Вы находитесь на странице: 1из 7

中国科技论文在线 http://www.paper.edu.

cn

Electric Power Systems Research 57 (2001) 173 – 179


www.elsevier.com/locate/epsr

Observations from measurements of the furfural content of oil


samples from transmission transformers
J.M.K. MacAlpine *, C.H. Zhang
Electrical Engineering Department, The Hong Kong Polytechnic Uni6ersity, Hong Kong, People’s Republic of China

Received 15 February 2000; received in revised form 18 May 2000; accepted 14 June 2000

Abstract

The concentration of the chemical furfural in transformer oil is well known to be an indicator of the extent to which the paper
insulation of the windings has deteriorated. However, the majority of publications on this topic are based on small-scale
laboratory investigations with very little on field experience with power transformers. This paper reports on the analysis of data
on the concentration of furfural in oil samples from 310 transmission transformers. The data showed that while high furfural
concentrations (FC’s) tended to occur in older transformers, there was no distinct trend. This, together with the lack of an upward
tendency for the FC in cases where two readings were taken several months apart, indicated that the deterioration in paper
strength and the associated increase in FC, occur in occasional and discrete steps. The model proposed is that these step-changes
are due either to internal faults causing extreme local overheating, or to overloading of the transformer causing general
overheating. A simulation based on these criteria gave a similar pattern of FC versus service age. Overall the results indicated an
upward trend of log(FC) versus length of service but with very large scatter and with clustering by manufacturer. It was clear that
the majority of transformers show negligible deterioration even after 20 years in service. This is in agreement with the above
scenario. There was reason to believe that transformers located in industrial areas were likely to have been overloaded during the
1980s, so an analysis by locality was done. This showed that the percentage of transformers with high (\ 4 mg/l) FC’s in
nominally industrial areas was double that of the rest. This difference, although suggestive, proved not to be statistically
significant. The model described indicates that, because of the auto-catalytic nature of the process, oil changes would be beneficial
where the FC level exceeds 4 mg/l: less deterioration will occur when the transformer is overloaded. © 2001 Elsevier Science B.V.
All rights reserved.

Keywords: Furfural analysis; Ageing; Transformer insulation

1. Introduction present study the results and subsequent analysis of


tests to determine the furfural concentration in 361 oil
The windings of oil-filled transformers use paper samples from transmission transformers are reported.
insulation and if this becomes weakened the conse- Paper is made from cellulose fibres dispersed in water
quence of a fault current may be severe: the inevitably and drained to form a mat. The cellulose fibres are
high forces on the windings may result in mechanical prepared from wood and form a natural long-chain
failure of the insulation and consequent inter-turn short polymer. The average length of the cellulose molecules
circuits. The reduction in strength of paper as it deteri- is linearly related to the tensile strength [1–3]. Reduc-
orates is thus of considerable importance. A major tion in the average length of the molecules from an
by-product of the degradation of paper is 2-furfuralde- initial 800 repeat units (or monomers) to 300 is typi-
hyde or ‘furfural’ whose presence can be used as an cally accompanied by a halving in the tensile strength,
indicator of the progress of the deterioration. In the but below an average length of 250 units the paper
generally becomes too weak to test. The most common
by-products from the scission of the cellulose molecules
* Corresponding author. Tel.: + 852-2766-6189; fax: +852-2330-
1544.
are water, carbon dioxide and furfural. This organic
E-mail address: eejmkmac@polyu.edu.hk (J.M.K. MacAlpine). liquid has a partition ratio of 80:20 between the paper

0378-7796/01/$ - see front matter © 2001 Elsevier Science B.V. All rights reserved. 转载
PII: S 0 3 7 8 - 7 7 9 6 ( 0 1 ) 0 0 0 9 9 - 2
中国科技论文在线 http://www.paper.edu.cn
174 J.M.K. MacAlpine, C.H. Zhang / Electric Power Systems Research 57 (2001) 173–179

and the oil [4]. The logarithm of the furfural concentra-


tion in the oil has been shown to decrease linearly with
the average length of the molecules [1,2], and hence
with the tensile strength of the paper. The furfural
concentration may be measured by liquid chromatogra-
phy [5,6].
The degradation rate of the paper and the conse-
quent production of furfural and water is increased by
the presence of water (auto-catalysis) [1] and — expo-
nentially — by temperature [7]. It would thus appear
that normal operation, and even small overloads, have
little effect on the paper insulation but that sig-
nificant rises in temperature approaching, or even ex-
ceeding, the rated allowable temperature rise could
have very severe effects on the condition of the paper
insulation. Fig. 1. The distribution of the transformers between manufacturers.
All of these conclusions, however, rely on lab-
oratory-scale testing. Relatively little has been pub- 2. The significance of the repeated measurements
lished on field experience with testing for furfural
levels in power transformers. Few utilities appear to In 22 cases, measurements were conducted on oil
have much data on regular testing as a preventative samples from a transformer whose oil had already been
measure; and, naturally, few of them are keen to publi- tested. These give extremely useful indications of both
cise the result of investigations into transformer fail- the rapidity of change in a given transformer and the
ures. repeatability of the tests.
The few cases published relate in general to individ- In the discussion following, where there are two tests
ual cases or to observations of a small group of trans- on oil samples from the same transformer, the first is
formers. They show the inherent difficulties in designated T1 and the second T2. Where there are three
quantitatively linking the measured furfural concentra- tests, the first and second are considered as one ‘T1 and
tions in transformer oil samples with weakness of the T2’ pair and the second and third as another ‘T1 and
insulation [8–10]. This is because an internal fault may T2’ pair. In Fig. 2, T2 is plotted against T1 which
cause heating, paper weakening and significant furfural shows T2 and T1 to be approximately equal, with T2 as
production in one part of the transformer, but may not often greater than, as less than, T1. There is no appar-
raise the overall furfural concentration in the oil very ent tendency for T2 to be greater than T1 as might
much. On the other hand an overload causing a tem- perhaps have been expected, and there is considerable
perature rise throughout the transformer could well scatter.
raise the furfural concentration significantly. In spite of Accordingly, Fig. 3 was plotted to show the percent-
the general paucity of field data, there seems to be a age difference between successive test results versus the
consensus that a concentration of 2 mg/l probably time in months between the two tests. It shows that
indicates significant degradation of the paper insula-
tion, while 20 mg/l indicates the paper has been weak-
ened to a dangerous degree.
The authors of this paper had the opportunity of
analysing measurements which had been made of the
furfural concentration (FC) in 361 oil samples from 310
transmission transformers belonging to an electrical
power utility in the PR of China. The samples were sent
in batches to a testing house near Beijing. The trans-
formers came from a number of different manufactur-
ers but over half were from one particular
manufacturer (Fig. 1).
This paper gives the results of the authors’ attempts
to ‘mine’ the data for information on two related
aspects: the reliability of the measurements and the
relationship between ageing and the service age and Fig. 2. The second of each pair of repeated tests plotted against the
loading history. first test.
中国科技论文在线 http://www.paper.edu.cn
J.M.K. MacAlpine, C.H. Zhang / Electric Power Systems Research 57 (2001) 173–179 175

Fig. 3. The percentage difference between successive test results versus the time in months between the two tests.

over a period of almost 2 years there is no significant The standard deviation of 25% was obtained for the
ageing trend. If the two data of just over 150% and the differences between pairs of results. Since the variance
one below −150% are discarded, the standard devia- (the square of the standard deviation) of the differences
tion of the remainder is 25%: the 95% confidence limits between pairs of results is twice that for the individual
of 950% are indicated in Fig. 3. The three extreme results, it follows that the estimated standard deviation
values are more than 6 standard deviations away from for the individual measurements is 25/
2 (or 18).
zero and cannot therefore be considered as part of the Consequently the tolerance range for the indi6idual FC
data population. measurements is 9 36%. This error level is surprisingly
This lack of any steady ageing or deterioration, as large: it is over twice as large as that found for tests in
well as the high variability, may also be seen in the which four different laboratories in Australia were com-
multiple-test cases. One transformer was tested five
pared [4] by independently measuring the furfural con-
times over a period of some 20 months. The results of
centration in five different oil samples.
the five tests (in mg/l) and the time intervals (in square
The poor repeatability of the measurements de-
brackets) are as follows:
scribed here may well originate in the long time in-
7.75[41/2 months] 10.98 [same day] 7.81 [12 months] evitably elapsing between the sample taking and the
measurements. The utility in question is some consider-
7.53 [3 months] 7.23. able distance from Beijing, where the furfural analysis
was done: the samples could not all be sent out on the
This indicates that even in the case of a transformer
same day and were held until a sizeable batch could
showing considerable deterioration (all values exceed 7
conveniently be sent to the testing laboratory.
mg/l) there is still no obvious change for the worse over
If in-house testing were found to be economically
a fairly long period. There is also a range of up to 40%
feasible the repeatability of the results would no doubt
in the data, again showing the rather large measure-
ment uncertainty. be greatly enhanced, and the subsequent FC results
The three 3-test cases are set out in Table 1. would be far more useful in determining the extent of
Again, there is no clear upward trend with time and the deterioration of the transformers.
the results show ranges of up to 50%.
The two very high values of percentage change pre- Table 1
Three cases where a set of three tests were carried out on the same
sumably indicate that an incident causing significant transformer
deterioration of the paper strength occurred in the
period between the two tests. T1 Time interval T2 Time interval T3
The surprisingly low result with a 7 month gap (months) (months)
between the two measurements was in fact a drop from
3.09 2 3.27 4 4.96
0.15 to 0.02 mg/l, the latter being the resolution limit of 11.05 12 8.08 3 8.78
the instrument. It seems likely that this was a special 4.11 4.5 4.08 3 4.08
case (or data collection error).
中国科技论文在线 http://www.paper.edu.cn
176 J.M.K. MacAlpine, C.H. Zhang / Electric Power Systems Research 57 (2001) 173–179

Fig. 6. The furfural content of oil samples from 190 Manufacturer ‘A’
transformers.
Fig. 4. The furfural concentration in the 361 transformer oil samples
plotted against service age, by manufacturer. loading history, and hence individual deterioration level
and trend. Consequently the data cannot be expected to
3. Overall results sit on a single trend line. The variation indicates that
individual histories are more important than simple
The furfural concentration (FC) of all 361 trans- ageing in determining condition.
former oil samples are plotted against service age in There is also a clear tendency for the data from
Fig. 4. The minimum resolution of the chromatograph transformers of a given manufacturer to cluster to-
in question is 0.02 mg/l, so data given as ‘B 0.02’ (i.e. gether. For example, it appears that transformers from
between 0 and 0.02 mg/l) has been plotted as 0.01 mg/l Manufacturer B have faired better than those of Manu-
for completeness. The majority of transformers clearly facturer A. This does not necessarily mean that present
show very little deterioration (FC’s below 1 mg/l) even day Manufacturer-B transformers are longer-lasting
after two decades of operation, but about 10% of them than those of Manufacturer A, but that this seems to be
have relatively high FC’s (more than 2 mg/l). the case for those manufactured 20 years ago.
Because of the log/linear relationship between FC Because of this clustering of each manufacturer’s
and paper strength referred in Section 1, it is reasonable transformers, the next two sections consider only data
to plot the FC against service years as a log/linear plot from the largest group, the Manufacturer-A transform-
(Fig. 5). There is indeed a general trend whereby the ers, in order to remove this source of variation. This set
higher FC levels occur on the older transformers but has been plotted as Fig. 6 and will be referred to later.
the correlation is low. This is not surprising when it is In passing it may be noted that there are 10 transform-
recalled the data represent ‘snapshots’ of one moment ers whose FC is greater than or equal to 2 mg/l (and
in the history of each transformer, each with its own four intermediate cases, 1–2 mg/l); but that the major-
ity of those over 12 years old (25 out of 39) continue in
good condition, that is, with FC values less than 1 mg/l.
It would seem likely that the 10 ‘poor-condition’ trans-
formers had a harder service life with more and longer
periods close to, or above, full rated load.
When the FC data was plotted against transformers
size in MVA, irrespective of age, no correlation was
observed (Fig. 7): larger transformers are neither better
nor worse than smaller ones in terms of paper deterio-
ration rates or tendencies. The transformers ranged
from 20 to 100 MVA.

4. Location

As has been observed in the previous section, the


Fig. 5. A log/linear plot of transformer oil furfural concentration individual histories seem more important than length of
versus service age by manufacturer. service in determining condition. However, no data on
中国科技论文在线 http://www.paper.edu.cn
J.M.K. MacAlpine, C.H. Zhang / Electric Power Systems Research 57 (2001) 173–179 177

industrial locations is greater than in all other areas (35


versus 18%). This difference was not found to be statis-
tically significant according to the  2 test of ‘goodness
of fit’ [11], probably mainly because of the relatively
small sample. It may also have been affected the inho-
mogeneity of the customer mix.

5. Simulation

It has been suggested earlier, that there should be


little or no deterioration under normal operation even
with short-term minor overloads; and that running at
temperatures significantly over the manufacturer’s rat-
ings would be required for appreciable deterioration to
Fig. 7. The furfural content of the transmission transformers plotted occur over the whole transformer, and hence for sub-
against their capacity.
stantial increases in FC to occur. This model was
written into a simulation in order to compare the
the loading history was available, other than the anec-
distributions obtained with Fig. 6.
dotal generalisation that there had been periods of
The simulation used a sample of 190 transformers,
considerable overloading for transformers serving in-
with the same age distribution as those from Manufac-
dustrial areas during the 1980s, when a rapid expansion
turer A, was used. It assumed a single significant incre-
of the industrial sector occurred. At this time the utility
ment in the FC to occur, with a 50% probability, once
concerned apparently had difficulty in keeping up with
each year. The size of the increment was made propor-
demand. Certainly there appears to be an abrupt in-
tional to the existing FC level (because of the autocata-
crease in the number of transformers with higher FC’s
lytic effect of the water), but with a random element:
in the group having between 13 and 20 years of service
in both Fig. 4 and Fig. 6. (New FC)
The locations of a group of transformers were there-
= (previous FC) + a (previous FC) (rand),
fore classified according to the predominant customer
type (Table 2) in order to investigate if the higher FC where rand is randomly chosen each time from a
levels tended to occur in these ‘industrial’ locations. To range between 0.5 and 1.0. The value of a was set to a
avoid the between-manufacturer variations referred to fractional value such that the average FC was the same
in the previous section, only the Manufacturer-A trans- as had been obtained in practice (Fig. 6).
formers were considered, and, of them, only those 39 Three examples of the distributions obtained are
which were over 12 years old. This latter restriction shown in Fig. 8. By contrast, the three example distri-
made the age group slightly more homogeneous, and butions in Fig. 9 are for the same simulation but with
also omitted those installed after the period of fast incremental increases in FC occurring, with a 50%
industrial expansion. probability, once each month. The value of a was again
Of these 39 transformers, 25 were still in good condi- set to a fractional value such that the average FC was
tion (FCB 1 mg/l), four were in intermediate condition the same as that obtaining with the 190 Manufacturer
(1B FC B 2 mg/l) and ten had relatively high FC-levels A transformers
(FC \ 2 mg/l), as shown in Table 2. The distributions shown in Fig. 8 are clearly fairly
The ‘predominant customer type’ for a given district similar to that in Fig. 6. For example, between 16 and
is inevitably a fairly rough classification, as there will 20 years of service the majority of transformers, in both
always be a mix of customers in any district. Neverthe- simulation and measured data, have low FC’s (less than
less, the proportion of ‘high-FC’ transformers in the l mg/l), and between 2 and 4 transformers have high

Table 2
FC levels by customer type

Commercial Residential Industrial Airport Totals

High(FC\2mg/l) 0 2 6 2 10
Intermediate 1 0 2 1 4
Low (FCB1 mg/l) 1 8 9 7 25
Totals: 2 10 17 10 39
中国科技论文在线 http://www.paper.edu.cn
178 J.M.K. MacAlpine, C.H. Zhang / Electric Power Systems Research 57 (2001) 173–179

6. Discussion

No gradual and systematic deterioration was visible


for 38 of the 40 transformers which were tested more
than once (Section 2). However, there were two cases
where the FC increased dramatically within a 21 month
period by large factors — and these are now being

Fig. 8. Three simulations of 190 transformers with possible yearly


increments in FC, proportional to, but smaller than, the existing FC.

FC’s (greater than 4 mg/l). By contrast, in the distribu-


tions in Fig. 9, the majority of transformers of between
16 and 20 years of service have FC’s greater than 1
mg/l, and between 5 and 8 transformers (twice as many
as in Fig. 8) have high FC’s.
The simulation agrees with the assertion that trans-
formers deteriorate mainly because of occasional and Fig. 9. Three simulations of 190 transformers with very small incre-
substantial FC increments, rather than many small but ments in FC possible every month. The increments in FC are
frequent increments. proportional to, but smaller than, the existing FC.
中国科技论文在线 http://www.paper.edu.cn
J.M.K. MacAlpine, C.H. Zhang / Electric Power Systems Research 57 (2001) 173–179 179

carefully and regularly monitored. These results show dents when either over-loading causes relatively high
that no, or negligible, deterioration takes place in trans- temperatures in the transformers or a fault causes
formers operated normally, but that sudden step local deterioration resulting in intense local heating.
changes in the FC can and do occur. This is also in This was supported by the results of simulations and
agreement with the large variation between transform- also by the results of a comparison of the FC levels in
ers, even those from the same manufacturer (Section 3), transformers 12 or more years old, and located in
and with the results of the simulation (Section 5). industrial zones, with those located elsewhere: those in
The simulation required the assumption that the industrial area where overloading was known to have
increments be proportional to the existing FC, in agree- taken place were twice as likely to have high FC’s.
ment with the auto-catalytic effect of the water, another It is suggested firstly that annual FC measurements
by-product of paper deterioration. This implies that should be made: there should be no significant changes
replacing the oil in high FC transformers would de- in the furfural concentration from year to year but if
crease the deteriorating effect of high temperature oper- such occur then either there has been an overload —
ation. If 4 mg/l were set as the alarm level above which which should have been recorded — or a fault has
an oil change and more regular FC monitoring were developed, causing severe local overheating.
required, then probably only one transformer would Secondly, oil replacement is recommended for trans-
need treatment each year (because only 15 of the 310 formers with high FC levels as this will lessen the
transformers were over 4 mg/l and the transformers deterioration rate during overloads.
range in age up to 30 years).
It was noted earlier, however, that the oil/paper
partition ratio for furfural is about 20:80 [4], so that the References
FC in the oil would rise over a matter of months to a
level determined by the relative proportions of paper [1] D.H. Shroff, A.W. Stannett, A review of paper ageing in power
and oil. If the volume of the oil is one hundred times transformers, Proc IEE 132 (1985) 312 – 319.
[2] D.J.T. Hill, T.T. Le, M. Darveniza, T. Saha, A study of the
that of the paper then, with a 1:5 partition ratio, 95% degradation of cellulosic insulation materials in a power trans-
of the furfural is in the oil. After replacing the oil, the former. Part III: degradation products of cellulose insulation
equilibrium FC would be reduced to 5% of what it had paper, Polymer Degradation and Stability 5l (1996) 211 –218.
been, both in the oil and the paper. This should ideally [3] D. Zheng, B. Lu, L. Yuan and D. Zheng,Thermal ageing behav-
decrease the step deterioration due to high-temperature ior of the oil-impregnated paper at 160°C, Proc. of the 5th
International Conference on Properties and Applications of
operation by a factor of 20. Dielectric Materials, Seoul, Korea, 25 – 30 May, 1997, pp.256–
Obviously, however, the condition of the paper — 258.
the tensile strength — would remain at the level sig- [4] D.M. Allan, Recent advances in the analysis and interpretation
nalled by the previous FC. This would require record- of aged insulation from operating power transformers, Proc. 5
keeping to ensure awareness of the ‘insulation age’ or International Conference on Properties and Applications of
Dielectric Materials, Seoul, Korea, 25 – 30 May, 1997.
condition of the transformer. Thus a transformer which [5] P.J. Burton, J. Graham, A.C. Hall, J.A. Laver and A.J.
has twice reached an FC of 4 mg/l and twice had its oil Oliver,Recent developments by CEGB to improve the prediction
replaced must be considered as an ‘8 mg/l plus’ trans- and monitoring of transformer performance, CIGRE Paper 12 –
former with the implied relatively weak insulating pa- 09, 1984.
per. Knowledge of how many transformers have [6] J. Unsworth, F. Mitchell, Degradation of electrical insulating
paper monitored with high performance liquid chromatography,
relatively weak paper insulation, and which are there- IEEE Trans. El 25 (1990) 737 – 746.
fore susceptible to failure under overcurrent conditions, [7] D.J.T. Hill, T.T. Le, M. Darveniza, T. Saha, A study of the
is an important factor in financial planning. degradation of cellulosic insulation materials in a power trans-
former. Part I: Molecular weight study of cellulose insulation
paper, Polymer Degradation and Stability 48 (1995) 79 – 87.
[8] D.M. Allan, Practical life-assessment technique for aged trans-
7. Conclusion former insulation, Proc.IEE Pt.A 140 (1993) 404 – 408.
[9] M.K. Domun,Condition monitoring of power transformers, IEE
Analysis of the repeated data and of the data overall Colloquium (Digest), V675, pp.2/1 – 2/3, 1994.
led to the conclusion that: [10] T.S.R. Murthy, Assessment of transformer insulation condition
by evaluation of paper-oil systems, Proc. IEEE Conference on
“ negligible deterioration of the insulating paper oc-
Electrical Insulation and Dielectric Phenomena, San Francisco,
curs in a 1 year period under normal operating 20-23 October, 1996, pp.332-335.
conditions; and [11] M.J. Moroney,Facts from figures, Chapter 15, Penguin (Har-
“ deterioration occurs as step increments during inci- mondsworth), 1951.

Вам также может понравиться