Академический Документы
Профессиональный Документы
Культура Документы
The oil in transformer construction serves double purpose of cooling and insulating. For use
in transformer tanks, oil has to fulfill certain specifications and must be carefully selected.
All oils are good insulators, but animal oils are either too viscous or tend to form fatty acids,
which attack fibrous materials (e.g. cotton) and so are unsuitable for transformers.
Vegetable oils are apt to be inconsistent in quality and, like animal oils, which alone are
suitable for electrical purposes, some have a bituminous and others a paraffin base. The
crude oil, as tapped is distilled, producing a range of volatile spirits and oils ranging from
the very light to the heavy, and ending with semi-solids like petroleum jelly, paraffin wax,
or bitumen.
The chemical composition of oil consists of four major generic class of organic compounds,
namely, paraffins, napthelenes, aromatics and olefines. All these are hydrocarbons and
hence insulating oil is called a pure hydrocarbon mineral oil. It is desirable to have more of
saturated paraffins, less of aromatic and/or napthalenes and none of olefines.
Refer Table-11.1 for the characteristics of oil as per IS:335-1983 are listed below :
Table-11.1 :
8 30 kv (rms)
(a) As received
50 kv (rms)
(b) After filtration
Dielectric dissipation factor (Tan ) at
9 0.005
90oC, max.
Specific resistance (resistivity), min.
30 x 1012 cm
10 (a) At 90oC
500 x 1012 cm
(b) At 27oC
Oxidation stability :
• Viscosity - determines the rate of cooling, and varies with temperature. A high
viscosity is an obvious disadvantage because of sluggish flow through small
apertures which it entails.
• Moisture Content - The amount of free and dissolved water present in the oil is its
moisture content and is expressed in ppm. Presence of moisture is harmful since it
adversely affects the electrical characteristics of oil and accelerates deterioration of
insulating paper.
• Flash Point - The temperature at which the vapour above an oil surface ignites
spontaneously is termed as flash point. A flash point not more than 1600C is usually
considered for safety reasons.
• Fire Point - The temperature at which an oil will ignite and continue burning is
about 25% above the flash point, or about 2000C.
• Pour Point - It is the temperature at which oil will flow under the prescribed
conditions. If the oil becomes too viscous or solidifies, it will hinder the formation of
convention currents and thus cooling of equipment will be severely affected.
• Electric Strength (BDV) - It is the voltage at which breakdown occurs between two
electrodes when oil is subjected to an electric field under prescribed conditions.
Electric strength is the basic parameter for insulation system design of a
transformer.
• Purity - The oil must not contain impurities such as sulphur and its compounds, as
sulphur causes corrosion of metal parts and accelerates the formation of sludge.
• Acidity - Among the products of oxidation of transformer oil are CO2, volatile water-
soluble organic acids, and water. These in combination can attack and corrode iron
and other metals. The provision of breathers not only prevent the ingress of damp
air, but helps on out-breathing to absorb any moisture produced by the oxidation of
oil.
• Oxidation Stability - It is the measure of neutralization value and sludge after oil is
aged by simulating the actual service conditions of a transformer. It is important to
find out for new oil but not for oil in service and shows the presence of natural
inhibitors which impart anti-oxidation characteristics to oil.
11.2 Sampling :
The condition of oil should be checked before use. Samples of oil from the transformer
should be taken from the bottom of the tank as both water and water saturated oil are
heavier than clean and dry oil and sink to the bottom of the container. The sample bottles
should be rinsed with oil.
Receptacles for samples should preferably be bottles of clear glass with ground glass
stoppers and of 1 litre capacity. Sample bottles should not be filled to the top. They shall be
clean and dry. If the electrical test cannot be carried out immediately, these bottles shall be
hermetically sealed to prevent contamination of oil. Touching the inside of a receptacle with
a damp hand or wiping round with an apparently clean dry cloth may seriously reduce the
breakdown strength of a sample of good oil.
When taking samples from the tank, remove all dirt from the sampling valve of plug. To
ensure that the valve is clean, allow some oil to flow into a separate receptacle before
collecting sample for testing for its dielectric strength as per the latest edition of IS:6792. It
is expected that every sample passes the test, if the normal transit and storage precautions
are taken.
TESTS
Tan , Resistivity,
Break Down Voltage Dissolved Gas
Interfacial Tension &
Test & Water Content. Analysis
Acidity Tests.
Monitoring is
Oil needs Filtration Oil needs Reclamation necessary to find
or Replacement out the gravity of
incipient fault.
Transformer needs
Result of Filtration Result of Reclamation
attention during
or Replacement.
usual outages.
The significance of various routine tests such as Break Down Voltage Test, Test to find the
Water Content, Resistivity, Di-electric Dissipation Factor (Tan ), Acidity, Interfacial Tension
are described below.
Break Down Voltage is the voltage at which the oil breaks down when subjected to an AC
electrical field with a continuously increasing voltage contained in a specific apparatus. The
voltage is expressed in KV.
BDV can reveal conductive contaminants, such as the rust or other metallic cuttings, dirt,
cellulosic fibres, filter dust or free water but it will not pinpoint the presence of dissolved
water below 80% saturation, acids or sludges.
Keeping in mind higher operating temperatures experience has shown that erroneous
conclusions can be drawn if the oil is tested at a temperature in excess of 400C because of
the phenomena of water solubility.
Sample of BDV should be protected from contact with light, air and moisture. The sample
should be drawn quickly kept in a sealed container and tested within a matter of few hours.
Water content is expressed as parts per million (ppm) w/w in oil. Water may originate from
the atmosphere or be produced by the deterioration of the insulating material. Its presence
in oil is harmful as it lowers the electric strength and resistivity of the oil and accelerates the
deterioration of the solid insulating materials, particularly paper.
A mineral oil of low water content is necessary to achieve adequate electrical strength to
maximize the insulation system life and to minimize metal corrosion.
It is the ratio of the DC potential gradient in volts per centimeter paralleling the current flow
within the specimens to the current density in amperes per square centimeter at a given
instant of time and under prescribed conditions. This is numerically equal to the resistance
between opposite faces of a centimeter cube of the liquid. It is expressed in Cm.
Dielectric Dissipation Factor is a Tangent of the angle by which the phase difference
between applied voltage and resulting current deviates from /2 radian when the dielectric of
the capacitor consists exclusively of the transformer oil.
Measurements of Tan , Resistivity and to a lesser extent the interfacial tension of the oil
enable contamination due to polar substances to be detected and periodically assessed.
[Polar substances are oil soluble compounds resulting from the oxidation of the oil itself, or
from the solution in the oil of external contaminants or materials used in the construction of
the equipment].
Power factor has been a traditional field test. However this test measures the leakage
current through the oil, which is a measure of the contamination or deterioration. It does
tell the presence of polar materials but other tests must be made to determine what polar
compounds are present.
When water is held in solution no appreciable effect on the oil's power nor dielectric
strength may take place. However since oil oxidation further increases oil's ability to
dissolve moisture, some type of sludges have very little effect on the overall power factor.
This test is very sensitive to the presence in oil of the soluble contaminants and aging
products. Changes in this characteristic can be monitored regularly.
It is the measure of the free organic and inorganic acids present together in the oil. It is
expressed in terms of the number of milligrams of KOH required to neutralize the total free
acids in one gram of the oil.
This is most common method that measures the acidity in transformers. The organic acids
are detrimental to the insulation system and can induce rusting of iron when moisture is
also present. An increase in neutralization number is an index to the rate of deterioration of
the oil. Sludge will be the inevitable product of an acid situation that is neglected.
A low acidity in oil is required to minimize electrical conduction and metal corrosion and to
maximize the life of the insulation system. How high acidity value can lead to sludge
formation is demonstrated in the following Table-11.3.5 (Historical Database indicating
relationship between Acidity and Sludge formation in Oil filled Transformers - 11 Years test
on 500 Transformers).
Table-11.4.5 :
Acidity
Percent of
S.No Units Sludged
mg of KOH/gm of 500
Oil
1 0.00 to 0.10 00 00
2 0.11 to 0.20 38 190
3 0.21 to 0.60 72 360
4 0.61 and above 100 500
11.4.6 Interfacial Tension Test :
It is a force necessary to detach a planar ring of platinum wire from the surface of the liquid
of higher surface tension that is upward from the water - oil surface. It is expressed in N/m
or Dynes/Cm.
The characteristic changes fairly rapidly during the first stages of aging. Afterwards the rate
of change decreases as the value themselves become lower.
The old workhorse of transformer oil quality testing is the less the tension. Interfacial
tension test results are thus related to the degree of the oils oxidation. The very first sign of
the sludge in solution may be in the range of 0.027 to 0.030 N/m while a badly sludging
deteriorated oil has an IFT of 0.018 N/m or less.
IFT test measures the tension at the interface between two immissible liquids oil and water
and is expressed in N/m. This test is extremely sensitive to the presence of oil decay
products and soluble polar contaminants from solid insulating materials.
Good clean oil will normally lay on top of water and will yield an IFT of 0.040 to 0.050 N/m.
Oil oxidation contaminants will lower the IFT even further. These contaminants are
hydrophilic which means they have an affinity for water molecules as well as for oil
molecules. At the interface the hydrophilic materials extend across to the water so that a
vertical linkage is established and thus the lateral linkage [Which makes up the surface
tension] is weakened. The interface is now less distinct and the tension at the interface is
reduced. The greater the concentration of contaminants less the tension. IFT values and
sludge formation can be understood from the following Table - 11.4.6 (Historical Database
indicating relationship between IFT and Sludge formation in Oil filled Transformers - 11
Years test on 500 Transformers).
Table-11.4.6 :
Interfacial
Tension Percent of
S.No Units Sludged
500
N/m
1 Below 0.014 100 500
2 0.014 to 0.016 85 425
3 0.016 to 0.018 69 345
4 0.018 to 0.020 35 175
5 0.020 to 0.022 33 165
6 0.022 to 0.024 30 150
7 Above 0.024 00 000
11.5 Relationship between Various Tests & Factors affecting Test Results :
The factors which affects the various test results are given in Table - 11.5 for a better
understanding of the results from interpretation point of view.
Table-11.5 :
Factors not
Factors Responsible
S.No Test Responsible for
for Results
Results
1 Break Down Voltage Free water, dirt, Dissolved water below
conductive particles 80% saturation, acids
and contaminants such and sludges.
as rust, metallic
cuttings, filter dust.
Sludges, oxidation
products, oil decay
Dielectric Dissipation
2 products, Dissolved water.
Factor (Tan )
contaminants, free
water.
Contaminants such as
3 Resistivity metal salts, water in all -
forms, acids.
Hydrophilic
contaminants like
soluble polar impurities,
4 Interfacial Tension
oil decay products
dissolved sludge, -
oxidation by products.
Organic and inorganic
5 Acidity acids, KOH consuming -
impurities.
Free water, dissolved
6 Water -
water, combined water.
11.6 Dissolved Gas Analysis :
Gases may be formed in all oil-filled electrical equipment due to natural aging, but also to a
much greater extent as a result of faults; i.e. heat flux generated in the core winding. The
principal mechanisms of gases formation includes Oxidation, Vapourisation, Insulation
decomposition, Oil breakdown, and Electrolytic action.
Operation with a fault may seriously damage the equipment and it is valuable to be able to
detect the fault at an early stage of development.
Usually, under normal conditions, the gas dissolved in the transformer oil has the following
composition : Nitrogen - 70 to 79%, Oxygen - 20 to 30%, and Methane - 0.1 to 0.2%;
Hydrogen & Acetylene are absent. A sharp change in the composition (for example, 50 to
70% Hydrogen, 3 to 10% Methane, 10 to 25% Acetylene, 4 to 8% Oxygen) testifies to a
grave internal fault accompanied by arcing (insulation puncture, shorted turns, flashover in
the contact system of the tap-changer, etc.). In case of minor faults not accompanied by
violent oil decomposition and gas evolution, the gas composition may be : 2 to 5%
Hydrogen, 0.5 to 1% Methane, 0.5 to 2% Acetylene, 85 to 92% Nitrogen and 5 to 8%
Oxygen. Such gas composition bears witness to a fault, such as shorted parallel conductors
in the windings, poor contacts in the tap connections or soldered joints, or closed paths in
the magnetic system of the core, which, if not remedied, may eventually lead to serious
trouble.
In case of a fault, its type and its severity may often be inferred from the composition of the
gases and the rate at which they are formed. In the case of an incipient fault, the gases
formed remain partly dissolved in the liquid insulation; free gases will divide between the
gaseous and liquid phases by diffusion. Diffusion and achievement of saturation both take
time, during which serious damage to the equipment can occur undetected.
Periodic analysis of oil samples for the amount and composition of dissolved gases forms a
means of detecting faults. (Normally once in a year for transformers 10MVA & above rating)
.
Depending upon the energy released in the core upon the occurrence of faults, the gases
are also different. Normally the faults are of four types as per the energy releases are
concerned.
c. Overheated Oil - Decomposition products include ethylene and methane, with smaller
quantities of hydrogen and ethane. A large quantity of Ethylene is a key indicator and,
if the fault is severe, traces of acetylene may be present.
d. Overheated Cellulose - Large quantities of carbon monoxide and carbon dioxide are
evolved from overheated cellulose. Other gases will also be present if the fault involves an
oil-impregnated structure. As cellulose will degrade under normal transformer operating
temperatures, CO and CO2 will be found in significant quantities in healthy transformers. A
significant increase in the CO/CO2 ratio is usually a key indicator of overheated
cellulose.
Threshold fault gas levels of various gases for transformers which have been in service for a
few years, as suggested by Dornenberg and Strittmatter and the U.S. Bureau of
Reclamation are mentioned below :
A convenient basis for fault diagnosis is the calculation of ratios of the concentrations of the
gases present. The ratios used in the interpretation methods summerised in Table-11.6.2
are :
Table-11.6.2 :