common 0 9 36 Orange/White/Blue 17
GND-0
dc Common 1 19 37 White/Red/Blue 35
GND-1
dc Common 1 20
dc Common 2 29
dc Common 3 39
dc Common 3 40

1771-WN Swing Arm


From 1771-IBN

Conversion Module Installation and Application Considerations


 The input delay times for the 1771-IBN module versus 1756-IB32 module are as follows:
1771-IBN 1756-IB32
a) Off-to-On Delay 6ms (+/-2ms) 1ms (plus selectable filter)
b) On-to-Off Delay 6ms (+/-2ms) 1ms (plus selectable filter)
 The 1771-IBN has 4 groups(allowing 4 seperate power supplies) and the 1756-IB32 has 2 groups.
This module/cable combination ties Groups 0 & 1 from the 1771-IBN to Group 0 on the 1756-IB32 and it ties Groups 2 & 3 from
the 1771-IBN to Group 1 on the 1756-IB32. Field wiring modification must be made to accommodate this if multiple supplies
were used. If 4 supplies were used, 2 must be removed.
 Refer to your 1771-IBN and 1756-IB32 Installation Manual wiring schematics and diagrams for more details.
[Reference Doc: 41170-929 (Version 02)]

Visit our website: www.ab.com


26 Publication 1492-SG121D-EN-P
Bulletin 1492
I/O Wiring Conversion Systems - PLC-5 1771 to ControlLogix 1756
Wiring Diagrams - Digital

Cat No. 1771-IC (Qty. 2) to 1756-IC16

WARNING There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module Cable


1492-CM1771-LD007 1492-C005005XE 1756-IC16
1 Black 10
GND-0
Not used A 2 White 9
GND-0
Input 0 0 3 Red 1
IN-0
Input 1 1 4 Green 2
IN-1
Input 2 2 5 Orange 3
IN-2
+ Input 3 3 6 Blue 4
IN-3
Input 4 4 7 White/Black 5
- IN-4
Input 5 5 8 Red/Black 6
IN-5
Input 6 6 9 Green/Black 7
IN-6
Input 7 7 10 Orange/Black 8
IN-7
GND-1 B 11 CABLE “A”
12
13 CABLE “B” 11
14 IN-8
12
15 IN-9
13
16 IN-10
14
17 IN-11
15
18 IN-12
16
19 IN-13
17
20 IN-14
18
IN-15
1771-WA Swing Arm 21 20
GND-1
22 19
From 1771-IC 23
GND-1
24
25

Conversion Module
1492-CM1771-LD007
1 Black
Not used A 2 White
Input 0 0 3 Red
Input 1 1 4 Green
Input 2 2 5 Orange
+ Input 3 3 6 Blue
Input 4 4 7 White/Black
- Input 5 5 8 Red/Black
Input 6 6 9 Green/Black

Input 7 7 10 Orange/Black

GND-1 B 11
12
13
14
15
16
17
18
19
20
1771-WA Swing Arm 21
22
From 1771-IC 23
24
25

Conversion Module Installation and Application Considerations


 This Bul. 1492 cable consists of 2 separate cables (cable “A” and cable “B”) wired to one 1756-IC16 RTB. Recommended cable
lengths of 0.5 M / 0.5 M are shown. See table 2 for other lengths.
 The input delay times for the 1771-IC module versus the 1756-IC16 module are as follows:
1771-IC 1756-IC16 w/ 1492-C005005XE
a) Off-to-On Delay 12ms (+/-7ms) 1ms max (plus selectable filter)
b) On-to-Off Delay 20ms (+/-7ms) 4ms max (plus selectable filter)
 The 1771-IC module is rated 42 to 56V DC. The 1756-IC16 module is rated 42 to 56V DC only.
 Refer to your 1771-IC and 1756-IC16 Installation Manual wiring schematics and diagrams for more details.
[Reference Doc: 41170-996 (Version 00)]

Visit our website: www.ab.com


Publication 1492-SG121D-EN-P 27
Bulletin 1492
I/O Wiring Conversion Systems - PLC-5 1771 to ControlLogix 1756
Wiring Diagrams - Digital

Cat No. 1771-ICD to 1756-IC16

WARNING There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module
1492-CM1771-LD001
Cable
Terminal A A 1492-CONCAB005X 1756-IC16
Terminal B B
Terminal C C 1 Black 10
RTN
Terminal D D 2 White 9
RTN
Input 00 00 3 Red 1
IN-0
Input 01 01 4 Green 2
IN-1
Input 02 02 5 Orange 3
IN-2
Input 03 03 6 Blue 4
IN-3
Input 04 04 7 White/Black 5
IN-4
Input 05 05 8 Red/Black 6
IN-5
Input 06 06 9 Green/Black 7
IN-6
Input 07 07 10 Orange/Black 8
IN-7
Input 10 10 11 Blue/Black 11
IN-8
Input 11 11 12 Black/White 12
IN-9
Input 12 12 13 Red/White 13
+ IN-10
Input 13 13 14 Green/White 14
IN-11
Input 14 14 15 Blue/White 15
IN-12
-- Input 15 15 16 Black/Red 16
IN-13
Input 16 16 17 White/Red 17
IN-14
Input 17 17 18 Orange/Red 18
IN-15
Terminal E E 19 Blue/Red 20
RTN
20 Red/Green 19
RTN
21
22
23
24
25

1771-WH Swing Arm


From 1771-ICD

Conversion Module Installation and Application Considerations


 This Bul. 1492 cable consists of a cable wired to one 1756-IC16 RTB. Recommended cable lengths of
0.5M or 1.0M (005=0.5M, 010=1.0M). See table 2 for other lengths.

 The input delay times for the 1771-ICD module versus the 1756-IC16 module are as follows:
1771-ICD 1756-IC16 w/ 1492-CONCAB005X
a) Off-to-On Delay 6ms (+/-2ms) 1ms max (plus selectable filter)
b) On-to-Off Delay 20ms (+/-1ms) 4ms max (plus selectable filter)

 The 1771-ICD module is rated 20V to 60V AC or DC. The 1756-IC16 module is rated 30V to 60V DC.
 Refer to your 1771-ICD and 1756-IC16 Installation Manual wiring schematics and diagrams for more details.
[Reference Doc: 41171-001 (Version 00)]

Visit our website: www.ab.com


28 Publication 1492-SG121D-EN-P
Bulletin 1492
I/O Wiring Conversion Systems - PLC-5 1771 to ControlLogix 1756
Wiring Diagrams - Digital

Cat No. 1771-ID (Qty. 2) to 1756-IA16I

WARNING There are several key application considerations and system specifications (bottom of drawing) when using
these components (conversion module, cable and output module). Read and understand these considerations
before installation. In addition, refer to the current draw requirements of the existing loads for this configuration
to ensure they are within the current ratings of the 1756 output module.

Conversion Module
1492-CM1771-LD012
1
Cable
2
3 1492-C005005XL c 1756-IA16I
4
5
4
JMP0
3 6
Orange
Blue
CABLE”A” 1
L1-0
N.C. 7 White/Black 2
L2-0
N.O. 8 Red/Black 3
L1-1
2 1 9 Green/Black 4
JMP1 L2-1
4 3 10 Orange/Black 5
L1-2
N.C. 11 Blue/Black 6
L2-2
N.O. 12 Black/White 7
L1-3
2 1 13 Red/White 8
JMP2 L2-3
3 14 Green/White 9
4 L1-4
L1-0 N.C. 15 Blue/White 10
1 L2-4
N.O. 16 Black/Red 11
L2-0 L1-5
2 2 1 17 White/Red 12
L1-1 L2-5
L1 L2 3 JMP3 18
4 3 Orange/Red
L2-1 4 25 NOT USED
N.C. 19 Blue/Red
L1-2 5 26 NOT USED
N.O. 20 Red/Green
L2-2 6 2 27 NOT USED
1 21 Orange/Green
L1-3 7 JMP4 28 NOT USED
4 3 22 Black/White/Red
L2-3 8 29 NOT USED
N.C. 23 White/Black/Red
L1-4 9 30 NOT USED
N.O. 24 Red/Black/White
L2-4 10 2 1 31 NOT USED
25 Green/Black/White
L1-5 11 JMP5 32 NOT USED
4 3 26 Orange/Black/White
L2-5 12 33 NOT USED
N.C. 27 Blue/Black/White
34 NOT USED
N.O. 28 Black/Red/Green
NOT USED
35
2
4
JMP6
1
3
29
30
White/Red/Green
Red/Black/Green
CABLE”B” 36 NOT USED
13
N.C. 31 Green/Black/Orange L1-6
14
N.O. 32 Orange/Black/Green L2-6
2 1 15
33 Blue/White/Orange L1-7
JMP7 16
3 34 Black/White/Orange L2-7
1771-WD Swing Arm 4
N.C. 35 White/Red/Orange
17 L1-8
18
From 1771-ID N.O. 36 Orange/White/Blue
19
L2-8
2 1 37 L1-9
20
L2-9
Conversion Module 21
L1-10
1492-CM1771-LD012 22
23
L2-10
L1-11
1 24 L2-11
2
3
4
5 Orange
JMP0 6 Blue
4 3
N.C. 7 White/Black
N.O. 8 Red/Black
2 1 9 Green/Black
JMP1 10
4 3 Orange/Black
N.C. 11 Blue/Black
N.O. 12 Black/White
2 1 13 Red/White
JMP2 14 Green/White
4 3
L1-6 N.C. 15 Blue/White
1
L2-6 N.O. 16 Black/Red
2 2 1 17 White/Red
L1-7 3 JMP3
4 3 18 Orange/Red
L2-7 4 N.C. 19 Blue/Red
L1-8 5
N.O. 20 Red/Green
L2-8 6 2 1 21 Orange/Green
L1-9 7 JMP4
L2-9 4 3 22 Black/White/Red
8 N.C. 23 White/Black/Red
L1-10 9
N.O. 24 Red/Black/White
L2-10 10 2 1 25 Green/Black/White
L1-11 11 JMP5
4 3 26 Orange/Black/White
L2-11 12
N.C. 27 Blue/Black/White
L1 L2 N.O. 28 Black/Red/Green
2 1 29 White/Red/Green
JMP6 30
4 3 Red/Black/Green
N.C. 31 Green/Black/Orange
N.O. 32 Orange/Black/Green
2 1 33 Blue/White/Orange
JMP7 34 Black/White/Orange
4 3
N.C. 35 White/Red/Orange
N.O. 36 Orange/White/Blue

1771-WD Swing Arm 2 1 37

From 1771-ID

CONVERSION MODULE INSTALLATION AND APPLICATION CONSIDERATIONS


c This Bul. 1492 cable consists of a cable wired to one 1756-IA16I RTB. Recommended cable lengths of
0.5M or 1.0M (005=0.5M, 010=1.0M). See table 2 for other lengths.
d The input delay times for the 1771-ID module versus the 1756-IA16I module are as follows:
1771-ID 1756-IA16I
a) Off-to-On Delay 24ms (+/-10ms) 10ms max (plus selectable filter)
b) On-to-Off Delay 24ms (+/-10ms) 8ms max (plus selectable filter)
e The 1771-ID module had a jumper selection of N.O. and N.C. outputs. The 1492-CM1771-LD012 conversion module
replaces the functionality. Make sure the jumper are on pins 1-2 .
f Refer to your 1771-ID and 1756-IA16I Installation Manual wiring schematics and diagrams for more details. Ensure
1756 input module ratings are not exceeded.

41170-993 (01)

Visit our website: www.ab.com


Publication 1492-SG121D-EN-P 29
Bulletin 1492
I/O Wiring Conversion Systems - PLC-5 1771 to ControlLogix 1756
Wiring Diagrams - Digital

Cat No. 1771-ID01(Qty. 2) to 1756-IM16I

WARNING There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module
1492-CM1771-LD012
1 Cable
2
3 1492-C005005XL 1756-IM16I
4
5
4
JMP0
3 6
Orange
Blue
CABLE”A” 1
L1-0
N.C. 7 White/Black 2
L2-0
N.O. 8 Red/Black 3
L1-1
2 1 9 Green/Black 4
JMP1 L2-1
4 3 10 Orange/Black 5
L1-2
N.C. 11 Blue/Black 6
L2-2
N.O. 12 Black/White 7
L1-3
2 1 13 Red/White 8
JMP2 L2-3
3 14 Green/White 9
4 L1-4
L2 L1 N.C. 15 Blue/White 10
L1-0 1 L2-4
LOAD N.O. 16 Black/Red 11
L2-0 L1-5
2 2 1 17 White/Red 12
L1-1 L2-5
3 JMP3 18
4 3 Orange/Red
L2-1 4 25 NOT USED
N.C. 19 Blue/Red
L1-2 5 26 NOT USED
N.O. 20 Red/Green
L2-2 6 2 27 NOT USED
1 21 Orange/Green
L1-3 7 JMP4 28 NOT USED
4 3 22 Black/White/Red
L2-3 8 29 NOT USED
N.C. 23 White/Black/Red
L1-4 9 30 NOT USED
N.O. 24 Red/Black/White
L2-4 10 2 1 31 NOT USED
25 Green/Black/White
L1-5 11 JMP5 32 NOT USED
4 3 26 Orange/Black/White
L2-5 12 33 NOT USED
N.C. 27 Blue/Black/White
34 NOT USED
N.O. 28 Black/Red/Green
NOT USED
35
2
4
JMP6
1
3
29
30
White/Red/Green
Red/Black/Green
CABLE”B” 36 NOT USED
13
N.C. 31 Green/Black/Orange L1-6
14
N.O. 32 Orange/Black/Green L2-6
2 1 15
33 Blue/White/Orange L1-7
JMP7 16
34 L2-7
1771-WD Swing Arm 4 3
N.C. 35
Black/White/Orange
White/Red/Orange
17 L1-8
18
From 1771-ID01 2
N.O.
1
36
37
Orange/White/Blue
19
L2-8
L1-9
20
Conversion Module 21
L2-9
L1-10
1492-CM1771-LD012 22
23
L2-10
L1-11
1 24 L2-11
2
3
4
5 Orange
JMP0 6
4 3 Blue
N.C. 7 White/Black
N.O. 8 Red/Black
2 1 9 Green/Black
JMP1 10
4 3 Orange/Black
N.C. 11 Blue/Black
N.O. 12 Black/White
2 1 13 Red/White
JMP2 14 Green/White
4 3
L1-6 N.C. 15 Blue/White
1
L2-6 N.O. 16 Black/Red
2 2 1 17 White/Red
L1-7 3 JMP3
4 3 18 Orange/Red
L2-7 4 N.C. 19 Blue/Red
L1-8 5
N.O. 20 Red/Green
L2-8 6 2 1 21 Orange/Green
L1-9 7 JMP4
L2-9 4 3 22 Black/White/Red
8 N.C. 23 White/Black/Red
L1-10 9
N.O. 24 Red/Black/White
L2-10 10 2 1
L2 L1 25 Green/Black/White
L1-11 11 JMP5
LOAD 4 3 26 Orange/Black/White
L2-11 12
N.C. 27 Blue/Black/White
N.O. 28 Black/Red/Green
2 1 29 White/Red/Green
JMP6 30
4 3 Red/Black/Green
N.C. 31 Green/Black/Orange
N.O. 32 Orange/Black/Green
2 1 33 Blue/White/Orange
JMP7 34 Black/White/Orange
4 3
N.C. 35 White/Red/Orange
N.O. 36 Orange/White/Blue
2 1
1771-WD Swing Arm 37

From 1771-ID01

Conversion Module Installation and Application Considerations


 This Bul. 1492 cable consists of 2 separate cables (cable “A” and cable “B”) wired to one 1756-IM16I RTB.
Each cable can be either
0.5M or 1.0M (005=0.5M, 010=1.0M). Ensure that cable A and cable B are connected to the correct module in the conversion
 The input delay times for the 1771-IM module versus the 1756-IM16I module are as follows:
1771-ID01 1756-IM16I w/ 1492-C005005XL
a) Off-to-On Delay 20ms (+/-10ms) 10ms max (plus selectable filter)
b) On-to-Off Delay 20ms (+/-10ms) 8ms max (plus selectable filter)
 The 1771-ID01module had a jumper selection of N.O. and N.C. outputs. The 1756-IM16I has both N.O. and N.C. outputs, but
selection is by wiring termination on the 1756 swing arm. The 1492-CM1771-LD012 conversion module replaces the functionality
of the 1771-ID01 jumpers with eight jumpers (JMP0 through JMP7). In the default position, the output will be N.O. If a N.C. output is
required, change the jumper from pins 1-2 to pins 3-4.
 Refer to your 1771-ID01 and 1756-IM16I Installation Manual wiring schematics and diagrams for more details. Ensure
1756 output module ratings are not exceeded. [Reference Doc: 41171-015 (Version 00)]

Visit our website: www.ab.com


30 Publication 1492-SG121D-EN-P
Bulletin 1492
I/O Wiring Conversion Systems - PLC-5 1771 to ControlLogix 1756
Wiring Diagrams - Digital

Cat No. 1771-ID16 to 1756-IA16I

WARNING There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and input module). Read and understand these
considerations before installation.
Conversion Module
1492-CM1771-LD004
1
2 Cable
3 1492-CONCAB005Y 1756-IA16I
4
L2 L2-0 2 5 Orange 2
Input 0 L2-0
1 6 Blue 1
4 IN-0
L2-1 7 White/Black 4
L2-1
Input 1 3 8 Red/Black 3
L1 6 IN-1
L2-2 9 Green/Black 6
5 L2-2
Input 2 10 Orange/Black 5
IN-2
L2-3 8 11 Blue/Black 8
L2-3
Input 3 7 12 Black/White 7
IN-3
L2-4 12 13 Red/White 10
11 L2-4
Input 4 14 Green/White 9
14 IN-4
L2-5 15 Blue/White 12
13 L2-5
Input 5 16 Black/Red 11
16 IN-5
L2-6 17 White/Red 14
15 L2-6
Input 6 18 Orange/Red 13
18 IN-6
L2-7 19 Blue/Red 16
17 L2-7
Input 7 20 Red/Green 15
22 IN-7
L2-10 21 Orange/Green 18
21 L2-8
Input 10 22 Black/White/Red 17
IN-8
L2-11 24 23 White/Black/Red 20
23 L2-9
Input 11 24 Red/Black/White 19
26 IN-9
L2-12 25 Green/Black/White 22
25 L2-10
Input 12 26 Orange/Black/White 21
28 IN-10
L2-13 27 Blue/Black/White 24
L2-11
Input 13 27 28 Black/Red/Green 23
32 IN-11
L2-14 29 White/Red/Green 26
31 L2-12
Input 14 30 Red/Black/Green 25
IN-12
L2-15 34 31 Green/Black/Orange 28
L2-13
Input 15 33 32 Orange/Black/Green 27
IN-13
L2-16 36 33 Blue/White/Orange 30
L2-14
Input 16 35 34 Black/White/Orange 29
IN-14
L2-17 38 35 White/Red/Orange 32
L2-15
Input 17 37 36 Orange/White/Blue 31
IN-15
Not used 9 37
Not used 10
Not used 19
Not used 20
Not used 29
Not used 30
Not used 39
Not used 40

1771-WN Swing Arm


From 1771-ID16
Conversion Module Installation and Application Considerations
 The input delay times for the 1771-ID16 module versus 1756-IA16I module are as follows:
1771-ID16 1756-IA16I
a) Off-to-On Delay 0.57ms 10ms max (plus selectable filter)
b) On-to-Off Delay 9ms or 18ms (selectable) 8ms max (plus selectable filter)
 The 1771-ID16 module is rated 74V to 138V AC and105V to 138V DC. The 1756-IA16I is rated 79V to 132V AC. If the input
source voltage is DC use a 1756-IH16I with this conversion module.
 Refer to your 1771-ID16 and 1756-IA16I Installation Manual wiring schematics and diagrams for more details.
[Reference Doc: 41170-931 (Version 02)]

Visit our website: www.ab.com


Publication 1492-SG121D-EN-P 31
Bulletin 1492
I/O Wiring Conversion Systems - PLC-5 1771 to ControlLogix 1756
Wiring Diagrams - Digital

Cat No. 1771-ID16 to 1756-IH16I

WARNING There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and input module). Read and understand these
considerations before installation.
Conversion Module
1492-CM1771-LD004
1
2 Cable
3 1492-CONCAB005Y 1756-IH16I
4
L2-0 2 5 Orange 2
- GND-0
Input 0 1 6 Blue 1
IN-0
L2-1 4 7 White/Black 4
+ GND-1
Input 1 3 8 Red/Black 3
IN-1
L2-2 6 9 Green/Black 6
GND-2
Input 2 5 10 Orange/Black 5
IN-2
L2-3 8 11 Blue/Black 8
GND-3
Input 3 7 12 Black/White 7
IN-3
L2-4 12 13 Red/White 10
GND-4
Input 4 11 14 Green/White 9
IN-4
L2-5 14 15 Blue/White 12
GND-5
Input 5 13 16 Black/Red 11
IN-5
L2-6 16 17 White/Red 14
GND-6
Input 6 15 18 Orange/Red 13
IN-6
L2-7 18 19 Blue/Red 16
GND-7
Input 7 17 20 Red/Green 15
IN-7
L2-10 22 21 Orange/Green 18
GND-8
Input 10 21 22 Black/White/Red 17
IN-8
L2-11 24 23 White/Black/Red 20
GND-9
Input 11 23 24 Red/Black/White 19
IN-9
L2-12 26 25 Green/Black/White 22
GND-10
Input 12 25 26 Orange/Black/White 21
IN-10
L2-13 28 27 Blue/Black/White 24
GND-11
Input 13 27 28 Black/Red/Green 23
IN-11
L2-14 32 29 White/Red/Green 26
GND-12
Input 14 31 30 Red/Black/Green 25
IN-12
L2-15 34 31 Green/Black/Orange 28
GND-13
Input 15 33 32 Orange/Black/Green 27
IN-13
L2-16 36 33 Blue/White/Orange 30
GND-14
Input 16 35 34 Black/White/Orange 29
IN-14
L2-17 38 35 White/Red/Orange 32
GND-15
Input 17 37 36 Orange/White/Blue 31
IN-15
Not used 9 37
Not used 10
Not used 19
Not used 20
Not used 29
Not used 30
Not used 39
Not used 40

1771-WN Swing Arm


From 1771-ID16

Conversion Module Installation and Application Considerations


 The input delay times for the 1771-ID16 module versus 1756-IH16I module are as follows:
1771-ID16 1756-IH16I
a) Off-to-On Delay 0.57ms 2ms max (plus selectable filter)
b) On-to-Off Delay 9ms or 18ms (selectable) 6ms max (plus selectable filter)
 The 1771-ID16 module is rated 74V to 138V AC and105V to 138V DC. The 1756-IH16I is rated 90V to 146V DC. If the input
source voltage is AC use a 1756-IA16I with this conversion module.
 Refer to your 1771-ID16 and 1756-IH16I Installation Manual wiring schematics and diagrams for more details.
[Reference Doc: 41170-932 (Version 02)]

Visit our website: www.ab.com


32 Publication 1492-SG121D-EN-P
Bulletin 1492
Bulletin 1771 to 1756 I/O Wiring Conversion System
Wiring Diagrams- Digital

Cat No. 1771-IG (Qty. 2) to 1756-IG16

WARNING There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module Cable


1492-CM1771-LA003 1492-C005005XS 1756-IG16
+ + DC A 13 Red/White CABLE”A” 10
+ DC -0
+ Input 0 0 25 Green/Black/White 1
Input IN-0
5V DC - Input 1 1 24 Red/Black/White 2
- Device IN-1
SUPPLY Input 2 2 23 White/Black/Red 3
IN-2
Input 3 3 22 Black/White/Red 4
IN-3
Input 4 4 21 Orange/Green 5
IN-4
Input 5 5 19 Blue/Red 6
IN-5
Input 6 6 18 Orange/Red 7
IN-6
Input 7 7 17 White/Red 8
Common IN-7
B 16 Black/Red 9
- DC -0
1 20
+ DC -1
2 11
IN-8
3 12
IN-9
4 13
IN-10
5 14
IN-11
6 15
IN-12
7 16
1771-WC Swing Arm 8 17
IN-13
IN-14
From 1771-IG 9 18
IN-15
10 19
11 - DC -1
12
14
15
20

SH

Conversion Module
1492-CM1771-LA003
+ + DC A 13 Red/White
+ Input 0 0 25 Green/Black/White
Input
5V DC - Input 1 1 24 Red/Black/White
- Device Input 2
SUPPLY 2 23 White/Black/Red
Input 3 3 22 Black/White/Red
Input 4 4 21 Orange/Green
Input 5 5 19 Blue/Red
Input 6 6 18 Orange/Red
Input 7 7 17 White/Red
Common B 16 Black/Red
1
2 CABLE”B”
3
4
5
6
7
1771-WC Swing Arm 8
From 1771-IG 9
10
11
12
14
15
20

SH

Conversion Module Installation and Application Considerations


 This Bul. 1492 cable consists of 2 separate cables (cable “A” and cable “B”) wired to one 1756-IG16 RTB.
Each cable can be either 0.5M or
1.0M (005=0.5M, 010=1.0M). Ensure that cable A and cable B are connected to the correct module in the conversion.
 The input delay times for the 1771-IG module versus the 1756-IG16 module are as follows:
1771-IG 1756-IG16 w/ 1492-C005005XS
a) Off-to-On Delay 1ms (+/-10ms) 270ms max (plus selectable filter)
b) On-to-Off Delay 1ms (+/-10ms) 390ms max (plus selectable filter)
 The 1771-IG module is rated 5V DC TTL INPUT MODULE. The 1756-IG16 module is rated 5V DC TTL INPUT MODULE only.
 Refer to your 1771-IG and 1756-IG16 Installation and User Manuals for additional information concerning comparisons of module wiring,
features and configuration details. [Reference Doc: 41171-027 (Version 00)]

Visit our website: www.ab.com


Publication 1492-SG121D-EN-P 33
Bulletin 1492
Bulletin 1771 to 1756 I/O Wiring Conversion System
Wiring Diagrams - Digital

Cat No. 1771-IGD to 1756-IG16

WARNING There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module
1492-CM1771-LD006
Cable
+ dc A 1492-CONCAB005X 1756-IG16
+ dc B
+ dc C 1 Black 10
DC-0+
+ dc D 2 White 9
RTN OUT-0
Input 00 00 3 Red 1
IN-0
Input 01 01 4 Green 2
IN-1
Input 02 02 5 Orange 3
+ IN-2
Input 03 03 6 Blue 4
IN-3
- Input 04 04 7 White/Black 5
IN-4
Input 05 05 8 Red/Black 6
IN-5
Input 06 06 9 Green/Black 7
IN-6
Input 07 07 10 Orange/Black 8
- + IN-7
DC Input Input 08 10 11 Blue/Black 11
Device IN-8
Input 09 11 12 Black/White 12
IN-9
Input 10 12 13 Red/White 13
IN-10
Input 11 13 14 Green/White 14
IN-11
Input 12 14 15 Blue/White 15
IN-12
Input 13 15 16 Black/Red 16
IN-13
Input 14 16 17 White/Red 17
IN-14
Input 15 17 18 Orange/Red 18
IN-15
19 Blue/Red 20
DC-1+
- dc E 20 Red/Green 19
RTN OUT-1
21
22
23
24
25

1771-WH, WHF, WHFB Swing Arm


From 1771-IGD

Conversion Module Installation and Application Considerations


 This Bul. 1492 cable consists of a cable wired to one 1756-IG16 RTB. Recommended cable lengths of 0.5M or 1.0M
(005=0.5M, 010=1.0M). See table 2 for other lengths.
 The 1771-IGD module output current limits versus 1756-IG16 limits are as follows:
1771-IGD 1756-IG16 w/ 1492-CONCAB005X
a) Current/Point 122mA 110mA
b) Current/Module 500mA 110mA
 The 1771-IGD is rated 5V DC. The 1756-IG16 is rated 4.5V to 5.5V DC.
 Refer to your 1771-IGD and 1756-IG16 Installation Manual wiring schematics and diagrams for more details.Ensure
1756 output module ratings are not exceeded. [Reference Doc: 41171-004 (Version 00)]

Visit our website: www.ab.com


34 Publication 1492-SG121D-EN-P
Bulletin 1492
Bulletin 1771 to 1756 I/O Wiring Conversion System
Wiring Diagrams- Digital

Cat No. 1771-IH (Qty. 2) to 1756-IC16

WARNING There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module Cable


1492-CM1771-LD007 1492-C005005XE 1756-IC16
1 Black 10
GND-0
Not used A 2 White 9
GND-0
Input 0 0 3 Red 1
IN-0
Input 1 1 4 Green 2
IN-1
Input 2 2 5 Orange 3
IN-2
+ Input 3 3 6 Blue 4
IN-3
Input 4 4 7 White/Black 5
- IN-4
Input 5 5 8 Red/Black 6
IN-5
Input 6 6 9 Green/Black 7
IN-6
Input 7 7 10 Orange/Black 8
IN-7
GND-0 B 11 CABLE “A”
12
13 CABLE “B” 11
14 IN-8
12
15 IN-9
13
16 IN-10
14
17 IN-11
15
18 IN-12
16
19 IN-13
17
20 IN-14
18
IN-15
1771-WA Swing Arm 21 20
GND-1
22 19
From 1771-IH 23
GND-1
24
25

Conversion Module
1492-CM1771-LD007
1 Black
Not used A 2 White
Input 0 0 3 Red
Input 1 1 4 Green
Input 2 2 5 Orange
+ Input 3 3 6 Blue
Input 4 4 7 White/Black
- Input 5 5 8 Red/Black
Input 6 6 9 Green/Black

Input 7 7 10 Orange/Black

GND-1 B 11
12
13
14
15
16
17
18
19
20
1771-WA Swing Arm 21
From 1771-IH 22
23
24
25

Conversion Module Installation and Application Considerations


 This Bul. 1492 cable consists of 2 separate cables (cable “A” and cable “B”) wired to one 1756-IC16 RTB. Recommended cable
lengths of 0.5 M / 0.5 M are shown. See table 2 for other lengths.
 The input delay times for the 1771-IH module versus the 1756-IC16 module are as follows:
1771-IH 1756-IC16 w/ 1492-C005005XE
a) Off-to-On Delay 15ms (+/-7ms) 1ms max (plus selectable filter)
b) On-to-Off Delay 15ms (+/-7ms) 4ms max (plus selectable filter)
 The 1771-IH module is rated 24V - 48V DC. The 1756-IC16 module is rated 30V - 60V DC.
 Refer to your 1771-IH and 1756-IC16 Installation Manual wiring schematics and diagrams for more details.
[Reference Doc: 41170-997 (Version 00)]

Visit our website: www.ab.com


Publication 1492-SG121D-EN-P 35
Bulletin 1492
Bulletin 1771 to 1756 I/O Wiring Conversion System
Wiring Diagrams - Digital

Cat No. 1771-IM (Qty. 2) to 1756-IM16I

WARNING There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module Cable


1492-CM1771-LD007 1492-C005005XH 1756-IM16I
1 Black 2
L2-0
Not used A 2 White 4
L2-0
Input 0 0 3 Red 1
IN-0
Input 1 1 4 Green 3
IN-1
Input 2 2 5 Orange 5
IN-2
L1 Input 3 3 6 Blue 7
IN-3
Input 4 4 7 White/Black 9
IN-4
Input 5 5 8 Red/Black 11
L2 IN-5
Input 6 6 9 Green/Black 13
IN-6
Input 7 7 10 Orange/Black 15
IN-7
L2 B 11 CABLE “A” 6
L2-0
12 8
L2-0
13 10
L2-0
14 12
L2-0
15 14
L2-0
16 16
L2-0
17
18
19
20 17
IN-8
1771-WA Swing Arm 21 19
21
IN-9
22
From 1771-IM 23 23
IN-10
IN-11
24 25
IN-12
25 27
IN-13
29
IN-14
31
IN-15
Conversion Module 18
L2-1
1492-CM1771-LD007 20
L2-1
22
1 L2-1
Black 24
Not used A 2 L2-1
White 26
3 L2-1
Input 0 0 Red 28
1 4 L2-1
Input 1 Green 30
5 Orange L2-1
Input 2 2 32
L1 6 L2-1
Input 3 3 Blue
Input 4 4 7 White/Black
Input 5 5 8 Red/Black
L2 Input 6 6 9 Green/Black

Input 7 7 10 Orange/Black

L2 B 11 CABLE “B”
12
13
14
15
16
17
18
19
20
1771-WA Swing Arm 21
22
From 1771-IM 23
24
25

Conversion Module Installation and Application Considerations


 This Bul. 1492 cable consists of 2 separate cables (cable “A” and cable “B”) wired to one 1756-IM16I RTB. Recommended cable
lengths of 0.5 M / 0.5 M are shown. See table 2 for other lengths.
 The input delay times for the 1771-IM module versus the 1756-IM16I module are as follows:
1771-IM 1756-IM16I w/ 1492-C005005XH
a) Off-to-On Delay 20ms (+/-6ms) 10ms max (plus selectable filter)
b) On-to-Off Delay 20ms (+/-6ms) 8ms max (plus selectable filter)
 The 1771-IM module is rated 220V to 240V AC. The 1756-IM16I module is rated 159 - 265V AC only.
 Refer to your 1771-IM and 1756-IM16I Installation Manual wiring schematics and diagrams for more details.
[Reference Doc: 41170-990 (Version 00)]

Visit our website: www.ab.com


36 Publication 1492-SG121D-EN-P
Bulletin 1492
Bulletin 1771 to 1756 I/O Wiring Conversion System
Wiring Diagrams- Digital

Cat No. 1771-IMD to 1756-IM16I

WARNING There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module
1492-CM1771-LD002
1
Terminal A A 2 Cable
Terminal B B 3 1492-CONCAB005Y 1756-IM16I
Terminal C C 4
Terminal D D 5 Orange 2
L2-0
Input 00 00 6 Blue 1
IN-0
7 White/Black 4
L2-1
Input 01 01 8 Red/Black 3
IN-1
9 Green/Black 6
L2-2
Input 02 02 10 Orange/Black 5
IN-2
11 Blue/Black 8
L2-3
Input 03 03 12 Black/White 7
IN-3
13 Red/White 10
L2-4
Input 04 04 14 Green/White 9
IN-4
15 Blue/White 12
L2-5
Input 05 05 16 Black/Red 11
IN-5
17 White/Red 14
L2-6
Input 06 06 18 Orange/Red 13
IN-6
19 Blue/Red 16
L2-7
Input 07 07 20 Red/Green 15
IN-7
21 Orange/Green 18
L2-8
Input 10 10 22 Black/White/Red 17
IN-8
23 White/Black/Red 20
L2-9
Input 11 11 24 Red/Black/White 19
IN-9
25 Green/Black/White 22
L2-10
Input 12 12 26 Orange/Black/White 21
IN-10
27 Blue/Black/White 24
L2-11
Input 13 13 28 Black/Red/Green 23
IN-11
29 White/Red/Green 26
L2-12
Input 14 14 30 Red/Black/Green 25
IN-12
31 Green/Black/Orange 28
L2-13
Input 15 15 32 Orange/Black/Green 27
IN-13
L1 33 Blue/White/Orange 30
L2-14
Input 16 16 34 Black/White/Orange 29
IN-14
35 White/Red/Orange 32
L2 L2-15
Input 17 17 36 Orange/White/Blue 31
IN-15
37
Terminal E E

1771-WH Swing Arm


From 1771-IMD

Conversion Module Installation and Application Considerations


 The input delay times for the 1771-IMD module versus 1756-IM16I module are as follows:
1771-IMD 1756-IM16I
a) Off-to-On Delay 15ms (+/-8ms) 10ms (plus selectable filter)
b) On-to-Off Delay 172ms (+/-56ms) 8ms (plus selectable filter)
 The 1771-IMD module is rated 184V AC to 250V AC and 166V-230V DC. The 1756-IM16I module is rated 159V to 265V
AC. A1756 input module with an equivalent DC voltage range to convert the 1771-IMD is not available.
 Refer to your 1771-IMD and 1756-IM16I Installation Manual wiring schematics and diagrams for more details.
[Reference Doc: 41170-928 (Version 02)]

Visit our website: www.ab.com


Publication 1492-SG121D-EN-P 37
Bulletin 1492
Bulletin 1771 to 1756 I/O Wiring Conversion System
Wiring Diagrams - Digital

Cat No. 1771-IN (Qty. 2) to 1756-IN16

WARNING There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module Cable


1492-CM1771-LD007 1492-C005005XE 1756-IN16
1 Black 10
L2-0
Not used A 2 White 9
L2-0
Input 0 0 3 Red 1
IN-0
Input 1 1 4 Green 2
IN-1
Input 2 2 5 Orange 3
IN-2
+ Input 3 3 6 Blue 4
IN-3
Input 4 4 7 White/Black 5
- IN-4
Input 5 5 8 Red/Black 6
IN-5
Input 6 6 9 Green/Black 7
IN-6
Input 7 7 10 Orange/Black 8
IN-7
GND-1 B 11 CABLE “A”
12
13 CABLE “B” 11
14 IN-8
12
15 IN-9
13
16 IN-10
14
17 IN-11
15
18 IN-12
16
19 IN-13
17
20 IN-14
18
IN-15
1771-WA Swing Arm 21 20
L2-1
22 19
From 1771-IN 23
L2-1
24
25

Conversion Module
1492-CM1771-LD007
1 Black
Not used A 2 White
Input 0 0 3 Red
Input 1 1 4 Green
Input 2 2 5 Orange
+ Input 3 3 6 Blue
Input 4 4 7 White/Black
- Input 5 5 8 Red/Black
Input 6 6 9 Green/Black

Input 7 7 10 Orange/Black

L2 B 11
12
13
14
15
16
17
18
19
20
1771-WA Swing Arm 21
22
From 1771-IN 23
24
25

Conversion Module Installation and Application Considerations


 This Bul. 1492 cable consists of 2 separate cables (cable “A” and cable “B”) wired to one 1756-IN16 RTB. Recommended cable
lengths of 0.5 M / 0.5 M are shown. See table 2 for other lengths.
 The input delay times for the 1771-IN module versus the 1756-IN16 module are as follows:
1771-IN 1756-IN16 w/ 1492-C005005XE
a) Off-to-On Delay 18ms (+/-10ms) 10ms max (plus selectable filter)
b) On-to-Off Delay 18ms (+/-10ms) 10ms max (plus selectable filter)
 The 1771-IN module is rated 24V AC. The 1756-IN16 module is rated 24V AC only.
 Refer to your 1771-IN and 1756-IN16 Installation Manual wiring schematics and diagrams for more details.
[Reference Doc: 41170-998 (Version 00)]

Visit our website: www.ab.com


38 Publication 1492-SG121D-EN-P
Bulletin 1492
Bulletin 1771 to 1756 I/O Wiring Conversion System
Wiring Diagrams- Digital

Cat No. 1771-IND to 1756-IN16

WARNING There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module
1492-CM1771-LD001
Cable
Terminal A A 1492-CONCAB005X 1756-IN16
Terminal B B
Terminal C C 1 Black 10
L2-0
Terminal D D 2 White 9
L2-0
Input 00 00 3 Red 1
IN-0
Input 01 01 4 Green 2
IN-1
Input 02 02 5 Orange 3
IN-2
Input 03 03 6 Blue 4
IN-3
Input 04 04 7 White/Black 5
IN-4
Input 05 05 8 Red/Black 6
IN-5
Input 06 06 9 Green/Black 7
IN-6
Input 07 07 10 Orange/Black 8
IN-7
Input 10 10 11 Blue/Black 11
IN-8
Input 11 11 12 Black/White 12
IN-9
Input 12 12 13 Red/White 13
L1 IN-10
Input 13 13 14 Green/White 14
IN-11
Input 14 14 15 Blue/White 15
IN-12
Input 15 15 16 Black/Red 16
L2 IN-13
Input 16 16 17 White/Red 17
IN-14
Input 17 17 18 Orange/Red 18
IN-15
Terminal E E 19 Blue/Red 20
L2-1
20 Red/Green 19
L2-1
21
22
23
24
25

1771-WH Swing Arm


From 1771-IND

Conversion Module Installation and Application Considerations


 This Bul. 1492 cable consists of a cable wired to one 1756-IN16 RTB. Recommended cable lengths of
0.5M or 1.0M (005=0.5M, 010=1.0M). See table 2 for other lengths.

 The input delay times for the 1771-IND module versus the 1756-IN16 module are as follows:
1771-IND 1756-IN16 w/ 1492-CONCAB005X
a) Off-to-On Delay 35ms (+/-10ms) @24V AC 10ms max (plus selectable filter)
b) On-to-Off Delay 45ms (+/-15ms) 10ms max (plus selectable filter)

 The 1771-IND module is rated 24V AC or DC. The 1756-IN16 module is rated 10V to 30V AC.

 Refer to your 1771-IND and 1756-IN16 Installation Manual wiring schematics and diagrams for more details.
[Reference Doc: 41170-002 (Version 00)]

Visit our website: www.ab.com


Publication 1492-SG121D-EN-P 39
Bulletin 1492
Bulletin 1771 to 1756 I/O Wiring Conversion System
Wiring Diagrams - Digital

Cat No. 1771- IND1 to 1756-IN16

WARNING There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module
1492-CM1771-LD001
Cable
Terminal A A 1492-CONCAB005X 1756-IN16
Terminal B B
Terminal C C 1 Black 10
L2-0
Terminal D D 2 White 9
L2-0
Input 00 00 3 Red 1
IN-0
Input 01 01 4 Green 2
IN-1
Input 02 02 5 Orange 3
IN-2
Input 03 03 6 Blue 4
IN-3
Input 04 04 7 White/Black 5
IN-4
Input 05 05 8 Red/Black 6
IN-5
Input 06 06 9 Green/Black 7
IN-6
Input 07 07 10 Orange/Black 8
IN-7
Input 10 10 11 Blue/Black 11
IN-8
Input 11 11 12 Black/White 12
IN-9
Input 12 12 13 Red/White 13
L1 IN-10
Input 13 13 14 Green/White 14
IN-11
Input 14 14 15 Blue/White 15
IN-12
Input 15 15 16 Black/Red 16
L2 IN-13
Input 16 16 17 White/Red 17
IN-14
Input 17 17 18 Orange/Red 18
IN-15
Terminal E E 19 Blue/Red 20
L2-1
20 Red/Green 19
L2-1
21
22
23
24
25

1771-WH Swing Arm


From 1771-IND1

Conversion Module Installation and Application Considerations


 This Bul. 1492 cable consists of a cable wired to one 1756-IN16 RTB. Recommended cable lengths of
0.5M or 1.0M (005=0.5M, 010=1.0M). See table 2 for other lengths.

 The input delay times for the 1771-IND1 module versus the 1756-IN16 module are as follows:
1771-IND1 1756-IN16 w/ 1492-CONCAB005X
a) Off-to-On Delay 25ms (+/-5ms) @48V AC 10ms max (plus selectable filter)
b) On-to-Off Delay 35ms (+/-10ms) 10ms max (plus selectable filter)

 The 1771-IND1 module is rated 48V AC. The 1756-IN16 module is rated 10V to 30V AC.

 Refer to your 1771-IND1 and 1756-IN16 Installation Manual wiring schematics and diagrams for more details.
[Reference Doc: 41170-003 (Version 00)]

Visit our website: www.ab.com


40 Publication 1492-SG121D-EN-P
Bulletin 1492
Bulletin 1771 to 1756 I/O Wiring Conversion System
Wiring Diagrams- Digital

Cat No. 1771-IQ (Qty. 2) to 1756-IB16I Sinking

WARNING There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module Cable


1492-CM1771-LD007 1492-C005005XK 1756-IB16I
1 Black 2
L2-0
Not used A 2 White 4
L2-0
IN 0 0 3 Red 1
IN-0
IN 1 1 4 Green 3
IN-1
IN 2 2 5 Orange 5
IN-2
+ IN 3 3 6 Blue 7
IN-3
IN 4 4 7 White/Black 9
_ IN-4
IN 5 5 8 Red/Black 11
IN-5
IN 6 6 9 Green/Black 13
IN-6
IN 7 7 10 Orange/Black 15
IN-7
L2 - 0 B 11 6
12 CABLE “A” 8
L2-0
L2-0
13 10
14 L2-0
12
L2-0
15 14
L2-0
16 16
17 L2-0
18
19
20 17
IN-8
1771-WA Swing Arm 21 19
IN-9
22 21
From 1771-IQ 23 23
IN-10
IN-11
24 25
IN-12
25 27
IN-13
29
IN-14
31
IN-15
18
L2-1
20 L2-1
22
L2-1
24
L2-1
26
L2-1
Conversion Module 28
L2-1
30
1492-CM1771-LD007 L2-1
32
L2-1
1 Black
Not used A 2 White
Input 0 0 3 Red
Input 1 1 4 Green
Input 2 2 5 Orange
+ Input 3 3 6 Blue
Input 4 4 7 White/Black
_ 8
Input 5 5 Red/Black
Input 6 6 9 Green/Black

Input 7 7 10 Orange/Black

L2 - 1 B 11
12 CABLE “B”
13
14
15
16
17
18
19
20
1771-WA Swing Arm 21
22
From 1771-IQ 23
24
25

Conversion Module Installation and Application Considerations


 This Bul. 1492 cable consists of 2 separate cables (cable “A” and cable “B”) wired to one 1756-IB16I RTB. Recommended cable
lengths of 0.5 M / 0.5 M are shown. See table 2 for other lengths.
 The input delay times for the 1771-IQ module versus the 1756-IB16I module are as follows:
1771-IQ 1756-IB16I w/ 1492-C005005XK
a) Off-to-On Delay 12ms (+/-14ms) 1ms max (plus selectable filter)
b) On-to-Off Delay 12ms (+/-7ms) 4ms max (plus selectable filter)
 The 1771-IQ module is rated 5V to 30V DC. The 1756-IB16I module is rated 10V to 30V DC only.
 Refer to your 1771-IQ and 1756-IB16I Installation Manual wiring schematics and diagrams for more details.
 For Sourcing applications use 1492-CM1771-LD014. [Reference Doc: 41170-992 (Version 00)]

Visit our website: www.ab.com


Publication 1492-SG121D-EN-P 41
Bulletin 1492
Bulletin 1771 to 1756 I/O Wiring Conversion System
Wiring Diagrams - Digital

Cat No. 1771-IQ (Qty. 2) to 1756-IB16I Sourcing

WARNING There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module
1492-CM1771-LD0014 Cable
1492-C005005XJ 1756-IB16I
1 Black
DC+ A 2 White
GND 00 0 3 Red 2
GND-0
GND 01 1 4 Green 4
GND-1
GND 02 2 5 Orange 6
GND-2
GND 03 3 6 Blue 8
GND-3
7 White/Black 1
IN - 0
8 Red/Black 3
IN - 1
9 Green/Black 5
+ IN - 2
10 Orange/Black 7
IN - 3
11 Blue/Black 9
- IN - 4
12 Black/White 11 IN - 5
13 Red/White 13 IN - 6
14 Green/White 15 IN - 7
GND 04 4 15 Blue/White 10
LOAD GND-4
GND 05 5 16 Black/Red 12
GND-5
GND 06 6 17 White/Red 14
GND-6
GND 07 7 18 Orange/Red 16
GND-7
DC - B 19 Blue/Red 34 GND-15
20 Red/Green
CABLE”A”
21
22
23
24
1771-WA Swing Arm 25
18
GND-8
From 1771-IQ 20
OUT-9
22
OUT-10
24
Conversion Module OUT-11
17
19 IN - 8
1492-CM1771-LD0014 21 IN - 9
23 IN - 10
IN - 11
25
IN - 12
1 Black
27
IN - 13
DC + A 2 White
29
IN - 14
GND 08 0 3 Red 31
IN - 15
GND 09 1 4 Green 26
GND-12
2 5 Orange 28
GND -10 GND-13
3 6 Blue 30
GND -11 GND-14
7 White/Black
32
GND-15
8 Red/Black 33
NOT-USED
9 Green/Black 35
+ NOT-USED
10 Orange/Black 36
NOT-USED
11 Blue/Black
-
12 Black/White
13 Red/White
14 Green/White
GND -12 4 15 Blue/White
LOAD
GND -13 5 16 Black/Red
GND -14 6 17 White/Red
GND -15 7 18 Orange/Red

DC - B 19 Blue/Red
20 Red/Green CABLE”B”
21
22
23
24
1771-WA Swing Arm 25

From 1771-IQ

Conversion Module Installation and Application Considerations


 This Bul. 1492 cable consists of 2 separate cables (cable “A” and cable “B”) wired to one 1756-IB16I RTB.
Each cable can be either 0.5M
or 1.0M (005=0.5M, 010=1.0M). Ensure that cable A and cable B are connected to the correct module in the conversion.
 The input delay times for the 1771-IQ module versus the 1756-IB16 module are as follows:
1771-IQ 1756-IB16I w/1492-C005005XJ
a) Off-to-On Delay 12ms (+/-14ms) 1ms max (plus selectable filter)
b) On-to-Off Delay 12ms (+/-14ms) 4ms max (plus selectable filter)
 The 1771-IQ module is rated 5V to 30V DC. The 1756-IB16I module is rated 10V to 30V SOURCING DC only.
 Refer to your 1771-IQ and 1756-IB16I Installation Manual wiring schematics and diagrams for more details.
 For Sinking applications use 1492-CM1771-LD007. [Reference Doc: 41170-991 (Version 00)]

Visit our website: www.ab.com


42 Publication 1492-SG121D-EN-P
Bulletin 1492
Bulletin 1771 to 1756 I/O Wiring Conversion System
Wiring Diagrams- Digital

Cat No. 1771-IQ16 to 1756-IB16I

WARNING There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and input module). Read and understand these consid
-
erations before installation.
Conversion Module
1492-CM1771-LD004
1
2 Cable
3 1492-CONCAB005Y 1756-IB16I
Sinking Input Example
4
Gnd-0 2 5 Orange 2
- Gnd-0
Input 0 1 6 Blue 1
IN-0
Gnd-1 4 7 White/Black 4
+ Gnd-1
Input 1 3 8 Red/Black 3
IN-1
Gnd-2 6 9 Green/Black 6
Gnd-2
Input 2 5 10 Orange/Black 5
IN-2
Gnd-3 8 11 Blue/Black 8
 Input 3 7 12 Black/White 7
Gnd-3
Sourcing IN-3
Gnd-4 12 13 Red/White 10
Input Gnd-4
Input 4 11 14 Green/White 9
Example IN-4
Gnd-5 14 15 Blue/White 12
- Gnd-5
Input 5 13 16 Black/Red 11
IN-5
Gnd-6 16 17 White/Red 14
+ Gnd-6
Input 6 15 18 Orange/Red 13
IN-6
Gnd-7 18 19 Blue/Red 16
Gnd-7
Input 7 17 20 Red/Green 15
IN-7
Gnd-10 22 21 Orange/Green 18
Gnd-8
Input 10 21 22 Black/White/Red 17
IN-8
Gnd-11 24 23 White/Black/Red 20
Gnd-9
Input 11 23 24 Red/Black/White 19
IN-9
Gnd-12 26 25 Green/Black/White 22
Gnd-10
Input 12 25 26 Orange/Black/White 21
IN-10
Gnd-13 28 27 Blue/Black/White 24
Gnd-11
Input 13 27 28 Black/Red/Green 23
IN-11
Gnd-14 32 29 White/Red/Green 26
Gnd-12
Input 14 31 30 Red/Black/Green 25
IN-12
Gnd-15 34 31 Green/Black/Orange 28
Gnd-13
Input 15 33 32 Orange/Black/Green 27
IN-13
Gnd-16 36 33 Blue/White/Orange 30
Gnd-14
Input 16 35 34 Black/White/Orange 29
IN-14
Gnd-17 38 35 White/Red/Orange 32
Gnd-15
Input 17 37 36 Orange/White/Blue 31
IN-15
Not used 9 37
Not used 10
Not used 19
Not used 20
Not used 29
Not used 30
Not used 39
Not used 40

1771-WN Swing Arm


From 1771-IQ16
Conversion Module Installation and Application Considerations
 The input delay times for the 1771-IQ16 module versus 1756-IB16I module are as follows:
1771-IQ16 1756-IB16I
a) Off-to-On Delay 0.57ms 1ms max (plus selectable filter)
b) On-to-Off Delay 0.57ms 4ms max (plus selectable filter)
 Both the 1771-IQ16 and 1756-IB16I allow operation with sourcing inputs. Refer to installation Instructions for details.
 Refer to your 1771-IQ16 and 1756-IH16I Installation Manual wiring schematics and diagrams for more details.
[Reference Doc: 41170-933 (Version 02)]

Visit our website: www.ab.com


Publication 1492-SG121D-EN-P 43
Bulletin 1492
Bulletin 1771 to 1756 I/O Wiring Conversion System
Wiring Diagrams - Digital

Cat No. 1771-IT (Qty. 2) to 1756-IB16

WARNING There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module Cable


1492-CM1771-LD007 1492-C005005XE 1756-IB16
1 Black 10
GND-0
Not used A 2 White 9
GND-0
Input 0 0 3 Red 1
IN-0
Input 1 1 4 Green 2
IN-1
Input 2 2 5 Orange 3
IN-2
+ Input 3 3 6 Blue 4
IN-3
Input 4 4 7 White/Black 5
- IN-4
Input 5 5 8 Red/Black 6
IN-5
Input 6 6 9 Green/Black 7
IN-6
Input 7 7 10 Orange/Black 8
IN-7
GND-1 B 11 CABLE “A”
12
13 CABLE “B” 11
14 IN-8
12
15 IN-9
13
16 IN-10
14
17 IN-11
15
18 IN-12
16
19 IN-13
17
20 IN-14
18
IN-15
1771-WA Swing Arm 21 20
GND-1
22 19
From 1771-IT 23
GND-1
24
25

Conversion Module
1492-CM1771-LD007
1 Black
Not used A 2 White
Input 0 0 3 Red
Input 1 1 4 Green
Input 2 2 5 Orange
+ Input 3 3 6 Blue
Input 4 4 7 White/Black
- Input 5 5 8 Red/Black
Input 6 6 9 Green/Black

Input 7 7 10 Orange/Black

GND-1 B 11
12
13
14
15
16
17
18
19
20
1771-WA Swing Arm 21
22
From 1771-IT 23
24
25

Conversion Module Installation and Application Considerations


 This Bul. 1492 cable consists of 2 separate cables (cable “A” and cable “B”) wired to one 1756-IB16 RTB. Recommended cable
lengths of 0.5 M / 0.5 M are shown. See table 2 for other lengths.
 The input delay times for the 1771-IT module versus the 1756-IB16 module are as follows:
1771-IT 1756-IB16 w/ 1492-C005005XE
a) Off-to-On Delay 0.6ms (+/-0.2ms) 1ms max (plus selectable filter)
b) On-to-Off Delay 0.6ms (+/-0.2ms) 2ms max (plus selectable filter)
 The 1771-IT module is rated 24V DC. The 1756-IB16 module is rated 24V DC only.
 Refer to your 1771-IT and 1756-IB16 Installation Manual wiring schematics and diagrams for more details.
[Reference Doc: 41170-999 (Version 00)]

Visit our website: www.ab.com


44 Publication 1492-SG121D-EN-P
Bulletin 1492
Bulletin 1771 to 1756 I/O Wiring Conversion System
Wiring Diagrams- Digital

Cat No. 1771-IV (Qty. 2) to 1756-IV16

WARNING There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module
1492-CM1771-LD014 Cable
1492-C005005XG 1756-IV16
1 Black
+DC-0 A 2 White
Cable A
INPUT 00 0 3 Red 1
IN-0
INPUT 01 1 4 Green 2
IN-1
INPUT 02 2 5 Orange 3
IN-2
INPUT 03 3 6 Blue 4
IN-3
7 White/Black 9
+DC-0
8 Red/Black 10 +DC-0
9 Green/Black
+
10 Orange/Black
11 Blue/Black
-
12 Black/White
13 Red/White
14 Green/White
INPUT 04 4 15 Blue/White 5
LOAD IN-4
INPUT 05 5 16 Black/Red 6
IN-5
INPUT 06 6 17 White/Red 7
IN-6
INPUT 07 7 18 Orange/Red 8
IN-7
-DC-0 B 19 Blue/Red
20 Red/Green

21
22
23
24
1771-WA Swing Arm 25 Cable B 11
IN-8
From 1771-IV 12
IN-9
13
Conversion Module 14
IN-10
IN-11
1492-CM1771-LD014 19
+DC-1
20
+DC-1

1 Black
+DC-1 A 2 White
INPUT 08 0 3 Red
INPUT 09 1 4 Green
INPUT 10 15
2 5 Orange IN-12
INPUT 11 16
3 6 Blue IN-13
17
7 White/Black IN-14
18
8 Red/Black IN-15
9 Green/Black
+
10 Orange/Black
11 Blue/Black
-
12 Black/White
13 Red/White
14 Green/White
INPUT 12 4 15 Blue/White
LOAD
INPUT 13 5 16 Black/Red
INPUT 14 6 17 White/Red
INPUT 15 7 18 Orange/Red

-DC-1 B 19 Blue/Red
20 Red/Green

21
22
23
24
1771-WA Swing Arm 25

From 1771-IV

Conversion Module Installation and Application Considerations


 This Bul. 1492 cable consists of 2 separate cables (cable “A” and cable “B”) wired to one 1756-IV16 RTB.
Each cable can be either 0.5M
or 1.0M (005=0.5M, 010=1.0M). Ensure that cable A and cable B are connected to the correct module in the conversion.
 The input delay times for the 1771-IV module versus the 1756-IV16 module are as follows:
1771-IV 1756-IV16 w/1492-C005005XG
a) Off-to-On Delay 15ms (+/-7ms) 1ms max (plus selectable filter)
b) On-to-Off Delay 15ms (+/-7ms) 2ms max (plus selectable filter)
 The 1771-IV module is rated 12 To 24V DC. The 1756-IV16 module is rated 10V To 30V DC only.
 Refer to your 1771-IV and 1756-IV16 Installation Manual wiring schematics and diagrams for more details.
[Reference Doc: 41170-989 (Version 00)]

Visit our website: www.ab.com


Publication 1492-SG121D-EN-P 45
Bulletin 1492
Bulletin 1771 to 1756 I/O Wiring Conversion System
Wiring Diagrams - Digital

Cat No. 1771-IVN to 1756-IV32

WARNING There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module Cable


1492-CM1771-LD005 1492-CONCAB005Z 1756-IV32

10-30V dc (0) 2 1 Black 18


DC-0 (+)
10-30V dc (2) 22 2 White 36
DC-1 (+)
3 Red
Input 00 3 4 Green 1
IN-0
Input 00 23 5 Orange 19
IN-16
Input 01 4 6 Blue 2
IN-1
Input 01 24 7 White/Black 20
IN-17
Input 02 5 8 Red/Black 3
IN-2
Input 02 25 9 Green/Black 21
IN-18
Input 03 6 10 Orange/Black 4
IN-3
Input 03 26 11 Blue/Black 22
IN-19
Input 04 7 12 Black/White 5
IN-4
Input 04 27 13 Red/White 23
IN-20
Input 05 8 14 Green/White 6
IN-5
Input 05 28 15 Blue/White 24
IN-21
Input 06 9 16 Black/Red 7
IN-6
Input 06 29 17 White/Red 25
IN-22
Input 07 10 18 Orange/Red 8
IN-7
Input 07 30 19 Blue/Red 26
IN-23
Input 10 13 20 Red/Green 9
IN-8
Input 10 33 21 Orange/Green 27
IN-24
Input 11 14 22 Black/White/Red 10
IN-9
Input 11 34 23 White/Black/Red 28
IN-25
- Input 12 15 24 Red/Black/White 11
IN-10
+ Input 12 35 25 Green/Black/White 29
IN-26
Input 13 16 26 Orange/Black/White 12
IN-11
Input 13 36 27 Blue/Black/White 30
IN-27
Input 14 17 28 Black/Red/Green 13
IN-12
Input 14 37 29 White/Red/Green 31
IN-28
Input 15 18 30 Red/Black/Green 14
IN-13
Input 15 38 31 Green/Black/Orange 32
IN-29
Input 16 19 32 Orange/Black/Green 15
IN-14
Input 16 39 33 Blue/White/Orange 33
IN-30
Input 17 20 34 Black/White/Orange 16
IN-15
Input 17 40 35 White/Red/Orange 34
IN-31
10-30V dc (0) 1 36 Orange/White/Blue 17
DC-0 (+)
10-30V dc (1) 11 37 White/Red/Blue 35
DC-1 (+)
10-30V dc (1) 12
10-30V dc (2) 21
10-30V dc (3) 31
10-30V dc (3) 32

1771-WN Swing Arm


From 1771-IVN
Conversion Module Installation and Application Considerations
 The input delay times for the 1771-IVN module versus 1756-IV32 module are as follows:
1771-IVN 1756-IV32
a) Off-to-On Delay 6ms (+/-2ms) 1ms (plus selectable filter)
b) On-to-Off Delay 6ms (+/-2ms) 2ms (plus selectable filter)
 The 1771-IVN has 4 groups (allowing 4 seperate power supplies) and the 1756-IV32 has 2 groups.
This module/cable combination ties Groups 0 & 1 from the 1771-IVN to Group 0 on the 1756-IV32 and it ties Groups 2 & 3
from the 1771-IVN to Group 1 on the 1756-IV32.Field wiring modification must be made to accommodate this if multiple
supplies were used. If 4 supplies were used, 2 must be removed.
 Refer to your 1771-IVN and 1756-IV32 Installation Manual wiring schematics and diagrams for more details.
[Reference Doc: 41170-934 (Version 02)]

Visit our website: www.ab.com


46 Publication 1492-SG121D-EN-P
Bulletin 1492
Bulletin 1771 to 1756 I/O Wiring Conversion System
Wiring Diagrams- Digital

Cat No. 1771-OA to 1756-OA8E

WARNING There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module
1492-CM1771-LD014
Cable
1492-CONCAB005U 1756-OA8E

1 Black 2 Not Used


L1 A 2 White 1
L2-0
Output 00 0 3 Red 3
OUT-0
Output 01 1 4 Green 5
OUT-1
Output 02 2 5 Orange 7
OUT-2
Output 03 3 6 Blue 9
OUT-3
7 White/Black 4
L1-0
8 Red/Black 6
L1-0
9 Green/Black 8
L1 L1-0
10 Orange/Black 10
L1-0
11 Blue/Black 12
L1-1
L2 12 Black/White 14
L1-1
13 Red/White 16
L1-1
14 Green/White 18
L1-1
Output 04 4 15 Blue/White 11
LOAD OUT-4
Output 05 5 16 Black/Red 13
OUT-5
Output 06 6 17 White/Red 15
OUT-6
Output 07 7 18 Orange/Red 17
OUT-7
L2 B 19 Blue/Red 19
L2-1
20 Red/Green 20
L1-1
21
22
23
24
25

1771-WA Swing Arm


From 1756-OA8E

Conversion Module Installation and Application Considerations


 This Bul. 1492 cable consists of a cable wired to one 1756-OA8E RTB. Recommended cable lengths of 0.5M or 1.0M (005=0.5M,
010=1.0M). See table 2 for other lengths.
 The 1771-OA module output current limits versus 1756-OA8E limits are as follows:
1771-OA 1756-OA8E w/ 1492-CONCAB005U
a) Current/Point 1.5A 2A
b) Current/Module 6A 4A @ 60°C
c) Surge Current/Pt 4A for 8.3ms 20A for 43 ms
 The 1771-OA has eight (8) 2A, 250V fuses - 1 per output. The 1756-OA8E is electronically fused per point. Refer to the 1756 -
OA8E Installation Manual for details on electronic fusing.
 Refer to your 1771-OA and 1756-OA8E Installation Manual wiring schematics and diagrams for more details. Ensure 1756 output
module ratings are not exceeded. [Reference Doc: 41170-943 (Version 01)]

Visit our website: www.ab.com


Publication 1492-SG121D-EN-P 47
Bulletin 1492
Bulletin 1771 to 1756 I/O Wiring Conversion System
Wiring Diagrams - Digital

Cat No. 1771-OAD to 1756-OA16

WARNING There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module
1492-CM1771-LD006
Cable
L1 A
1492-CONCAB005X 1756-OA16
L1 B
L1 C 1 Black 10
L1-0
L1 D 2 White 9
L2-0
Output 00 00 3 Red 1
OUT-0
Output 01 01 4 Green 2
OUT-1
L1 Output 02 02 5 Orange 3
OUT-2
Output 03 03 6 Blue 4
OUT-3
Output 04 04 7 White/Black 5
L2 OUT-4
Output 05 05 8 Red/Black 6
OUT-5
Output 06 06 9 Green/Black 7
OUT-6
Output 07 07 10 Orange/Black 8
OUT-7
Output Output 10 10 11 Blue/Black 11
OUT-8
Device Output 11 11 12 Black/White 12
OUT-9
Output 12 12 13 Red/White 13
OUT-10
Output 13 13 14 Green/White 14
OUT-11
Output 14 14 15 Blue/White 15
OUT-12
Output 15 15 16 Black/Red 16
OUT-13
Output 16 16 17 White/Red 17
OUT-14
Output 17 17 18 Orange/Red 18
OUT-15
19 Blue/Red 20
L2 L1-1
E 20 Red/Green 19
L2-1
21
22
23
24
25

1771-WH, WHF, WHFB Swing Arm


From 1771-OAD

Conversion Module Installation and Application Considerations


 This Bul. 1492 cable consists of a cable wired to one 1756-OA16 RTB. Recommended cable lengths of 0.5M or 1.0M (005=0.5M,
010=1.0M). See table 2 for other lengths.
 The 1771-OAD module output current limits versus 1756-OA16 limits are as follows:
1771-OAD 1756-OA16 w/ 1492-CONCAB005X
a) Current/Point 2A 0.5A
b) Current/Module 8A 4A
c) Surge Current/point 25A for 100ms 5A for 43ms
 The L2 terminal (Terminal E) on the 1771-OAD module was an optional connection, but it is required for the 1756-OA16. This
connection must be added if it was not connected.
 The 1771-OAD is rated 10V to 138V AC. The 1756-OA16 is rated 74V to 256V AC.
 Refer to your 1771-OAD and 1756-OA16 Installation Manual wiring schematics and diagrams for more details. Ensure 1756 output
module ratings are not exceeded. [Reference Doc: 41170-935 (Version 01)]

Visit our website: www.ab.com


48 Publication 1492-SG121D-EN-P
Bulletin 1492
Bulletin 1771 to 1756 I/O Wiring Conversion System
Wiring Diagrams- Digital

Cat No. 1771-OAN to 1756-OA16 (Qty. 2)

WARNING There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and input module). Read and understand these
considerations before installation.
Conversion Module
1492-CM1771-LD013
Cable
L1 1 1492-CONCAB005S3 1756-OA16
L1
L1 11
L2 10 1 Black 10
L2 L1-0
L2 20 2 White 9
L2-0
Output 00 2 3 Red 1
OUT-0
Output 01 3 4 Green 2
OUT-1
Output Output 02 4 5 Orange 3
OUT-2
Device Output 03 5 6 Blue 4
OUT-3

MODULE A
Output 04 6 7 White/Black 5
OUT-4
Output 05 7 8 Red/Black 6
OUT-5
Output 06 8 9 Green/Black 7
OUT-6
Output 07 9 10 Orange/Black 8
11 OUT-7
Output 10 12 Blue/Black 11
12 OUT-8
Output 11 13 Black/White 12
13 OUT-9
Output 12 14 Red/White 13
14 OUT-10
Output 13 15 Green/White 14
15 OUT-11
Output 14 16 Blue/White 15
16 OUT-12
Output 15 17 Black/Red 16
17 OUT-13
Output 16 18 White/Red 17
OUT-14
Output 17 19 18 Orange/Red 18
OUT-15
19 Blue/Red 20
L1-1
19
L2-1
L1 21
L1 31 1756-OA16
L2 30 20 Red/Green 10 L1-0
L2 40 21 Orange/Green 9 L2-0
Output 00 22 22 Black/White/Red 1 OUT-0
Output 01 23 23 White/Black/Red 2 OUT-1
Output 02 24 24 Red/Black/White 3 OUT-2
Output 03 25 25 Green/Black/White 4 OUT-3
5

MODULE B
Output 04 26 26 Orange/Black/White OUT-4
Output 05 27 27 Blue/Black/White 6 OUT-5
Output 06 28 28 Black/Red/Green 7 OUT-6
Output 07 29 29 White/Red/Green 8 OUT-7
Output 10 32 30 Red/Black/Green 11 OUT-8
Output 11 33 31 Green/Black/Orange 12 OUT-9
Output 12 34 32 Orange/Black/Green 13 OUT-10
Output 13 35 33 Blue/White/Orange 14 OUT-11
Output 14 36 34 Black/White/Orange 15 OUT-12
Output 15 37 35 White/Red/Orange 16 OUT-13
Output 16 38 36 Orange/White/Blue 17 OUT-14
Output 17 39 37 White/Red/Blue 18 OUT-15
20 L1-1
19 L2-1
1771-WN Swing Arm
From 1771-OAN

Conversion Module Installation and Application Considerations


 This Bul. 1492 cable consists of a cable wired to two 1756-OA16 RTB. Recommended cable lengths of 0.5M or 1.0M (005=0.5M,
010=1.0M). See table 2 for other lengths.
 The 1771-OAN module output current limits versus 1756-OA16 limits are as follows:
1771-OAN 1756-OA16 w/ 1492-CONCAB005S3
a) Current/Point 1A 0.5A
b) Current/Module 8A (32 pts) 2A (16 pts)
c) Surge Current/Point 10A for 25ms 5A for 43ms
 The 1771-OAN has 4 groups (allowing 4 separate power supplies). This module/cable combination ties all 4 groups from the 1771-OAN
together. Field wiring modification must be made to accommodate this if mulitple supplies were used. If more than 1 supply was used, all but
1 of the power supplies must be removed.
 The 1771-OAN did not allow connections for L2, however the 1756-OA16 requires an L2 connection for proper operation. The 1771-OAN
did not use terminals 10, 20, 30, 40. These terminals have been reassigned for an L2 connection in this application. The installer must
rewire L2 to one of these terminals.
 Refer to your 1771-OAN and 1756-OA16 Installation Manual wiring schematics and diagrams for more details. Ensure 1756 output
module ratings are not exceeded.
 This configuration uses two (2) 1756-OA16 output modules to replace a single 1771-OAN output module. This may require the use of a
larger 1756 I/O chassis and conversion mounting assembly. Ensure there is sufficient panel space to allow for this possibility.
[Reference Doc: 41170-942 (Version 02)]

Visit our website: www.ab.com


Publication 1492-SG121D-EN-P 49
Bulletin 1492
Bulletin 1771 to 1756 I/O Wiring Conversion System
Wiring Diagrams - Digital

Cat No. 1771-OB (Qty. 2) to 1756-OB16D

WARNING There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module
1492-CM1771-LD014 Cable
1492-C005005XF 1756-OB16D
1 Black CABLE”A”
L1 A 2 White 16
GND-0
Output 00 0 3 Red 1
OUT-0
Output 01 1 4 Green 3
OUT-1
Output 02 2 5 Orange 5
OUT-2
Output 03 3 6 Blue 7
OUT-3
7 White/Black 2
+DC-0
8 Red/Black 4
+DC-0
9 Green/Black 6
+ +DC-0
10 Orange/Black 8
+DC-0
11 Blue/Black 10
- +DC-0
12 Black/White 12
+DC-0
13 Red/White 14
+DC-0
14 Green/White
Output 04 4 15 Blue/White 9
LOAD OUT-4
Output 05 5 16 Black/Red 11
OUT-5
Output 06 6 17 White/Red 13
OUT-6
Output 07 7 18 Orange/Red 15
OUT-7
L2 B 19 Blue/Red 16
GND-0
20 Red/Green

21 NOT USED
22
23 CABLE”B”
24
32
1771-WA Swing Arm 25
17
GND-1
OUT-8
19
From 1771-OB Conversion Module 21
OUT-9
OUT-10
23
1492-CM1771-LD014 18
OUT-11
+DC-1
20
+DC-1
1 Black 22
+DC-1
L1 A 2 White 24
+DC-1
Output 00 0 3 Red 26
+DC-1
Output 01 1 4 Green 28
+DC-1
Output 02 2 5 Orange 30
25 +DC-1
Output 03 3 6 Blue
OUT-12
7 White/Black 27
OUT-13
8 Red/Black 29
OUT-14
9 Green/Black 31
+ OUT-15
10 Orange/Black 32
34 GND-1
11 Blue/Black
GND-1
- 33
12 Black/White
NOT USED
13 Red/White 35
36 NOT USED
14 Green/White
ONT USED
Output 04 4 15 Blue/White
LOAD
Output 05 5 16 Black/Red
Output 06 6 17 White/Red
Output 07 7 18 Orange/Red

L2 B 19 Blue/Red
20 Red/Green

21
22
23
24
1771-WA Swing Arm 25

From 1771-OB

Conversion Module Installation and Application Considerations


 This Bul. 1492 cable consists of 2 separate cables (cable “A” and cable “B”) wired to one 1756-OB16D RTB. Each cable can be either
0.5M or 1.0M (005=0.5M, 010=1.0M). Ensure that cable A and cable B are connected to the correct module in the conversion.
 The 1771-OB module output current limits versus 1756-OB16D limits are as follows:
1771-OB 1756-OB16D w/ 1492-C005005XF
a) Current/Point 1.5A 2A
b) Current/Module 6A 4A @ 60°C
c) Surge Current/Point 4A for 8.3ms 4A for 10ms
 The 1771-OB has eight (8) 2A, 250V fuses - 1 per output. The 1756-OB16D is a DIAGNOSTIC MODULE. Refer to the 1756-OB16D
Installation Manual for details on diagnostics.
 Refer to your 1771-OB and 1756-OB16D Installation Manual wiring schematics and diagrams for more details. Ensure 1756 output
module ratings are not exceeded. [Reference Doc: 41170-988 (Version 00)]

Visit our website: www.ab.com


50 Publication 1492-SG121D-EN-P
Bulletin 1492
Bulletin 1771 to 1756 I/O Wiring Conversion System
Wiring Diagrams- Digital

Cat No. 1771-OBD to 1756-OB16E

WARNING There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module
1492-CM1771-LD006
Cable
+ dc A 1492-CONCAB005X 1756-OB16E
+ dc B
+ dc C 1 Black 10
DC-0+
+ dc D 2 White 9
RTN OUT-0
Output 00 00 3 Red 1
OUT-0
Output 01 01 4 Green 2
OUT-1
+ Output 02 02 5 Orange 3
OUT-2
Output 03 03 6 Blue 4
- OUT-3
Output 04 04 7 White/Black 5
OUT-4
Output 05 05 8 Red/Black 6
OUT-5
Output 06 06 9 Green/Black 7
OUT-6
Output 07 07 10 Orange/Black 8
OUT-7
- dc Output + Output 10 10 11 Blue/Black 11
OUT-8
Device Output 11 11 12 Black/White 12
OUT-9
Output 12 12 13 Red/White 13
OUT-10
Output 13 13 14 Green/White 14
OUT-11
Output 14 14 15 Blue/White 15
OUT-12
Output 15 15 16 Black/Red 16
OUT-13
Output 16 16 17 White/Red 17
OUT-14
Output 17 17 18 Orange/Red 18
OUT-15
19 Blue/Red 20
L2 DC-1+
E 20 Red/Green 19
RTN OUT-1
21
22
23
24
25

1771-WH, WHF, WHFB Swing Arm


From 1771-OBD

Conversion Module Installation and Application Considerations


 This Bul. 1492 cable consists of a cable wired to one 1756-OA16 RTB. Recommended cable lengths of 0.5M or 1.0M (005=0.5M,
010=1.0M). See table 2 for other lengths.
 The 1771-OBD module output current limits versus 1756-OB16E limits are as follows:
1771-OBD 1756-OB16E w/ 1492-CONCAB005X
a) Current/Point 2A 1A
b) Current/Module 8A 4A
c) Surge Current/point 4A for 10ms 2A for 10ms
 The 1771-OBD has a single 10A, 250V rectifier fuse (1/4 x 1 1/4 inch). The 1756-OB16E is electronically fused per
group. Refer to the 1756-OB16E Installation Manual for details on electronic fusing.
 The 1771-OBD is rated 10V to 60V DC. The 1756-OB16E is rated 10V to 31.2V DC. If the load source voltage is greater than 30V
DC, then use the 1756-OC8 with the 1492-CM1771-LD008F conversion module.
 Refer to your 1771-OBD and 1756-OB16E Installation Manual wiring schematics and diagrams for more details. Ensure 1756 output
module ratings are not exceeded. [Reference Doc: 41170-936 (Version 01)]

Visit our website: www.ab.com


Publication 1492-SG121D-EN-P 51
Bulletin 1492
Bulletin 1771 to 1756 I/O Wiring Conversion System
Wiring Diagrams - Digital

Cat No. 1771-OBD to 1756-OC8 (Qty. 2)

WARNING There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module Cable


1492-CM1771-LD008F 1492-CONCAB005S1 1756-OC8
1 Black 2 DC-0(+)
2 White 1 OUT-0
3 Red 3 OUT-1
4 Green 5 OUT-2
5 Orange 7 OUT-3
9 RTN OUT-0
6 Blue 4 DC-0(+)

MODULE A
7 White/Black 6 DC-0(+)
8 Red/Black 8 DC-0(+)
9 Green/Black 10 RTN OUT-0
DC(+) A 10 Orange/Black 12 DC-1(+)
DC(+) B 11 Blue/Black 14 DC-1(+)
DC(+) C 12 Black/White 16 DC-1(+)
DC(+) D 13 Red/White 18
+ DC-1(+)
Output 00 00 14 Green/White 11 OUT-4
Output 01 01 15 Blue/White 13 OUT-5
-
Output 02 02 16 Black/Red 15 OUT-6
Output 03 03 17 White/Red 17 OUT-7
Output 04 04 19
LOAD RTN OUT-1
Output 05 05 18 Orange/Red 20 RTN OUT-1
Output 06 06
Output 07 07 1756-OC8
Output 10 10 19 Blue/Red 2 DC-0(+)
Output 11 11 20 Red/Green 1 OUT-0
Output 12 12 21 Orange/Green 3 OUT-1
Output 13 13 22 Black/White/Red 5 OUT-2
Output 14 14 23 White/Black/Red 7 OUT-3
Output 15 15 9 RTN OUT-0

MODULE B
Output 16 16 24 Red/Black/White 4
DC-0(+)
Output 17 17 25 Green/Black/White 6
DC-0(+)
26 Orange/Black/White 8
DC(-) DC-0(+)
E 27 Blue/Black/White 10
RTN OUT-0
28 Black/Red/Green 12
DC-1(+)
29 White/Red/Green 14
DC-1(+)
30 Red/Black/Green 16
DC-1(+)
31 Green/Black/Orange 18
1771-WH, WHF, WHFB Swing Arm DC-1(+)
32 Orange/Black/Green 11
From 1771-OBD OUT-4
33 Blue/White/Orange 13
OUT-5
34 Black/White/Orange 15
OUT-6
35 White/Red/Orange 17
OUT-7
36 19
RTN OUT-1
37 White/Red/Blue 20
RTN OUT-1

Conversion Module Installation and Application Considerations


 This Bul. 1492 cable consists of a cable wired to two 1756-OC8 RTB. Recommended cable lengths of 0.5M or 1.0M (005=0.5M,
010=1.0M). See table 2 for other lengths.
 The 1771-OBD module output current limits versus 1756-OC8 limits are as follows:
1771-OBD 1756-OC8 w/ 1492-CONCAB005S1
a) Current/Point 2A 2A
b) Current /Module 8A 8A
c) Surge Current /Point 4A for 10ms 4A for 10ms
 The 1771-OBD has a single 10A, 250V rectifier fuse (1/4 x 1 1/4 inch ). The 1756-OC8 is NOT fused ,as such a
2AG fuse clip and 10A fuse is provided on the 1492-CM1771-LD008F conversion module.
 The 1771-OBD is rated 10V to 60V DC. The 1756-OC8 is rated 30V to 60V DC. If the load source voltages is less
than 30V DC, then use 1756-OB16E with the 1492-CM1771-LD006 conversion module.
 This configuration uses two(2) 1756-OC8 output modules to replace a single 1771-OBD output module. This may require
the use of a larger 1756 I/O chassis and conversion mounting assembly. Ensure there is sufficient panel space to allow for
this possibility.
 Refer to your 1771-OBD and 1756-OC8 Installation Manual wiring schematics and diagrams for more details. Ensure
1756 output module ratings are not exceeded. [Reference Doc: 41170-937 (Version 01)]

Visit our website: www.ab.com


52 Publication 1492-SG121D-EN-P
Bulletin 1492
Bulletin 1771 to 1756 I/O Wiring Conversion System
Wiring Diagrams- Digital

Cat No. 1771-OBDS to 1756-OB16E

WARNING There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module
1492-CM1771-LD006
Cable
+ dc A 1492-CONCAB005X 1756-OB16E
+ dc B
+ dc C 1 Black 10
DC-0+
+ dc D 2 White 9
RTN OUT-0
Output 00 00 3 Red 1
OUT-0
Output 01 01 4 Green 2
OUT-1
Output 02 02 5 Orange 3
+ OUT-2
Output 03 03 6 Blue 4
OUT-3
- Output 04 04 7 White/Black 5
OUT-4
Output 05 05 8 Red/Black 6
OUT-5
Output 06 06 9 Green/Black 7
OUT-6
Output 07 07 10 Orange/Black 8
- + OUT-7
dc Output Output 10 10 11 Blue/Black 11
Device OUT-8
Output 11 11 12 Black/White 12
OUT-9
Output 12 12 13 Red/White 13
OUT-10
Output 13 13 14 Green/White 14
OUT-11
Output 14 14 15 Blue/White 15
OUT-12
Output 15 15 16 Black/Red 16
OUT-13
Output 16 16 17 White/Red 17
OUT-14
Output 17 17 18 Orange/Red 18
OUT-15
19 Blue/Red 20
DC-1+
- dc E 20 Red/Green 19
RTN OUT-1
21
22
23
24
25

1771-WH, WHF, WHFB Swing Arm


From 1171-OBDS

Conversion Module Installation and Application Considerations


 This Bul. 1492 cable consists of a cable wired to one 1756-OB16E RTB. Recommended cable lengths of 0.5M or 1.0M
(005=0.5M, 010=1.0M). See table 2 for other lengths.
 The 1771-OBDS module output current limits versus 1756-OB16E limits are as follows:
1771-OBDS 1756-OB16E w/ 1492-CONCAB005X
a) Current/Point 1A 1A
b) Current/Module 8A 8A
c) Surge Current/Point 4A for 10ms 2A for 10ms
 The 1771-OBDS has a single 12A, 250V rectifier fuse (1/4 x 1-1/4 inch). The 1756-OB16E is electronically fused per
group. Refer to the 1756-OB16E Installation Manual for details on electronic fusing.
 The 1771-OBDS is rated 10V to 40V DC. The 1756-OB16E is rated 10V to 31.2V DC. If the load source voltage is greater
than 30V DC, then use the 1756-OC8 with the 1492-CM1771-LD008F conversion module.
 Refer to your 1771-OBDS and 1756-OB16E Installation Manual wiring schematics and diagrams for more details. Ensure
1756 output module ratings are not exceeded. [Reference Doc: 41171-005 (Version 00)]

Visit our website: www.ab.com


Publication 1492-SG121D-EN-P 53
Bulletin 1492
Bulletin 1771 to 1756 I/O Wiring Conversion System
Wiring Diagrams - Digital

Cat No. 1771-OBN to 1756-OB32

WARNING There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module Cable


1492-CM1771-LD009F 1492-CONCAB005Z 1756-OB32
10-30V dc(0) 1
10-30V dc(1) 11 1 Black 18 DC-0(+)
10-30V dc(2) 21 2 White 36 DC-1(+)
10-30V dc(3) 31 3 Red
Output 00 2 4 Green 1 OUT-0
Output 00 22 5 Orange 19 OUT-16
Output 01 3 6 Blue 2 OUT-1
Output 01 23 7 White/Black 20 OUT-17
Output 02 4 8 Red/Black 3 OUT-2
Output 02 24 9 Green/Black 21 OUT-18
Output 03 5 10 Orange/Black 4
+ OUT-3
Output 03 25 11 Blue/Black 22 OUT-19
- Output 04 6 12 Black/White 5 OUT-4
Output 04 26 13 Red/White 23 OUT-20
Output 05 7 14 Green/White 6
LOAD OUT-5
Output 05 27 15 Blue/White 24 OUT-21
Output 06 8 16 Black/Red 7 OUT-6
Output 06 28 17 White/Red 25 OUT-22
Output 07 9 18 Orange/Red 8 OUT-7
Output 07 29 19 Blue/Red 26 OUT-23
Output 10 12 20 Red/Green 9 OUT-8
Output 10 32 21 Orange/Green 27
22
OUT-24
Output 11 13 Black/White/Red 10 OUT-9
Output 11 33 23 White/Black/Red 28 OUT-25
Output 12 14 24 Red/Black/White 11 OUT-10
Output 12 34 25 Green/Black/White 29
OUT-26
Output 13 15 26 Orange/Black/White 12
OUT-11
Output 13 35 27 Blue/Black/White 30
OUT-27
Output 14 16 28 Black/Red/Green 13
OUT-12
Output 14 36 29 White/Red/Orange 31
OUT-28
Output 15 17 30 Red/Black/Green 14
OUT-13
Output 15 37 31 Green/Black/Orange 32
OUT-29
Output 16 18 32 Orange/Black/Green 15
OUT-14
Output 16 38 33 Blue/White/Orange 33
OUT-30
Output 17 19 34 Black/White/Orange 16
OUT-15
Output 17 39 35 White/Red/Orange 34
OUT-31
Common 0 10 36 Orange/White/Blue 17
RTN OUT-0
Common 1 20 37 White/Red/Blue 35
RTN OUT-1
Common 2 30
Common 3 40

1771-WN Swing Arm


From 1771-OBN

Conversion Module Installation and Application Considerations


The 1771-OBN module output current limits versus 1756-OB32 limits are as follows:
1771-OBN 1756-OB32w/1492-CONCAB005Z
a) Current/Point 0.5A 0.35A @ 60˚C
b) Current/Module 8A 6A @ 60˚C
c) Surge Current/Point 2A for 10ms 1A for 10ms
 The 1771-OBN has four (4) 4A, 250V rectifier fuses. The 1756-OB32 is NOT fused, as such four (4) 2AG fuse clips and 4A
fuses are provided on the 1492-CM1771-LD009F conversion module.
 The 1492-CONAB005Z is limited to 3A per pin.
 The 1771-OBN has 4 groups (allowing 4 separate power supplies) and the 1756-OB32 has 2 groups. This module/cable
combination ties Groups 0 & 1 from the 1771-OBN to Group 0 on the 1756-OB32 and Groups 2 & 3 from the 1771-OBN to
Group 1 on the 1756-OB32. Field wiring modification must be made to accommodate this if multiple supplies were used.
If 4 supplies were used, 2 must be removed.
 Refer to your 1771-OBN and 1756-OB32 Installation Manual wiring schematics and diagrams for more details. Ensure
1756 output module ratings are not exceeded. [Reference Doc: 41170-938 (Version 01)]

Visit our website: www.ab.com


54 Publication 1492-SG121D-EN-P
Bulletin 1492
Bulletin 1771 to 1756 I/O Wiring Conversion System
Wiring Diagrams- Digital

Cat No. 1771-OC to 1756-OC8

WARNING There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module
1492-CM1771-LD014
Cable
1492-CONCAB005V 1756-OC8
1 Black 9
RTN-0
+DC A 2 White 10
RTN-0
Output 00 0 3 Red 1
OUT-0
Output 01 1 4 Green 3
OUT-1
Output 02 2 5 Orange 5
OUT-2
Output 03 3 6 Blue 7
OUT-3
7 White/Black 2
+DC-0
8 Red/Black 4
+DC-0
9 Green/Black 6
+DC +DC-0
10 Orange/Black 8
+DC-0
11 Blue/Black 12
+DC-1
-DC 12 Black/White 14
+DC-1
13 Red/White 16
+DC-1
14 Green/White 18
+DC-1
Output 04 4 15 Blue/White 11
LOAD OUT-4
Output 05 5 16 Black/Red 13
OUT-5
Output 06 6 17 White/Red 15
OUT-6
Output 07 7 18 Orange/Red 17
OUT-7
RTN B 19 Blue/Red 19
RTN-1
20 Red/Green 20
RTN-1
21
22
23
24
25

1771-WA Swing Arm


From 1771-OC

Conversion Module Installation and Application Considerations


 This Bul. 1492 cable consists of a cable wired to one 1756-OC8 RTB. Recommended cable lengths of 0.5M or 1.0M (005=0.5M,
010=1.0M). See table 2 for other lengths.
 The 1771-OC module output current limits versus 1756-OC8 limits are as follows:
1771-OC 1756-OC8 w/ 1492-CONCAB005V
a) Current/Point 1.5A 2A
b) Current/Module 8A 8A @ 60°C
c) Surge Current/Point 4A for 1.0ms 4A for 10ms
 The 1771-OC has eight (8) 2A, 250V fuses - 1 per output. Refer to the 1756-OC8 Installation Manual for details.
 Refer to your 1771-OC and 1756-OC8 Installation Manual wiring schematics and diagrams for more details. Ensure 1756 output module
ratings are not exceeded. [Reference Doc: 41171-020 (Version 00)]

Visit our website: www.ab.com


Publication 1492-SG121D-EN-P 55
Bulletin 1492
Bulletin 1771 to 1756 I/O Wiring Conversion System
Wiring Diagrams - Digital

Cat No. 1771-OD (Qty. 2) to 1756-OA16I

There are several key application considerations and system specifications (bottom of drawing) when using
WARNING
these components (conversion module, cable and output module). Read and understand these considerations
before installation. In addition, refer to the current draw requirements of the existing loads for this configuration
to ensure they are within the current ratings of the 1756 output module.
CONVERSION MODULE
1492-CM1771-LD012
1
1
2 1492-C005005XM
3
4
1756-OA16I
5
4
JMP0
3 6
Orange
Blue
CABLE”A” 2
L1-0
N.C. 7 White/Black 1
L2-0
N.O. 8 Red/Black 4
L1-1
2 1 9 Green/Black 3
JMP1 L2-1
4 3 10 Orange/Black 6
L1-2
N.C. 11 Blue/Black 5
L2-2
N.O. 12 Black/White 8
L1-3
2 1 13 Red/White 7
JMP2 L2-3
3 14 Green/White 10
4 L1-4
L2 L1 N.C. 15 Blue/White 9
L1-0 1 L2-4
LOAD N.O. 16 Black/Red 12
L2-0 L1-5
2 2 1 17 White/Red 11
L1-1 L2-5
3 JMP3 18
4 3 Orange/Red
L2-1 4 25 NOT USED
N.C. 19 Blue/Red
L1-2 5 26 NOT USED
N.O. 20 Red/Green
L2-2 6 2 27 NOT USED
1 21 Orange/Green
L1-3 7 JMP4 28 NOT USED
4 3 22 Black/White/Red
L2-3 8 29 NOT USED
N.C. 23 White/Black/Red
L1-4 9 30 NOT USED
N.O. 24 Red/Black/White
L2-4 10 2 1 31 NOT USED
25 Green/Black/White
L1-5 11 JMP5 32 NOT USED
4 3 26 Orange/Black/White
L2-5 12 33 NOT USED
N.C. 27 Blue/Black/White
34 NOT USED
N.O. 28 Black/Red/Green
NOT USED
35
2
4
JMP6
1
3
29
30
White/Red/Green
Red/Black/Green
CABLE”B” 36 NOT USED
14
N.C. 31 Green/Black/Orange L1-6
13
N.O. 32 Orange/Black/Green L2-6
2 1 16
33 Blue/White/Orange L1-7
JMP7 15
3 34 Black/White/Orange L2-7
1771-WD Swing Arm 4
N.C. 35 White/Red/Orange
18 L1-8
17
From 1771-OD N.O. 36 Orange/White/Blue
20
L2-8
2 1 37 L1-9
19
L2-9
CONVERSION MODULE 22
L1-10
1492-CM1771-LD012 21
24
L2-10
L1-11
1 23 L2-11
2
3
4
5 Orange
JMP0 6
4 3 Blue
N.C. 7 White/Black
N.O. 8 Red/Black
2 1 9 Green/Black
JMP1 10
4 3 Orange/Black
N.C. 11 Blue/Black
N.O. 12 Black/White
2 1 13 Red/White
JMP2 14 Green/White
4 3
L1-6 N.C. 15 Blue/White
1
L2-6 N.O. 16 Black/Red
2 2 1 17 White/Red
L1-7 3 JMP3
4 3 18 Orange/Red
L2-7 4 N.C. 19 Blue/Red
L1-8 5
N.O. 20 Red/Green
L2-8 6 2 1 21 Orange/Green
L1-9 7 JMP4
L2-9 4 3 22 Black/White/Red
8 N.C. 23 White/Black/Red
L1-10 9
N.O. 24 Red/Black/White
L2-10 10 2 1
L2 L1 25 Green/Black/White
L1-11 11 JMP5
LOAD 4 3 26 Orange/Black/White
L2-11 12
N.C. 27 Blue/Black/White
N.O. 28 Black/Red/Green
2 1 29 White/Red/Green
JMP6 30
4 3 Red/Black/Green
N.C. 31 Green/Black/Orange
N.O. 32 Orange/Black/Green
2 1 33 Blue/White/Orange
JMP7 34 Black/White/Orange
4 3
N.C. 35 White/Red/Orange
N.O. 36 Orange/White/Blue

1771-WD Swing Arm 2 1 37

From 1771-OD

CONVERSION MODULE INSTALLATION AND APPLICATION CONSIDERATIONS


1 This Bul. 1492 cable consists of 2 separate cables (cable “A” and “B”) wired to one 1756-IM16I RTB. Each cable can be either
0.5M or 1.0M (005=0.5M, 010=1.0M). Ensure that cable A and cable B are connected to the correct module in the conversion.
2 The 1771-OD module output resistive current limits versus 1756-OA16I limits are as follows:
(NOTE: for switching and inductive current ratings, refer to the modules Installation Instructions)
1771-OD 1756-OA16I w/ 1492-CONCAB005XM
a) Current/Point 0.2A @ 138V AC 2A @ 240V AC
1A @ 30V DC 2A @ 30V DC
0.25A@ 125V DC 0.25A @ 125V DC
2 The 1492-COO5005XM is limited to 3A per pin.
3 The 1771-OD module had a jumper selection of N.O. and N.C. outputs. The 1756-OA16I has both N.O. and N.C. outputs, but
selection is by wiring termination on the 1756 swing arm. The 1492-CM1771-LD012 conversion module replaces the functionality
of the 1771-OD jumpers with eight jumpers (JMP0 through JMP7). In the default position, the output will be N.O.. If a N.C. output is
required, change the jumper from pins 1-2 to pins 3-4.
4 Refer to your 1771-OD and 1756-OA16I Installation Manual wiring schematics and diagrams for more details. Ensure
1756 output module ratings are not exceeded. 41170-994 (01)

Visit our website: www.ab.com


56 Publication 1492-SG121D-EN-P
Bulletin 1492
Bulletin 1771 to 1756 I/O Wiring Conversion System
Wiring Diagrams- Digital

Cat No. 1771-OD16 to 1756-OA16I

WARNING There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module
1492-CM1771-LD010F

NotUsed 9 1
NotUsed 10 2 Cable
NotUsed 19 3 1492-CONCAB005Y 1756-OA16I
NotUsed 20 4
L1-0 2 5 Orange 2
L1-0
Output 0 1 6 Blue 1
L1 LOAD OUT-0
L1-1 4 7 White/Black 4
L1-1
Output 1 3 8 Red/Black 3
OUT-1
L1-2 6 9 Green/Black 6
L2 L1-2
Output 2 5 10 Orange/Black 5
OUT-2
L1-3 8 11 Blue/Black 8
L1-3
Output 3 7 12 Black/White 7
OUT-3
L1-4 12 13 Red/White 10
L1-4
Output 4 11 14 Green/White 9
OUT-4
L1-5 14 15 Blue/White 12
L1-5
Output 5 13 16 Black/Red 11
OUT-5
L1-6 16 17 White/Red 14
L1-6
Output 6 15 18 Orange/Red 13
OUT-6
L1-7 18 19 Blue/Red 16
L1-7
Output 7 17 20 Red/Green 15
OUT-7
L1-8 22 21 Orange/Green 18
L1-8
Output 8 21 22 Black/White/Red 17
OUT-8
L1-9 24 23 White/Black/Red 20
L1-9
Output 9 23 24 Red/Black/White 19
OUT-9
L1-10 26 25 Green/Black/White 22
L1-10
Output 10 25 26 Orange/Black/White 21
OUT-10
L1-11 28 27 Blue/Black/White 24
L1-11
Output 11 27 28 Black/Red/Green 23
OUT-11
L1-12 32 29 White/Red/Green 26
L1-12
Output 12 31 30 Red/Black/Green 25
OUT-12
L1-13 34 31 Green/Black/Orange 28
L1-13
Output 13 33 32 Orange/Black/Green 27
OUT-13
L1-14 36 33 Blue/White/Orange 30
L1-14
Output 14 35 34 Black/White/Orange 29
OUT-14
L1-15 38 35 White/Red/Orange 32
L1-15
Output 15 37 36 Orange/White/Blue 31
OUT-15
Not used 29 37
Not used 30
Not used 39
Not used 40

1771-WN Swing Arm


From 1771-OD16

Conversion Module Installation and Application Considerations


 This Bul. 1492 cable consists of a cable wired to one 1756-OA16I RTB. Recommended cable lengths of 0.5M or 1.0M
(005=0.5M, 010=1.0M). See table 2 for other lengths.
 The 1771-OD16 module output current limits versus 1756-OA16I limits are as follows:
1771-OD16 1756-OA16I w/ 1492-CONCAB005Y
a) Current/Point 2A 1A
b) Current/Module 8A 4A
b) Surge Current/Point 20A for 100ms 20A for 43ms
 The 1771-OD16 has sixteen (16) 3A ,250V recifier fuses.
The 1756-OA16I is NOT fused,as such sixteen (16) 2AG fuse
clips are provided on the 1492-CM1771-LD010F conversion module. Max fuse rating is 1.5A based on 1756-OA16I.
 The 1771-OD16 is rated 74V to 138V AC and 105V to 138V DC. The 1756-OA16I is rated 74V to 265V AC. A1756 isolated
output module with an equivalent DC voltage range to convert the1771 -OD16 is not available.
 Refer to your 1771-OD16 and 1756-OA16I Installation Manual wiring schematics and diagrams for more details. Ensure 1756
output module rating are not exceeded. [Reference Doc: 41170-939 (Version 01)]

Visit our website: www.ab.com


Publication 1492-SG121D-EN-P 57
Bulletin 1492
Bulletin 1771 to 1756 I/O Wiring Conversion System
Wiring Diagrams - Digital

Cat No. 1771-ODD to 1756-OA16I

WARNING There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module
1492-CM1771-LD010F

Not Used 9 1
Not Used 10 2 Cable
Not Used 19 3 1492-CONCAB005Y 1756-OA16I
Not Used 20 4
L1-0 2 5 Orange 2
L1-0
Ouput 0 1 6 Blue 1
L1 LOAD OUT-0
L1-1 4 7 White/Black 4
L1-1
Ouput 1 3 8 Red/Black 3
OUT-1
L2 L1-2 6 9 Green/Black 6
L1-2
Ouput 2 5 10 Orange/Black 5
OUT-2
L1-3 8 11 Blue/Black 8
L1-3
Ouput 3 7 12 Black/White 7
OUT-3
L1-4 12 13 Red/White 10
L1-4
Ouput 4 11 14 Green/White 9
OUT-4
L1-5 14 15 Blue/White 12
L1-5
Ouput 5 13 16 Black/Red 11
OUT-5
L1-6 16 17 White/Red 14
L1-6
Ouput 6 15 18 Orange/Red 13
OUT-6
L1-7 18 19 Blue/Red 16
L1-7
Ouput 7 17 20 Red/Green 15
OUT-7
L1-8 22 21 Orange/Green 18
L1-8
Ouput 8 21 22 Black/White/Red 17
OUT-8
L1-9 24 23 White/Black/Red 20
L1-9
Ouput 9 23 24 Red/Black/White 19
OUT-9
L1-10 26 25 Green/Black/White 22
L1-10
Ouput 10 25 26 Orange/Black/White 21
OUT-10
L1-11 28 27 Blue/Black/White 24
L1-11
Ouput 11 27 28 Black/Red/Green 23
OUT-11
L1-12 32 29 White/Red/Green 26
L1-12
Ouput 12 31 30 Red/Black/Green 25
OUT-12
L1-13 34 31 Green/Black/Orange 28
L1-13
Ouput 13 33 32 Orange/Black/Green 27
OUT-13
L1-14 36 33 Blue/White/Orange 30
L1-14
Ouput 14 35 34 Black/White/Orange 29
OUT-14
L1-15 38 35 White/Red/Orange 32
L1-15
Ouput 15 37 36 Orange/White/Blue 31
OUT-15
Not Used 29 37
Not Used 30
Not Used 39
Not Used 40

1771-WN Swing Arm


From 1771-ODD

Conversion Module Installation and Application Considerations


 This Bul. 1492 cable consists of a cable wired to one 1756-OA16I RTB. Recommended cable lengths of 0.5M or 1.0M
(005=0.5M, 010=1.0M). See table 2 for other lengths.
 The 1771-ODD module output current limits versus 1756-OA16I limits are as follows:
1771-ODD 1756-OA16I w/ 1492-CONCAB005Y
a) Current/Point 2A 2A
b) Current/Module 8A 5A
c) Surge Current/Point 20A for 100ms 20A for 43ms
 The 1771-ODD has sixteen (16) 3A, 250V rectifier fuses.
The 1756-OA16I is NOT fused, as such sixteen(16) 2AG fuses
and clips are provided on the 1492-CM1771-LD010F conversion module. Max fuse rating is 1.5A based on 1756-OA16I.
 The 1771-ODD is rated 74V to 138V AC. The 1756-OA16I is rated 74V to 265V AC.
 Refer to your 1771-ODD and 1756-OA16I Installation Manual wiring schematics and diagrams for more details. Ensure 1756
output module ratings are not exceeded. [Reference Doc: 41171-009 (Version 00)]

Visit our website: www.ab.com


58 Publication 1492-SG121D-EN-P
Bulletin 1492
Bulletin 1771 to 1756 I/O Wiring Conversion System
Wiring Diagrams- Digital

Cat No. 1771-ODZ (Qty. 2) to 1756-OA16I

WARNING There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module
1492-CM1771-LD012
1
2
Cable
3
4
1492-CONCAB005Y 1492-C005005XP 1756-OA16I
JMP0
5
6
Orange
CABLE”A”
4 3 Blue 2
L1-0
N.C. 7 White/Black 4
L1-0
N.O. 8 Red/Black 1 L2-0
2 1 9 Green/Black 3
JMP1 L2-1
4 3 10 Orange/Black 6 L1-1
N.C. 11 Blue/Black 8
L1-1
N.O. 12 Black/White 5
L2-2
2 1 13 Red/White 7
JMP2 L2-3
4 3 14 Green/White 10
L1-2
Out-0 N.O./N.C. N.C. 15 Blue/White 12
1 L1-2
L1 N.O. 16 Black/Red 9 L2-4
+V0/1 2 2 1 17 White/Red 11 L2-5
Out-1 N.O./N.C. 3 JMP3
L2 LOAD 4 3 18 Orange/Red 14
Out-2 N.O./N.C. 4 L1-3
N.C. 19 Blue/Red 16 L1-3
+V2/3 5
N.O. 20 Red/Green 13 L2-6
Out-3 N.O./N.C. 6 2 1 21 Orange/Green 15
Out-4 N.O./N.C. 7 JMP4 L2-7
+ 4 3 22 Black/White/Red
+V4/5 8 N.C. 23 White/Black/Red
Out-5 N.O./N.C. 9
- LOAD N.O. 24 Red/Black/White
Out-6 N.O./N.C. 10 2 1 25 Green/Black/White
+V6/7 11 JMP5
4 3 26 Orange/Black/White
Out-7 N.O./N.C. 12 27
N.C. Blue/Black/White
N.O. 28 Black/Red/Green
2 1 29 White/Red/Green
JMP6 30
4 3 Red/Black/Green
N.C. 31 Green/Black/Orange
N.O. 32 Orange/Black/Green
2 1 33 Blue/White/Orange
JMP7 34 Black/White/Orange
4 3
N.C. 35
1771-WD Swing Arm N.O. 36
White/Red/Orange
Orange/White/Blue
33
34
NOT USED
NOT USED
2 1 37
From 1771-ODZ 35
36
NOT USED
NOT USED

Conversion Module
1492-CM1771-LD012
1
2
3
4
5
CABLE”B”
Orange
JMP0 6
4 3 Blue 18 L1-4
N.C. 7 White/Black 20
L1-4
N.O. 8 Red/Black 17
2 L2-8
1 9 Green/Black 19
JMP1 10 L2-9
4 3 Orange/Black 22
L1-5
N.C. 11 Blue/Black 24
L1-5
N.O. 12 Black/White 21 L2-10
2 1 13 Red/White 23
JMP2 L2-11
4 3 14 Green/White 26
L1-4
Out-0 N.O./N.C. N.C. 15 Blue/White 28
1 L1-6
L1 N.O. 16 Black/Red 25 L2-12
+V0/1 2 2 1 17 White/Red 27 L2-13
Out-1 N.O./N.C. 3 JMP3
L2 LOAD 4 3 18 Orange/Red 30
Out-2 N.O./N.C. 4 L1-7
N.C. 19 Blue/Red 32
+V2/3 5 L1-7
N.O. 20 Red/Green 29 L2-14
Out-3 N.O./N.C. 6 2 1 21 Orange/Green 31
Out-4 N.O./N.C. 7 JMP4 L2-15
+ 4 3 22 Black/White/Red
+V4/5 8 N.C. 23 White/Black/Red
Out-5 N.O./N.C. 9
- LOAD N.O. 24 Red/Black/White
Out-6 N.O./N.C. 10 2 1 25 Green/Black/White
+V6/7 11 JMP5
4 3 26 Orange/Black/White
Out-7 N.O./N.C. 12
N.C. 27 Blue/Black/White
N.O. 28 Black/Red/Green
2 1 29 White/Red/Green
JMP6 30
4 3 Red/Black/Green
N.C. 31 Green/Black/Orange
N.O. 32 Orange/Black/Green
2 1 33 Blue/White/Orange
JMP7 34 Black/White/Orange
4 3
N.C. 35 White/Red/Orange

1771-WD Swing Arm 2


N.O.
1
36
37
Orange/White/Blue

From 1771-ODZ

Conversion Module Installation and Application Considerations


 This Bul. 1492 cable consists of 2 separate cables (cable “A” and cable “B”) wired to one 1756-OA16I RTB.
Each cable can be either
0.5M or 1.0M (005=0.5M, 010=1.0M). Ensure that cable A and cable B are connected to the correct module in the conversion
 The 1771-ODZ module output resistive current limits versus 1756-OA16I limits are as follows:
1771-ODZ 1756-OA16I w/ 1492-C005005XP
a) Current/Point 2A 2A
b) Current/Module 6A 5A @ 60°C
c) Surge Current/Point 20A for 100ms 20A for 43ms
 The 1771-ODZ module had a jumper selection of N.O. and N.C. outputs. The 1756-OA16I has both N.O. and N.C. outputs, but
selection is by wiring termination on the 1756 swing arm. The 1492-CM1771-LD012 conversion module replaces the functionality
of the 1771-ODZ jumpers with eight jumpers (JMP0 through JMP7). In the default position, the output will be N.O. If a N.C. output is
required, change the jumper from pins 1-2 to pins 3-4.
 Refer to your 1771-ODZ and 1756-OA16I Installation Manual wiring schematics and diagrams for more details. Ensure 1756 output
module ratings are not exceeded. [Reference Doc: 41171-016 (Version 00)]

Visit our website: www.ab.com


Publication 1492-SG121D-EN-P 59
Bulletin 1492
Bulletin 1771 to 1756 I/O Wiring Conversion System
Wiring Diagrams - Digital

Cat No. 1771-OG (Qty. 2) to 1756-OG16

WARNING There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module Cable


1492-CM1771-LA003 1492-C005005XS 1756-OG16
+ + DC A 13 Red/White CABLE”A” 10
+ DC -0
+ Output 0 0 25 Green/Black/White 1
Output OUT-0
5V DC - Output 1 1 24 Red/Black/White 2
- Device OUT-1
SUPPLY Output 2 2 23 White/Black/Red 3
OUT-2
Output 3 3 22 Black/White/Red 4
OUT-3
Output 4 4 21 Orange/Green 5
OUT-4
Output 5 5 19 Blue/Red 6
OUT-5
Output 6 6 18 Orange/Red 7
OUT-6
Output 7 7 17 White/Red 8
Common OUT-7
B 16 Black/Red 9
- DC -0
1 20
+ DC -1
2 11
OUT-8
3 12
OUT-9
4 13
OUT-10
5 14
OUT-11
6 15
OUT-12
7 16
1771-WC Swing Arm 8 17
OUT-13
OUT-14
From 1771-OG 9 18
OUT-15
10 19
11 - DC -1
12
14
15
20

SH

Conversion Module
1492-CM1771-LA003
+ + DC A 13 Red/White
+ Output 8 0 25 Green/Black/White
Output
5V DC - Output 9 1 24 Red/Black/White
- Device Output 10
SUPPLY 2 23 White/Black/Red
Output 11 3 22 Black/White/Red
Output 12 4 21 Orange/Green
Output 13 5 19 Blue/Red
Output 14 6 18 Orange/Red
Output 15 7 17 White/Red
Common B 16 Black/Red
1
2 CABLE”B”
3
4
5
6
7
1771-WC Swing Arm 8
From 1771-OG 9
10
11
12
14
15
20

SH

Conversion Module Installation and Application Considerations


 This Bul. 1492 cable consists of 2 separate cables (cable “A” and cable “B”) wired to one 1756-OG16 RTB.
Each cable can be either 0.5M or
1.0M (005=0.5M, 010=1.0M). Ensure that cable A and cable B are connected to the correct module in the conversion.
 The input delay times for the 1771-OG module versus the 1756-OG16 module are as follows:
1771-OG 1756-OG16 w/ 1492-C005005XS
a) Off-to-On Delay 1ms (+/-10ms) 45ms max (plus selectable filter)
b) On-to-Off Delay 1ms (+/-10ms) 145ms max (plus selectable filter)
 The 1771-OG module is rated 5V DC TTL INPUT MODULE. The 1756-OG16 module is rated 5V DC TTL INPUT MODULE only.
 Refer to your 1771-OG and 1756-OG16 Installation and User Manuals for additional information concerning comparisons of module wiring,
features and configuration details. [Reference Doc: 41171-028 (Version 00)]

Visit our website: www.ab.com


60 Publication 1492-SG121D-EN-P
Bulletin 1492
Bulletin 1771 to 1756 I/O Wiring Conversion System
Wiring Diagrams- Digital

Cat No. 1771-OGD to 1756-OG16

WARNING There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module
1492-CM1771-LD006
Cable
+ dc A 1492-CONCAB005X 1756-OG16
+ dc B
+ dc C 1 Black 10
DC-0+
+ dc D 2 White 9
RTN OUT-0
Output 00 00 3 Red 1
OUT-0
Output 01 01 4 Green 2
OUT-1
Output 02 02 5 Orange 3
+ OUT-2
Output 03 03 6 Blue 4
OUT-3
- Output 04 04 7 White/Black 5
OUT-4
Output 05 05 8 Red/Black 6
OUT-5
Output 06 06 9 Green/Black 7
OUT-6
Output 07 07 10 Orange/Black 8
- + OUT-7
dc Output Output 10 10 11 Blue/Black 11
Device OUT-8
Output 11 11 12 Black/White 12
OUT-9
Output 12 12 13 Red/White 13
OUT-10
Output 13 13 14 Green/White 14
OUT-11
Output 14 14 15 Blue/White 15
OUT-12
Output 15 15 16 Black/Red 16
OUT-13
Output 16 16 17 White/Red 17
OUT-14
Output 17 17 18 Orange/Red 18
OUT-15
19 Blue/Red 20
DC-1+
- dc E 20 Red/Green 19
RTN OUT-1
21
22
23
24
25

1771-WH, WHF, WHFB Swing Arm


From 1171-OGD

Conversion Module Installation and Application Considerations


 This Bul. 1492 cable consists of a cable wired to one 1756-OG16 RTB. Recommended cable lengths of 0.5M or 1.0M
(005=0.5M, 010=1.0M). See table 2 for other lengths.
 The 1771-OGD module output current limits versus 1756-OG16 limits are as follows:
1771-OGD 1756-OG16 w/ 1492-CONCAB005X
a) Current/Point 1mA 24mA
b) Current/Module 310mA 384mA
 The 1771-OGD has a single 10A, 250V rectifier fuse (1/4 x 1-1/4 inch). The 1756-OG16 is electronically fused per
group. Refer to the 1756-OG16 Installation Manual for details on electronic fusing.
 The 1771-OGD is rated 10V to 60V DC. The 1756-OG16 is rated 10V to 31.2V DC.
 Refer to your 1771-OGD and 1756-OG16 Installation Manual wiring schematics and diagrams for more details. Ensure
1756 output module ratings are not exceeded. [Reference Doc: 41171-006 (Version 00)]

Visit our website: www.ab.com


Publication 1492-SG121D-EN-P 61
Bulletin 1492
Bulletin 1771 to 1756 I/O Wiring Conversion System
Wiring Diagrams - Digital

Cat No. 1771-OM (Qty. 2) to 1756-OA16

WARNING There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module
1492-CM1771-LD014 Cable
1492-C005005XG 1756-OA16
1 Black
L1-0 A 2 White Cable “A”
OUTPUT 00 0 3 Red 1
OUT-0
OUTPUT 01 1 4 Green 2
OUT-1
OUTPUT 02 2 5 Orange 3
OUT-2
OUTPUT 03 3 6 Blue 4
OUT-3
7 White/Black 10
L1-0
8 Red/Black
L1 9 Green/Black
+
10 Orange/Black
11 Blue/Black
-
L2 12 Black/White
13 Red/White
14 Green/White
OUTPUT 04 4 15 Blue/White 5
LOAD OUT-4
OUTPUT 05 5 16 Black/Red 6
OUT-5
OUTPUT 06 6 17 White/Red 7
OUT-6
OUTPUT 07 7 18 Orange/Red 8
OUT-7
L2-0 B 19 Blue/Red 9 L2-0
20 Red/Green

21
22
23
24
1771-WA Swing Arm 25 Cable “B”
11
OUT-8
12
From 1771-OM 13
OUT-9
OUT-10
Conversion Module 14
OUT-11
20
1492-CM1771-LD014 L1-1

1 Black
L1-1 A 2 White
INPUT 08 0 3 Red
INPUT 09 1 4 Green
INPUT 10 15
2 5 Orange OUT-12
INPUT 11 16
3 6 Blue OUT-13
17
7 White/Black OUT-14
18
8 Red/Black OUT-15
19
L1 9 Green/Black L2-1
10 Orange/Black
11 Blue/Black

L2 12 Black/White
13 Red/White
14 Green/White
INPUT 12 4 15 Blue/White
LOAD
INPUT 13 5 16 Black/Red
INPUT 14 6 17 White/Red
INPUT 15 7 18 Orange/Red
L2-1 B 19 Blue/Red
20 Red/Green

21
22
23
24
1771-WA Swing Arm 25

From 1771-OM

Conversion Module Installation and Application Considerations


 This Bul. 1492 cable consists of 2 separate cables (cable “A” and cable “B”) wired to one 1756-OA16 RTB. Each cable can be either 0.5M
or 1.0M (005=0.5M, 010=1.0M). Ensure that cable A and cable B are connected to the correct module in the conversion.
 The 1771-OM module output current limits versus 1756-OA16 limits are as follows:
1771-OM 1756-OA16 w/ 1492-CONCAB005XG
a) Current/Point 2A 0.5 @ 60°C
b) Current/Module 6A 4A @ 60°C
c) Surge Current/Point 20A for 100ms 5A for 43ms
 The 1771-OM module is rated 220V to 240V AC. The 1756-OA16 module is rated 74V to 265V AC only.
 Refer to your 1771-OM and 1756-OA16 Installation Manual wiring schematics and diagrams for more details. Ensure 1756 output module
ratings are not exceeded. [Reference Doc: 41171-022 (Version 00)]

Visit our website: www.ab.com


62 Publication 1492-SG121D-EN-P
Bulletin 1492
Bulletin 1771 to 1756 I/O Wiring Conversion System
Wiring Diagrams- Digital

Cat No. 1771-OMD to 1756-OA16

WARNING There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module
1492-CM1771-LD006

Cable
L1 A
1492-CONCAB005X 1756-OA16
L1 B
L1 C 1 Black 10
L1-0+
L1 D 2 White 9
L2-0
Output 00 00 3 Red 1
OUT-0
Output 01 01 4 Green 2
OUT-1
L1 Output 02 02 5 Orange 3
OUT-2
Output 03 03 6 Blue 4
OUT-3
Output 04 04 7 White/Black 5
OUT-4
L2 Output 05 05 8 Red/Black 6
OUT-5
Output 06 06 9 Green/Black 7
OUT-6
Output 07 07 10 Orange/Black 8
- + OUT-7
Output 10 10 11 Blue/Black 11
LOAD OUT-8
Output 11 11 12 Black/White 12
OUT-9
Output 12 12 13 Red/White 13
OUT-10
Output 13 13 14 Green/White 14
OUT-11
Output 14 14 15 Blue/White 15
OUT-12
Output 15 15 16 Black/Red 16
OUT-13
Output 16 16 17 White/Red 17
OUT-14
Output 17 17 18 Orange/Red 18
OUT-15
19 Blue/Red 20
L1-1+
L2 E 20 Red/Green 19
L2-1
21
22
23
24
25

1771-WH, WHF, WHFB Swing Arm


From 1771-OMD

Conversion Module Installation and Application Considerations


 This Bul. 1492 cable consists of a cable wired to one 1756-OA16 RTB. Recommended cable lengths of0.5M or 1.0M
(005=0.5M, 010=1.0M). See table 2 for other lengths.
 The 1771-OMD module output current limits versus 1756-OA16 limits are as follows:
1771-OMD 1756-OA16 w/ 1492-CONCAB005X
a) Current/Point 2A 0.5A
b) Current/Module 8A 4A
c) Surge Current/Point 25A for 100ms 5A for 43ms
 The 1771-OMD has a single 10A, 250V rectifier fuse (1/4 x 1 1/4 inch). The 1756-OA16 has a mechanical 3.15A @250V AC
slow blow fuse. Refer to the 1756-OA16 Installation Manual for details on electronic fusing.
 The 1771-OMD is rated 184V to 250V AC. The 1756-OA16 is rated 74V to 265V AC. If the load source voltage is greater than
30V DC, then use the 1756-OC8 with the 1492-CM1771-LD008F conversion module.
 Refer to your 1771-OMD and 1756-OA16 Installation Manual wiring schematics and diagrams for more details.Ensure 1756
output module ratings are not exceeded. [Reference Doc: 41171-007 (Version 00)]

Visit our website: www.ab.com


Publication 1492-SG121D-EN-P 63
Bulletin 1492
Bulletin 1771 to 1756 I/O Wiring Conversion System
Wiring Diagrams - Digital

Cat No. 1771-ON to 1756-ON8

WARNING There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module
1492-CM1771-LD014
Cable
1492-CONCAB005W 1756-ON8
1 Black 9
NOT USED
L1 A 2 White 2
L1-0
Output 00 0 3 Red 1
OUT-0
Output 01 1 4 Green 3
OUT-1
Output 02 2 5 Orange 5
OUT-2
Output 03 3 6 Blue 7
OUT-3
7 White/Black 4
L1-0
8 Red/Black 6
L1-0
9 Green/Black 8
L1 L1-0
10 Orange/Black 10
L1-0
11 Blue/Black 12
L1-1
L2 12 Black/White 14
L1-1
13 Red/White 16
L1-1
14 Green/White 18
L1-1
Output 04 4 15 Blue/White 11
LOAD OUT-4
Output 05 5 16 Black/Red 13
OUT-5
Output 06 6 17 White/Red 15
OUT-6
Output 07 7 18 Orange/Red 17
OUT-7
L2 B 19 Blue/Red 19
NOT USED
20 Red/Green 20
L1-1
21
22
23
24
25

1771-WA Swing Arm


From 1771-ON

Conversion Module Installation and Application Considerations


 This Bul. 1492 cable consists of a cable wired to one 1756-ON8 RTB. Recommended cable lengths of 0.5M or 1.0M (005=0.5M,
010=1.0M). See table 2 for other lengths.
 The 1771-ON module output current limits versus 1756-ON8 limits are as follows:
1771-ON 1756-ON8 w/ 1492-CONCAB005W
a) Current/Point 1.5A 2A
b) Current/Module 6A 5A @ 60°C
c) Surge Current/Point 4A for 10ms 20A for 43ms
 The 1771-ON has eight (8) 2A, 250V fuses - 1 per output. The 1756-ON8 is electronically fused per point. Refer to the 1756-ON8
Installation Manual for details on electronic fusing.
 Refer to your 1771-ON and 1756-ON8 Installation Manual wiring schematics and diagrams for more details. Ensure 1756 output module
ratings are not exceeded. [Reference Doc: 41171-021 (Version 00)]

Visit our website: www.ab.com


64 Publication 1492-SG121D-EN-P
Bulletin 1492
Bulletin 1771 to 1756 I/O Wiring Conversion System
Wiring Diagrams- Digital

Cat No. 1771-OND to 1756-ON8 (Qty. 2)

WARNING There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module Cable


1492-CM1771-LD006 1492-CONCAB005S2 1756-ON8
2 L1-0
4
L1 A L1-0
6
L1 B L1-0
8
L1-0
L1 C 1 Black 10
L1-0
L1 D 2 White
9 NOT USED
Output 00 00 3 Red 1 OUT-0
Output 01 01 4 Green 3
OUT-1
L1 Output 02 02 5 Orange 5
OUT-2
Output 03 03 6 Blue 7
OUT-3
Output 04 04 7 White/Black 11
13 OUT-4
L2 Output 05 05 8 Red/Black
OUT-5
Output 06 06 9 Green/Black 15
OUT-6
Output 07 07 10 Orange/Black 17
OUT-7
Output Output 10 10 11 Blue/Black
19 NOT USED
Device Output 11 11 12 Black/White
L1-1
Output 12 12 13 Red/White 14
L1-1
Output 13 13 14 Green/White 16
L1-1
Output 14 14 15 Blue/White 18
L1-1
Output 15 15 16 Black/Red 20
L1-1
Output 16 16 17 White/Red
Output 17 17 18 Orange/Red
19 Blue/Red
L2 E 20 Red/Green 1756-ON8
21 2
22 L1-0
4
23 L1-0
6
24 L1-0
8
25 L1-0
10
L1-0
9 NOT USED
1 OUT-8
3
OUT-9
5
OUT-10
1771-WH, WHF Swing Arm 7
OUT-11
From 1771-OND 11
13 OUT-12
OUT-13
15
OUT-14
17
OUT-15
19 NOT USED
L1-1
14
L1-1
16
Conversion Module Installation and Application Considerations L1-1
18
L1-1
 This Bul. 1492 cable consists of a cable wired to two 1756-ON8 RTB. Recommended cable lengths of 20
L1-1
0.5M or 1.0M (005=0.5M, 010=1.0M). See table 2 for other lengths.
 The 1771-OND module output current limits versus (2)1756-ON8 limits are as follows:
1771-OND 1756-ON8 w/ 1492-CONCAB005S2
a) Current/Point 2A 2A
b) Current/Module 8A 5A
c) Surge Current/Point 25A for 100ms 20A for 43ms
 The L2 terminal (Terminal E) on the 1771-ON8 module was an optional connection, but it is required for the 1756-OA16.
This connection must be added if it was not connected.
 The 1771-OND is rated 24V AC. The 1756-ON8 is rated 10V to 30V AC.
 Refer to your 1771-OND and 1756-ON8 Installation Manual wiring schematics and diagrams for more details. Ensure
1756 output module ratings are not exceeded. [Reference Doc: 41171-008 (Version 00)]

Visit our website: www.ab.com


Publication 1492-SG121D-EN-P 65
Bulletin 1492
Bulletin 1771 to 1756 I/O Wiring Conversion System
Wiring Diagrams - Digital

Cat No. 1771-OQ (Qty. 2) to 1756-OB16I

WARNING There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module
1492-CM1771-LA004 Cable
1492-C005005XT 1756-OB16I
Not Used
DC-1
18 18 Orange/Red Cable “A” 2
17 17 White/Red
1 DC-1
OUTPUT-0 16 16 Black/Red OUTPUT-0
LOAD DC-1 4
15 15 Blue/White DC-1
OUTPUT 1 14 14 Green/White 3
+ OUTPUT 1
OUTPUT 2 13 13 Red/White 5
OUTPUT 2
DC-2 12 12 Black/White 6
- OUTPUT 3 11 11 Blue/Black 7 DC-2
10 OUTPUT 3
LOAD DC-2 10 Orange/Black 8
DC-2
DC-3 9 9 Green/Black 10
DC-3
OUTPUT-4 8 8 Red/Black 9
OUTPUT-4
DC-3 7 7 White/Black 12
DC-3
OUTPUT 5 6 6 Blue 11
OUTPUT 5
OUTPUT 6 5 5 Orange 13
OUTPUT 6
DC-4 4 4 Green 14 DC-4
OUTPUT 7 3 3 Red 15
OUTPUT 7
DC-4 2 2 White 16
DC-4
Not Used 1 1 Black

18
1771-WF Swing Arm 17 DC-1
OUTPUT-8
20
From 1771-OQ DC-1
19
OUTPUT 9
21
OUTPUT 10
22
DC-2
Conversion Module 23
OUTPUT 11
24
1492-CM1771-LA004 Cable “B” 26
DC-2
DC-3
25
OUTPUT-12
28
Not Used 18 18 Orange/Red DC-3
27
DC-1 17 17 White/Red OUTPUT 13
29
OUTPUT-8 16 16 Black/Red OUTPUT 14
LOAD 30 DC-4
DC-1 15 15 Blue/White 31
OUTPUT 9 14 14 Green/White
OUTPUT 15
32
+ OUTPUT 10 13 13 Red/White DC-4
DC-2 12 12 Black/White
33 NOT USED
- 11 11 34 NOT USED
OUTPUT 11 Blue/Black
35 NOT USED
DC-2 10 10 Orange/Black
LOAD 36 NOT USED
DC-3 9 9 Green/Black
OUTPUT-12 8 8 Red/Black
DC-3 7 7 White/Black
OUTPUT 13 6 6 Blue

OUTPUT 14 5 5 Orange

DC-4 4 4 Green
OUTPUT 15 3 3 Red

DC-4 2 2 White
Not Used 1 1 Black

1771-WF Swing Arm


From 1771-OQ

Conversion Module Installation and Application Considerations


 This Bul. 1492 cable consists of 2 separate cables (cable “A” and cable “B”) wired to one 1756-OB16I RTB.
Each cable can be either
0.5M or 1.0M (005=0.5M, 010=1.0M). Ensure that cable A and cable B are connected to the correct module in the conversion
 The 1771-OQ module output resistive current limits versus 1756-OB16I limits are as follows:
1771-OQ 1756-OB16I w/ 1492-C005005XT
a) Current/Point 2.25A 2A
b) Current/Module 9A 8A
c) Surge Current/Point 4A for 10ms 4A for 10ms
 The 1771-OQ is rated 10V to 32V DC. The 1756-OB16I is rated 10V to 30V DC.
 Refer to your 1771-OQ and 1756-OB16I Installation Manual wiring schematics and diagrams for more details. Ensure 1756 output
module ratings are not exceeded. [Reference Doc: 41171-033 (Version 00)]

Visit our website: www.ab.com


66 Publication 1492-SG121D-EN-P
Bulletin 1492
Bulletin 1771 to 1756 I/O Wiring Conversion System
Wiring Diagrams- Digital

Cat No. 1771-OQ16 to 1756-OB16I

WARNING There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module
1492-CM1771-LD010F

Not Used 9 1
Not Used 10 2 Cable
Not Used 19 3 1492-CONCAB005Y 1756-OB16I
Not Used 20 4
DC-0 2 5 Orange 2
LOAD DC-0
Ouput 0 1 6 Blue 1
+ OUT-0
DC-1 4 7 White/Black 4
DC-1
Ouput 1 3 8 Red/Black 3
OUT-1
- DC-2 6 9 Green/Black 6
DC-2
Ouput 2 5 10 Orange/Black 5
OUT-2
DC-3 8 11 Blue/Black 8
DC-3
Ouput 3 7 12 Black/White 7
OUT-3
DC-4 12 13 Red/White 10
DC-4
Ouput 4 11 14 Green/White 9
OUT-4
DC-5 14 15 Blue/White 12
DC-5
Ouput 5 13 16 Black/Red 11
OUT-5
DC-6 16 17 White/Red 14
DC-6
Ouput 6 15 18 Orange/Red 13
OUT-6
DC-7 18 19 Blue/Red 16
DC-7
Ouput 7 17 20 Red/Green 15
OUT-7
DC-8 22 21 Orange/Green 18
DC-8
Ouput 8 21 22 Black/White/Red 17
OUT-8
DC-9 24 23 White/Black/Red 20
DC-9
Ouput 9 23 24 Red/Black/White 19
OUT-9
DC-10 26 25 Green/Black/White 22
DC-10
Ouput 10 25 26 Orange/Black/White 21
OUT-10
DC-11 28 27 Blue/Black/White 24
DC-11
Ouput 11 27 28 Black/Red/Green 23
OUT-11
DC-12 32 29 White/Red/Green 26
DC-12
Ouput 12 31 30 Red/Black/Green 25
OUT-12
DC-13 34 31 Green/Black/Orange 28
DC-13
Ouput 13 33 32 Orange/Black/Green 27
OUT-13
DC-14 36 33 Blue/White/Orange 30
DC-14
Ouput 14 35 34 Black/White/Orange 29
OUT-14
DC-15 38 35 White/Red/Orange 32
DC-15
Ouput 15 37 36 Orange/White/Blue 31
OUT-15
Not Used 29 37
Not Used 30
Not Used 39
Not Used 40

1771-WN Swing Arm


From 1771-OQ16

Conversion Module Installation and Application Considerations


 This Bul. 1492 cable consists of a cable wired to one 1756-OB16I RTB. Recommended cable lengths of
0.5M or 1.0M (005=0.5M, 010=1.0M). See table 2 for other lengths.
 The 1771-OQ16 module output current limits versus 1756-OB16I limits are as follows:
1771-OQ16 1756-OB16I w/ 1492-CONCAB005Y
a) Current/Point 2A 2A
b) Current/Module 32A 8A
c) Surge Current/Point 4A for 10ms 4A for 10ms
 The 1771-OQ16 has sixteen (16) 3A, 250V rectifier fuses. The 1756-OB16I is NOT fused, as such sixteen(16) 2AG fuses
and clips are provided on the 1492-CM1771-LD010F conversion module. Max fuse rating is 1.5A based on 1756-OA16I.
 The 1771-OQ16 is rated 10V to 32V DC. The 1756-OB16I is rated 10V to 30V DC.
 Refer to your 1771-OQ16 and 1756-OB16I Installation Manual wiring schematics and diagrams for more details. Ensure
1756 output module ratings are not exceeded. [Reference Doc: 41171-010 (Version 00)]

Visit our website: www.ab.com


Publication 1492-SG121D-EN-P 67
Bulletin 1492
Bulletin 1771 to 1756 I/O Wiring Conversion System
Wiring Diagrams - Digital

Cat No. 1771-OR (Qty. 2) to 1756-OA16I

WARNING There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module
1492-CM1771-LD012
1
2
Cable
3
4
1492-CONCAB005Y 1492-C005005XR 1756-OA16I
5
4
JMP0
3 6
Orange
Blue CABLE ”A” 2
L2-0
N.C. 7 White/Black
N.O. 8 Red/Black 1
L1-0
2 1 9 Green/Black 3
JMP1 L1-1
4 3 10 Orange/Black 5
L1-2
N.C. 11 Blue/Black
N.O. 12 Black/White 4 L2-1
2 1 13 Red/White 6
JMP2 L2-2
4 3 14 Green/White 8
L2-3
N.C. 15 Blue/White
0-IN 1
N.O. 16 Black/Red 9
2 L1-3
0-OUT 2 1 17 White/Red 11
3 JMP3 L1-4
1-IN 3 18 Orange/Red 13
4 L1-5
1-OUT 4 N.C. 19 Blue/Red
2-IN 5 10
N.O. 20 Red/Green
L2-4
2-OUT 6 2 1 12
21 Orange/Green
L2-5
3-IN 7 JMP4 22
4 3 Black/White/Red
8 N.C.
3-OUT 23 White/Black/Red
9
4-IN N.O. 24 Red/Black/White
10 2 1 25
4-OUT Green/Black/White
L2 L1 5-IN 11 JMP5
4 3 26 Orange/Black/White
5-OUT 12 27
LOAD N.C. Blue/Black/White
N.O. 28 Black/Red/Green
2 1 29 White/Red/Green
JMP6 30
4 3 Red/Black/Green
N.C. 31 Green/Black/Orange
N.O. 32 Orange/Black/Green
2 1 33 Blue/White/Orange 26 NOT USED
JMP7 34 Black/White/Orange NOT USED
4 3 27
N.C. 35 White/Red/Orange 28 NOT USED
N.O. 36 Orange/White/Blue
1771-WD Swing Arm 2 1 37
29
30
NOT USED
NOT USED
NOT USED
From 1771-OR 31
32 NOT USED
33 NOT USED
Conversion Module 34
35
NOT USED
NOT USED
1492-CM1771-LD012 36 NOT USED

1
2
3
4
5 Orange
CABLE ”B”
JMP0 6
4 3 Blue 14
L2-6
N.C. 7 White/Black
N.O. 8 Red/Black 15
L1-6
2 1 9 Green/Black 17
JMP1 L1-7
4 3 10 Orange/Black 19
L1-8
N.C. 11 Blue/Black
N.O. 12 Black/White 16 L2-7
2 1 13 Red/White 18
JMP2 L2-8
4 3 14 Green/White 20
L2-9
6-IN N.C. 15 Blue/White
1
N.O. 16 Black/Red 21
6-OUT 2 L1-9
2 1 17 White/Red 23 L1-10
L2 L1 7-IN 3 JMP3
4 3 18 Orange/Red 25
7-OUT 4 L1-11
LOAD N.C. 19 Blue/Red
8-IN 5 22
N.O. 20 Red/Green
L2-10
8-OUT 6 2 1 24
21 Orange/Green
L2-11
9-IN 7 JMP4
4 3 22 Black/White/Red
9-OUT 8 N.C. 23 White/Black/Red
10-IN 9
N.O. 24 Red/Black/White
10-OUT 10 2 1 25 Green/Black/White
11-IN 11 JMP5 26
4 3 Orange/Black/White
11-OUT 12 27
N.C. Blue/Black/White
N.O. 28 Black/Red/Green
2 1 29 White/Red/Green
JMP6 30
4 3 Red/Black/Green
N.C. 31 Green/Black/Orange
N.O. 32 Orange/Black/Green
2 1 33 Blue/White/Orange
JMP7 34 Black/White/Orange
4 3
1771-WD Swing Arm N.C. 35
36
White/Red/Orange
Orange/White/Blue
N.O.
From 1771-OR 2 1 37

Conversion Module Installation and Application Considerations


 This Bul. 1492 cable consists of 2 separate cables (cable “A” and cable “B”) wired to one 1756-OA16I RTB.
Each cable can be either
0.5M or 1.0M (005=0.5M, 010=1.0M). Ensure that cable A and cable B are connected to the correct module in the conversion
 The 1771-OR module output resistive current limits versus 1756-OA16I limits are as follows:
1771-OR 1756-OA16I w/ 1492-C005005XR
a) Current/Point 2A 2A
b) Current/Module 6A 5A @ 60°C
c) Surge Current/Point 15A for 100ms 20A for 43ms
 The 1771-OR module had a jumper selection of N.O. and N.C. outputs. The 1756-OA16I has both N.O. and N.C. outputs, but
selection is by wiring termination on the 1756 swing arm. The 1492-CM1771-LD012 conversion module replaces the functionality
of the 1771-OR jumpers with eight jumpers (JMP0 through JMP7). In the default position, the output will be N.O. If a N.C. output is
required, change the jumper from pins 1-2 to pins 3-4.
 Refer to your 1771-OR and 1756-OA16I Installation Manual wiring schematics and diagrams for more details. Ensure 1756 output
module ratings are not exceeded. [Reference Doc: 41171-017 (Version 00)]

Visit our website: www.ab.com


68 Publication 1492-SG121D-EN-P
Bulletin 1492
Bulletin 1771 to 1756 I/O Wiring Conversion System
Wiring Diagrams- Digital

Cat No. 1771-OVN to 1756-OV16E (Qty. 2)

WARNING There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and input module). Read and understand these
considerations before installation.
Conversion Module
1492-CM1771-LD013
Cable
L1 1
L1
L1 11
1492-CONCAB005S3 1756-OV16E
L1-0 
L2 10 1 Black 10
L2 20 2 White 9
L2 L2-0
Output 00 2 3 Red 1
OUT-0
Output 01 3 4 Green 2
OUT-1
Output Output 02 4 5 Orange 3
Device OUT-2
Output 03 5 6 Blue 4
OUT-3

MODULE A
Output 04 6 7 White/Black 5
OUT-4
Output 05 7 8 Red/Black 6
OUT-5
Output 06 8 9 Green/Black 7
OUT-6
Output 07 9 10 Orange/Black 8
OUT-7
Output 10 12 11 Blue/Black 11
OUT-8
Output 11 13 12 Black/White 12
OUT-9
Output 12 14 13 Red/White 13
OUT-10
Output 13 15 14 Green/White 14
15 OUT-11
Output 14 16 Blue/White 15
16 OUT-12
Output 15 17 Black/Red 16
OUT-13
Output 16 18 17 White/Red 17
OUT-14
Output 17 19 18 Orange/Red 18
OUT-15
19 Blue/Red 20
L1-1 
19
L2-1
L1 21
L1 31 1756-OV16E
L2 30 20 Red/Green 10
L1-0
L2 40 21 Orange/Green 9
L2-0

Output 00 22 22 Black/White/Red 1
OUT-0
Output 01 23 23 White/Black/Red 2
OUT-1
Output 02 24 24 Red/Black/White 3
OUT-2
Output 03 25 25 Green/Black/White 4
OUT-3

MODULE B
Output 04 26 26 Orange/Black/White 5
OUT-4
Output 05 27 27 Blue/Black/White 6
OUT-5
Output 06 28 28 Black/Red/Green 7
OUT-6
Output 07 29 29 White/Red/Green 8
OUT-7
Output 10 32 30 Red/Black/Green 11
OUT-8
Output 11 33 31 Green/Black/Orange 12
OUT-9
Output 12 34 32 Orange/Black/Green 13
OUT-10
35 33 Blue/White/Orange 14
Output 13 OUT-11
Output 14 36 34 Black/White/Orange 15
OUT-12
Output 15 37 35 White/Red/Orange 16
OUT-13
38 36 Orange/White/Blue 17
Output 16 OUT-14
Output 17 39 37 White/Red/Blue 18
OUT-15
20 L1-1
1771-WN Swing Arm 19 L2-1

From 1771-OVN

Conversion Module Installation and Application Considerations


 This Bul. 1492 cable consists of a cable wired to two 1756-OV16E RTB. Recommended cable lengths of 0.5M or 1.0M (005=0.5M,
010=1.0M). See table 2 for other lengths.
 The 1771-OVN module output current limits versus 1756-OV16E limits are as follows:
1771-OVN 1756-OV16E w/ 1492-CONCAB005S3
a) Current/Point 0.5A 1A
b) Current/Module 8A (32 pts) 8A (16 pts)
c) Surge Current/Point 2A for 10ms 2A for 10ms
 The 1771-OVN has 4 groups (allowing 4 separate power supplies). This module/cable combination ties all 4 groups from the
1771-OVN together. Field wiring modification must be made to accommodate this if mulitple supplies were used. If more than 1 supply
was used, all but 1 of the power supplies must be removed.
 The 1771-OVN did not allow connections for L2, however the 1756-OV16E requires an L2 connection for proper operation. The 1771-
OVN did not use terminals 10, 20, 30, 40. These terminals have been reassigned for an L2 connection in this application. The installer must
rewire L2 to one of these terminals.
 Refer to your 1771-OVN and 1756-OV16E Installation Manual wiring schematics and diagrams for more details. Ensure 1756 output
module ratings are not exceeded.
 This configuration uses two (2) 1756-OV16E output modules to replace a single 1771-OVN output module. This may require the use of a
larger 1756 I/O chassis and conversion mounting assembly. Ensure there is sufficient panel space to allow for this possibility.
[Reference Doc: 41171-018 (Version 00)]

Visit our website: www.ab.com


Publication 1492-SG121D-EN-P 69
Bulletin 1492
Bulletin 1771 to 1756 I/O Wiring Conversion System
Wiring Diagrams - Digital

Cat No. 1771-OW to 1756-OX8I

WARNING There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module
1492-CM1771-LD012
1
2 Cable
3 1492-CONCAB005Y 1756-OX8I
4
5 Orange 2
JMP0 3 L1-0
4 6 Blue 1 OUT-0 N.C.
N.C. 7 White/Black 4 L1-0
N.O. 8 Red/Black 3
9 Green/Black
OUT-0 N.O.
2 1 6
JMP1 3 L1-1
4 10 Orange/Black 5 OUT-1 N.C.
N.C. 11 Blue/Black 8 L1-1
N.O. 12 Black/White 7
OUT-1 N.O.
2 1 13 Red/White 10 L1-2
4 JMP2 3 14 Green/White 9
OUT-2 N.C.
N.C. 15 Blue/White 12
L1 Out-0 N.O./N.C. 1 L1-2
+V0/1 2 N.O. 16 Black/Red 11
OUT-2 N.O.
3 2 1 17 White/Red 14
L2 Out-1 N.O./N.C. L1-3
LOAD 4 JMP3 3 18 Orange/Red 13
Out-2 N.O./N.C. 4 OUT-3 N.C.
5 N.C. 19 Blue/Red 16
+V2/3 L1-3
6 N.O. 20 Red/Green 15
Out-3 N.O./N.C. OUT-3 N.O.
2 1 21 Orange/Green 18
Out-4 N.O./N.C. 7 L1-4
4 JMP4 3 22 Black/White/Red 17
+ +V4/5 8 OUT-4 N.C.
N.C. 23 White/Black/Red 20
Out-5 N.O./N.C. 9 L1-4
LOAD N.O. 24 Red/Black/White 19
- Out-6 N.O./N.C. 10 OUT-4 N.O.
+V6/7 11
2 1 25 Green/Black/White 22 L1-5
4 JMP5 3 26 Orange/Black/White 21
Out-7 N.O./N.C. 12 OUT-5 N.C.
N.C. 27 Blue/Black/White 24
L1-5
N.O. 28 Black/Red/Green 23
OUT-5 N.O.
2 1 29 White/Red/Green 26
JMP6 3 L1-6
4 30 Red/Black/Green 25 OUT-6 N.C.
N.C. 31 Green/Black/Orange 28
L1-6
N.O. 32 Orange/Black/Green 27
OUT-6 N.O.
2 1 33 Blue/White/Orange 30
JMP7 3 L1-7
4 34 Black/White/Orange 29
OUT-7 N.C.
N.C. 35 White/Red/Orange 32 L1-7
N.O. 36 Orange/White/Blue 31
OUT-7 N.O.
2 1 37

1771-WD Swing Arm


From 1771-OW

Conversion Module Installation and Application Considerations


 This Bul. 1492 cable consists of a cable wired to one 1756-OX8I RTB. Recommended cable lengths of 0.5M or 1.0M (005=0.5M),
010=1.0M). See table 2 for other lengths.
 The 1771-OW module output resistive current limits versus 1756-OX8I limits are as follows:
(NOTE: For switching and inductive current ratings, refer to the modules Installation Instructions)
1771-OW 1756-OX8I w/ 1492-CONCAB005Y
a) Current/Point 0.2A @ 138V AC 2A @ 240V AC
1A @ 30V DC 2A @ 30V DC
0.25A @ 125V DC 0.25A @ 125V DC
 The 1771-OW module had a jumper selection of N.O. and N.C. outputs. The 1756-OX8I has both N.O. and N.C. outputs, but
selection is by wiring termination on the 1756 swing arm. The 1492-CM1771-LD012 conversion module replaces the functionality
of the 1771-OW jumpers with eight jumpers (JMP0 through JMP7). In the default position, the output will be N.O. If a N.C. output is
required, change the jumper from pins 1-2 to pins 3-4.
 Refer to your 1771-OW and 1756-OX8I Installation Manual wiring schematics and diagrams for more details. Ensure 1756 output
module ratings are not exceeded. [Reference Doc: 41170-941 (Version 01)]

Visit our website: www.ab.com


70 Publication 1492-SG121D-EN-P
Bulletin 1492
Bulletin 1771 to 1756 I/O Wiring Conversion System
Wiring Diagrams- Digital

Cat No. 1771-OW16 to 1756-OW16I

WARNING There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module
1492-CM1771-LD011

Output 10 (NC) 17 1
Output 11 (NC) 20 2 Cable
Output 12 (NC) 23 3 1492-CONCAB005Y 1756-OW16I
Output 13 (NC) 26 4
L1 Common 00 2 5 Orange 2
Output 00 L1-0
1 6 Blue 1
LOAD OUT-0 N.O.
Common 01 4 7 White/Black 4
L1-1
Output 01 3 8 Red/Black 3
L2 6 OUT-1 N.O.
Common 02 9 Green/Black 6
5 L1-2
Output 02 10 Orange/Black 5
OUT-2 N.O.
Common 03 8 11 Blue/Black 8
L1-3
Output 03 7 12 Black/White 7
OUT-3 N.O.
Common 04 10 13 Red/White 10
9 L1-4
Output 04 14 Green/White 9
12 OUT-4 N.O.
Common 05 15 Blue/White 12
11 L1-5
Output 05 16 Black/Red 11
14 OUT-5 N.O.
Common 06 17 White/Red 14
+ L1-6
Output 06 13 18 Orange/Red 13
- LOAD OUT-6 N.O.
Common 07 16 19 Blue/Red 16
15 L1-7
Output 07 20 Red/Green 15
19 OUT-7 N.O.
Common 10 21 Orange/Green 18
18 L1-8
Output 10 (NO) 22 Black/White/Red 17
OUT-8 N.O.
Common 11 22 23 White/Black/Red 20
21 L1-9
Output 11(NO) 24 Red/Black/White 19
25 OUT-9 N.O.
Common 12 25 Green/Black/White 22
24 L1-10
Output 12 (NO) 26 Orange/Black/White 21
28 OUT-10 N.O.
Common 13 27 Blue/Black/White 24
L1-11
Output 13 (NO) 27 28 Black/Red/Green 23
31 OUT-11 N.O.
Common 14 29 White/Red/Green 26
30 L1-12
Output 14 (NO) 30 Red/Black/Green 25
OUT-12 N.O.
Common 15 34 31 Green/Black/Orange 28
L1-13
Output 15 (NO) 33 32 Orange/Black/Green 27
OUT-13 N.O.
Common 16 37 33 Blue/White/Orange 30
L1-14
Output 16 (NO) 36 34 Black/White/Orange 29
OUT-14 N.O.
Common 17 40 35 White/Red/Orange 32
L1-15
Output 17 (NO) 39 36 Orange/White/Blue 31
OUT-15 N.O.
Output 14 (NC) 29 37
Output 15 (NC) 32
Output 16 (NC) 35
Output 17 (NC) 38

1771-WN Swing Arm


From 1771-OW16
Conversion Module Installation and Application Considerations
 The 1771-OW16 module output resistive current limits versus 1756-OW16I limits are as follows:
1771-OW16 1756-OW16I w/ 1492-CONCAB005Y
a) Current/Point 2A @ 250V AC 2A @ 240V AC
2A @ 30V DC 2A @ 30V DC
0.3A @ 150V DC 0.25A @ 125V AC
 The 1492-CONCAB005Y is limited to 3A per pin.
 The 1771-OW16 has N.O. and N.C. relay contact outputs. The 1756-OW16I has N.O. relay contact outputs only. The conver-
sion module does not convert the N.C. to N.O. contacts. If the 1771-OW16 N.C. outputs were being used, the installer must
rewire the 1771-WN swing arm and move the N.C. wires to the N.O. output terminals. In addition, the control Logix programming
will need to be changed to simulate a N.C. relay with this output.
 Refer to your 1771-OW16 and 1756-OW16I Installation Manual wiring schematics and diagrams for more details.
Ensure 1756 output module ratings are not exceeded. Reference Doc: 41170-940 (Version 01)]

Visit our website: www.ab.com


Publication 1492-SG121D-EN-P 71
Bulletin 1492
Bulletin 1771 to 1756 I/O Wiring Conversion System
Wiring Diagrams - Digital

Cat No. 1771-OWNA to 1756-OW16I (Qty. 2)

WARNING There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and input module). Read and understand these
considerations before installation.
Conversion Module
1492-CM1771-LD013
Cable
L1 L1 1 1492-CONCAB005S4 1756-OW16I
L1 11
L2
L2
10
20
1
2
Black 2
L1-0 
White
L2 L2-0
Output 00 2 3 Red 1
OUT-0
Output 01 3 4 Green 3
OUT-1
Output Output 02 4 5 Orange 5
Device OUT-2
Output 03 5 6 Blue 7
OUT-3

MODULE A
Output 04 6 7 White/Black 9
OUT-4
Output 05 7 8 Red/Black 11
OUT-5
Output 06 8 9 Green/Black 13
OUT-6
Output 07 9 10 Orange/Black 15
11 OUT-7
Output 10 12 Blue/Black 17
OUT-8
Output 11 13 12 Black/White 19
OUT-9
Output 12 14 13 Red/White 21
OUT-10
Output 13 15 14 Green/White 23
OUT-11
Output 14 16 15 Blue/White 25
16 OUT-12
Output 15 17 Black/Red 27
OUT-13
Output 16 18 17 White/Red 29
OUT-14
Output 17 19 18 Orange/Red 31
OUT-15
19 Blue/Red 4
6 L1-1
L1-1
32 
L1-1
34
L1-1
L1 21
L1 31 1756-OW16I
L2
L2
30
40
20 Red/Green 2
L1-0 
21 Orange/Green
L2-0
Output 00 22 22 Black/White/Red 1
OUT-0
Output 01 23 23 White/Black/Red 3
OUT-1
Output 02 24 24 Red/Black/White 5
OUT-2
Output 03 25 25 Green/Black/White 7
OUT-3

MODULE B
Output 04 26 26 Orange/Black/White 9
OUT-4
Output 05 27 27 Blue/Black/White 11
OUT-5
Output 06 28 28 Black/Red/Green 13
OUT-6
Output 07 29 29 White/Red/Green 15
OUT-7
Output 10 32 30 Red/Black/Green 17
OUT-8
Output 11 33 31 Green/Black/Orange 19
OUT-9
Output 12 34 32 Orange/Black/Green 21
OUT-10
35 33 Blue/White/Orange 23
Output 13 OUT-11
Output 14 36 34 Black/White/Orange 25
OUT-12
Output 15 37 35 White/Red/Orange 27
OUT-13
38 36 Orange/White/Blue 29
Output 16 OUT-14
Output 17 39 37 White/Red/Blue 31
OUT-15
4
6 L1-1
L1-1
1771-WN Swing Arm 32

L1-1
From 1771-OWNA 34
L1-1

Conversion Module Installation and Application Considerations


 This Bul. 1492 cable consists of a cable wired to two 1756-OW16I RTB. Recommended cable lengths of 0.5M or 1.0M (005=0.5M, 010=1.0M).
See table 2 for other lengths.
 The 1771-OWNA module output current limits versus 1756-OW16I limits are as follows:
1771-OWNA 1756-OW16I w/ 1492-CONCAB005S4
a) Current/Point 1A 0.5A
b) Current/Module 12A (32 pts) 2A (16 pts)
 The 1771-OWNA has 4 groups (allowing 4 separate power supplies). This module/cable combination ties all 4 groups from the 1771 -OWNA
together. Field wiring modification must be made to accommodate this if mulitple supplies were used. If more than 1 supply wa s used, all but
1 of the power supplies must be removed.
 The 1771-OWNA did not allow connections for L2, however the 1756-OW16I requires an L2 connection for proper operation. The 1771-OWNA
did not use terminals 10, 20, 30, 40. These terminals have been reassigned for an L2 connection in this application. The installer must rewire L2 to
one of these terminals.
 Refer to your 1771-OWNA and 1756-OW16I Installation Manual wiring schematics and diagrams for more details. Ensure 1756 output module
ratings are not exceeded.
 This configuration uses two (2) 1756-OW16I output modules to replace a single 1771-OWNA output module. This may require the use of a
larger 1756 I/O chassis and conversion mounting assembly. Ensure there is sufficient panel space to allow for this possibility.
 1756-OW16I output modules has all inputs jumpered together pins 2 through 34 even.
[Reference Doc: 41171-019 (Version 00)]

Visit our website: www.ab.com


72 Publication 1492-SG121D-EN-P
Bulletin 1492
Bulletin 1771 to 1756 I/O Wiring Conversion System
Wiring Diagrams- Digital

Cat No. 1771-OY to 1756-OX8I

WARNING There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module
1492-CM1771-LD012
1
2 Cable
3
1492-CONCAB005Y 1756-OX8I
4
5 Orange 2
JMP0 L1-0
4 3 6 Blue 1
OUT-0 N.C.
N.C. 7 White/Black 4
L1-0
N.O. 8 Red/Black 3
OUT-0 N.O.
2 1 9 Green/Black 6
JMP1 L1-1
4 3 10 Orange/Black 5
OUT-1 N.C.
N.C. 11 Blue/Black 8
L1-1
N.O. 12 Black/White 7
2 1 OUT-1 N.O.
13 Red/White 10
JMP2 L1-2
4 3 14 Green/White 9
OUT-2 N.C.
Out-0 N.O./N.C. N.C. 15 Blue/White 12
1 L1-2
L1 N.O. 16 Black/Red 11
+V0/1 2 OUT-2 N.O.
2 1 17 White/Red 14
Out-1 N.O./N.C. 3 JMP3 L1-3
L2 LOAD 4 3 18 Orange/Red 13
Out-2 N.O./N.C. 4 OUT-3 N.C.
N.C. 19 Blue/Red 16
+V2/3 5 L1-3
N.O. 20 Red/Green 15
Out-3 N.O./N.C. 6 OUT-3 N.O.
2 1 21 Orange/Green 18
Out-4 N.O./N.C. 7 JMP4 L1-4
+ 4 3 22 Black/White/Red 17
+V4/5 8 OUT-4 N.C.
N.C. 23 White/Black/Red 20
Out-5 N.O./N.C. 9 L1-4
- LOAD N.O. 24 Red/Black/White 19
Out-6 N.O./N.C. 10 2 1 OUT-4 N.O.
25 Green/Black/White 22
+V6/7 11 JMP5 L1-5
4 3 26 Orange/Black/White 21
Out-7 N.O./N.C. 12 OUT-5 N.C.
N.C. 27 Blue/Black/White 24
L1-5
N.O. 28 Black/Red/Green 23
OUT-5 N.O.
2 1 29 White/Red/Green 26
JMP6 L1-6
4 3 30 Red/Black/Green 25
OUT-6 N.C.
N.C. 31 Green/Black/Orange 28
L1-6
N.O. 32 Orange/Black/Green 27
2 1 OUT-6 N.O.
33 Blue/White/Orange 30
JMP7 L1-7
4 3 34 Black/White/Orange 29
OUT-7 N.C.
N.C. 35 White/Red/Orange 32
L1-7
N.O. 36 Orange/White/Blue 31
OUT-7 N.O.
1771-WD Swing Arm 2 1 37
From 1771-OY

Conversion Module Installation and Application Considerations


 This Bul. 1492 cable consists of a cable wired to one 1756-OX8I RTB. Recommended cable lengths of 0.5M or 1.0M (005=0.5M),
010=1.0M). See table 2 for other lengths.
 The 1771-OY module output resistive current limits versus 1756-OX8I limits are as follows:
(NOTE: For switching and inductive current ratings, refer to the modules Installation Instructions)
1771-OY 1756-OX8I w/ 1492-CONCAB005Y
a) Current/Point 100mA @ 138V AC 2A @ 240V AC
100mA @ 125V DC 2A @ 30V DC
0.25A @ 125V DC
 The 1771-OY module had a jumper selection of N.O. and N.C. outputs. The 1756-OX8I has both N.O. and N.C. outputs, but
selection is by wiring termination on the 1756 swing arm. The 1492-CM1771-LD012 conversion module replaces the functionality
of the 1771-OY jumpers with eight jumpers (JMP0 through JMP7). In the default position, the output will be N.O. If a N.C. output is
required, change the jumper from pins 1-2 to pins 3-4.
 Refer to your 1771-OY and 1756-OX8I Installation Manual wiring schematics and diagrams for more details. Ensure 1756 output
module ratings are not exceeded. [Reference Doc: 41171-011 (Version 00)]

Visit our website: www.ab.com


Publication 1492-SG121D-EN-P 73
Bulletin 1492
Bulletin 1771 to 1756 I/O Wiring Conversion System
Wiring Diagrams - Digital

Cat No. 1771-OYL to 1756-OX8I

WARNING There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module
1492-CM1771-LD012
1
2 Cable
3
1492-CONCAB005Y 1756-OX8I
4
5 Orange 2
JMP0 L1-0
4 3 6 Blue 1
OUT-0 N.C.
N.C. 7 White/Black 4
L1-0
N.O. 8 Red/Black 3
OUT-0 N.O.
2 1 9 Green/Black 6
JMP1 L1-1
4 3 10 Orange/Black 5
OUT-1 N.C.
N.C. 11 Blue/Black 8
L1-1
N.O. 12 Black/White 7
2 1 OUT-1 N.O.
13 Red/White 10
JMP2 L1-2
4 3 14 Green/White 9
OUT-2 N.C.
Out-0 N.O./N.C. N.C. 15 Blue/White 12
1 L1-2
L1 N.O. 16 Black/Red 11
+V0/1 2 OUT-2 N.O.
2 1 17 White/Red 14
Out-1 N.O./N.C. 3 JMP3 L1-3
L2 LOAD 4 3 18 Orange/Red 13
Out-2 N.O./N.C. 4 OUT-3 N.C.
N.C. 19 Blue/Red 16
+V2/3 5 L1-3
N.O. 20 Red/Green 15
Out-3 N.O./N.C. 6 OUT-3 N.O.
2 1 21 Orange/Green 18
Out-4 N.O./N.C. 7 JMP4 L1-4
+ 4 3 22 Black/White/Red 17
+V4/5 8 OUT-4 N.C.
N.C. 23 White/Black/Red 20
Out-5 N.O./N.C. 9 L1-4
- LOAD N.O. 24 Red/Black/White 19
Out-6 N.O./N.C. 10 2 1 OUT-4 N.O.
25 Green/Black/White 22
+V6/7 11 JMP5 L1-5
4 3 26 Orange/Black/White 21
Out-7 N.O./N.C. 12 OUT-5 N.C.
N.C. 27 Blue/Black/White 24
L1-5
N.O. 28 Black/Red/Green 23
OUT-5 N.O.
2 1 29 White/Red/Green 26
JMP6 L1-6
4 3 30 Red/Black/Green 25
OUT-6 N.C.
N.C. 31 Green/Black/Orange 28
L1-6
N.O. 32 Orange/Black/Green 27
2 1 OUT-6 N.O.
33 Blue/White/Orange 30
JMP7 L1-7
4 3 34 Black/White/Orange 29
OUT-7 N.C.
N.C. 35 White/Red/Orange 32
L1-7
N.O. 36 Orange/White/Blue 31
OUT-7 N.O.
1771-WD Swing Arm 2 1 37
From 1771-OYL

Conversion Module Installation and Application Considerations


 This Bul. 1492 cable consists of a cable wired to one 1756-OX8I RTB. Recommended cable lengths of 0.5M or 1.0M (005=0.5M),
010=1.0M). See table 2 for other lengths.
 The 1771-OYL module output resistive current limits versus 1756-OX8I limits are as follows:
(NOTE: For switching and inductive current ratings, refer to the modules Installation Instructions)
1771-OYL 1756-OX8I w/ 1492-CONCAB005Y
a) Current/Point 100mA @ 24V AC 2A @ 240V AC
100mA @ 24V DC 2A @ 30V DC
0.25A @ 125V DC
 The 1771-OYL module had a jumper selection of N.O. and N.C. outputs. The 1756-OX8I has both N.O. and N.C. outputs, but
selection is by wiring termination on the 1756 swing arm. The 1492-CM1771-LD012 conversion module replaces the functionality
of the 1771-OYL jumpers with eight jumpers (JMP0 through JMP7). In the default position, the output will be N.O. If a N.C. output is
required, change the jumper from pins 1-2 to pins 3-4.
 Refer to your 1771-OYL and 1756-OX8I Installation Manual wiring schematics and diagrams for more details. Ensure 1756 output
module ratings are not exceeded. [Reference Doc: 41171-012 (Version 00)]

Visit our website: www.ab.com


74 Publication 1492-SG121D-EN-P
Bulletin 1492
Bulletin 1771 to 1756 I/O Wiring Conversion System
Wiring Diagrams- Digital

Cat No. 1771-OZ to 1756-OX8I

WARNING There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module
1492-CM1771-LD012
1
2 Cable
3
4
1492-CONCAB005Y 1756-OX8I
5 Orange 2
JMP0 L1-0
4 3 6 Blue 1
OUT-0 N.C.
N.C. 7 White/Black 4
L1-0
N.O. 8 Red/Black 3
OUT-0 N.O.
2 1 9 Green/Black 6
JMP1 L1-1
4 3 10 Orange/Black 5
OUT-1 N.C.
N.C. 11 Blue/Black 8
L1-1
N.O. 12 Black/White 7
2 1 OUT-1 N.O.
13 Red/White 10
JMP2 L1-2
4 3 14 Green/White 9
OUT-2 N.C.
Out-0 N.O./N.C. N.C. 15 Blue/White 12
1 L1-2
L1 N.O. 16 Black/Red 11
+V0/1 2 OUT-2 N.O.
2 1 17 White/Red 14
Out-1 N.O./N.C. 3 JMP3 L1-3
L2 LOAD 4 3 18 Orange/Red 13
Out-2 N.O./N.C. 4 OUT-3 N.C.
N.C. 19 Blue/Red 16
+V2/3 5 L1-3
N.O. 20 Red/Green 15
Out-3 N.O./N.C. 6 OUT-3 N.O.
2 1 21 Orange/Green 18
Out-4 N.O./N.C. 7 JMP4 L1-4
+ 4 3 22 Black/White/Red 17
+V4/5 8 OUT-4 N.C.
N.C. 23 White/Black/Red 20
Out-5 N.O./N.C. 9 L1-4
- LOAD N.O. 24 Red/Black/White 19
Out-6 N.O./N.C. 10 2 1 OUT-4 N.O.
25 Green/Black/White 22
+V6/7 11 JMP5 L1-5
4 3 26 Orange/Black/White 21
Out-7 N.O./N.C. 12 OUT-5 N.C.
N.C. 27 Blue/Black/White 24
L1-5
N.O. 28 Black/Red/Green 23
OUT-5 N.O.
2 1 29 White/Red/Green 26
JMP6 L1-6
4 3 30 Red/Black/Green 25
OUT-6 N.C.
N.C. 31 Green/Black/Orange 28
L1-6
N.O. 32 Orange/Black/Green 27
2 1 OUT-6 N.O.
33 Blue/White/Orange 30
JMP7 L1-7
4 3 34 Black/White/Orange 29
OUT-7 N.C.
N.C. 35 White/Red/Orange 32
L1-7
N.O. 36 Orange/White/Blue 31
OUT-7 N.O.
2 1 37

1771-WD Swing Arm


From 1771-OZ

Conversion Module Installation and Application Considerations


 This Bul. 1492 cable consists of a cable wired to one 1756-OX8I RTB. Recommended cable lengths of 0.5M or 1.0M (005=0.5M),
010=1.0M). See table 2 for other lengths.
 The 1771-OZ module output resistive current limits versus 1756-OX8I limits are as follows:
(NOTE: For switching and inductive current ratings, refer to the modules Installation Instructions)
1771-OZ 1756-OX8I w/ 1492-CONCAB005Y
a) Current/Point 100mA @ 138V AC 2A @ 240V AC
100mA @ 138V DC 2A @ 30V DC
0.25A @ 125V DC
 The 1771-OZ module had a jumper selection of N.O. and N.C. outputs. The 1756-OX8I has both N.O. and N.C. outputs, but
selection is by wiring termination on the 1756 swing arm. The 1492-CM1771-LD012 conversion module replaces the functionality
of the 1771-OZ jumpers with eight jumpers (JMP0 through JMP7). In the default position, the output will be N.O. If a N.C. output is
required, change the jumper from pins 1-2 to pins 3-4.
 Refer to your 1771-OZ and 1756-OX8I Installation Manual wiring schematics and diagrams for more details. Ensure 1756 output
module ratings are not exceeded. [Reference Doc: 41171-013 (Version 00)]

Visit our website: www.ab.com


Publication 1492-SG121D-EN-P 75
Bulletin 1492
Bulletin 1771 to 1756 I/O Wiring Conversion System
Wiring Diagrams - Digital

Cat No. 1771-OZL to 1756-OX8I

WARNING There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module
1492-CM1771-LD012
1
2 Cable
3
4
1492-CONCAB005Y 1756-OX8I
5 Orange 2
JMP0 L1-0
4 3 6 Blue 1
OUT-0 N.C.
N.C. 7 White/Black 4
L1-0
N.O. 8 Red/Black 3
OUT-0 N.O.
2 1 9 Green/Black 6
JMP1 L1-1
4 3 10 Orange/Black 5
OUT-1 N.C.
N.C. 11 Blue/Black 8
L1-1
N.O. 12 Black/White 7
2 1 OUT-1 N.O.
13 Red/White 10
JMP2 L1-2
4 3 14 Green/White 9
OUT-2 N.C.
Out-0 N.O./N.C. N.C. 15 Blue/White 12
1 L1-2
L1 N.O. 16 Black/Red 11
+V0/1 2 OUT-2 N.O.
2 1 17 White/Red 14
Out-1 N.O./N.C. 3 JMP3 L1-3
L2 LOAD 4 3 18 Orange/Red 13
Out-2 N.O./N.C. 4 OUT-3 N.C.
N.C. 19 Blue/Red 16
+V2/3 5 L1-3
N.O. 20 Red/Green 15
Out-3 N.O./N.C. 6 OUT-3 N.O.
2 1 21 Orange/Green 18
Out-4 N.O./N.C. 7 JMP4 L1-4
+ 4 3 22 Black/White/Red 17
+V4/5 8 OUT-4 N.C.
N.C. 23 White/Black/Red 20
Out-5 N.O./N.C. 9 L1-4
- LOAD N.O. 24 Red/Black/White 19
Out-6 N.O./N.C. 10 2 1 OUT-4 N.O.
25 Green/Black/White 22
+V6/7 11 JMP5 L1-5
4 3 26 Orange/Black/White 21
Out-7 N.O./N.C. 12 OUT-5 N.C.
N.C. 27 Blue/Black/White 24
L1-5
N.O. 28 Black/Red/Green 23
OUT-5 N.O.
2 1 29 White/Red/Green 26
JMP6 L1-6
4 3 30 Red/Black/Green 25
OUT-6 N.C.
N.C. 31 Green/Black/Orange 28
L1-6
N.O. 32 Orange/Black/Green 27
2 1 OUT-6 N.O.
33 Blue/White/Orange 30
JMP7 L1-7
4 3 34 Black/White/Orange 29
OUT-7 N.C.
N.C. 35 White/Red/Orange 32
L1-7
N.O. 36 Orange/White/Blue 31
OUT-7 N.O.
2 1 37

1771-WD Swing Arm


From 1771-OZL

Conversion Module Installation and Application Considerations


 This Bul. 1492 cable consists of a cable wired to one 1756-OX8I RTB. Recommended cable lengths of 0.5M or 1.0M (005=0.5M),
010=1.0M). See table 2 for other lengths.
 The 1771-OZL module output resistive current limits versus 1756-OX8I limits are as follows:
(NOTE: For switching and inductive current ratings, refer to the modules Installation Instructions)
1771-OZL 1756-OX8I w/ 1492-CONCAB005Y
a) Current/Point 100mA @ 138V AC 2A @ 240V AC
100mA @ 138V DC 2A @ 30V DC
0.25A @ 125V DC
 The 1771-OZL module had a jumper selection of N.O. and N.C. outputs. The 1756-OX8I has both N.O. and N.C. outputs, but
selection is by wiring termination on the 1756 swing arm. The 1492-CM1771-LD012 conversion module replaces the functionality
of the 1771-OZL jumpers with eight jumpers (JMP0 through JMP7). In the default position, the output will be N.O. If a N.C. output is
required, change the jumper from pins 1-2 to pins 3-4.
 Refer to your 1771-OZL and 1756-OX8I Installation Manual wiring schematics and diagrams for more details. Ensure 1756 output
module ratings are not exceeded. [Reference Doc: 41171-014 (Version 00)]

Visit our website: www.ab.com


76 Publication 1492-SG121D-EN-P
Bulletin 1492
Bulletin 1771 to 1756 I/O Wiring Conversion System
Wiring Diagrams - Analog

Cat No. 1771-IFE to 1756-IF16 (Differential Current)

Visit our website: www.ab.com


Publication 1492-SG121D-EN-P 77
Bulletin 1492
Bulletin 1771 to 1756 I/O Wiring Conversion System
Wiring Diagrams - Analog

Cat No. 1771-IFE to 1756-IF16 (Differential Voltage)

Visit our website: www.ab.com


78 Publication 1492-SG121D-EN-P
Bulletin 1492
Bulletin 1771 to 1756 I/O Wiring Conversion System
Wiring Diagrams - Analog

Cat No. 1771-IFE to 1756-IF16 (Single-ended Current)

Visit our website: www.ab.com


Publication 1492-SG121D-EN-P 79
Bulletin 1492
Bulletin 1771 to 1756 I/O Wiring Conversion System
Wiring Diagrams - Analog

Cat No. 1771-IFE to 1756-IF16 (Single-ended Voltage)

Visit our website: www.ab.com


80 Publication 1492-SG121D-EN-P
Bulletin 1492
Bulletin 1771 to 1756 I/O Wiring Conversion System
Wiring Diagrams - Analog

Cat No. 1771-IFF to 1756-IF16 (Differential Current)

Visit our website: www.ab.com


Publication 1492-SG121D-EN-P 81
Bulletin 1492
Bulletin 1771 to 1756 I/O Wiring Conversion System
Wiring Diagrams - Analog

Cat No. 1771-IFF to 1756-IF16 (Differential Voltage)

Visit our website: www.ab.com


82 Publication 1492-SG121D-EN-P
Bulletin 1492
Bulletin 1771 to 1756 I/O Wiring Conversion System
Wiring Diagrams - Analog

Cat No. 1771-IFF to 1756-IF16 (Single-ended Current)

Visit our website: www.ab.com


Publication 1492-SG121D-EN-P 83
Bulletin 1492
Bulletin 1771 to 1756 I/O Wiring Conversion System
Wiring Diagrams - Analog

Cat No. 1771-IFF to 1756-IF16 (Single-ended Voltage)

Visit our website: www.ab.com


84 Publication 1492-SG121D-EN-P
Bulletin 1492
Bulletin 1771 to 1756 I/O Wiring Conversion System
Wiring Diagrams - Analog

Cat No. 1771-IL to 1756-IF8I (Voltage)

There are several key application considerations and system specifications (bottom of drawing) when using
WARNING
these components (conversion module, cable and input module). Read and understand these considerations
before installation.

Conversion Module
1492-CM1771-LA004 Cable
1756-IF8I
1492-CONACAB005L8
4-Wire Transmitter
+ + Vout_CH0 18 18 Orange/Red 2
Power Supply Transmitter RTN_CH0 17 17 6 Vout_CH0
- White/Red
- RTN_CH0
Vout_CH1 16 16 Black/Red 1
RTN_CH1 15 15 Vout_CH1
Blue/White 5 RTN_CH1
Vout_CH2 14 14 Green/White 10
RTN_CH2 13 13 Vout_CH2
Red/White 14
12 RTN_CH2
Vout_CH3 12 Black/White 9
RTN_CH3 11 11 Blue/Black 13 Vout_CH3
10 RTN_CH3
10 Orange/Black
9 9 Green/Black
Vout_CH4 8 8 Red/Black 18
7 7 Vout_CH4
RTN_CH4 White/Black 22
Vout_CH5 6 6 Blue 17 RTN_CH4
RTN_CH5 5 5 Orange
Vout_CH5
21 RTN_CH5
Vout_CH6 4 4 Red / Black 26
3 White / Black Vout_CH6
RTN_CH6 3 30
Vout_CH7 2 2 Blue RTN_CH6
25 Vout_CH7
RTN_CH7 1 1 Orange 29 RTN_CH7

3 3 N.C. 23 N.C.
4 N.C. 24 N.C.
7 N.C. 27 N.C.
8 N.C. 28 N.C.
11 N.C. 31 N.C.
12 N.C. 32 N.C.
15 N.C. 33 N.C.
SH 16 N.C. 34 N.C.
19 N.C. 35 N.C.
3 20 N.C. 36 N.C.

1771-WF Swing Arm


From 1771-IL

This Bul. 1492 cable consists of a cable wired to one 1756-IF8I RTB. Recommended cable lengths of
0.5M or 1.0M (005=0.5M, 010=1.0M).
SHIELD GROUNDING: In some installations, the field wiring shield was grounded on the 1771 chassis. If this was
the case, the installer must remove these shield connections from the 1771 chassis and they can be connected
to the grounding stud on the 1492-CM1771-LA004 module. The pre-wired cable used between the 1492-CM1771-LA004
module and the 1756-IF8I [1492-CONACAB005L8] provides a shield ground lug to ground the shield at the 1756
ControlLogix chassis, this must be connected. Do NOT connect this ground lug to the conversion module grounding stud.
The 1771-IL input configuration was software configured, as is the 1756-IF8I. Please ensure the correct configuration
in the 1756-IF8I.
Refer to your 1771-IL and 1756-IF8I Installation and User Manuals for additional information concerning comparisons
of module wiring, features and configuration details.

Visit our website: www.ab.com


Publication 1492-SG121D-EN-P 85
Bulletin 1492
Bulletin 1771 to 1756 I/O Wiring Conversion System
Wiring Diagrams - Analog

Cat No. 1771-IL to 1756-IF8I (Current)

There are several key application considerations and system specifications (bottom of drawing) when using
WARNING
these components (conversion module, cable and input module). Read and understand these considerations
before installation.

Conversion Module
1492-CM1771-LA004 Cable
1756-IF8I
1492-CONACAB005K8
4-Wire Transmitter
+ + Channel0 18 18 Orange/Red 4
Power Supply Transmitter Channel0 17 17 Iin_CH0
- White/Red 6
- 16 16
RTN_CH0
Channel1 Black/Red 3
Channel1 15 15 Iin_CH1
Blue/White 5 RTN_CH1
Channel2 14 14 Green/White 12
13
Iin_CH2
Channel2 13 Red/White 14
12 RTN_CH2
Channel3 12 Black/White 11
11 11 13 Iin_CH3
Channel3 Blue/Black
10 RTN_CH3
10 Orange/Black
9 9 Green/Black
2-Wire
Transmitter Channel4 8 8 Red/Black 20
+ Channel4 7 7 White/Black 22 Iin_CH4
6 6 Blue RTN_CH4
- Channel5 19
Channel5 5 5 Orange 21 Iin_CH5
4 RTN_CH5
Channel6 4 Red / Black 28
3 Iin_CH6
Channel6 3 White / Black 30
2 RTN_CH6
Channel7 2 Blue 27 Iin_CH7
Channel7 1 1 Orange 29 RTN_CH7

1 N.C. 23 N.C.
2 N.C. 24 N.C.
7 N.C. 25 N.C.
8 N.C. 26 N.C.
9 N.C. 31 N.C.
10 N.C. 32 N.C.
SH
15 N.C. 33 N.C.
16 N.C. 34 N.C.
17 N.C. 35 N.C.
18 N.C. 36 N.C.
1771-WF Swing Arm
From 1771-IL

CONVERSION MODULE INSTALLATION AND APPLICATION CONSIDERATIONS


This Bul. 1492 cable consists of a cable wired to one 1756-IF6I RTB. Recommended cable lengths of
0.5M or 1.0M (005=0.5M, 010=1.0M).
SHIELD GROUNDING: In some installations, the field wiring shield was grounded on the 1771 chassis. If this was
the case, the installer must remove these shield connections from the 1771 chassis and they can be connected
to the grounding stud on the 1492-CM1771-LA004 module. The pre-wired cable used between the 1492-CM1771-LA004
module and the 1756-IF8I [1492-CONACAB005K8] provides a shield ground lug to ground the shield at the 1756
ControlLogix chassis, this must be connected. Do NOT connect this ground lug to the conversion module grounding stud.
The 1771-IL input configuration was software configured, as is the 1756-IF8I. Please ensure the correct configuration
in the 1756-IF8I.
Refer to your 1771-IL and 1756-IF8I Installation and User Manuals for additional information concerning comparisons
of module wiring, features and configuration details.

Visit our website: www.ab.com


86 Publication 1492-SG121D-EN-P
Bulletin 1492
Bulletin 1771 to 1756 I/O Wiring Conversion System
Wiring Diagrams - Analog

Cat No. 1771-IL to 1756-IF6I (Voltage)

Visit our website: www.ab.com


Publication 1492-SG121D-EN-P 87
Bulletin 1492
Bulletin 1771 to 1756 I/O Wiring Conversion System
Wiring Diagrams - Analog

Cat No. 1771-IL to 1756-IF6I (Differential Current)

Visit our website: www.ab.com


88 Publication 1492-SG121D-EN-P
Bulletin 1492
Bulletin 1771 to 1756 I/O Wiring Conversion System
Wiring Diagrams - Analog

Cat No. 1771-IL to 1756-IF6I (Voltage - Qty. 2)

Visit our website: www.ab.com


Publication 1492-SG121D-EN-P 89
Bulletin 1492
Bulletin 1771 to 1756 I/O Wiring Conversion System
Wiring Diagrams - Analog

Cat No. 1771-IL to 1756-IF6I (Current- Qty. 2)

Conversion Module
1492-CM1771-LA004 Cable
1492-CONACAB005T1 1756-IF6I
4-Wire Transmitter
+ + Channel0 18 18 Orange/Red 3 IN-0/I
Power Supply Transmitter - Channel0 17 17 White/Red 5
RET-0
- Channel1 16 16 Black/Red 4
IN-1/I
Channel1 15 15 Blue/White 6
RET-1
Channel2 14 14 Green/White 9
IN-2/I
Channel2 13 13 Red/White 11
RET-2
Channel3 12 12 Black/White 10 IN-3/I
Channel3 11 11 Blue/Black 12
RET-3
10 10 Orange/Black 1
9 9 Green/Black IN-0/V
2-Wire 2
Channel4 8 8 Red/Black IN-1/V
Transmitter 7
+ Channel4 7 7 White/Black IN-2/V
8
6 6 Blue IN-3/V
- Channel5
Channel5 5 5 Orange
Channel6 4 4 Green
Channel6 3 3 Red 17
Channel7 2 2 White 19 IN-4/I
1 1 RET-4
Channel7 Black 18
IN-5/I
20 RET-5
15 IN-4/V
16 IN-5/V

 SH

1771-WF Swing Arm 1756-IF6I


From 1771-IL 3 IN-0/I
5
RET-0
4
IN-1/I
6
RET-1
9
IN-2/I
11
RET-2
10 IN-3/I
12
RET-3
1
IN-0/V
2
IN-1/V
7
IN-2/V
8
IN-3/V

17
19 IN-4/I
RET-4
18
IN-5/I
20 RET-5
15 IN-4/V
16 IN-5/V

Conversion Module Installation and Application Considerations


 This Bul. 1492 cable consists of a cable wired to two 1756-IF6I RTB. Recommended cable lengths of 0.5M or
1.0M (005=0.5M, 010=1.0M). See table 2 for other lengths.
 SHIELD GROUNDING: In some installations, the field wiring shield was grounded on the 1771 chassis. If this was
the case, the installer must remove these shield connections from the 1771 chassis and they can be connected to the grounding stud on the
1492-CM1771-LA004 module. The pre-wired cable used between the 1492-CM1771-LA004 module and the 1756-IF6I [1492-CONACAB005T1]
provides a shield ground lug to ground the shield at the 1756 ControlLogix chassis, this must be connected. Do NOT connect this ground lug to the
conversion module grounding stud.
 The 1771-IL input configuration was software configured, as is the 1756-IF6I. Please ensure the correct configuration in the 1756-IF6I.
 Refer to your 1771-IL and 1756-IF6I Installation and User Manuals for additional information concerning comparisons of module wiring, features
and configuration details.
 This configuration uses two (2) 1756-IF6I output modules to replace a single 1771-IL output module. This may require the use of a larger 1756
I/O chassis and conversion mounting assembly. Ensure there is sufficient panel space to allow for this possibility.
[Reference Doc: 41171-032 (Version 00)]

Visit our website: www.ab.com


90 Publication 1492-SG121D-EN-P
Bulletin 1492
Bulletin 1771 to 1756 I/O Wiring Conversion System
Wiring Diagrams - Analog

Cat No. 1771- IR to 1756-IR6I

Visit our website: www.ab.com


Publication 1492-SG121D-EN-P 91
Bulletin 1492
Bulletin 1771 to 1756 I/O Wiring Conversion System
Wiring Diagrams - Analog

Cat No. 1771-IXE to 1756-IT6I2

Visit our website: www.ab.com


92 Publication 1492-SG121D-EN-P
Bulletin 1492
Bulletin 1771 to 1756 I/O Wiring Conversion System
Wiring Diagrams - Analog

Cat No. 1771-IXE to 1756-IRT8I

Conversion Module
Cable
1492-CM1771-LA005 SER “B”
1492-CONACAB005G8 1756-IRT8I
Thermocouple
+ In_CH0+ 18 18 Orange/Red 3
In_CH0+
In_CH0- 17 17 White/Red 4
- In_CH0-
In_CH1+ 16 16 Black/Red 7
In_CH1+
In_CH1- 15 15 Blue/White 8
In_CH1-
In_CH2+ 14 14 Green/White 11 In_CH2+
In_CH2- 13 13 Red/White 12 In_CH2-
In_CH3+ 12 15
12 Black/White In_CH3+
In_CH3- 11 16
11 Blue/Black In_CH3-
CJC+ 10 10 Orange/Black 19 In_CH4+
CJC- 9 9 Green/Black 20 In_CH4-
In_CH4+ T
8 8 Red/Black 23 In_CH5+
In_CH4- 7 7 White/Black 24 In_CH5-
In_CH5+ 6 Blue 1 CJC+
6
In_CH5- 5 Orange 2 CJC-
5
In_CH6+ 4 27
4 Red/Black In_CH6+
In_CH6- 3 28
3 White/Black In_CH6-
In_CH7+ 2 2 Blue 31
In_CH7+
In_CH7- 1 1 Orange 32 In_CH7-

SH 5 N.C. 18 N.C.
6 N.C. 21 N.C.
9 N.C. 22 N.C.
10 N.C. 25 N.C.
13 N.C. 26 N.C.
14 N.C. 29 N.C.
17 N.C. 30 N.C.

1771-WI Swing Arm


From 1771-IXE
CONVERSION MODULE INSTALLATION AND APPLICATION CONSIDERATIONS
This Bul. 1492 cable consists of a cable wired to one 1756-IRT8I RTB. Recommended cable lengths of
0.5M or 1.0M (005=0.5M, 010=1.0M).
SHIELD GROUNDING: In some installations, the field wiring shield was grounded on the 1771 chassis. If this was
the case, the installer must remove these shield connections from the 1771 chassis and they can be connected
to the grounding stud on the 1492-CM1771-LA005 SER”B” module. The pre-wired cable used between the 1492-CM1771-LA005 SER”B”
module and the 1756-IRT8I [1492-CONACAB005G8] provides a shield ground lug to ground the shield at the 1756
ControlLogix chassis, this must be connected. Do NOT connect this ground lug to the conversion module grounding stud.
The 1771-IXE has built CJC (cold junction compensation) into the swing-arm. The conversion module [1492-CM1771-LA005 SER”B”]
passes this CJC signal to the 1756-IRT8I. Ensure that the 1756-IRT8I is configured for external CJC.
The 1771-IXE input configuration was software configured, as is the 1756-IRT8I. Please ensure the correct configuration
in the 1756-IRT8I.
Refer to your 1771-IXE and 1756-IRT8I Installation and User Manuals for additional information concerning comparisons
of module wiring, features and configuration details.

Visit our website: www.ab.com


Publication 1492-SG121D-EN-P 93
Bulletin 1492
Bulletin 1771 to 1756 I/O Wiring Conversion System
Wiring Diagrams - Analog

Cat No. 1771-IXHR to 1756-IT6I2

Visit our website: www.ab.com


94 Publication 1492-SG121D-EN-P
Bulletin 1492
Bulletin 1771 to 1756 I/O Wiring Conversion System
Wiring Diagrams - Analog

Cat No. 1771-IXHR to 1756-IRT8I

Conversion Module
Cable
1492-CM1771-LA005 SER “B”
1492-CONACAB005G8 1756-IRT8I
Thermocouple
+ In_CH0+ 18 18 Orange/Red 3
In_CH0+
In_CH0- 17 17 White/Red 4
- In_CH0-
In_CH1+ 16 16 Black/Red 7
In_CH1+
In_CH1- 15 15 Blue/White 8
In_CH1-
In_CH2+ 14 14 Green/White 11 In_CH2+
In_CH2- 13 13 Red/White 12
In_CH3+ In_CH2-
12 12 Black/White 15 In_CH3+
In_CH3- 11 16
11 Blue/Black In_CH3-
CJC+ 10 10 Orange/Black 19 In_CH4+
CJC- 9 9 Green/Black 20 In_CH4-
In_CH4+ T
8 8 Red/Black 23 In_CH5+
In_CH4- 7 7 White/Black 24 In_CH5-
In_CH5+ 6 Blue 1 CJC+
6
In_CH5- 5 Orange 2 CJC-
5
In_CH6+ 4 27
4 Red/Black In_CH6+
In_CH6- 3 28
3 White/Black In_CH6-
In_CH7+ 2 2 Blue 31
In_CH7+
In_CH7- 1 1 Orange 32 In_CH7-

SH 5 N.C. 18 N.C.
6 N.C. 21 N.C.
9 N.C. 22 N.C.
10 N.C. 25 N.C.
13 N.C. 26 N.C.
14 N.C. 29 N.C.
17 N.C. 30 N.C.

1771-WI Swing Arm


From 1771-IXHR
CONVERSION MODULE INSTALLATION AND APPLICATION CONSIDERATIONS
This Bul. 1492 cable consists of a cable wired to one 1756-IRT8I RTB. Recommended cable lengths of
0.5M or 1.0M (005=0.5M, 010=1.0M).
SHIELD GROUNDING: In some installations, the field wiring shield was grounded on the 1771 chassis. If this was
the case, the installer must remove these shield connections from the 1771 chassis and they can be connected
to the grounding stud on the 1492-CM1771-LA005 SER”B” module. The pre-wired cable used between the 1492-CM1771-LA005 SER”B”
module and the 1756-IRT8I [1492-CONACAB005G8] provides a shield ground lug to ground the shield at the 1756
ControlLogix chassis, this must be connected. Do NOT connect this ground lug to the conversion module grounding stud.

The 1771-IXHR has built CJC (cold junction compensation) into the swing-arm. The conversion module [1492-CM1771-LA005 SER”B”]
passes this CJC signal to the 1756-IRT8I. Ensure that the 1756-IRT8I is configured for external CJC.
The 1771-IXHR input configuration was software configured, as is the 1756-IRT8I. Please ensure the correct configuration
in the 1756-IRT8I.
Refer to your 1771-IXHR and 1756-IRT8I Installation and User Manuals for additional information concerning comparisons
of module wiring, features and configuration details.

Visit our website: www.ab.com


Publication 1492-SG121D-EN-P 95
Bulletin 1492
Bulletin 1771 to 1756 I/O Wiring Conversion System
Wiring Diagrams - Analog

Cat No. 1771-OFE1 to 1756-OF6VI

Visit our website: www.ab.com


96 Publication 1492-SG121D-EN-P
Bulletin 1492
Bulletin 1771 to 1756 I/O Wiring Conversion System
Wiring Diagrams - Analog

Cat No. 1771-OFE2 to 1756-OF6CI

Visit our website: www.ab.com


Publication 1492-SG121D-EN-P 97
Bulletin 1492
Bulletin 1771 to 1756 I/O Wiring Conversion System
Wiring Diagrams - High Resolution Isolated Analog

Cat No. 1771-NIS to 1756-IF6CIS (Qty. 2)

WARNING There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Interface Module
1771-RTP4
B1
Cable “B” 1756-IF6CIS
SH N/A
 W2 B2 N/A
1492-CONACAB020N2
W3 B3 N/A
R8 B4 15 Red

 12 I-RTN-3
I8 B5 16 White/Red
10 I-OUT-3
S8 A4
O8 A5
R7 B8 18 Green
11 I-RTN-2
I7 B9 19 Yellow
9 I-OUT-2
S7 A6
O7 A7
R6 B12 21 Brown I-RTN-1
6
I6 B13 22 White/Black
I-OUT-1
S6 4
A8
O6 A9
R5 B16 24 Black
I-RTN-0
5
I5 B17 25 Violet
3 I-OUT-0
O5 A10
S5 A11

W1 A1 N/A
CR A2 N/A
Cable “A” 1756-IF6CIS
CL A3 N/A 1492-CONACAB020N2
R4 B12 15 Red
12 I-RTN-3 
I4 B13 16 White/Red
10 I-OUT-3
S4 A12
A13
- O4
R3 B14 18 Green
24VDC CURRENT 11 I-RTN-2
I3 B15 19 Yellow
SUPPLY LOAD
S3 9 I-OUT-2
A14
+ O3 A15
R2 B16 21 Brown
6 I-RTN-1
I2 B17 22 White/Black
4 I-OUT-1
S2 A16
O2 A17
+ 24VDC - R1 B18 24 Black
CURRENT SUPPLY 5 I-RTN-0
I1 B19 25 Violet
LOAD 3 I-OUT-0
O1 A19
S1 A18

Conversion Module Installation and Application Considerations


 Cables are available in 2.0m, or 5.0m
 Terminals starting with A are the lower row of terminals, B terminals are the upper row.
 Follow your PLC Analog User Manual for proper shield grounding instructions.
 RTN terminals are internally connected on the 1756-IF6CIS.
 Terminals w1, w2, w3, are spares used for field wire convenience. NOTE: This is only true for module RTP4. The
Bul. 1492 cable does not connect to these terminals.
[Reference Doc: 41171-073 (Version 00)]

Visit our website: www.ab.com


98 Publication 1492-SG121D-EN-P
Bulletin 1492
Bulletin 1771 to 1756 I/O Wiring Conversion System
Wiring Diagrams - High Resolution Isolated Analog

Cat No. 1771-NIV to 1756-IF6I (Current - Qty. 2)

WARNING There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Interface Module
1771-RTP3
SH B1 Cable “B”
N/A 1756-IF6I
 W2 B2 N/A
1492-CONACAB020N3
W3 B3 N/A
R8 B4 15 White/Red
12 RTN-3

 I8 B5 16 Orange
10 IN-3/I
S8 A4
8 IN-3/V
O8 A5
- R7 B8 18 Green
24VDC CURRENT 11 RTN-2
I7 B9 19 White/Orange
SUPPLY LOAD 9 IN-2/I
S7
+ O7
A6
A7
7 IN-2/V
R6 B12 21 White/Black
RTN-1
6
I6 B13 22 Gray
4 IN-1/I
S6 A8
2 IN-1/V
O6 A9
R5 B16 24 White RTN-0
5
I5 B17 25 Black
3 IN-0/I
O5 A10 IN-0/V
1
S5 A11

W1 A1 N/A
Cable “A”
CR A2 N/A 1756-IF6I
1492-CONACAB020N3
CL A3 N/A
R4 B12 15 White/Red
12 RTN-3

I4 B13 16 Orange
10 IN-3/I
S4 A12
8 IN-3/V
O4 A13
R3 B14 18 Green
11 RTN-2
I3 B15 19 White/Orange
S3 9 IN-2/I
A14
O3 7 IN-2/V
A15
R2 B16 21 White/Black
6 RTN-1
I2 B17 22 Gray
S2 4 IN-1/I
A16
O2 2 IN-1/V
A17
+ 24VDC - R1 B18 24 White
CURRENT SUPPLY 5 RTN-0
LOAD I1 B19 25 Black
3 IN-0/I
O1 A19
1 IN-0/V
S1 A18

Conversion Module Installation and Application Considerations


 Cables are available in 2.0m, or 5.0m
 Terminals starting with A are the lower row of terminals, B terminals are the upper row.
 Follow your PLC Analog User Manual for proper shield grounding instructions.
 RTN terminals are internally connected on the 1756-IF6I.
 Terminals w1, w2, w3, are spares used for field wire convenience. NOTE: This is only true for module RTP3. The
Bul. 1492 cable does not connect to these terminals.
[Reference Doc: 41171-074 (Version 00)]

Visit our website: www.ab.com


Publication 1492-SG121D-EN-P 99
Bulletin 1492
Bulletin 1771 to 1756 I/O Wiring Conversion System
Wiring Diagrams - High Resolution Isolated Analog

Cat No. 1771-NIV to 1756-IF6I (Voltage - Qty. 2)

WARNING There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Interface Module 1756-IF6I


1771-RTP4
Cable “B”
SH B1 N/A
 W2 B2 N/A
1492-CONACAB020N7
W3 B3 N/A
15

R8 B4 White/Red
12 RTN-3 
I8 B5 16 Red
8 IN-3V
S8 A4
O8 A5
- R7 B8 19 Green
VOLTAGE 11 RTN-2
I7 B9 18 Yellow
LOAD 7 IN-2V
+ S7
O7
A6
A7
R6 B12 22 White/Black
6 RTN-1
I6 B13 21 Brown
S6 2 IN-1V
A8
O6 A9
R5 B16 24 Black
5 RTN-0
I5 B17 25 Violet
1 IN-0V
O5 A10
S5 A11

W1 A1 N/A
CR A2 N/A
Cable “A” 1756-IF6I
CL A3 N/A
1492-CONACAB020N7
R4 B12 15 White/Red
12 RTN-3

I4 B13 16 Red
8 IN-3V
S4 A12
O4 A13
R3 B14 18 Green
11 RTN-2
I3 B15 19 Yellow
S3 7 IN-2V
A14
O3 A15
R2 B16 21 White/Black
6 RTN-1
I2 B17 22 Brown
S2 2 IN-1V
A16
O2 A17
- R1 B18 24 Black
VOLTAGE 5 RTN-0
I1 B19 25 Violet
LOAD 1 IN-0V
+ O1
S1
A19
A18

Conversion Module Installation and Application Considerations


 Cables are available in 2.0m, or 5.0m
 Terminals starting with A are the lower row of terminals, B terminals are the upper row.
 Follow your PLC Analog User Manual for proper shield grounding instructions.
 RTN terminals are internally connected on the 1756-IF6I.
 Terminals w1, w2, w3, are spares used for field wire convenience. NOTE: This is only true for module RTP4. The
Bul. 1492 cable does not connect to these terminals.
[Reference Doc: 41171-080 (Version 00)]

Visit our website: www.ab.com


100 Publication 1492-SG121D-EN-P
Bulletin 1492
Bulletin 1771 to 1756 I/O Wiring Conversion System
Wiring Diagrams - High Resolution Isolated Analog

Cat No. 1771-NIV to 1756-IF6I (Qty. 2, Current and Voltage)

WARNING There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Interface Module
Cable “B”
1771-RTP4
1492-CONACAB010N3 
SH B1 N/A
(Current)
 W2 B2 N/A 1756-IF6I
W3 B3 N/A
R8 B4 15 White/Red 
 I8 B5 16 Orange
12 RTN-3
10 IN-3/I
S8 A4
8 IN-3/V
- O8
R7
A5
B8 18 Green
CURRENT 11 RTN-2
I7 B9 19 White/Orange
LOAD 9 IN-2/I
S7 A6
7 IN-2/V
+ O7 A7
R6 B12 21 White/Black
6 RTN-1
I6 B13 22 Gray
4 IN-1/I
S6 A8
O6 2 IN-1/V
A9
R5 B16 24 White
5 RTN-0
I5 B17 25 Black
3 IN-0/I
O5 A10
1 IN-0/V
S5 A11

Cable “A”
W1 A1 N/A
CR
1492-CONACAB010N7  1756-IF6I
A2 N/A
CL A3 N/A
(Voltage)
R4 B12 15 White/Red
12 RTN-3 
I4 B13 16 Orange
S4 A12 8 IN-3V
O4 A13
R3 B14 18 Green
I3 B15 19 White/Orange
11 RTN-2
S3 7 IN-2V
A14
O3 A15
R2 B16 21 White/Black
I2 6 RTN-1
B17 22 Gray
S2 2 IN-1V
A16
O2 A17
- R1 B18 24 White
Voltage 5 RTN-0
LOAD I1 B19 25 Black
1 IN-0V
+ O1 A19
S1 A18

Conversion Module Installation and Application Considerations


 Cables are available in 2.0m, or 5.0m
 Terminals starting with A are the lower row of terminals, B terminals are the upper row.
 Follow your PLC Analog User Manual for proper shield grounding instructions.
 RTN terminals are internally connected on the 1756-IF6I.
 Terminals w1, w2, w3, are spares used for field wire convenience. NOTE: This is only true for module RTP3. The
Bul. 1492 cable does not connect to these terminals.
[Reference Doc: 41171-038 (Version 00)]

Visit our website: www.ab.com


Publication 1492-SG121D-EN-P 101
Bulletin 1492
Bulletin 1771 to 1756 I/O Wiring Conversion System
Wiring Diagrams - High Resolution Isolated Analog

Cat No. 1771-NIV to 1756-IF6I (Qty. 2, Voltage and Current)

WARNING There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Interface Module 1756-IF6I


1771-RTP4 Cable “B”
SH B1 N/A 1492-CONACAB020N7 
 W2 B2 N/A (Voltage)
W3 B3 N/A
15

R8 B4 White/Red
12 RTN-3 
I8 B5 16 Red
8 IN-3V
S8 A4
O8 A5
- R7 B8 19 Green
VOLTAGE 18 11 RTN-2
I7 B9 Yellow
LOAD 7 IN-2V
+ S7
O7
A6
A7
R6 B12 22 White/Black
6 RTN-1
I6 B13 21 Brown
S6 2 IN-1V
A8
O6 A9
R5 B16 24 Black
5 RTN-0
I5 B17 25 Violet
1 IN-0V
O5 A10
S5 A11

Cable “A”
W1 A1 N/A
CR A2 N/A
1492-CONACAB010N3  1756-IF6I
CL A3 N/A
(Current)
R4 B12 15 White/Red
12 RTN-3 
I4 B13 16 Red
10 IN-3/I
S4 A12
8 IN-3/V
O4 A13
R3 B14 18 Green
11 RTN-2
I3 B15 19 Yellow
S3 9 IN-2/I
A14
O3 7 IN-2/V
A15
R2 B16 21 White/Black
I2 6 RTN-1
B17 22 Brown
S2 4 IN-1/I
A16
O2 2 IN-1/V
A17
- R1 B18 24 Black
CURRENT 5 RTN-0
I1 B19 25 Violet
LOAD 3 IN-0/I
+ O1
S1
A19
A18
1 IN-0/V

Conversion Module Installation and Application Considerations


 Cables are available in 2.0m, or 5.0m
 Terminals starting with A are the lower row of terminals, B terminals are the upper row.
 Follow your PLC Analog User Manual for proper shield grounding instructions.
 RTN terminals are internally connected on the 1756-IF6I.
 Terminals w1, w2, w3, are spares used for field wire convenience. NOTE: This is only true for module RTP4. The
Bul. 1492 cable does not connect to these terminals.
[Reference Doc: 41171-039 (Version 00)]

Visit our website: www.ab.com


102 Publication 1492-SG121D-EN-P
Bulletin 1492
Bulletin 1771 to 1756 I/O Wiring Conversion System
Wiring Diagrams - High Resolution Isolated Analog

Cat No. 1771-NIV1 to 1756-IF6I (Qty. 2, Voltage)

WARNING There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Interface Module 1756-IF6I


1771-RTP4
Cable “B”
SH B1 N/A
 W2 B2 N/A
1492-CONACAB020N7
W3 B3 N/A
15

R8 B4 White/Red
12 RTN-3 
I8 B5 16 Red
8 IN-3V
S8 A4
O8 A5
- R7 B8 18 Green
VOLTAGE 19 11 RTN-2
I7 B9 Yellow
LOAD 7 IN-2V
+ S7
O7
A6
A7
R6 B12 21 White/Black
6 RTN-1
I6 B13 22 Brown
S6 2 IN-1V
A8
O6 A9
R5 B16 24 Black
5 RTN-0
I5 B17 25 Violet
1 IN-0V
O5 A10
S5 A11

W1 A1 N/A
CR A2 N/A
Cable “A” 1756-IF6I
CL A3 N/A
1492-CONACAB020N7
R4 B12 15 White/Red
12 RTN-3

I4 B13 16 Red
8 IN-3V
S4 A12
O4 A13
R3 B14 18 Green
11 RTN-2
I3 B15 19 Yellow
S3 7 IN-2V
A14
O3 A15
R2 B16 21 White/Black
6 RTN-1
I2 B17 22 Brown
2 IN-1V
S2 A16
O2 A17
- R1 B18 24 Black
VOLTAGE 5 RTN-0
I1 B19 25 Violet
LOAD 1 IN-0V
+ O1
S1
A19
A18

Conversion Module Installation and Application Considerations


 Cables are available in 2.0m, or 5.0m
 Terminals starting with A are the lower row of terminals, B terminals are the upper row.
 Follow your PLC Analog User Manual for proper shield grounding instructions.
 RTN terminals are internally connected on the 1756-IF6I.
 Terminals w1, w2, w3, are spares used for field wire convenience. NOTE: This is only true for module RTP4. The
Bul. 1492 cable does not connect to these terminals.
[Reference Doc: 41171-078 (Version 00)]

Visit our website: www.ab.com


Publication 1492-SG121D-EN-P 103
Bulletin 1492
Bulletin 1771 to 1756 I/O Wiring Conversion System
Wiring Diagrams - High Resolution Isolated Analog

Cat No. 1771-NOC to 1756-OF6CI (Qty. 2)

WARNING There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Interface Module
1771-RTP3 or RTP4
SH B1 N/A
Cable “B”
 W2 B2 N/A 1492-CONACAB020N1 1756-OF6CI
W3 B3 N/A
R8 B4 12

15 White/Red
RTN-3 
I8 B5
S8 A4
O8 A5 4 Orange 8 OUT-3
R7 B8 18 Green 11 RTN-2
I7 B9
S7 A6
O7 A7 7 White/Orange 7 OUT-2
R6 B12 21 White/Black 6 RTN-1
I6 B13
S6 A8
O6 A9 10 Gray 2 OUT-1
R5 B16 24 Black 5 RTN-0
I5 B17
O5 A10 13 White 1 OUT-0
S5 A11

W1 A1 N/A
Cable “A” 1756-OF6CI
CR A2 N/A
CL A3 N/A
1492-CONACAB020N1
R4 B12 15 12
White/Red
RTN-3 
I4 B13
S4 A12
O4 A13 4 Orange 8 OUT-3
R3 B14 18 Green 11 RTN-2
I3 B15
S3 A14
O3 A15 7 White/Orange 7 OUT-2
R2 B16 21 White/Black 6 RTN-1
I2 B17
S2 A16
O2 A17 10 2
+
Gray
OUT-1
R1 B18 24 Black 5
CURRENT RTN-0
LOAD I1 B19
O1 A19 13 1 OUT-0
- S1 A18 White

Conversion Module Installation and Application Considerations


 Cables are available in 2.0m, or 5.0m
 Terminals starting with A are the lower row of terminals, B terminals are the upper row.
 Follow your PLC Analog User Manual for proper shield grounding instructions.
 RTN terminals are internally connected on the 1756-OF6CI.
 Terminals w1, w2, w3, are spares used for field wire convenience. NOTE: This is only true for modules RTP3 and
RTP4. The Bul. 1492 cable does not connect to these terminals.
[Reference Doc: 41171-072 (Version 00)]

Visit our website: www.ab.com


104 Publication 1492-SG121D-EN-P
Bulletin 1492
Bulletin 1771 to 1756 I/O Wiring Conversion System
Wiring Diagrams - High Resolution Isolated Analog

Cat No. 1771-NOC to 1756-OF8

WARNING There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Interface Module
1771-RTP3 or 1771-RTP4 1756-OF8
SH B1 Cable “B”
W2 B2 1492-CONACAB020N8
W3 B3
R8 B4 15 White/Red
 I8 B5
S8 A4
O8 A5 4 Orange 20 I-OUT-7
R7 B8 18 Green
16 I-RTN
I7 B9
S7 A6
O7 A7 7 White/Orange 14 I-OUT-6
R6 B12 21 White/Black
I6 B13 22
S6 A8
O6 A9 10 Gray
10 I-OUT-5
R5 B16 24 Black
6 I-RTN
I5 B17
O5 A10 13 White
4 I-OUT-4
S5 A11

W1 A1
Cable “A”
CR A2
CL A3
1492-CONACAB020N8
R4 B12 15 White/Red 
I4 B13
S4 A12
O4 A13 4 Orange
19 I-OUT-3
R3 B14 18 Green
15 I-RTN
I3 B15
S3 A14
O3 A15 7 White/Orange 13 I-OUT-2
R2 B16 21 White/Black
I2 B17
S2 A16
O2 A17 10 Gray
9 I-OUT-1
R1 B18 24 Black
CURRENT 5 I-RTN
LOAD I1 B19
O1 A19 13
S1 3 I-OUT-0
A18 White

Conversion Module Installation and Application Considerations


 Cables are available in 2.0m, or 5.0m
 Terminals starting with A are the lower row of terminals, B terminals are the upper row.
 Follow your PLC Analog User Manual for proper shield grounding instructions.
 RTN terminals are internally connected on the 1756-OF8.
 Terminals w1, w2, w3, are spares used for field wire convenience. NOTE: This is only true for module RTP3 and RTP4.
The Bul. 1492 cable does not connect to these terminals.
 The 1771-NOC module provides channel to channel isolation, the 1756-OF8 does not. A conversion from 1771-NOC to an
isolated 1756-OF8 is avalible.
[Reference Doc: 41171-079 (Version 00)]

Visit our website: www.ab.com


Publication 1492-SG121D-EN-P 105
Bulletin 1492
Bulletin 1771 to 1756 I/O Wiring Conversion System
Wiring Diagrams - High Resolution Isolated Analog

Cat No. 1771-NOV to 1756-OF6VI (Qty. 2)

WARNING There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Interface Module
1771-RTP3 or RTP4
SH B1 N/A
Cable “B”
 W2 B2 N/A 1492-CONACAB020N1 1756-OF6VI
W3 B3 N/A
R8 B4 12

15 White/Red
RTN-3 
I8 B5
S8 A4
O8 A5 4 Orange 8 OUT-3
R7 B8 18 Green 11 RTN-2
I7 B9
S7 A6
O7 A7 7 White/Orange 7 OUT-2
R6 B12 21 White/Black 6 RTN-1
I6 B13
S6 A8
O6 A9 10 Gray 2 OUT-1
R5 B16 24 Black 5 RTN-0
I5 B17
O5 A10 13 White 1 OUT-0
S5 A11

W1 A1 N/A
Cable “A” 1756-OF6VI
CR A2 N/A
CL A3 N/A
1492-CONACAB020N1
R4 B12 15 12
White/Red
RTN-3 
I4 B13
S4 A12
O4 A13 4 Orange 8 OUT-3
R3 B14 18 Green 11 RTN-2
I3 B15
S3 A14
O3 A15 7 White/Orange 7 OUT-2
R2 B16 21 White/Black 6 RTN-1
I2 B17
S2 A16
O2 A17 10 Gray 2
- R1 B18 24 Black 5
OUT-1
VOLTAGE RTN-0
LOAD I1 B19
O1 A19 13 1 OUT-0
+ S1 A18 White

Conversion Module Installation and Application Considerations


 Cables are available in 2.0m, or 5.0m
 Terminals starting with A are the lower row of terminals, B terminals are the upper row.
 Follow your PLC Analog User Manual for proper shield grounding instructions.
 RTN terminals are internally connected on the 1756-OF6VI.
 Terminals w1, w2, w3, are spares used for field wire convenience. NOTE: This is only true for modules RTP3 and
RTP4. The Bul. 1492 cable does not connect to these terminals.
[Reference Doc: 41171-081 (Version 00)]

Visit our website: www.ab.com


106 Publication 1492-SG121D-EN-P
Bulletin 1492
Bulletin 1771 to 1756 I/O Wiring Conversion System
Wiring Diagrams - High Resolution Isolated Analog

Cat No. 1771-NR to 1756-IR6I

WARNING There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Interface Module
1771-RTP4
B1
Cable “B”
SH N/A 1756-IR6I
W2 B2 N/A
1492-CONACAB020N4
W3 B3 N/A
R8 B4 15 12 RTN-3 
I8 B5 16 10 IN-3/B
S8 A4
O8 A5 4 8 IN-3/A
R7 B8 18 11 RTN-2
I7 B9 19
RTD 9 IN-2/B
TRANSMITTER S7 A6
O7 A7 7 7 IN-2/A
R6 B12 21
6 RTN-1
I6 B13 22
S6 4 IN-1/B
A8
O6 A9 10
2 IN-1/A
R5 B16 24
5 RTN-0
I5 B17 25
3 IN-0/B
O5 A10 13
1 IN-0/A
S5 A11

W1 A1 N/A
Cable “A”
CR A2 N/A 1756-IR6I
1492-CONACAB020N4
CL A3 N/A
R4 B12 15 White/Red
12 RTN-3 
I4 B13 16 Red
10 IN-3/B
S4 A12
O4 A13 4 Orange 8 IN-3/A
R3 B14 18 Green
11 RTN-2
I3 B15 19 Yellow
9 IN-2/B
S3 A14
O3 A15 7 White/Orange
7 IN-2/A
R2 B16 21 White/Black
I2 6 RTN-1
B17 22 Brown
S2 4 IN-1/B
A16
O2 A17 10 Gray
2 IN-1/A
R1 B18 24 Black
5 RTN-0
I1 B19 25 Violet
RTD 3 IN-0/B
TRANSMITTER O1 A19 13 White
1 IN-0/A
S1 A18

Conversion Module Installation and Application Considerations


 Cables are available in 2.0m, or 5.0m
 Terminals starting with A are the lower row of terminals, B terminals are the upper row.
 Follow your PLC Analog User Manual for proper shield grounding instructions.
 RTN terminals are internally connected on the 1756-IR6I.
 Terminals w1, w2, w3, are spares used for field wire convenience. NOTE: This is only true for module RTP4. The Bul.
1492 cable does not connect to these terminals.

[Reference Doc: 41171-075 (Version 00)]

Visit our website: www.ab.com


Publication 1492-SG121D-EN-P 107
Bulletin 1492
Bulletin 1771 to 1756 I/O Wiring Conversion System
Wiring Diagrams - High Resolution Isolated Analog

Cat No. 1771-NT1 to 1756-IT6I (Qty. 2)

WARNING There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

1771-RT41 1
1492-CONACAB020N5 1756-IT6I
4 SH B1 Cable “B”
W1 A1
2 White/Red
R4 B2 15 12 RTN-3
I4 B3 16 Red
8 IN-3
S4 A2
O4 A3
THERMOCOUPLE
- R3 B4 18 Green
Yellow
11 RTN-2
I3 B5 19
7 IN-2
S3 A4
+ O3 A5

White/Violet
10 CJC+
Thermocouple White/Grey
14 CJC-

R2 B6 21 White/Black
6 RTN-1
I2 B7 22 Brown
2 IN-1
S2 A6
O2 A7
R1 B8 24 Black
5 RTN-0
I1 B9 25 Violet
1 IN-0
O1 A9
S1 A8

1771-RT41 1
1492-CONACAB020N5 1756-IT6I
4 SH B1 Cable “A”
W1 A1
2 White/Red
R4 B2 15 12 RTN-3
I4 B3 16 Red
8 IN-3
S4 A2
O4 A3
THERMOCOUPLE
- R3 B4 18 Green
Yellow
11 RTN-2
I3 B5 19
7 IN-2
S3 A4
+ O3 A5
White/Violet
10 CJC+
Thermocouple White/Grey
14 CJC-

R2 B6 21 White/Black
6 RTN-1
I2 B7 22 Brown
2 IN-1
S2 A6
O2 A7
R1 B8 24 Black
5 RTN-0
I1 B9 25 Violet
1 IN-0
O1 A9
S1 A8

CONVERSION MODULE INSTALLATION


AND APPLICATION CONSIDERATIONS
 Cables are available in 2.0M or 5.0M.
 Terminals starting with A are the lower row of
terminals, B terminals are the upper row.
 Follow your PLC Analog User Manual for proper
shield grounding instructions. 41171-076 (02)
 Terminals W1, W2 and W3 are spares used for field wire
convenience. NOTE. This is only true for modules RT41 .
The Bul. 1492 cable does not connect to these terminals.

Visit our website: www.ab.com


108 Publication 1492-SG121D-EN-P
Bulletin 1492
Bulletin 1771 to 1756 I/O Wiring Conversion System
Wiring Diagrams - High Resolution Isolated Analog

Cat No. 1771-NT1 to 1756-IT6I2 (Qty. 2)

WARNING There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

1771-RT41 1
1492-CONACAB020N6 1756-IT6I2
4 SH B1 Cable “B”
W1 A1
2 White/Red
R4 B2 15 12 RTN-3
I4 B3 16 Red
11 IN-3
S4 A2
O4 A3
THERMOCOUPLE
- B4 18 Green
R3 10 RTN-2
I3 B5 19 Yellow
9 IN-2
S3 A4
+ O3 A5
White/Violet
3 CJC+
Thermocouple White/Grey
4 CJC-

R2 B6 21 White/Black
8 RTN-1
I2 B7 22 Brown
7 IN-1
S2 A6
O2 A7
R1 B8 24 Black
6 RTN-0
I1 B9 25 Violet
5 IN-0
O1 A9
S1 A8

1771-RT41 1
1492-CONACAB020N6 1756-IT6I2
4 SH B1 Cable “A”
W1 A1
2 White/Red
R4 B2 15 12 RTN-3
I4 B3 16 Red
11 IN-3
S4 A2
O4 A3
THERMOCOUPLE
- R3 B4 18 Green
Yellow
10 RTN-2
I3 B5 19
9 IN-2
S3 A4
+ O3 A5

White/Violet
3 CJC+
Thermocouple White/Grey
4 CJC-

R2 B6 21 White/Black
8 RTN-1
I2 B7 22 Brown
7 IN-1
S2 A6
O2 A7
R1 B8 24 Black
6 RTN-0
I1 B9 25 Violet
5 IN-0
O1 A9
S1 A8

CONVERSION MODULE INSTALLATION


AND APPLICATION CONSIDERATIONS
 Cables are available in 2.0M or 5.0M.
 Terminals starting with A are the lower row of
terminals, B terminals are the upper row.
 Follow your PLC Analog User Manual for proper
shield grounding instructions. 41171-086 (00)
 Terminals W1, W2 and W3 are spares used for field wire
convenience. NOTE. This is only true for modules RT41 .
The Bul. 1492 cable does not connect to these terminals.

Visit our website: www.ab.com


Publication 1492-SG121D-EN-P 109
Bulletin 1492
Bulletin 1771 to 1756 I/O Wiring Conversion System
Wiring Diagrams - High Resolution Isolated Analog

Cat No. 1771-NT2 to 1756-IT6I2 (Qty. 2)

WARNING There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

1771-RT41 1
1492-CONACAB020N6 1756-IT6I2
4 SH B1 Cable “B”
W1 A1
2 White/Red
R4 B2 15 12 RTN-3
I4 B3 16 Red
11 IN-3
S4 A2
O4 A3
THERMOCOUPLE
- R3 B4 18 Green
Yellow
10 RTN-2
I3 B5 19
9 IN-2
S3 A4
+ O3 A5
White/Violet
3 CJC+
Thermocouple White/Grey
4 CJC-

R2 B6 21 White/Black
8 RTN-1
I2 B7 22 Brown
7 IN-1
S2 A6
O2 A7
R1 B8 24 Black
6 RTN-0
I1 B9 25 Violet
5 IN-0
O1 A9
S1 A8

1771-RT41 1
1492-CONACAB020N6 1756-IT6I2
4 SH B1 Cable “A”
W1 A1
2 White/Red
R4 B2 15 12 RTN-3
I4 B3 16 Red
11 IN-3
S4 A2
O4 A3
THERMOCOUPLE
- R3 B4 18 Green
Yellow
10 RTN-2
I3 B5 19
9 IN-2
S3 A4
+ O3 A5
White/Violet
3 CJC+
Thermocouple White/Grey
4 CJC-

R2 B6 21 White/Black
8 RTN-1
I2 B7 22 Brown
7 IN-1
S2 A6
O2 A7
R1 B8 24 Black
6 RTN-0
I1 B9 25 Violet
5 IN-0
O1 A9
S1 A8

CONVERSION MODULE INSTALLATION


AND APPLICATION CONSIDERATIONS
 Cables are available in 2.0M or 5.0M.
 Terminals starting with A are the lower row of
terminals, B terminals are the upper row.
 Follow your PLC Analog User Manual for proper
shield grounding instructions. 41171-077 (01)
 Terminals W1, W2 and W3 are spares used for field wire
convenience. NOTE. This is only true for modules RT41 .
The Bul. 1492 cable does not connect to these terminals.

Visit our website: www.ab.com


110 Publication 1492-SG121D-EN-P
Bulletin 1492
Bulletin 1771 to 1756 I/O Wiring Conversion System
Wiring Diagrams - High Resolution Isolated Analog, Combination Modules

Cat No. 1771-NIVR to 1756-IF6I (Voltage) and 1756-IR6I (RTD)

WARNING There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Interface Module
1771-RTP4
Cable “B”
SH B1 N/A 1756-IR6I
1492-CONACAB020N4
W2 B2 N/A
W3 B3 N/A
R8 B4 15 12 RTN-3 
 I8 B5 16 10 IN-3/B
S8 A4
O8 A5 4 8 IN-3/A
R7 B8 18 11 RTN-2
I7 B9 19
RTD 9 IN-2/B
TRANSMITTER S7 A6
O7 A7 7 7 IN-2/A
R6 B12 21
6 RTN-1
I6 B13 22
S6 4 IN-1/B
A8
O6 A9 10
2 IN-1/A
R5 B16 24
5 RTN-0
I5 B17 25 3 IN-0/B
O5 A10 13
1 IN-0/A
S5 A11

W1 A1 N/A
CR A2 N/A
Cable “A” 1756-IF6I
CL A3 N/A
1492-CONACAB020N7
R4 B12 15 White/Red
12 RTN-3

I4 B13 16 Red
8 IN-3V
S4 A12
O4 A13
R3 B14 18 Green
11 RTN-2
I3 B15 19 Yellow
S3 7 IN-2V
A14
O3 A15
R2 B16 21 White/Black
6 RTN-1
I2 B17 22 Brown
S2 2 IN-1V
A16
O2 A17
- R1 B18 24 Black
VOLTAGE 5 RTN-0
I1 B19 25 Violet
LOAD 1 IN-0V
+ O1
S1
A19
A18

Conversion Module Installation and Application Considerations


 Cables are available in 2.0m, or 5.0m
 Terminals starting with A are the lower row of terminals, B terminals are the upper row.
 Follow your PLC Analog User Manual for proper shield grounding instructions.
 RTN terminals are internally connected on the 1756-IF6I & IR6I.
 Terminals w1, w2, w3, are spares used for field wire convenience. NOTE: This is only true for module RTP4. The
Bul. 1492 cable does not connect to these terminals.
[Reference Doc: 41171-082 (Version 00)]

Visit our website: www.ab.com


Publication 1492-SG121D-EN-P 111
Bulletin 1492
Bulletin 1771 to 1756 I/O Wiring Conversion System
Wiring Diagrams - High Resolution Isolated Analog, Combination Modules

Cat No. 1771-NIVR to 1756-IF6I (Current) and 1756-IR6I (RTD)

WARNING There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Interface Module
1771-RTP4
Cable “B”
SH B1 N/A 1756-IR6I
1492-CONACAB020N4
W2 B2 N/A
W3 B3 N/A
R8 B4 15 12 RTN-3 
 I8 B5 16 10 IN-3/B
S8 A4
O8 A5 4 8 IN-3/A
R7 B8 18 11 RTN-2
I7 B9 19
RTD 9 IN-2/B
TRANSMITTER S7 A6
O7 A7 7 7 IN-2/A
R6 B12 21
6 RTN-1
I6 B13 22
S6 4 IN-1/B
A8
O6 A9 10
2 IN-1/A
R5 B16 24
5 RTN-0
I5 B17 25 3 IN-0/B
O5 A10 13
1 IN-0/A
S5 A11

W1 A1 N/A
Cable “A”
CR A2 N/A 1756-IF6I
1492-CONACAB020N3
CL A3 N/A
R4 B12 15 White/Red
12 RTN-3

I4 B13 16 Orange
10 IN-3/I
S4 A12
8 IN-3/V
O4 A13
R3 B14 18 Green
11 RTN-2
I3 B15 19 White/Orange
S3 9 IN-2/I
A14
O3 7 IN-2/V
A15
R2 B16 21 White/Black
6 RTN-1
I2 B17 22 Gray
4 IN-1/I
S2 A16
O2 2 IN-1/V
A17
- R1 B18 24 White
VOLTAGE 5 RTN-0
I1 B19 25 Black
LOAD 3 IN-0/I
+ O1
S1
A19
A18
1 IN-0/V

Conversion Module Installation and Application Considerations


 Cables are available in 2.0m, or 5.0m
 Terminals starting with A are the lower row of terminals, B terminals are the upper row.
 Follow your PLC Analog User Manual for proper shield grounding instructions.
 RTN terminals are internally connected on the 1756-IF6I & IR6I.
 Terminals w1, w2, w3, are spares used for field wire convenience. NOTE: This is only true for module RTP4. The
Bul. 1492 cable does not connect to these terminals.
[Reference Doc: 41171-083 (Version 00)]

Visit our website: www.ab.com


112 Publication 1492-SG121D-EN-P
Bulletin 1492
Bulletin 1771 to 1756 I/O Wiring Conversion System
Wiring Diagrams - High Resolution Isolated Analog, Combination Modules

Cat No. 1771-NIVT to 1756-IF6I (Voltage) and 1756-IT6I (Thermocouple)

WARNING There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Interface Module
1771-RTP1
Cable “B”
4 SH B1 1492-CONACAB010N5 1756-IT6I
W2 B2
2 W3 B3
White/Red
R8 B4 15 12 RTN-3
I8 B5 16 Red
11 IN-3
THERMOCOUPLE S8 A4
O8 A5
- B8 18 Green
R7 10 RTN-2
I7 B9 19 Yellow
9 IN-2
S7 A6
+ O7 A7
R6 B12 21 White/Black
8 RTN-1
I6 B13 22 Brown
7 IN-1
S6 A8
O6 A9
R5 B16 24 Black
6 RTN-0
I5 B17 25 Violet
5 IN-0
O5 A10
S5 A11
10 CJC+
CABLE “B” CJC-
14 14
Thermocouple 1

W1 A1
CR A2 Cable “A” 1756-IF6I
CL A3 1492-CONACAB020N7
R4 B12 15 12 RTN-3
I4 B13 16
8 IN-3V
S4 A12
O4 A13
R3 B14 18
11 RTN-2
I3 B15 19
S3 7 IN-2V
A14
O3 A15
R2 B16 21 6 RTN-1
I2 B17 22 2 IN-1V
S2 A16
O2 A17
- R1 B18 24
VOLTAGE 5 RTN-0
I1 B19 25
LOAD 1 IN-0V
O1
+ S1
A19
A18

Conversion Module Installation and Application Considerations


Cables are available in 2.0m, or 5.0m
Terminals starting with A are the lower row of terminals, B terminals are the upper row.
Follow your PLC Analog User Manual for proper shield grounding instructions.
RTN terminals are internally connected on the 1756-IF6I.
Terminals w1, w2, w3, are spares used for field wire convenience. NOTE: This is only true for module RTP4. The
Bul. 1492 cable does not connect to these terminals.
[Reference Doc: 41171-084 (Version 00)]

Visit our website: www.ab.com


Publication 1492-SG121D-EN-P 113
Bulletin 1492
Bulletin 1771 to 1756 I/O Wiring Conversion System
Wiring Diagrams - High Resolution Isolated Analog, Combination Modules

Cat No. 1771-NIVT to 1756-IF6I (Current) and 1756-IT6I (Thermocouple)

WARNING There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Interface Module
1771-RTP1

SH B1 Cable “B” 1756-IT6I


4
W2 B2 1492-CONACAB010N5
2 W3 B3
White/Red
R8 B4 15 12 RTN-3
I8 B5 16 Red
8 IN-3
THERMOCOUPLE S8 A4
O8 A5
- R7 B8 18 Green
Yellow
11 RTN-2
I7 B9 19
7 IN-2
S7 A6
+ O7 A7
R6 B12 21 White/Black
6 RTN-1
I6 B13 22 Brown
2 IN-1
S6 A8
O6 A9
R5 B16 24 Black
5 RTN-0
I5 B17 25 Violet
1 IN-0
O5 A10
S5 A11
10 CJC+
CABLE “B” CJC-
14 14
Thermocouple 1

W1 A1 N/A Cable “A”


CR A2
1756-IF6I
N/A
1492-CONACAB010N3
CL A3 N/A
R4 B12 15 White/Red
12 RTN-3

I4 B13 16 Orange
10 IN-3/I
S4 A12
8 IN-3/V
O4 A13
R3 B14 18 Green
11 RTN-2
I3 B15 19 White/Orange
S3 9 IN-2/I
A14
O3 7 IN-2/V
A15
R2 B16 21 White/Black
6 RTN-1
I2 B17 22 Gray
4 IN-1/I
S2 A16
2 IN-1/V
O2 A17
- R1 B18 24 White
RTN-0
CURRENT 5
I1 B19 25 Black
LOAD 3 IN-0/I
O1
+ S1
A19
A18
1 IN-0/V

Conversion Module Installation and Application Considerations


 Cables are available in 2.0m, or 5.0m
 Terminals starting with A are the lower row of terminals, B terminals are the upper row.
 Follow your PLC Analog User Manual for proper shield grounding instructions.
 RTN terminals are internally connected on the 1756-IF6I.
 Terminals w1, w2, w3, are spares used for field wire convenience. NOTE: This is only true for module RTP4. The
Bul. 1492 cable does not connect to these terminals.
[Reference Doc: 41171-085 (Version 00)]

Visit our website: www.ab.com


114 Publication 1492-SG121D-EN-P
Allen-Bradley, Rockwell Software, and ControlLogix are trademarks of Rockwell Automation, Inc.

Publication 1492-SG121D-EN-P – October 2014


Supercedes Publication 1492-SG121C-EN-P – June 2013 Copyright ©2014 Rockwell Automation, Inc. All Rights Reserved. Printed in USA.

Вам также может понравиться