Академический Документы
Профессиональный Документы
Культура Документы
1. Contractor shall submit to Saudi Aramco for review and approval working drawings of the
pre-stressing system proposed for use.
2. Contractor shall submit six (6) sets of such drawings for initial review. Saudi Aramco shall
return one (1) approved set or one (1) set with corrections and modifications. After
modification, six (6) sets showing any required corrections shall be submitted for final
approval.
3. Working drawings shall be submitted sufficiently in advance of the start of the affected
work to allow time for review by Saudi Aramco and correction by the Contractor of the
drawings without delaying the approved programmed commencement of the Work.
4. Such time shall be proportional to the complexity of the work but, in no case, shall such
time be less than two months.
5. The working drawings of the pre-stressing system shall show complete details and
substantiating calculations of the method and materials the Contractor proposes to use in
the pre-stressing operations, including any additions or rearrangement of reinforcing steel
and any revision in concrete dimensions from that shown on the plans.
6. Such details shall outline the method and sequence of stressing and shall include complete
specifications and details of the pre-stressing steel and anchoring devices, working stresses,
anchoring stresses, stress-strain curves of the pre-stressing steel, anticipated gauge
pressures, cable profiles, elongation of pre-stressing cables, type of ducts and all other data
pertaining to the pre-stressing operation, including the proposed arrangement of the pre-
stressing steel in the members.
7. The designs shall be prepared and signed by a qualified contractor's Structural Engineer
who has been approved in advance by Saudi Aramco.
8. Approval of working drawings and other submittals does not absolve the Contractor of the
responsibility for any of his Contractual obligations.
9. No additional payment will be made to the Contractor for any changes required as a result
of reviews or approvals.
10. The Contractor shall submit for approval experience records and qualification details of all
the Contractor's key structural design, fabrication, installation, and quality control
personnel who will be working on the pre-stressing and concrete operation.
11. Once approved, the Contractor shall not change or substitute any of the personnel without
the prior approval of the Saudi Aramco.
12. All criteria covered by this Section on submittals and approval shall also apply to any
subcontractor intended to be employed respective to pre-stressed concrete work.
5.04.3 Materials
5.04.3.1 Concrete. Concrete shall be controlled, mixed and handled as specified in 09-
SAMSS0097, as per TQ No. Section 5.01, "Portland Concrete Cement" in these General
Specifications, unless otherwise specified herein or on the drawings. Class shall be as indicated.
Concrete for prestressed work shall be designated Class S, having a 28-day cylinder test
compressive strength of not less than three hundred fifty (350) kilograms per square centimeter.
5.04.3.2 Concrete Reinforcement. Concrete reinforcement shall be in accordance with Section
5.02, "Reinforcing Steel" in these General Specifications unless otherwise specified herein or on
the drawings.
5.04.3.3 Prestressing Reinforcement.
1. Prestressing reinforcement shall be high tensile strength steel wire, high-tensile strength
seven wire strand or high-tensile strength alloy bars as called for on the plans or in these
specifications.
2. High-tensile strength wire shall conform to AASHTO M 204.
3. High-tensile strength seven-wire strand shall conform to the requirements of AASHTO M
203.
4. High-tensile strength alloy bars shall be stress relieved and then cold stretched to a
minimum of nine hundred (900) MPa. After cold stretching, the physical properties shall
be as follows:
Minimum ultimate tensile strength 1000 MPa
Minimum yield strength, measured by the 0.7 percent extension under load method shall
not be less than 900 MPa
Minimum modulus of elasticity 172369 MPa
Minimum elongation in 20 mm bar diameter after rupture 4 percent, min.
Diameter tolerance +0.76 mm, - 0.25 mm
5. Subject to the Saudi Aramc approval, prestressing steel manufactured to standards
equivalent to those indicated herein may be used, provided that all requirements be
satisfied.
6. In addition to the requirements of ASTM A722 for deformed bars, the reduction of area
shall be determined from a bar which the deformations have been removed. Such a bar
shall be machined no more than necessary to remove the deformations over a length of
three hundred (300) millimeters and reduction will be based on the area of the machined
portions.
7. All bars in any individual member shall be of the same grade, unless otherwise permitted
by the Saudi Aramco.
8. When bars are to be extended by the use of couplers, the assembled units shall have a
tensile strength of not less than the manufacturer's minimum guaranteed ultimate tensile
strength of the bars.
9. Failure of any one sample to meet this requirement will be cause for the rejection of the
heat of the bars and lot of couplers.
10. The location of the couplers in the member shall be subject to the approval of the Saudi
Aramco.
11. Wire shall be straightened if necessary to produce equal stress in all wires or wire groups
or parallel lay cables that are to be stressed simultaneously or when necessary to ensure
proper positioning in the ducts.
12. Where wires are to be button-headed, the buttons shall be cold formed symmetrically about
the axis of the wires.
13. The buttons shall develop the minimum guaranteed ultimate tensile strength of the wire.
14. No cold forming process shall be used that causes indentations in the wire. Button heads
shall not contain wide open splits, more than two (2) splits per head, or splits not parallel
with the axis of the wire.
15. Tendons shall not be welded within the length to be tensioned and, unless other methods
of cutting are approved by Saudi Aramco, tendons shall be sawn or cropped using an
abrasive disc cutter.
5.04.3.4 Duct Enclosures.
1. Duct enclosures shall be rigid ferrous metal galvanized and mortar tight. Ducts shall be
fabricated with either welded or interlocked seams. Galvanizing of the welded seam will
not be required.
2. Ducts shall have sufficient strength to maintain their correct alignment during placing of
concrete.
3. Joints between sections of duct shall be positive metallic connections which do not result
in angle changes at the joints. Waterproof tape shall be used at the connections.
4. Ducts shall be bent without crimping or flattening.
5. Transition couplings, connecting said ducts to anchoring devices need not be galvanized.
6. When approved by the Saudi Aramco, ducts shall be of the flexible, corrugated type,
delivered to the site on large diameter wooden drums.
7. Ducts shall be protected from rusting, damage, oil, or any other deleterious matter.
8. All ducts or anchorage assemblies shall be provided with pipes or other suitable
connections for the injection of grout after prestressing.
9. Joints in adjacent ducts shall be staggered by at least thirty (30) centimeters.
10. Provide ducts with an inside diameter at least ten (10) millimeters larger than the nominal
diameter of a single wire, bar, or strand tendon.
11. For multiple wire, bar or strand tendons, provide a duct cross-sectional area at least two (2)
times the net area of the prestressing steel.
12. Ducts for prestressing steel when bars are used shall have a minimum inside diameter ten
(10) millimeters larger than the diameter of the bars to be used.
5.04.3.5 Anchorages.
1 All anchorages shall be approved cast anchorages complying with the requirements of BS
5557 or approved equivalent specifications and capable of securing the permanent type
anchoring device.
2 All anchorages and couplers for posttensioning shall be capable of holding the
prestressing steel at a load producing a stress of not less than ninety-five (95) percent of
the specified ultimate tensile strength of the prestressing steel.
3 The coupling of tendons shall not reduce the elongation at rupture below the requirements
of the tendon itself.
4 Couplers and coupler components shall be enclosed in housings long enough to permit
necessary movements.
5 Couplers for tendons shall be used only at locations specifically indicated or approved by
the Saudi Aramco.
6 Couplers shall not be used as points of sharp tendon curvature.
7 Anchorage devices shall have a minimum clear concrete or grout coverage of fifty (50)
millimeters in every direction.
8 Alternate corrosion protection methods for anchorages shall be shown on the shop
drawings submitted by the Contractor.
9 The prestressing force shall be effectively distributed to the concrete by means of an
approved anchoring device.
10 Any allowance for draw-in of the tendon during anchoring shall be in accordance with
the Saudi Aramco's instructions, and the actual slip occurring shall be recorded for each
individual anchorage.
11 When headed wires are used, the outside edge of any hold for any prestressing wire,
through a stressing washer or through an unthreaded bearing ring or plate, shall not be
less than six (6) millimeters from the root of the thread of the washer or from the edge of
the ring or plate.
12 If loop tendon anchorages are used, they shall be enclosed in ducts for their entire length.
5.04.3.6Grout.
1 The Grout shall conform to the following requirements:
- Portland Cement Conforming to ASTM C 150, Type 1 and Water conforming to
MRDTM 514.
- Maximum water cement ratio: 0.45
- Initial Set of 3.5 MPa with a 161 mm2 probe according to AASHTO T 197.
- Minimum compressive strength per AASHTO T 106.
o Three days: 23 MPa
o Seven days: 30 MPa
o Twenty-eight days: 35 MPa
2 The grout shall be mixed for a minimum of two minutes and until a uniform consistency
is obtained.
3 The pumpability of the grout shall be determined in accordance with the US Corp of
Engineers Method ASTM C 939.
4 The efflux time of the grout sample immediately after mixing shall not be less than eleven
(11) seconds.
5 The flow cone test does not apply to grout which incorporates a thixotropic additive.
6 Admixtures, if used, should impart the properties of low water content, good flowability,
minimum bleed and expansion if desired.
7 Its formulation should contain no chemicals in quantities that may have harmful effect on
the prestressing steel or cement. Admixtures containing chlorides (as C1 in excess of
0.5% by weight of admixture), fluorides, sulfites and nitrates shall not be used.
8 Aluminum powder of the proper fineness and quantity or other approved gas evolving
material which is well dispersed through the other admixture may be used to obtain five
(5) to ten (10) percent unrestrained expansion of the grout.
9 All admixtures should be used in accordance with the instructions of the manufacturer.
5.04.4 EQUIPMENT.
1 Equipment shall conform to the requirements specified in the Contractor's Program of
Work as approved by the Saudi Aramco.
2 Equipment for effectively distributing the load from anchoring devices to the concrete
shall be such that the final unit compressive stress on the concrete directly underneath the
plate or assembly does not exceed twenty (20) MPa.
3 Jacks used to stress tendons shall be equipped with either a pressure gauge or a load cell
for determining the jacking stress.
4 The pressure gauge shall have an accurately reading dial at least one hundred fifty (150)
millimeters in diameter and each jack and its gauge shall be calibrated as a unit with the
cylinder extension in the approximate position that it will be at final jacking force, and
shall be accompanied by a certified calibration chart.
5 The load cell shall be calibrated and shall be provided with an indicator by means of
which the prestressing force in the tendon may be determined.
6 The range of the load cell shall be such that the lower ten percent (10%) of the
manufacturer's rated capacity will not be used in determining the jacking stress.
7 Grouting equipment shall be capable at a pressure of at least seven (7) kilograms per
square centimeter (0.669 MPa).
8 Grouting equipment shall be furnished with a pressure gauge having a full-scale reading
of not more than twenty (20) kilograms per square centimeter (2.07 MPa).
9 Reciprocating pumps or equipment that produces a pulsating flow shall not be used.
10 Grouting equipment shall be thoroughly washed with clean water at least once every three
(3) hours during the grouting operations and at the end of use each day.
11 Unless waived by the Saudi Aramco, a complete grouting plant for immediate use in case
of emergency or breakdown of the equipment in operation shall be available on stand-by.
12 When vents are required, standby flushing equipment capable of developing a pumping
pressure of eighteen (18) kilograms per square centimeter and/or sufficient capacity to
flush out any partially grouted ducts shall be provided.
13 Grout injection pipes shall be fitted with positive mechanical shutoff valves. Vents and
ejection pipes shall be fitted with valves capable of withstanding the pumping pressure.
5.03.4.23 Precast Concrete. In addition, precast concrete Work shall conform to the following
requirements, except when otherwise specifically indicated on the plans or approved by the
Saudi Aramco:
1. The Contractor shall submit shop drawings showing complete information for the
fabrication and installation of precast concrete units.
2. The drawings shall indicate member dimensions and cross-section, location, size and type
of reinforcement and special reinforcement and lifting devices necessary for handling and
erection.
3. The drawings shall detail the erection procedure for precast units, sequence of erection
and required handling equipment.
4. Each precast unit shall be identified to correspond to the sequence and procedure of
installation.
5. All inserts, anchorage devices that are to be embedded, openings, connections, joints, and
accessories shall be indicated on the drawings.
6. Precast concrete units shall be delivered to the site in such quantities and at such times as
will assure the continuity of the installation.
7. Units shall be stored so as to ensure against cracking, distortion, staining, or other
physical damage, and so that markings are visible.
8. Units shall be lifted and supported at the designated lift points only.
9. All parts of the supporting structure and the conditions under which the precast concrete
work is to be erected shall be examined and verified.
10. Installation shall not proceed until unsatisfactory conditions have been corrected.
11. Design modifications may be made only as necessary to meet field conditions and to
ensure proper fitting of the Work, and only as approved by the Saudi Aramco.
12. If design modifications are anticipated, the Contractor shall provide complete design
calculations and drawings prepared by a qualified professional, for approval by the Saudi
Aramco.
13. Concrete shall be placed in a continuous operation to prevent the formation of seams or
planes of weakness in precast units.
14. Placed concrete shall be thoroughly consolidated in each precast unit by internal and
external vibration without dislocation of or damage to reinforcement and built-in items.
15. Precast units shall be provided with permanent markings to identify pick-up points and
orientation in the structure, complying with the markings indicated on the approved shop
drawings.
16. The date of casting shall be imprinted on each precast unit where it will not show in the
finished structure.
17. Curing by low-pressure steam, by steam vapor, by radiant heat and moisture, or other
similar process may be employed to accelerate concrete hardening and to reduce the
curing time, only as approved by and to the satisfaction of the Saudi Aramco.
18. Powder-actuated fasteners for surface attachment of accessory items in any precast,
prestressed unit shall not be used, unless approved in writing by the precast manufacturer,
if any, and only as approved by and to the satisfaction of the Saudi Aramco.
19. Grouting connections and joints after precast concrete units have been placed and
secured, shall be performed as follows:
19.01 Cement grout consisting by volume of one (1) part Portland cement, two and one-
half (2 1/2) parts sand, and only enough water to properly mix and for hydration.
19.02 Shrinkage-resistant grout consisting of premixed compound and only enough water
to provide a flowable mixture without segregation or bleeding.
19.03 Forms or other acceptable method shall be provided to retain the grout in place,
until sufficiently hard to support itself.
19.04 Pack spaces with stiff grout material, tamping until voids are completely filled.
19.05 Place grout to finish smooth, plumb, and level with adjacent concrete surfaces.
19.06 Keep grout damp for not less than twenty-four (24) hours after it has taken its
initial set.
19.07 Promptly remove any grout material from exposed surfaces before it hardens.
1. Pre-stressing shall be applied when concrete is at least 10 days old, and have
achieved a minimum compressive strength of 40MPA.
2. Pre-stressing jacks and their gauges shall be is good working condition and free
from any error.
3. The jacking force for each anchor shall be applied simultaneously, tendons shall
be jacked maintaining symmetry in respect of axis of the girder and with approval
of the Saudi Aramco representative and according to recommendation of the
manufacturer.
4. If the specified stressing force has been applied and the expected extension has
not been attained, stressing may continue to the expected extension, the maximum
applied force however shall not exceed the specified force by5%.
5. If the expected extension has been achieved before the specified force has been
applied, stressing may continue to the specified force, the maximum extension
achieved however shall not exceed the specified extension by 5%.
6. If the above said procedure fails to produce satisfactory results, all stressing shall
cease and the situation shall be reported to Saudi Aramco representative.
7. Extension shall be checked 24 hours after the cables have been anchored to guard
against the possibility, if any, of significant slow slippage.
8. If average observed slow slip at cable anchorage exceeds 3mm, the matter shall be
reported to Saudi Aramco representative for further instruction.
9. All cables which satisfy the above said criteria shall immediately be grouted
taking care that cables remaining unstressed are not accidently blocked due to
grout leakage.
10. Cables shall be grouted after pre-stressing per AASHTO specifications. The
compressive strength of the grout mortar at 28 days shall be 40 MPA.
11. The internal cross section area of sheathing shall be at least 2 times the net area of
the pre-stressing cables
12. If the contractor request to use a different pre-stressing system from that shown
on the drawings, or proposes to make any modification to suit his construction
methodology, he shall use a technically equivalent system and submit full set of
relevant design calculations and detailed shop drawings for approval. Contractor
can use the proposed system subject to approval of Saudi Aramco.
13. Before casting concrete, check sizes and location of all openings required for
ducts, pipes, electrical conduits and other items to be embedded in concrete or
otherwise incorporated in structural work.
14. All exposed concrete edges shall be chamfered 20mm.
15. Unless otherwise noted, minimum cover shall be:
i. Pre-stressing steel and main reinforcement – 50mm
ii. Stirrups and ties – 40mm
16. The tops faces of piers and abutment bearing shelves, other than the bearing seats,
shall have a minimum slope of 5% towards their edges.
17. All forms and false work shall be approved by Saudi Aramco.
18.