Referrence Table 502.01 Referrence Table 502.01

Minimum Efficiency Requirements for Unitary Air Conditioners and Condensing Units Water Chilling Packages - Minimum Efficiency Requirements
Equipment Equipment
Type Example Type
Refference Minimum Minimum Refference Minimum
Size Heating Subcategory or Efficiency Efficiency Test Equipment Type Size Category Minimum Efficiency (T3) Test procedure
Efficiency (T1)
Equipment Type Category Section Type Rating Condition (T1) (T3) Procedure

* Split Ducted 9.5 6.6 T1-ARI 2.8 COP


Spilt System
210/240 Air cooled, with condenser, electrically
A
* Split Décor.
Air Conditioners, air cooled
<65,000
All
EER EER F Air cooled chiller
operated
All capacities 3.05 IPLV 1.9 COP
* Package Btu/h T3- T1-ARI 210/240
9.5 6.6
* Cassette Single Package ISO5151
* FAHU-DX EER EER 3.1 COP
Air cooled, without condenser, electrically
<=30,000 8 5.7
G Air cooled chiller
operated
All capacities
3.45 IPLV
2.1 COP
B * Window Type
Through-the-wall, air cooled
Bth/h
All Single Package
EER EER T1-ARI 550/590

<65,000 9.2 6.4 Water cooled Chiller 4.2 COP


C_ Small-duct high-velocity air cooled
Bth/h
All Split System Water cooled, electrically operated, positive
EER EER
H displacement (reciprocating)
All capacities
5.05 IPLV
2.75 COP
T3-ISO 5151
Electric 9.5 6.6
Split System and T1-ARI
resistance
Single Package 340/360
(or none) EER EER T1-ARI 550/590
>=65,000
Btu/h and T3- <150 tons 4.45 COP 2.9 COP
<135,000 9.5 6.6 ISO5151
* Split Ducted
Btu/h Split System and
All other Water cooled, electrically operated, positive
Single Package I >=150 tons and
EER EER Water cooled Chiller displacement (rotary screw and scroll) 4.9 COP 3.2 COP T3-ISO 5151
<300 tons
* Split Décor.
* Package Electric
* Cassette Split System and 9.5 6.6 >= 300 tons 5.6 COP 3.6 COP
>=135,00 resistance
Single Package
* FAHU-DX 0 Btu/h (or none) EER EER <150 tons 6.0 COP
and
<240,000 9.5 6.6 Water cooled Chiller 6.5 COP
Split System and >=150 tons and
Btu/h All other
Single Package <300 tons
A Air Conditioners, air cooled EER EER J Water cooled, electrically operated, centrifugal 7.1 IPLV T1-ARI 550/590
Electric 9.5 6.6 6.5COP
Split System and
resistance >=300 tons
>=240,00 Single Package
(or none) EER EER 7.68 IPLV
0 Btu/h
and
<760,000 9.5 6.6 K Air cooled chiller Air-cooled absorption single effect All capacities 0.7 COP
Split System and
Btu/h All other
Single Package
EER EER L Water cooled Chiller Water-cooled absorption single effect All capacities 0.7 COP

Electric ARI 560


Split System and 9 6.3 Absorbtion Chiller 1.1 COP
resistance
Single Package M Absorption double effect, indirect-fired All capacities
(or none) EER EER 1.1 IPLV
>=760,00
0 Btu/h
Split System and 9 6.3 Absorbtion chiller 1.2 COP
All other
Single Package N Absorption double effect, direct-fired All capacities
EER EER 1.2 IPLV

<65,000 Split System and 14 ARI (a) The chiller equipment requirements applies to all chillers, including where the design leaving fluid
All temperature is <4.5°C.
Btu/h Single Package 210/240
EER
Electric
Split System and 14
O District Cooling
Split System >=65,000 resistance
Single Package
Package Btu/h and (or none) EER
<135,000
Btu/h Split System and 14
D All other
Single Package
EER
Air conditioners, water and Electric
evaporatively cooled Split System and 14
>=135,00 resistance
0 Btu/h Single Package ARI
(or none) EER
and 340/360
<240,000 14
Split System and
Btu/h All other
Single Package
EER
Electric 14 EER
Split System and
De Split System
>=240,00
resistance
Single Package
Package (or none) 12.4 IPLV
0 Btu/h
Split System and
D All other
Single Package
14 EER
Condensing T1-ARI
11.5 7.8
Unit 365
>=135,00
E Condensing units, air cooled
0 Btu/h
EER EER
T3-
ISO5151
(a) Integrated Part Load Values (IPLVs) and part rating conditions are only applicable to equipment with capacity
modulation.
(b) Test Procedure (T3) in accordance with ISO5151
SUMMERY OF THERMAL LOAD CALCULATION 1/3/2014 V1
Plot No.
Condensate Recovery is Optional
Project

Hide Empty Rows Demand


Consultant

(Eqiupment & Type References) Number No. of Outdoor Occupant Control Calculated AC Load First Selection Second Selection Outdoor
Units Reference of Area Volume Indoor Unit
Reference Location People Air Desnity Electric Power kW Efficiency Electric Power kW Efficiency Unit
/ No. Typical Check Figures
Type Floors (DCV) Total Sensible Flow Rate Quantity Total Sensible Flow Rate Indoor Outdoor T1 T3 Quantity Total Sensible Flow Rate Indoor Outdoor T1 T3
Ref. Tables
m2 No. L/s No./100 m2 Requirement kW kW L/s kW/m2 L/s.m2 No. kW kW L/s kW kW EER COP IPLV EER COP No. kW kW L/s kW kW EER COP IPLV EER COP V/PH/HZ V/PH/HZ
AC 01 A Split Ducted Kitchen 1.00 50.50 7.00 13.86 13.30 11.50 925.00 0.26 18.32 1.00 14.00 9.30 930.00 4.65 10.10 1.00 14.00 9.30 930.00 4.65 10.10 230/1/50 230/1/50
AC 02 A Split Ducted Dining 1.00 67.10 40.00 59.61 12.70 9.30 828.00 0.19 12.34 1.00 14.00 9.30 930.00 4.65 10.10 1.00 14.00 9.30 930.00 4.65 10.10 230/1/50 230/1/50
AC 03 A Split Ducted Dish Wash & Packing 1.00 40.90 5.00 12.22 7.10 5.90 465.00 0.17 11.37 1.00 8.50 5.90 507.00 2.47 11.70 1.00 8.50 5.90 507.00 2.47 11.70 220-240/1/50 220-240/1/50
AC-04 A Split Décor. Office 01 1.00 31.32 3.00 9.58 3.60 3.20 245.00 0.11 7.82 1.00 4.20 3.20 250.00 1.24 11.50 1.00 4.20 3.20 250.00 1.24 11.50 230/1/50 230/1/50
AC-05 A Split Décor. Office 02 1.00 27.30 3.00 10.99 3.40 3.10 230.00 0.12 8.42 1.00 4.20 3.20 250.00 1.24 11.50 1.00 4.20 3.20 250.00 1.24 11.50 230/1/50 230/1/50
AC-06 A Split Décor. Watchman 1.00 10.80 1.00 9.26 1.80 1.70 160.00 0.17 14.81 1.00 2.00 1.80 188.00 0.46 14.00 1.00 2.00 1.80 188.00 0.46 14.00 230/1/50 230/1/50
TOTAL 6.00 227.92 59.00 0.00 25.89 41.90 34.70 2853.00 0.18 12.52 6.00 46.90 32.70 3055.00 14.71 0.00 6.00 46.90 32.70 3055.00 14.71 0.00
Total Outdoor Air Total Electric Power Total Electric Power
L/s 0.00 58.28 W/m2 64.54 W/m2 64.54
Btu/hr.ft 2 W/Ft2 6.00 W/Ft2 6.00