Академический Документы
Профессиональный Документы
Культура Документы
Abstract: Usually, acoustic partial discharge (PD) and vibration measurements take
place on the outside tank wall of power transformers. This contribution determines new
approaches for acoustic PD measurements within the oil volume of the transformer
combined with electromagnetic in-oil measurements. Scope of the work is an acoustic
and ultra-high frequency (UHF) detection of PD and additional recording of transformer
vibrations during service. For in-oil measurements a combined sensor is presented, which
allows simultaneous detection of all three signals. After a short introduction of
measurement principles, the requirements of a combined in-oil sensor are defined
including mechanical demands and signal processing. A diplexer integrated into the
combined sensor is introduced to separate the considered frequency spectra. Tests in a
laboratory setup with a first prototype estimate if these requirements are met. Therefore,
the setup uses reproducible, synthesized PD signals generated by an acoustic signal
generator and an UHF pulser. Second measurements use a needle-sphere electrode
emitting realistic UHF and acoustic signals. Vibrations are simulated with a small winding,
which is mechanically excited. The combined sensor is compared to the UHF antennas
and acoustic accelerometers. Finally, the influence of the electric field strength being
unavoidable at inside-tank measurements is evaluated.
798
OD5-04
(e.g. lamination sheets). The Weiss Domains in mountable to DN 80 and DN 50 oil valves
metal align themselves along the time-varying variable insertion depth, the sensor head
magnetic main flux induced by the applied voltage. reaches into the transformer tank
At load condition, current-related effects oil-proof, temperature resistant up to 80° C
superimpose magnetostriction. Forces of the continuous, 120° C short-term and
alternating magnetic field affect current-carrying pressure resistant up to 5 bar
windings leading to an oscillation of the active part.
The basic oscillation for both phenomena is twice 2.2 Principle of measurement
the electrical frequency [7]. The entire frequency
range is usually small, reaching up to approx. The block diagram in Figure 2 illustrates the mode
1 kHz [6]. of operation. All signals, piezo-electric or UHF,
couple into the physical sensor unit. The UHF
2 COMBINED IN-OIL MEASUREMENT signal is filtered by a passive high pass, providing
50 Ohms impedance up to 1 GHz. Because the
Both, acoustic measurements for PD and piezo-electric effect provides only very low output
vibrations cope with the problem of the stiff, self- voltage, the signal has to be amplified by a circuit
supporting tank, which is influencing both, the with high input impedance (in the GOhm range).
signal strength (damping) and the signal to noise The amplifier also operates as low pass (LP) to
ratio (SNR). Therefore, methods for measurents supress frequencies within the UHF range. The
directly inside the transformer oil are determined. amplified signals are separated by an active low
Piezo-electric sensors represent a suitable pass filter for vibrations. PD acoustics are filtered
technology to detect changes of pressure caused by an active band pass (BP) ideally operating from
by acoustic waves. Their frequency range is suited 55 kHz to 200 kHz. Active filters are used due to
for vibration and PD acoustic measurements. their amplification, smaller dimensions and better
pass band tuning.
Unfortunately, the access to the transformers
inside is limited by the amount of available oil
valves. Most transformers are equipped with only
2-3 valves, which can be used for in-oil
measurements. Therefore, a sensor is required,
that is able to measure pressure changes by the
piezo-electric effect and electromagnetic waves
simultaneously. Thus, the sensor should work from Figure 2: Block diagram of diplexer to separate
100 Hz up to the GHz range. Separate signal signals from UHF PD, acoustic PD and sinusoidal
outputs should be available for vibrations, acoustic vibration signals to separate outputs. On the left:
PD and UHF PD. The mechanic design of the sensor receiving all signals simultaneously
sensor has to be attachable to existing oil valves. A
prototype designed to meet the requirements is The transfer functions of the three separated signal
shown in Figure 1. Compared to the combined paths within the diplexer are shown in Figure 3.
acoustic sensor presented in [8], this version is
also suited for UHF signals. A diplexer with three
output N-connectors is integrated in the handle of Acoustic
presented sensor. Vibration PD
s
UHF
799
OD5-04
800
OD5-04
801
OD5-04
802
OD5-04
5 REFERENCES
i
Figure 14: Simulation of the electrical field [1] International Electrotechnical Commission,
strength in the test tank setup at applied voltage IEC 60270 High-Voltage Ttest Techniques -
VRMS = 70 kV Partial Discharge Measurements, 3. Edition,
Geneva, Switzerland, 2000.
However, vibration measurement is influenced by [2] S. Coenen, S. Tenbohlen, S. Markalous, T.
the electric field. Figure 15 shows the influence Strehl, „Sensitivity of UHF PD Measurements
compared to a noise measurement of the in Power Transformers,“ in IEEE Transactions
combined sensor. At 50 Hz the effect of the electric on Dielectrics and Electrical Insulation, Vol.
field results in an increased noise level. Because 15, , No. 6, 2008.
50 Hz is usually not considered for vibration
analysis, the interference is acceptable. At 100 Hz [3] M. D. Judd, „Experience with UHF Partial
the maximum coupling of the electric field into the Discharge Detection and Location in Power
vibration measurment path is max. 10dB above Transformers,“ in Electrical Insulation
noise and hence sufficiently low. Concluding, the Conference, Maryland, USA, 2011.
effect of the electric field on vibration measurement [4] E. Howells, E. Norton, „Detection of Partial
is tolerable. Discharges in Transformers Using Acoustic
Emission Techniques,“ IEEE Transactions of
Power Apparatus and Systems, PAS-97,
1997.
[5] S. Markalous, Detection and Location of
Partial Discharges in Power Transformers
using acoustic and electromagnetic signals,
Stuttgart: Sierke Verlag, 2006.
[6] M. Beltle, S. Tenbohlen, „Usability of Vibration
Measurement for Power Transformer
Diagnosis and Monitoring,“ in International
Conference on Condition Monitoring and
Diagnosis (CMD), Bali, Indonesia, 2012.
[7] B. García, J. Burgo, and Á. Alonso,
„Transformer Tank Vibration Modeling as a
Method of Detecting Winding Deformations
Part I: Theoretical Foundation,“ IEEE
Figure 15: Frequency spectrum comparing Transactions on Power Delivery, Vol. 21, No.
vibration measurement and influence of the electric 1, pp. 157-163, January 2006.
field. blue: noise measurement of combined sensor
green: coupling at ERMS ~9 kV/m, [8] M. Beltle, M. Siegel, S. Tenbohlen, „Analysis
orange: coupling at ERMS ~22 kV/m of Methods for PD-Detection and Vibration
Measurement,“ in Diagnostik Elektrischer
4 CONCLUSION Betriebsmittel, Fulda, Germany, 15-16
November, 2012.
The contribution presents a prototype of a [9] S. Coenen, S. Tenbohlen, T. Strehl, S.
combined sensor being able to measure Markalous, „Fundamental Characteristics of
transformer vibrations, PD acoustics and UHF PD UHF PD Probes and the Radiation Behavior of
signals simultaneously. Signals are separated by PD Sources in Power Transformers,“ in
an included frequency diplexer. The combined International Symposium on High Voltage
sensor is designed for application inside power Engineering (ISH), Cape Town, South Africa,
transformers. Laboratory tests evaluate proper 2009.
operation of the combined sensor. Its abilities and [10] E. Howells, E.T. Norton, "Parameters Affecting
limits compared to conventional sensors are the Velocity of Sound in Transformer Oil,"
determined. The combined sensor is IEEE Transactions on Power Apparatus and
advantageous to conventional techniques Systems, PAS-103, No.5, pp. 1111 -1115,
concerning signal quality and SNR. Outside tank May 1984.
803