Академический Документы
Профессиональный Документы
Культура Документы
Functional Description
This Operating Manual is protected by copyright and exclusively serves the purpose contractually agreed between
02 June 2008 – Rev. 0 GEA Luftkühler – Chapter 0 Service and Support Page 1 of 8
customer and manufacturer. Any use other than intended which includes reproduction of the entire or partial document
in whatever form as well as utilization of its contents or parts thereof is prohibited unless the express written approval
of the manufacturer has been obtained. In the event of contraventions compensation for damages will be claimed.
Moreover, further claims will be raised as deemed necessary.
Overview
Table of Contents
1 Introduction ....................................................................................................................... 3
1.1 Operating Principle ................................................................................................. 3
1.2 Overview of Air Cooler Components ..................................................................... 4
2 Commissioning ................................................................................................................... 5
2.1 Liquid or Gas Coolers............................................................................................... 5
02 June 2008 – Rev. 0 GEA Luftkühler – Chapter 0 Service and Support Page 2 of 8
Function and Design
1 Introduction
The tube bundle is usually of stilted design using a supporting steel structure
which enables the air to be drawn in from below via the fan. For maintenance
purposes the steel structure is often provided with walkways, handrails and
access ladders. To improve its capacity the air cooler may optionally be
equipped with an intake air humidification system. To prevent the cooler from
freezing up when the flow of product has been stopped and the fans switched
off heating bundles may optionally be arranged below the tube bundle and
louvers mounted above the tube bundle. The heating bundles serve to heat
the product inside the tube bundles. Louvers are provided to cover the tube
bundles and thus shall prevent free or natural convection.
Bracing
Support
Fan hub
2 Commissioning
Attention!
When filling in medium no dirt from feed pipework must enter the
tube bundles. – Otherwise, capacity losses, tube clogging and tube
distortion may be caused which may lead to inadmissible tempera-
ture differences and, during cold periods, freeze-up hazards.
Note:
The temperature of the medium to be filled in must at least be 10 °C
above the pour point. It must be made sure that tubes or tube sec-
tions cannot freeze up. Vent the tube bundles without delay and cir-
culate the product because flowing product freezes not as easily as
stationary product does.
Carefully vent the tube bundle. – The venting nozzles of the tube bundles
must be reclosed only after filling has been completed.
Attention!
After venting no gas cushions must remain. – Otherwise, capacity
losses, risk of inadmissible temperature differences and, during cold
periods, freeze-up hazards.
The temperature of the tube bundle must be slowly raised until operating
temperature is reached. – At no point must the temperature increase ex-
ceed 50°C per minute.
Note:
When switching on fan drives not provided with return stops the re-
spective motor protection switch may trip if the fans have reversely
rotated before the drives are switched on.
Switch the fans on, if possible at increasing speed, otherwise one after
the other. – Make sure they run up to speed smoothly and check for un-
usual noise.
Note:
After the system has been shut down the fan drives must be run for
approx. 2 hours once a month to make sure moisture that may have
ingressed can evaporate and the bearings are adequately lubricated
(motor, fan bearing system etc.). This operation has to be docu-
mented. – If louvers are mounted they may remain closed during
this period.
Close off the inlet and outlet point at the tube bundles.
Carefully empty all tube bundles. – For this purpose open all inlet and
discharge pipe connections and all draining and venting nozzles. Also
empty all other parts of the tubing system.
Note:
If the air cooler shall be shut down for a longer period of time or
permanently the tube bundles have to be either dried or filled with
nitrogen.
Drying
Blow the residual liquid out of the return sections by means of com-
pressed air or extract it by suction.
If it has been determined that no residual water is inside the tube bundles:
Nitrogen Filling
Close off the flanges and lug closures by means of blank flanges.
Check the pressure gauge monthly and adjust the pressure if necessary.
Note:
In the event of temperature changes the nitrogen pressure will also
vary.