Вы находитесь на странице: 1из 13

Licensed copy from CIS: watermanpart, Waterman Partnership, 21/01/2017, Uncontrolled Copy.

A single copy of this document is licensed to

watermanpart

On

21/01/2017

This is an uncontrolled copy. Ensure use of the


most current version of the document by searching
the Construction Information Service.
Structural fire engineering design: Digest 487
materials behaviour – masonry Part 3
R de Vekey PhD MRSC CChem DIC
digest
BRE Centre for Whole Life Construction and Conservation
Licensed copy from CIS: watermanpart, Waterman Partnership, 21/01/2017, Uncontrolled Copy.

This Digest is part of a suite of related documents containing guidance


for the construction industry on structural fire engineering design. The
intention is to produce performance based guidance that brings
together fire engineering and structural engineering providing a
framework within which designers are free to develop site specific
solutions based on real performance criteria. The Digests contain
information complementary to the existing and emerging fire
engineering codes and standards. Each Digest may be used in isolation
or as part of the full integrated suite.
In this Part, three broad design methodologies for masonry are described:
● traditional prescriptive, test based;
● simple performance based by combining test based and other data; Figure 1 Perforated building blocks with
● via modelling. mortarless interlocking vertical joints which
need rendering both sides to give optimum
fire insulation

Masonry is a very versatile material and, in all its ● As infill walls in frames which divide up spaces
roles, may bear loads resulting from applied forces and provide sound insulation, fire resistance,
such as wind, stacking forces, impacts and seismic thermal insulation and security barriers
events. It may also provide sound insulation, fire between them while providing shear stiffness to
resistance, thermal insulation and security barriers the overall structure.
between the internal spaces and the external
environment or between two internal spaces. Masonry is inherently fire resistant and refractory
External walls also provide barriers to snow, rain, (ie heat resistant). It has moderately good thermal
sun and wind, and all walls can provide attractive insulation properties so that it can also be used as a
and durable finishes internally and, more protective layer for other materials such as iron,
commonly, externally. There are three broad steel and timber used in structural roles. It can also
applications of masonry in modern construction. be used to form columns, piers and other vertical
loadbearing elements, and – when reinforced or
● Complete loadbearing structures in which formed into arches – beams and floors.
masonry walls bear the vertical loads of the Since the Great Fire of London, masonry party
walls above, the floors, roofs etc, occupancy walls have been accepted as one of the better ways
loads, and satisfy many other functions. of providing fire barriers between adjacent
dwellings and for compartmentalising larger
● As exterior cladding walls in which the buildings to prevent the spread of fire.
masonry resists the actions of rain, weather,
movement and any locally imposed vertical and
lateral loads while providing shear stiffness to
the overall structure.
2
Integrity (criterion E)
Basic fire design principles for masonry
A separating barrier wall will be deemed to fail if it allows
In the context of designing masonry structures to resist fire, significant amounts of hot gases or flames to penetrate during
virtually all historical and contemporary design methods are the test which ignite a standard cotton test sample.
based on the performance of masonry elements and never on
the whole performance of complete masonry structures. One Thermal insulation (criterion I)
of the reasons is that masonry is only very rarely the sole A separating barrier wall will be deemed to fail if it allows the
material in a structure. It is almost always combined with temperature of the side opposite the fire face to exceed a
timber or concrete floors and roofs; timber or steel in internal specified level. In EN 1996-1-2 the specific requirement is
Licensed copy from CIS: watermanpart, Waterman Partnership, 21/01/2017, Uncontrolled Copy.

partitions; metal fixings and many other materials. This that the average temperature of the face remote from the fire
diversity of materials complicates structures to the point should not rise by more than 140 ºC and that the temperature
where it would not be economically feasible to consider rise at any point should not rise by more than 180 ºC.
testing every material in a structure. It also makes calculation
methods for whole structures too complex to solve routinely. Mechanical impact (criterion M)
As a result most design methods (in Codes and Standards) The wall should resist a lateral horizontal impact load. In
are based on the performance of elements: for masonry, EN 1996-1-2 the specific requirement is that the wall should
usually panel walls. Three principle options have been resist a horizontal load as specified in EN 1363-2.
explored for design methods which are: Walls or elements not carrying out a separating function
● design by worst-case testing of specific complete element (eg a masonry column within a room) are not judged by these
(usually panel) types and their tabulation. Times to failure integrity and insulation criteria.
under a standardised test regime are tabulated. Most of the
available data only covers unperforated walls; Spread of flame
● design by synthesis of layer sub-elements, assessed either Most conventional masonry elements do not contain
by testing or on the basis of simplified models; sufficient content of organic compounds to support surface
● full design, using theoretical models which take into spread of fire, intrinsic conflagration or charring and
account all possible modes of failure. therefore will normally have a rating of A1 for the purposes
of classification without test. Some products are
All the alternative methods have to deal with three main manufactured incorporating integral layers of foamed
potential criteria, R, E and I (see below), for failure of organic polymer, either within hollow cores on one surface or
compartment separating barriers in fire (modes of failure), in the form of a sandwich structure with an organic core. In
and, in special circumstances, two further criteria, M and standard fire tests these have been shown to give no problem,
spread of flame. provided that the foam layer is contained within a masonry
cavity and layered elements are tied to prevent separation.
Stability (criterion R) Clearly, if the foam layer is exposed within or without the
A wall acting as a fire barrier will be deemed to fail if it building, the products would have to be rated for surface
collapses or is structurally damaged so that it no longer spread of flame.
supports an applied load or action. Typically, loadbearing Additionally, some masonry products incorporate organic
walls are tested with an applied vertical load. Non- aggregates and if this content exceeds 1% they are required to
loadbearing walls, which just bear their own weight and that be assessed by test.
of any applied finishes, are not usually judged under this
criterion. Loadbearing walls will, by definition of the test
methodology, have a restraint at the base and the top of the
wall but may not have restraints at the vertical edges. Some
tests on non-loadbearing panels are carried out between
vertical restraining reactions to evaluate the effect of
differential heating and expansion on bowing. Test methods
usually exclude support from other restraints such as floors or
roof structures or conventional masonry returns (which are
the most common supports in practice) but are carried out on
wall sizes which would normally span between such
restraints.
3

Fire performance of masonry materials Ancillary materials used to improve the fire
Firstly, masonry needs to be defined. It is an assemblage of
resistance of masonry
discrete pieces (units) of natural stone, clay, concrete, Although masonry, in most of its forms, is intrinsically
calcium silicate, gypsum, glass etc, stabilised and sealed with resistant to the effects of fire, it depends on connections to
mortar. The mortar is an inorganic setting mastic usually other stabilising elements to maintain its stability. Moreover,
containing sand and a hydraulic binder. The units can be any many fire performance characteristics can be improved by
shape but are most effective when in the form of rectangular use of metal ties, reinforcement and surface coatings. Most
prisms which naturally bond together to give optimum masonry contains openings to allow human access, service
Licensed copy from CIS: watermanpart, Waterman Partnership, 21/01/2017, Uncontrolled Copy.

stability and strength. Although unmortared (dry-stone) penetrations, ventilation and natural light entry. Ancillary
walls exist, they would automatically fail the integrity and materials may be required to prevent fire leakage via these
insulation criteria and so cannot be considered. Some openings.
products used in continental Europe have an interlocking
baffle in place of the vertical mortar joints (Figure 1, page 1) Stability ancillaries
and will only be satisfactory as a fire barrier if both masonry Smaller masonry box structures are intrinsically stable if they
faces are coated with a fire resistant finish such as render or are masonry bonded at corners and junctions, and tied at the
plaster. intersections with floor and roof structures. In cases where
Because of the wide range of masonry products, fire masonry bonding is difficult, or inadvisable due to
performance is diverse. However, a number of basic rules differential movement problems, metal ties may be used. The
operate and determine the performance; these are that: two leaves of cavity walls act in common by using ties. In
● all masonry materials are sufficiently refractory to prevent longer, flatter structures, vertical movement joints become
wholesale melting or significant softening when subject to necessary to protect against movement cracking. Some
normal building fires. Some surface melting may occur in continuity at joints can be provided by using slip ties at these
longer fires. junctions; alternatively they may be located at vertical
● most masonry materials are inherently completely non- intersecting walls and are independently tied. Horizontal
flammable. movement joints are also necessary at the heads of panels
● most masonry materials, in thicknesses exceeding requiring slip ties to stabilise the masonry and possibly some
125 mm, have sufficient thermal resistance to prevent form of movement-tolerant fire resistant sealing system such
failure by the insulation criterion for several hours. as intumescent paint or sealants, or rolling seals.
● most masonry materials, even in dry conditions, contain Infill walls in frame structures need ties at their peripheries
sufficient equilibrium moisture content within their pore to ensure that the walls are retained under a fire load.
system to delay temperature rise above 100 ºC for a Bed joint reinforcement is widely used for crack
considerable time. prevention and may reduce the risk of failure due to bowing
● most masonry materials have a sufficiently open porosity in fires by acting as a catenary support while itself being
to allow the free escape of volatile components, so protected from the full effects of the fire by the masonry.
preventing explosive spalling type failures. Floors and roofs are tied using straps complying with
● very low porosity masonry materials (eg engineering prescriptive specifications given in Approved Document
bricks and granites) normally have a high tensile strength A1/2 to the Building Regulations[2] or in the small building
and insufficient volatile content to suffer explosive code, BS 8103-1[3] (Figure 2).
spalling type failures. However, some dense concrete
products may have sufficient combined water to be prone
to spalling.
● hollow and perforated masonry units may suffer * Strap only required
in special cases
progressive spalling of the fire face due to shearing
of the cross webs by thermally induced
differential strains.
● while bowing of masonry is a potential
*
mechanism for failure and is discussed at
length by Cooke[1], it has not been the
*
predominant mode of failure in
simulation tests. *

*
Figure 2 Typical positions for straps in loadbearing
domestic houses recommended in BS 8103-1
4

Surface coatings The test methods reflect the type of restraint conditions for
which there will be a reasonable body of data. For instance,
The use of surface coatings on masonry to improve other non-loadbearing walls may be tested with no top restraint
factors such as rain and air resistance, thermal resistance, beyond a simple support. This means that any restraint
flatness and appearance is widespread. Most non-flammable against vertical expansion that is likely to occur in infill
coatings will also improve the fire performance, particularly panels in frames during a fire will not be modelled in the test
of the fire-affected side, provided that they are well-bonded data. However this support applies to any panel with a soft
and don’t suffer premature spalling. Incorporating light joint or flexible fire stop at the top. Equally, test apparatus
reinforcement in these coatings (eg wire meshes, expanded may have no restraint against horizontal expansion although
Licensed copy from CIS: watermanpart, Waterman Partnership, 21/01/2017, Uncontrolled Copy.

metals or fibrous additives such as glass or polypropylene) this would be an unusual edge condition in real panels, either
may improve their resistance to spalling; insulating infilled or spanning between walls at right angles. However,
aggregates (eg exfoliated vermiculite or perlite) can improve many panels in modern buildings will have vertical soft
their performance as thermal barriers. joints; these would usually provide simple support but offer
no restraint against horizontal expansion. Many tests are
recorded as restrained (ie where a panel is built into a frame);
Design using current Codes of practice the panel may self-load during a fire test due to expansion but
the resultant in-plane stresses are not measured.
The main design method used is design-by-test of specific In a test, a loadbearing panel will have a simple lateral
complete elements (usually unperforated panel) types. support at the top together with a load applied either to the top
Times-to-failure under a standardised test regime are using deadweights or hydraulic rams or to the bottom using
tabulated. These methods are entirely prescriptive in function hydraulic rams. This means that there is no restraint against
and are based on assumed worst-case test scenarios where the vertical expansion beyond the reaction of the load.
fire load is not limited and temperatures might reach between Loadbearing test panels are not normally supported at their
1000 and 1100 °C. vertical edges although this is an unusual support condition in
The Standards (listed in ‘Further reading’ on page 12) are real walls.
generally descriptive methods of test. The tests are broadly All these restraint conditions are only usually important to
simulations of what has been observed to occur in real fires the mechanism if failure is due to structural collapse and only
but they are formalised and embody many assumptions about affect integrity failure or temperature rise if they induce
support, restraint and wall size (about 3 x 3 m). Also, in most cracking. This means that the bulk of the available fire testing
cases, they only simulate the case of an infinite fire load. For data cannot be used to develop structural behaviour models
masonry they are almost invariably tests of panels either since a structural failure will not have occurred.
regarded as non-loadbearing such as internal partition walls, On the basis of such testing and subject to factors of safety,
infill walls in frame structures, and cladding; or loadbearing lists of wall types are drawn up in which each wall is defined
walls, most commonly used in small dwelling houses and by material type (eg concrete); its geometrical form (eg
small-to-medium rise flats. Columns and piers can also be hollow block); the gross thickness of the wall; and the type,
tested but very little data exists in the public domain for thickness and number of layers of covering (eg gypsum
masonry elements other than plain unperforated walls. (The plaster). The slenderness ratio of walls is not covered
bibliography at the end of this Digest contains a list of explicitly but is covered, in effect, by the thickness in relation
appropriate national and international standards.) to the standard test wall dimensions. In UK codes, special
Figures 3 and 4 opposite, based on the UK Code of tabulations are provided for cavity walls but European codes
practice[4], give a graphic feel for the likely performance of base performance on that of the fire affected leaf. Recent
some typical walls; but for the full range of wall types and work in Australia by Gnanakrishnan, Lawther et al [6,7] has
detailed options and variations, it is essential to consult the indicated that cavity walls may underperform single leaves in
tables in the latest version of the appropriate Code[5] . See some support circumstances due to a collapse mode which
also ‘Further reading’. results from bowing of tied leaves.
Design, then, is carried out simply by choosing a tabulated
wall format which meets the performance specification, in
terms of hours of resistance, demanded by the Building
Regulations for the position of the wall in the building and
subject to any other requirements such as structure,
appearance, sound insulation etc.
Other fire related factors (eg seals at junctions and where
the wall is penetrated for services or other reasons) are dealt
with by associated codes.
5

200
Plastered perforated,
60% solid
180
Bare perforated, 75%
solid
Vermiculite plastered
160 perforated, 75% solid

Bare solid
140
Vermiculite plastered
Licensed copy from CIS: watermanpart, Waterman Partnership, 21/01/2017, Uncontrolled Copy.

solid
Minimum wall thickness (mm)

120

100

80

60

40

20

0
6 4 3 2 1 0.5
Fire period (hours)

Figure 3 Performance measured by testing clay brickwork (Code of practice BS 5628-3)

Hollow block (dense


aggregate)
200 Solid brick (clay, calcil or
concrete)
Hollow block (lightweight
aggregate)
Solid block (dense
aggregate)

150 Solid block (lightweight


aggregate)
Minimum wall thickness (mm)

Solid AAC block

100

50

0
6 4 3 2 1.5 1 0.5
Fire period (hours)

Figure 4 Performance measured by testing a range of masonry walling (Code of practice BS 5628-3)
6

Performance issues not necessarily More flexible methods in development


covered by existing simple rules Over the last two decades there has been some attempt to
In a report to the UK government by de Vekey[8], a number of develop more flexible design methods for masonry which
new developments in masonry design and materials were eliminate the need to carry out individual tests on every minor
proposed for which there was no existing test data and for variant wall form and innovation. There are a number of
which no calculation method was available. The codes around the world which have either tentative or more
developments are listed in Table 1. developed simple calculation methods for masonry. These
may be published by consortia of materials producers or by
Licensed copy from CIS: watermanpart, Waterman Partnership, 21/01/2017, Uncontrolled Copy.

standards-making bodies such as CEN and ASTM.


Two main approaches are in development:
● a calculated interpolation of the existing database of test
results covered later in this section;
● complete modelling of the fire process using fundamental
physical data which is covered, by reference to
publications, in the next section.

Table 1 New developments in masonry practice for which there is no fire test data
Development Possible implications in a fire event Possible design remedy

1 Insulated cavities The insulation may cause a more rapid Limited research[9,10] suggested that there
temperature rise of the hot leaf and thus was no significant problem§
greater thermal shock
2 Cavity walls filled with combustible insulants Insulants may ignite and spread fire Limited research[9,10] indicated that there was
through the cavity (but limited air supply) no combustion in a closed cavity§
3 Structural grade polyurethane foam used as a As 2 above As 2 above§
replacement wall tie system
4 Polymer foam faced concrete units with foam As 2 above Probably as 2 above§
face in a cavity
5 Polymer foam filled hollow concrete units Insulants may ignite (but very limited air Probably as 2 above§
supply)
6 Polymer-foam sandwich concrete units Loss of bonding layer of foam may Stiff non-flammable ties should be built into
destabilise the wall the bed joints to ensure a post-fire connection§
7 Polymer-foam insulation permanent shuttering There will be melting and possibly ignition Protective sheathing/coating should not rely
blocks for concrete walls during a fire event upon adhesion to the foam but should have
non-flammable ties to the concrete§
8 Glued special bricks Debonding at the glue line may detach Some metal ties spanning the glue line should
return walls and reduce stability be included within the mortar beds
9 The use of units with high volume proportion of May reduce the resistance to spalling It may be advisable to use a reinforced
perforations to construct fire walls erosion and thus the overall fire plaster/render coat over this type of wall or
performance derate the fire period
10 Cavity wall ties with either a plastic body or Will be destroyed thus reducing stability of A minimal level of fire resistant ties should
bonding system (eg polymer plugs and screws) cavity walls (may be advantageous in some be used in addition to the plastic type where
expanders or resin-bonded ties circumstances) the fire period exceeds 1/2 hour§
11 Cold-formed metal section framing backing Could fail in a fire and destabilise outer leaf It is important to protect the framing against
walls cladding fire
12 Plastic cavity closer devices May allow fire to jump either way between Use masonry closers or build- in a protected
an internal space and a cavity layer
13 Cavity walls with stiff ties, limited support at Deflection of the loaded leaf can snap the Ensure that all walls are tied at their vertical
vertical edges and a fire affecting the loaded tied-on outer leaf and cause early structural edges. Check the potential bow of walls not
leaf (Gnanakrishnan et al [6,7]) collapse of the whole wall tied at their vertical edges (Cooke[1])
14 Masonry units with >1% organic content (due May compromise inherent resistance to Requirement in EN 771 series of standards to
to the use of recycled waste materials) ignition of the masonry product establish reaction to fire via a test

§ Many of these materials will be damaged or destroyed and may need reinstatement if a building is reused after a fire event. Some fire-resistant insulation materials may
markedly increase the fire period to insulation failure but polymer-based insulants should be neglected in this context.
7
A method derived from the German DIN standard is were excluded so that any method based on this data set
embodied in the current draft code, EN 1996-1-2[5], which would need some rules to deal with potential stability
involves a thermal transmission rate and surface erosion rate. failures. To match UK practice this data has been reanalysed
However, it is not clearly set out and implies much higher in two categories:
rates of erosion than have been reported in fire tests. In the ● lower density concretes (type 1 concretes in BS 5628-3)
USA the method developed by the Brick Institute of with a density range up to around 1100 kg/m3;
America (BIA) and the National Concrete Masonry ● higher density concretes (type 2) denser than 1100 kg/m3.
Association (NCMA)[11] is based on the concept of the
‘equivalent thickness’ of the masonry material which is, in Type 1 would include all aerated concretes and concretes
Licensed copy from CIS: watermanpart, Waterman Partnership, 21/01/2017, Uncontrolled Copy.

effect, the thickness of the solid material present averaged made with lightweight aggregates such as expanded clay
over the face area of the unit or units. The American method and foamed slag. Type 2 includes concretes made with
also involves a nationally accepted combination rule for natural aggregates and blends. Additionally the smaller
layers of different masonry types, voids and finishes in a body of data has been analysed for plaster or render coated
composite wall. This is shown as the formulae[12]: equivalent wall types. Figures 5 and 6 are simple linear
regressions forced through zero for the type 1 aggregate
R = (R10.59 + R20.59 + . . . Rn0.59 + As)1.7 wall tests, and Table 2 (page 8) presents the regression data
for all four groups analysed. The American method actually
where: employs four density categories and uses a non-linear curve
R = fire resistance of the whole assembly in hours such as a parabolic fit, but this introduces more parameters
R1, R2 and Rn = resistances of individual layers of masonry and complexity for only a small improvement in fit to the
material (wythes) in hours derived from tabulated values data at the upper resistance levels.
As = 0.3 factor for each continuous air space of between 12.6 As can be seen, the data is quite consistent for the main
and 88.9 mm width case of bare walls and produces quite modest confidence
intervals. The rather limited data set for plastered walls
A further plaster layer factor is included within the bracket inevitably generates larger confidence bands.
for gypsum-sand plaster finishes which is derived from a In order to test the application of the principle to UK
further table based on thickness and the number of faces materials, data from the somewhat limited published
covered. database[14,15,16] has been obtained and the equivalent
The Australian draft code also uses parameters of wall thickness assessed from the recorded data. This data was
thickness, material and coating type but has some explicit then superimposed over the confidence intervals produced
slenderness ratio limits included to control potential from the US data in Figures 5 and 6. The UK data shows
stability problems. that, with odd exceptions, the UK trend line would give a
A large body of test data from historical American tests of generally safe result. The few results outside the wider
concrete blockwork is available[13] which allows a sensible confidence bands for individual points may be due to special
statistical analysis of the fire resistance period (or rating) circumstances and might require further investigation. The
versus the ‘equivalent thickness’. This body of data is formulae could be varied to cover the effects of finishes
sufficiently large to tolerate the removal of misleading data while multi-layer walls could be dealt with by using addition
such as those from tests which are terminated before any rules with a further safety factor included if required.
failure mode operates; also tests which failed due to stability

8 8 Predicted Y with estimated 90% CIs for regression line


Predicted Y with estimated 90% CIs for regression line and and single points with 26 data points (crosses only)
single points with 106 data points (yellow triangles only)
7 7

6 6
Time to failure (hours)
Time to failure (hours)

5 5

4 4

3 3

2 2

1 1

0 0
0 20 40 60 80 100 120 140 160 180 200 220 240 0 20 40 60 80 100 120 140 160 180 200 220 240
Equivalent thickness of the wall (mm) Equivalent thickness of the wall (mm)

Figure 5 Linear regression forced through zero for bare lower Figure 6 Linear regression forced through zero for plastered
density concrete blockwork data from the USA[14] with UK data concrete lower density blockwork data from the USA[13] with UK
superimposed (green triangles) data superimposed (red squares)
8

Table 2 Linear regression results for concrete masonry walls based on data from USA
Linear regression data forced through zero: for time = constant (C) x equivalent thickness
Material Number Slope Standard Students t Regression Residual Probability Confidence intervals
of data† error coefficient standard level for slope
(C) (R) deviation (%) Lower Upper

Bare dense aggregate 94 0.022 4.64 47.0 0.98 0.56 90 0.021 0.023
concrete blockwork E-4
Plastered dense 19 0.027 23.8 11.3 0.93 1.26 90 0.023 0.031
Licensed copy from CIS: watermanpart, Waterman Partnership, 21/01/2017, Uncontrolled Copy.

aggregate concrete E-4


blockwork
Bare lightweight 105 0.026 6.41 41.2 0.97 0.77 90 0.025 0.027
aggregate concrete E-4
blockwork
Plastered lightweight 25 0.036 35.6 10.1 0.90 1.44 90 0.03 0.042
aggregate concrete E-4
blockwork
† Less 1 degree of freedom

For type 1 materials the formula for the line would be: Design by modelling: the future
R = (0.026 + 0.1P) x TE Thermal insulation
Mathematical modelling of thermal conduction processes,
where: to indicate whether walls are likely to fail as a result of
R = fire resistance period in hours temperature rise on the non-fire face, is fairly well
TE = equivalent thickness in mm understood. In principle, to create a workable model only
P = coating factor which is zero for bare walls and 1 for requires information on the thermal conductivity versus
plastered or rendered walls with a minimum thickness of temperature characteristics, the heat capacity, and the area
layers of 12 mm. (This factor could be made more proportions of the materials forming the wall. There are,
intelligent if better input data could be located.) however, the following factors which must be taken into
account.
For design purposes it would probably be simpler to regress
the data so as to give a thickness for a desired fire resistance ● Damp walls will release water by evaporation at
period. It would then be necessary to decide on a factor of somewhere around 100 °C which will increase the
safety, either linked to the confidence limits for the data effective heat capacity until all the water is driven off.
points or as a reduction in the slope coefficient. A similar
approach has been adopted for fired clay masonry walls[17]. ● Any wall which contains a material which has physically
In Australia a similar approach has been adopted but using or chemically bound water as part of its constitution will
a stepped graph of the fire period (equivalent to a tabulated lose the water at a temperature between 100 and 800 °C;
value) in relation to gross thickness. A further parameter, the this endothermic process will also increase the effective
slenderness ratio, is used to ensure the stability of heat capacity, delaying any rise in temperature. Typical
loadbearing walls. materials are concretes and mortars.
Figures 7 and 8, derived from Australian research [18,19] are
typical graphs showing the database of tests and the draft ● Some radiation and convection will take place in hollow
Standards Association of Australia (SAA) code line. and perforated masonry units, and partially bypass the
A slenderness ratio limit method, along the lines of the conduction paths.
Australian proposal, is suggested to control stability failures
which would also take into account the loading, support and ● Metal ancillary products (eg wall ties) may yield local
restraint condition of the wall, and special cases such as areas of enhanced conduction which become significant
cavity walls. for very low conduction units (eg aircrete).

● Spalling of the fire face may reduce the effective thickness


during the course of a test.
9
300

Wall failed Draft SAA code line

250 Test terminated Proposed code line

200
Time to structural failure (mins)
Licensed copy from CIS: watermanpart, Waterman Partnership, 21/01/2017, Uncontrolled Copy.

150

100

50

0
40 80 120 160 200 240
Wall thickness (mm)

Figure 7 Australian data for thermal (criterion I) failure of clay masonry in relation to gross wall thickness with a proposed code line

300

Draft SAA
Wall failed
code line

250 Test Proposed


terminated code line

200
Time to structural failure (mins)

150

100

50

0
10 15 20 25 30
Slenderness ratio

Figure 8 Australian data for stability (criterion R) failure of clay masonry plotted versus slenderness ratio with a proposed code line
10
Because of these complicating factors and the dynamic Solid, single leaf walls made with hollow or perforated
nature of fire development, it is not as simple as it would masonry units
first appear to predict, completely, performance using a These units increase the thermal insulation by introducing
model. Relevant data, for the range of temperatures in fires, partial air gaps but reduce the stability because they erode
on conductivity, specific heat, thermal expansion more easily.
coefficient, density, and strength are reported in various
publications[5,20,21]. Very slender, solid, single leaf walls made with solid
masonry units supported in restraining frames
Integrity At least one example has been reported to have failed by
Licensed copy from CIS: watermanpart, Waterman Partnership, 21/01/2017, Uncontrolled Copy.

Penetration of walls by fire is a rare mode of failure for collapse (Davy and Ashton[14]).
masonry and therefore models, currently, do not cover such
failure events. Gnanakrishnan and Lawther [22] have published several
papers in which finite element modelling was applied to the
Structural failure behaviour of walls and the results were compared to physical
Most existing data supports models which predict thermal testing. In their 1989 paper[7] they proposed a model for
behaviour but a separate model is required to predict single leaf walls based on a computation of bowing which, in
structural behaviour to be used in parallel with thermal turn, was based on data for thermal gradients, thermal
modelling. Where structural failure occurs, the picture expansion coefficients, strength and Young’s modulus over a
becomes much more complex because of the diversity of range of temperatures. They have also investigated several
walling materials, restraint conditions and potential failure examples of cavity walls and found that a wall with no
modes. vertical edge supports – but vertically loaded on the inner, fire
resisting leaf – fails structurally; this is because the restrained
Solid, single leaf walls made with non-loadbearing solid or loaded inner leaf bows and fails the cooler outer leaf by
masonry units supported in restraining frames loading it via the wall ties. The whole wall then fails when the
These tend to bow towards the fire because of differential eccentricity of the now-unpropped inner leaf reaches the
thermal expansion restrained at the edge. Despite the bowing, critical level. A wall loaded on both leaves equally, or only on
the stability endowed by the restraining frames normally the outer leaf, was much less affected by this mechanism.
means that the overall failure is not structural (eg Davy and Gnanakrishnan and Lawther have tried to use a bowing
Ashton[11]). model to predict structural failure of fire walls.
One of the main problems of many of the tests and the
Solid, single leaf walls made with loadbearing solid associated mathematical models described in this Digest is
masonry units supported in restraining frames or at top that they are based on traditionally accepted fire-test edge
and base conditions, particularly those of free vertical edges; these
These also bow but less due to the compression stress and are a long way away from the edge conditions present in
failure is rarely structural. most real masonry walls. This means that both the tests and
the associated models may give erroneous predictions for real
walls.
11

References [12] Uniform Building Code Standard 7-7. Methods for calculating fire
resistance of steel, concrete, wood, concrete masonry and clay
[1] Cooke G M E. Thermal bowing in fire and how it affects building masonry construction. International Conference of Building Officials,
design. BRE Information Paper IP 21/88. Garston, BRE Bookshop, 1994. Part IV, pp3-115 to 3-119.
1988. [13] National Concrete Masonry Association. A compilation of fire
[2] Department of the Environment and the Welsh Office. The tests on concrete masonry assemblies. SBCCI Public Safety Testing
Building Regulations 1991 Approved Document A1/2 (1992 edition). and Evaluation Services Inc, June 1993, Vol 1-5. Herndon (VA), NCMA,
London, The Stationery Office, 1991. 1991.
[3] British Standards Institution. Structural design of low-rise [14] Davey N and Ashton L A. Fire tests on structural elements.
buildings. Code of practice for stability, site investigation, foundations National Building Studies Research Paper 12. London, The Stationery
Licensed copy from CIS: watermanpart, Waterman Partnership, 21/01/2017, Uncontrolled Copy.

and ground floor slabs for housing. British Standard BS 8103-1:1995. Office, 1953.
London, BSI, 1995. [15] Fisher R W and Smart P M T. Results of fire resistance tests on
[4] British Standards Institution. Code of practice for use of elements of building construction.
masonry. Materials and components, design and workmanship. British [16] Fisher K. Fire resistance of brickwork: Regulatory requirements
Standard BS 5628-3:2001. London, BSI, 2001. and test performances, Procs of British Ceramic Society (September
[5] European Committee for Standardisation. Eurocode 6. Design 1982), No.30, pp65–80.
of masonry structures. General rules. Structural fire design. prEN [17] Nunn M A. Calculated fire resistance of clay masonry assemblies
1996-1-2:2001. based on the equivalent thickness method. Procs of 7th North
[6] Gnanakrishnan N, Lawrence S J and Lawther R. Behaviour of American Masonry Conference, Notre Dame, 1996, 2 1033–1043.
cavity brick walls exposed to fire. Proceedings of 8th International [18] Lawrence S J and Gnanakrishnan N. Masonry: developments
Brick/Block Masonry Conference, Dublin, 1988, pp981–990. in design for fire. Australian Institute of Building papers, Vol 2 (January
[7] Gnanakrishnan N and Lawther R. Some aspects of the 1988).
performance of single leaf masonry construction. International [19] National Building Technology Centre. The fire resistance of
Symposium on Fire Engineering for Building Structures and Safety, masonry walls (a summary of Australian research and its relevance to
Institution of Engineers (Australia), Melbourne, 1989, pp93–99. codes and regulations). Technical Record 531. Sydney, NBTC
[8] de Vekey R C. The performance of masonry in fires: a review. BRE (Commonwealth Scientific and Industrial Research Organisation),
Client Report CR45/93. Garston, BRE, 1993. 1988.
[9] de Vekey R C. The fire performance of insulated cavity walls. BRE [20] Edgell G J. The effect of fire on masonry and masonry structures.
Note N52/97. Garston, BRE, 1997. A Review. British Ceramic Research Association Technical Note 333.
[10] de Vekey R C. The fire performance of insulated cavity walls. Stoke on Trent, British Ceramic Research Ltd, 1982.
Procs of 5th International Masonry Conference, London, 1998 (British [21] de Vekey R C. Best practice guide for fire engineering. Task 10 –
Masonry Society Procs 8, pp229–234). masonry. BRE client project report 80988. Garston, BRE, 2002.
[11] National Concrete Masonry Association. TEK manual for [22] Gnanakrishnan N and Lawther R. Modelling the structural
concrete masonry design and construction (CD-rom). Herndon (VA), behaviour of single leaf masonry walls exposed to fire, p124.
NCMA, 2001.
12

Further reading
Fire test Standards (national)
BS 476-1:1953 Fire tests on building materials and structures
BS 476-8:1972 Test methods and criteria for the fire resistance of elements of building construction
BS 476-20:1987 Method for determination of the fire resistance of elements of construction (general principles)
BS 476-21:1987 Method for determination of the fire resistance of loadbearing elements of construction
BS 476-22:1987 Method for determination of the fire resistance of non-loadbearing elements of construction
E.119-81, 1981 Standard of fire tests of building construction and materials. Annual book of American Society
for Testing and Materials (ASTM) Standards, Part 18, pp879–964
Licensed copy from CIS: watermanpart, Waterman Partnership, 21/01/2017, Uncontrolled Copy.

CAN/ULC-S101-M89 Standard methods of fire endurance tests of building construction and materials. Ottawa,
Standards Council of Canada, 1989
AS 1530 - l985: Part 4 Fire resistance tests of elements of building construction. Sydney, Standards
Association of Australia, 1985
National Building Code of Canada (NBC): Part 3 Fire protection, occupant safety and accessibility) 1995
Appendix A, A-9.10.3.1 and Appendix D

Fire test Standards (international)


EN 1363-1 Fire resistance tests. General requirements
EN 1364-1 Fire resistance of non-loadbearing elements. Walls BRE is committed to providing
EN 1365-1 Fire resistance of loadbearing elements. Walls impartial and authoritative information
on all aspects of the built environment
EN 1366-2 Fire resistance tests on service installations. Dampers
for clients, designers, contractors,
EN 1366-3 Fire resistance tests on service installations. Penetration seals engineers, manufacturers, occupants,
EN 1366-4 Fire resistance tests on service installations. Linear gap seals etc. We make every effort to ensure
the accuracy and quality of information
and guidance when it is first published.
National fire codes and regulations giving tabulated fire periods for masonry walls
However, we can take no responsibility
BS 5628-3:1985 Code of practice for use of masonry. Materials and components, design and workmanship (and for the subsequent use of this
amendments) information, nor for any errors or
The Building Regulations (Northern Ireland) 1990, Statutory Rules of Northern Ireland 1990 No 59. Belfast, The omissions it may contain.
Stationery Office, 1990
BRE is the UK’s leading centre of
Technical Standards for compliance with the Building Standards (Scotland) Regulations 1990. Edinburgh, The expertise on building and construction,
Stationery Office, 1990 and the prevention and control of fire.
The Building Regulations 1991 Approved Document A: Structure (1992 Edition). London, The Stationery Office, Contact BRE for information about its
services, or for technical advice, at:
1991
BRE, Garston, Watford WD25 9XX
The Building Regulations 1991 Approved Document B: Fire Safety (1992 Edition). London, The Stationery Office, Tel: 01923 664000
1991 Fax: 01923 664098
AS 3700 - 1988 Masonry Code. Sydney, Standards Association of Australia, 1988 email: enquiries@bre.co.uk
Website: www.bre.co.uk

Other BRE and FBE publications concerned with fire engineering and fire design Details of BRE publications are available
from:
Digest 462 Steel structures supporting composite floor slabs: design for fire
www.brebookshop.com
BR 128 Guidelines for the construction of fire-resisting structural elements or
BR 135 Fire performance of external thermal insulation for walls of multi-storey buildings IHS Rapidoc (BRE Bookshop)
(2nd edition) Willoughby Road
Bracknell RG12 8DW
BR 368 Design methodologies for smoke and heat exhaust ventilation
Tel: 01344 404407
BR 459 Fire safety engineering. A reference guide Fax: 01344 714440
FB 5 New fire design method for steel frames with composite floor slabs email: brebookshop@ihsrapidoc.com

Published by BRE Bookshop


Requests to copy any part of this
Acknowledgement publication should be made to:
This Digest has been produced with the support of the Office of the BRE Bookshop,
Building Research Establishment,
Deputy Prime Minister Watford WD25 9XX
Tel: 01923 664761
Fax: 01923 662477
email: brebookshop@emap.com

© Copyright BRE 2004


July 2004
ISBN 1 86081 704 1

www.bre.co.uk

Вам также может понравиться