POWER TRANSFORMER

No-load Loss and Load Loss Calculation

I. For 300MVA 230kV auto transformer


1.OSFZ11-300000/230 Technical data
Voltage:230±10×1.25%/135/34.5 kV
Rated power:300000/300000/100000 kVA (HV/MV/LV)
Rated current: 753.1/ 1283/ 1673.5 A (HV/MV/LV)
Impedance:HV-LV/ HV-MV/ MV-LV:16%/13%/29%
Vector group:YNa0d1
Frequency:50 Hz
Cooling method:ONAN/ONAF
Transformer type: step down transformer

2.Load loss calculation


Load loss calculation at principal tap
◆Resistance loss=HV winding resistance loss+ MV winding resistance loss

=3×0.09076×753.1 2 +3×0.11636×529.9 2
=252.446 kW
◆Other loss=HV winding stray loss+ MV winding stray loss+ lead loss+ tank clamp
stray loss
=9.729+6.509+2.524+252.446×26.85%
=86.544 kW

◆Total load loss=252.446+86.544=338.99 kW

3.Core data and no-load loss calculation

Address: No. 369 West Avenue, Sanmen County, Zhejiang Province, P.R.China PC: 317100
Tel: +86-13968503566 Fax: +86-10-8306 5679 Email: john@sanbian.cn Http://www.sanbian.cn
⑴. Core data
This auto transformer uses three phase five limbs structure of core. The silicon steel
type is 23RK080. The diameter of limb is Φ800mm, the window height is 1960mm, Mo:

2180 mm,Mo’:1310 mm, cross section of limb is 4598.964 cm 2 ,the maximum sheet

width of limb is 780mm, the total weight of core is 54844 kg. The flux density of core is
1.702T, the unit loss is 0.8W/kg.
⑵.No-load loss calculation
◆No-load loss=core weight×unit loss×craft factor K
=54844×0.82×1.12
=50.37 kW

II. For 120MVA 132kV power transformer


1.SFZ11-120000/132 technical data
Voltage:132±8×1.25%/34.5 kV
Rated power:120000/120000 kVA
Rated current: 524.9/ 2008.2 A (HV/LV)
Impedance:12%
Vector group:Dyn1
Frequency:50 Hz
Cooling method:ONAN/ONAF
Transformer type: step down transformer

2.Load loss calculation


Load loss calculation at principal tap
◆Resistance loss=HV winding resistance loss+ LV winding resistance loss

=3×0.44851×303 2 +3×0.007575×2008.2 2

Address: No. 369 West Avenue, Sanmen County, Zhejiang Province, P.R.China PC: 317100
Tel: +86-13968503566 Fax: +86-10-8306 5679 Email: john@sanbian.cn Http://www.sanbian.cn
=215.179 kW
◆Other loss=HV winding stray loss+ LV winding stray loss+ lead loss+ tank clamp
stray loss
=8.589+4.168+2.228+215.179×7.46%
=31.037 kW

◆Total load loss=215.179+31.037=246.216 kW

3.Core data and no-load loss calculation


⑴. Core data
This auto transformer uses three phase five limbs structure of core. The silicon steel
type is 30RK100,The diameter of limb is Φ780,window height:2120 mm,Mo:1580

mm,Mo’:1010 mm,cross section of limb:4366.746 cm 2 ,the maximum sheet width

of limb:760 mm,the total weight of core:47688 kg. The flux density of core:1.708 T,
unit loss:1.034 W/kg
⑵.No-load loss calculation
◆No-load loss=core weight×unit loss×craft factor K
=47688×1.034×1.12
=55.234 kW