Вы находитесь на странице: 1из 1

DATA SHEET LECTROTEK

TEMPRA-VP SYSTEMS

Tempra-VP Valve Electric Positioner


• Electronic, solid-state
• Input 4-20mA etc. from Controllers
• Output Up-Down relays to control
Electric Actuators
• Position feedback 0-135Ω (max 2K)
• Bargraph display for valve position
• DIN std cutout 92x92 mm

1.0 SPECIFICATIONS
Inputs, output
Input 0/4-20 mA or 0,1-5Vdc signal from PID
Controllers, PLC, DCS etc. (Control Signal) 2.0 FUNCTION
Feedback Input 0-135 oms (max 2K, specify) Tempra-VP is part of Lectrotek’s ¼ DIN-size
for valve position feedback. Tempra-series control room instruments.
Output forward-reverse relays to drive electric
actuators, rated 7A, 240VAC. The instrument provides an Auto-Manual
Power Supply 240/110 VAC, 50 Hz or 24Vdc operating interface between controllers/ PLCs/
Accuracy 0.25% FS +/- 1 digit DCS systems and electric final operating
elements such as Motorised Control Valves,
Dimensions/Environmental Electrically-actuated Dampers etc. It accepts
Dimensions 96x96x170 mm dc inputs from control signal, and provides a
Panel Cutout 92x92 mm DIN std. forward-reverse relay output to drive the
Enclosure ABS enclosure, plug-in boards. operating circuit of the reversible-motor of the
Protection IP40 protection. electric actuator. A potentiometric/slide-wire
Operation 55oC and 90% RH maximum. resistance feedback from the electric actuator
provides the feedback input to the Tempra-VP
Fascia for the balancing circuit.
Display 10-segment LED bargraph for VP.
LEDs to indicate Up-Down relay operation 3.0 OPERATION TEMPRA-AM provides an
and Feedback failure condition Up-Down relay outputs in accordance with a
Manual operation Optional Auto-Manual control DC signal (0/4-20 mAdc etc.) which is
controls available on order. compared with the present valve position
signaled by the resistance signal feedback.
Also refer to products for similar applications LEDs are provided to indicate the relays Up or
• LTRON-AML µP-based Auto-Manual Loader Down operation; both are OFF in relays de-
• Minima-AM A/M Loaders in 72 mm² size energised condition.
• TEMPRA-AM Auto-Manual Loaders with DC
Signal (4-20 mA etc.) inputs/outputs. 4.0 OPTIONS
1. Auto/Manual operation by A/M switch.
2. Feedback position retransmission
signal, via 0/4-20 mAdc.

LECTROTEK SYSTEMS PVT. LTD.


9 Electronic Estate, Pune-Satara Road, Pune-411009
Tel. +91-20-4220313,4220383 Fax 4223932
Email lspl@vsnl.com Website www.lectrotek.com