To change coefficient

Enter “E”
Press “+” and select Basic Function & press “E”
Press “+” and select reference parameter and press “E”
Select Cal. Ref Density and press “E”
Now density is +0.5000 e-3
Now press”+”

Access code shall be asked. Which is 83. Now cursor will be on first digit. Press + to select number 8 as
first number and press “E” . Now press + to select number 3 as second digit and theren press “E” and

again press”E”. Message will appear that u are in programming mode.

Now change density by using +, - and “E”.

Now press “+” and “-“ together to come out. Press together many times (4 to 5 time) till you can view
main screen.
FOR EXTRA DENSITY PARAETER CONFIGURATION
Enter “E”
Press “+” and select Basic Function & press “E”
Press “+” and select MODBUS 485 and press “E”
Select CONFIGURE and press “E”
TAG NAME and press “E”
ADDRESS and press “E”
BOUD RATE and press “E”
PROG MODE and press “E”
STOP BITS and press “E”
1-8-3-2 and press “E”
DELAY and press “E”
Write prob ofer ma
Scan rey 1 to 6
7th press “+” set to 02015 sing + & - key.

If Access code shall be asked. Which is 83. Now cursor will be on first digit. Press + to select number 8 as
first number and press “E” . Now press + to select number 3 as second digit and theren press “E” and
again press”E”. Message will appear that u are in programming mode.

Now change any number by using +, - and “E”.


Now press “+” and “-“ together to come out. Press together many times (4 to 5 time) till you can view
main screen.
FOR EXTRA DENSITY PARAETER CONFIGURATION
Enter “E”

Now press “+” till TOTALIZER OPTION & Press “E”

Now press “+” till Handling totalizer & Press “E”

Option is PRESET ALL TOTAL

If Access code shall be asked. Which is 83. Now cursor will be on first digit. Press + to select number 8 as
first number and press “E” . Now press + to select number 3 as second digit and theren press “E” and
again press”E”. Message will appear that u are in programming mode.Now change any number by using
+, - and “E”.

After access code press + both option shall be available for yes & no.

Now press + to select yes

Now enter

Sure . press “+” to select yes. Press “E”

Now “NO” Option is available.

Pres “+” & “-“ simultaneously contionusly till you get main screen.

FOR VIEWING ERROR


PRESS ENTER

PRESS “+” TILL SUPERVISION & press “E”

Select System and press “E” (Press + for up & down for options)

Select Operation and press “E”

Messagen shall be there “SYSTEM OK” & Press “E”

At top “Prev. Sys. Cond.” Option can be viewed.

Press “+”
If Access code shall be asked. Which is 83. Now cursor will be on first digit. Press + to select number 8 as
first number and press “E” . Now press + to select number 3 as second digit and theren press “E” and
again press”E”. Message will appear that u are in programming mode.Now change any number by using
+, - and “E”.

Press “+” to view list.

Press “+” & “_” together to come out to main screen.

Cabling

4,5 –

6,7-

8- ground

9,10- temp

11, 12 – density

41,42 –

Troubleshooting on 3.08.15 =

Following error was observed, Fluid temp max, range freq out, noise limit CH0, Range freq out.

After PLT EXEC.CURR.LIM, FLUID INHOM. Errors were observed.

Engineer concerned was Mr. Abhishek = 9930822824


RESET PROCEDURE OF MASS FLOWMETER-MUPL

There are three touch-buttons provided just below the display of mass flow-meter. ‘-/+’ are for scrolling
up/down or pervious/next, and ‘E’ is for enter command. Stepwise procedure for resetting the totalizer
reading to zero is given below:
Press ‘E’
Press ‘+’ to scroll down till you reach Totalizer Option
Press ‘E’
Press ‘+’ to scroll down till you reach Handling Totalizer
Press ‘E’
Reset All Total is displayed
Press ‘+’
Option for process code (****) will appear
Press ‘+’ and digit ‘0’ will appear in place of first *
Digit value can be changed (0-9) by pressing ‘+’
Process code is 83
Press ‘+’ till first digit is ‘8’
Press ‘E’ to go to next *
Press ‘+’ till second digit is ‘3’
Press ‘E’ to go to next *
Press ‘E’ to go to next *
Press ‘E’
Both Yes and No options will be displayed
Press ‘+’ to scroll to Yes
Press ‘E’
Are You Sure option will be displayed
Press ‘+’ to scroll to Yes
Press ‘E’
All totals will be reset and only No option will be displayed
Press ‘+’ & ‘-’ simultaneously to go back till you get main display showing MFM reading

MASS FREQUENCY SIMULUTION


PRESS “E” for main menu

Go to output by using press “+” or “ –“

Press ‘ E ‘ and go to pulse frequency output 1

Press ‘ E ‘ for go to configuration

Press ‘ E ‘ for go to Frequency

Press ‘ E ‘ for go to mass flow


Press ‘ E ‘ for enter Password

Press ‘ + ‘ to enter Digit “83”

Eater ‘ E ‘ for change frequency

Press ‘ + ‘ for change freq

Press ‘ E ‘ for enter

Then press ‘ + ‘ & ‘ – ‘ both for back & main menu

SIMULATION OFF
Main menu-Output -Pulse frequency output 1- Configuration- Frequency - Then press “E”

Press “+” go to Off then press “E”

Then back to main screen by using “+” & “-“