Cable Selection Chart,

09/24/2019
acc. to VDE 0100 part 523/6.81

Group 2 Group 3
Cable Cable
35oC A 40oC A 45oC A 50oC A 55oC A 35oC A 40oC A 45oC A 50oC A 55oC A
Sizes Sizes

1.5 16.92 15.66 14.22 12.78 10.98 2.5 30.08 27.84 25.28 22.72 19.52

2.5 24.44 22.62 20.54 18.46 15.86 4 39.48 36.54 33.18 29.82 25.62

4 31.96 29.58 26.86 24.14 20.74 6 50.76 46.98 42.66 38.34 32.94

6 41.36 38.28 34.76 31.24 26.84 10 68.62 63.51 57.67 51.83 44.53

10 57.34 53.07 48.19 43.31 37.21 16 92.12 85.26 77.42 69.58 59.78

16 77.08 71.34 64.78 58.22 50.02 25 121.26 112.23 101.91 91.59 78.69

25 101.52 93.96 85.32 76.68 65.88 35 148.52 137.46 124.82 112.18 96.38

35 126.9 117.45 106.65 95.85 82.35 50 186.12 172.26 156.42 140.58 120.78

50 157.92 146.16 132.72 119.28 102.48 70 230.3 213.15 193.55 173.95 149.45

70 194.58 180.09 163.53 146.97 126.27 95 274.48 254.04 230.68 207.32 178.12

95 192.7 178.35 161.95 145.55 125.05 120 323.36 299.28 271.76 244.24 209.84

120 274.48 254.04 230.68 207.32 178.12 150 367.54 340.17 308.89 277.61 242.42

150 314.9 291.45 264.65 237.85 204.35 185 421.12 389.76 353.92 318.08 273.28

185 359.08 332.34 301.78 271.22 233.02 240 496.32 459.36 417.12 374.88 322.08

240 425.82 394.11 357.87 321.63 276.33 300 571.52 528.96 480.32 431.68 370.88

300 491.62 455.01 413.17 371.33 319.03 400 682.44 631.62 573.54 515.46 442.86

500 780.2 722.1 655.7 589.3 506.3

Group 2: Multiple-core conductors, e.g. sheathed conductors,


conduit wires, lead sheath conductors, flat conductors, movable conductors.

Group 3: Single-core conductors with minimum spacing equal to their own diameter.

Material: Cu
Insulation: PVC

Prepared By: Raza Jafri file:///conversion/tmp/scratch/438855756.xls