Вы находитесь на странице: 1из 1

MATERIAL LIST

ITEM SIZE
N NO. DESCRIPTION (DN) QTY.
G4 B5/6 SEE ISO 1 EQUAL TEE, TYPE-A, P235GH, DIN 2848, 6.3MM THK., 200X200 1
MODIFICATION TERNA
50HTK01BR009 SERIES 2, RUBBER LINED WITH MIN. THICKNESS 6.0MM,

365
365 X= -701 / 50UVE_F MODIFICATION ANAGNOSTOU (ANG) FLANGED END, SEAMLESS
Y= +1961 / 50UVE_13
CONN TO 2 PIPE, P235GH, DIN EN 10216-2, O.D. 219.1MM, 6.3MM 200 3
Z= EL.+15613
LIMESTONE CLASSIFIER 1 / 50 HTK01BB003/N2_DN200_OVERFLOW DISCHARGE THK., RUBBER LINED WITH MIN. THICKNESS 6.0MM, FLANGED

365
200 mm RFFE PN10 END, SEAMLESS
X= -959 / 50UVE_F 3 ELBOW, 45 DEG., LR (R=1.5D), MODEL-3D, TYPE-A, 200 2
Y= +2218 / 50UVE_13 DN200 P235GH, DIN 2848, 6.3MM THK., SERIES 2, RUBBER LINED
Z= EL.+15981 WITH MIN. THICKNESS 6.0MM, FLANGED END, SEAMLESS
B5/6
DN200 4 GSK : GASKET 200 2
1
5 STUD BOLT, M20 X 110mm, C-St 8.8 (Galv.), DIN 976-1 20 48
DN200X200
ORIENT 6 HEXAGONAL NUT, M20, C-St 8 (Galv.), DIN EN ISO 4032 20 96

1408
E 44.90 S
X= -959 / 50UVE_F
Y= +2218 / 50UVE_13 2
Z= EL.+15613

190 B5/6
190

3
B5/6 X= -959 / 50UVE_F
Y= +2218 / 50UVE_13
Z= EL.+13650

68
20

1726
1. FOR VALVES (IDENTIFIED BY KKS), REFER VALVE LIST.
X= +1815 / 50UVE_E 2. FOR SPECIALITIES (IDENTIFIED BY KKS), REFER DATA SHEET.
Y= -2355 / 50UVE_14 REFERENCE DOCUMENTS / DRAWINGS
Z= EL.+11924
190 2 DRAWING / DOCUMENT TITLE DRAWING / DOCUMENT NO.
INSULATION SPECIFICATION 4311-0-023-IF03-21372
B5/6 PAINTING SPECIFICATION 4311-0-023-IF03-21373
190 WELDING SPECIFICATION 4311-X-XXX-XXXX-XXXXX
3 B5/6 PIPE MATERIAL SPECIFICATION (PMC) 4311-0-027-IB16-21360
26 LINE LIST (ARC SCOPE) 4311-0-020-IK15-21701
17
17 VALVE LIST (ARC SCOPE) 4311-0-020-IK01-21702
700

7
PIPING LIST (MHPSE) 4311-A-HT_-IK15-10001
DN200

SUPPORT LIST 4311-X-XXX-XXXX-XXXXX


2

CONN TO G4
LIMESTONE SLURRY TANK/50HTK10BB001/N7_DN200_SLURRY INLET FROM BALL MILL #1
200 mm RFFE PN16
X= +1815 / 50UVE_E AA 22-06-2018 SECOND ISSUE VVP AKG SMA
Y= -2355 / 50UVE_14
-- 20-11-2017 ISSUED FOR APPROVAL VVP AKG SMA
Z= EL.+11034
REV. DATE DESCRIPTION DESIGN CHECK APPR'D
PROJECT OWNER
FIELD WELD/ WELD TYPE LEGEND FOR EXAMINATION AND TESTING HOLDS:
WELD NO. DN (MM) (1) PTOLEMAIS UNIT V
SHOP WELD CF/BR/FIL/SL
UT RT MT PT S H VT 660 MW POWER PLANT
(2)
ULTRASONIC CONTRACT DMKT - 11 09 5052
RADIOGRAPHIC (3)
NOTES: CONTRACTOR
MAGNETIC PARTICLE TESTING
PENETRANT TESTING (1) ALL DIMENSIONS ARE IN 'MM' UNLESS OTHERWISE STATED.
SURFACE CRACK (2) BRANCH ORIENTATION INTERPRETATION (EXAMPLES) :
HARDNESS (a) E 30.0 N : STARTING FROM EAST DIRECTION, ROTATE 30 DEG. TOWARDS NORTH
VISUAL (b) U 20.0 E 1.0 N : STARTING FROM VERTICALLY UP DIRECTION, ROTATE 20 DEG. TOWARDS EAST, AND
1 DEG. TOWARDS NORTH
(3) WELDS TO BE FIXED BY ERECTION / FABRICATION CONTRACTOR. FW = FIELD WELD ; SW = SHOP WELD .
CF BR FL SL (4) EXTENT OF NDT TO BE FIXED BY ERECTION CONTRACTOR. ENGINEER
% % % %
(5) COORDINATES AT KEYPOINTS INSIDE A BUILDING ARE REFERENCED FROM NEAREST BUILDING GRID.
UT COORDINATES REFERENCED FROM "ABS" ARE ABSOLUTE COORDINATES - APPLICABLE FOR OUTDOOR AREA.
CF CIRCUMFERENTIAL WELDS
RT DESIGN CODE DIN EN 13480 TITLE
+Z (UP) PROPRIETARY INFORMATION PIPING ISOMETRIC DRAWING
MT BR BRANCH WELDS Transmittal, reproduction, dissemination and/or PWHT NO
PT editing of this document as well as utilization of INSULATION PURPOSE
FL FILLET WELDS its contents and communication thereof to others
P
S +Y +X without express authorization are prohibited. INSULATION THICKNESS 40 MM LINE KKS : 50HTK01BR010 SYSTEM KKS : HTK
SL SEAL WELDS Offenders will be held liable for payment of DESIGN TEMPERATURE 80 °C
H NO damages. All rights created by patent grant or SCALE DRAWING NO. SHEET REV. NO.
RT ST registration of a utility model or design patent DESIGN PRESSURE 7.0 bar-g
VT H EA are reserved. NTS 4311-A-HTK-ID12-21462 1 OF 1 AA
TEST PRESSURE 10.0 bar-g