Вы находитесь на странице: 1из 7

IECEx Certificate

of Conformity
INTERNATIONAL ELECTROTECHNICAL COMMISSION
IEC Certification Scheme for Explosive Atmospheres
for rules and details of the IECEx Scheme visit www.iecex.com

Certificate No.: IECEx KEM 09.0034X Issue No: 4 Certificate history:


Issue No. 4 (2017-11-29)
Status: Current Issue No. 3 (2016-07-28)
Page 1 of 4 Issue No. 2 (2015-03-26)
Date of Issue: 2017-11-29 Issue No. 1 (2012-12-10)
Issue No. 0 (2009-11-05)
Applicant: Rosemount Inc.
8200 Market Boulevard
Chanhassen, MN 55317
United States of America

Equipment: Transmitter Model 3051, Type 3051C, 3051T, 3051L, 3051CFA, 3051CFC and 3051CFP
Optional accessory:

Type of Protection: Ex db

Marking:
Ex db IIC T6...T4 Ga/Gb

Approved for issue on behalf of the IECEx R. Schuller


Certification Body:

Position: Certification Manager

Signature:
(for printed version)

Date:

1. This certificate and schedule may only be reproduced in full.


2. This certificate is not transferable and remains the property of the issuing body.
3. The Status and authenticity of this certificate may be verified by visiting the Official IECEx Website.

Certificate issued by:


DEKRA Certification B.V.
Meander 1051
6825 MJ Arnhem
The Netherlands
IECEx Certificate
of Conformity
Certificate No: IECEx KEM 09.0034X Issue No: 4

Date of Issue: 2017-11-29


Page 2 of 4

Manufacturer: Rosemount Inc.


8200 Market Boulevard
Chanhassen, MN 55317
United States of America

Additional Manufacturing location(s):


Additional Manufacturing Locations are Included in Annex 2
This certificate is issued as verification that a sample(s), representative of production, was assessed and tested and found to comply with the
IEC Standard list below and that the manufacturer's quality system, relating to the Ex products covered by this certificate, was assessed and
found to comply with the IECEx Quality system requirements. This certificate is granted subject to the conditions as set out in IECEx Scheme
Rules, IECEx 02 and Operational Documents as amended.

STANDARDS:
The electrical apparatus and any acceptable variations to it specified in the schedule of this certificate and the identified documents, was found
to comply with the following standards:

IEC 60079-0 : 2011 Explosive atmospheres - Part 0: General requirements


Edition:6.0
IEC 60079-1 : 2014-06 Explosive atmospheres - Part 1: Equipment protection by flameproof enclosures "d"
Edition:7.0
IEC 60079-26 : 2014-10 Explosive atmospheres – Part 26: Equipment with Equipment Protection Level (EPL) Ga
Edition:3.0

This Certificate does not indicate compliance with electrical safety and performance requirements other than those expressly included in the

Standards listed above.

TEST & ASSESSMENT REPORTS:


A sample(s) of the equipment listed has successfully met the examination and test requirements as recorded in

Test Report:

NL/KEM/ExTR09.0038/03 NL/KEM/ExTR09.0038/04

Quality Assessment Report:

GB/BAS/QAR06.0058/05 GB/BAS/QAR06.0072/08 GB/BAS/QAR07.0014/07


GB/BAS/QAR07.0024/06 GB/BAS/QAR07.0036/06 GB/BAS/QAR10.0012/05
GB/BAS/QAR11.0012/04 GB/BAS/QAR13.0012/02
IECEx Certificate
of Conformity
Certificate No: IECEx KEM 09.0034X Issue No: 4

Date of Issue: 2017-11-29


Page 3 of 4

Schedule

EQUIPMENT:
Equipment and systems covered by this certificate are as follows:

Transmitter Model 3051, Type 3051C, 3051T, 3051L, 3051CFA, 3051CFC and 3051CFP, are microprocessor based transmitters,
used to convert the measured process pressure into digital or analog signals, available in single housing version.

For details on the nomenclature, thermal data and electrical data see Annex 1 to this certificate.

SPECIFIC CONDITIONS OF USE: YES as shown below:

The device contains a thin wall diaphragm less than 1 mm thick that forms a boundary between EPL Ga (process connection) and EPL
Gb (all other parts of the equipment). The model code and datasheet are to be consulted for details of the diaphragm material. During
installation, maintenance and use the environmental conditions to which the diaphragm shall be subjected shall be taken into account.
The manufacturer's instructions for installation and maintenance shall be followed in detail to assure safety during its expected lifetime.

Flameproof joints are not intended for repair. 

Non-standard paint options may cause risk from electrostatic discharge. Avoid installations that could cause electrostatic build-up on
painted surfaces, and only clean the painted surfaces with a damp cloth. If paint is ordered through a special option code, contact the
manufacturer for more information.
IECEx Certificate
of Conformity
Certificate No: IECEx KEM 09.0034X Issue No: 4

Date of Issue: 2017-11-29


Page 4 of 4

DETAILS OF CERTIFICATE CHANGES (for issues 1 and above):

The following changes were assessed:

1. Addition of new isolating diaphragm material options


2. Minor updates to drawings
3. Removal of Metran manufacturing facility

Annex:

381998900-Annex 1.pdf

381998900-Annex 2.pdf
Annex 1 to IECEx Report NL/KEM/ExTR09.0038/04
Annex 1 to Certificate of Conformity IECEx KEM 09.0034X, issue 4
Annex 1 to EU-Type Examination Certificate KEMA 00ATEX2013 X, issue 8

Description

Transmitter Model 3051, Type 3051C, 3051L, 3051T, 3051CFA, 3051CFC and 3051CFP, are
microprocessor based transmitters, used to convert the measured process pressure into digital or analog
signals.

Type designation

3051 C …
I II variants

Designation Explanation Value Explanation


I Model 3051 Transmitter
C Co-Planar
T Inline
L Liquid Level
II Type
CFA Annubar Flowmeter
CFC Compact Flowmeter
CFP Integral Oriface Flowmeter

Variants

1,2,3,4,5,P9 310 bar maximum pressure


Static Pressure Ranges 1380 bar maximum pressure
6
(Model 3051T only)
A 4-20 mA w/ HART
F Foundation fieldbus
Signal output
W Profibus PA
M Low Power 1-5 V Hart
2 316L SST
3 Alloy C-276
4 Alloy 400
Isolating diaphragm material
5 Tantalum
6 Gold Plated Alloy 400
7 Gold Plated SST
A Aluminum ½ NPT
B Aluminum M20x1.5
E Low Copper Aluminum ½ NPT
Ex d housing material and entries
F Low Copper Aluminum M20x1.5
J SST ½ NPT
K SST M20x1.5
- No Display
Display and Interface Options M4 LCD Display with Operator interface
M5 LCD Display
0 No temperature option
Temperature option T Integral RTD
For models 3051CFA, 3051CFC and 3051CFP only. R Remote thernowell and RTD
Conduit Electrical Connector Custom Not in scope of this certificate

Page 1 of 2
Form 124
Version 2 (2013-07)
DEKRA Certification B.V. Meander 1051, 6825 MJ Arnhem P.O. Box 5185, 6802 ED Arnhem The Netherlands
T +31 88 9683000 F +31 88 9683100 www.dekra-certification.com Registered Arnhem 09085396
Annex 1 to IECEx Report NL/KEM/ExTR09.0038/04
Annex 1 to Certificate of Conformity IECEx KEM 09.0034X, issue 4
Annex 1 to EU-Type Examination Certificate KEMA 00ATEX2013 X, issue 8

Variants (continued)

Wireless Options Custom Not in scope of this certificate


Condition as listed in the certificate
Non-standard paint Custom
applies
Note: Other variants may appear in the Type designation, but are not relevant for this certificate.

Thermal data

The relation between process connection temperature, ambient temperature and temperature class is as
follows:

Process connection temperature range Ambient temperature range Temperature class


[°C] [°C]
-60 °C to +70 °C -60 °C to +70 °C T6
-60 °C to +80 °C -60 °C to +80 °C T5
-60 °C to +120 °C -60 °C to +80 °C T4

Electrical data

Power supply 10.5 – 42.4 Vdc, 9 – 32 Vdc or 6 – 12 Vdc


Output 4 – 20 mA with digital HART, a fieldbus signal or a low power 1 – 5 Vdc signal

Page 2 of 2
Annex 2 to Certificate of Conformity IECEx KEM 09.0034X, issue 4

Description

Transmitter Model 3051, Type 3051C, 3051L, 3051T, 3051CFA, 3051CFC and 3051CFP, are
microprocessor based transmitters, used to convert the measured process pressure into digital or analog
signals.

Manufacturer locations:

Manufacturing Site Location QAR number


Rosemount Inc. 8200 Market Blvd GB/BAS/QAR06.0072/08
Chanhassen
MN 55317, United States of America
Rosemount Inc. 6021 Innovation Blvd, GB/BAS/QAR06.0072/08
Shakopee
MN 55379, United States of America
Rosemount Inc. 12001 Technology Drive GB/BAS/QAR06.0072/08
Eden Prairie
MN 55344, United States of America
Beijing Rosemount Far East Co No 2, South of Shengfang Road GB/BAS/QAR06.0058/05
Ltd Qian Gao Mi Dian
Economic Development Zone
Da Xing District
Beijing 102600
China
Emerson (Beijing) Instrument No 2, South of Shengfang Road GB/BAS/QAR06.0058/05
Co Ltd Qian Gao Mi Dian
Economic Development Zone
Da Xing District
Beijing 102600
China
Emerson Process Management 1 Pandan Crescent GB/BAS/QAR07.0014/07
Asia Pacific Pte Ltd Singapore 128461

EPM (India) Private Ltd A - 145/4, TTC Industrial Area GB/BAS/QAR07.0024/06


MIDC, Near Kopperkerane
Pawane
Navi Mumbai, India
Emerson Process Management Argelsrieder Feld 3 GB/BAS/QAR07.0036/06
GmbH & Co. OHG D-82234 Wessling
Germany
Emerson FZE (Rosemount P.O. Box 17033, GB/BAS/QAR10.0012/05
Division) Dubai, United Arab Emirates

Emerson Process Management Road 112, Intersection 263 GB/BAS/QAR11.0012/04


Arabia Jubail, Saudi Arabia
Emerson Process Management 471 Mountain Highway GB/BAS/QAR13.0012/02
Aust Pty Ltd Bayswater, Melbourne
Victoria 3153, Australia

Page 1 of 1
Form 124
Version 2 (2013-07)
DEKRA Certification B.V. Meander 1051, 6825 MJ Arnhem P.O. Box 5185, 6802 ED Arnhem The Netherlands
T +31 88 9683000 F +31 88 9683100 www.dekra-certification.com Registered Arnhem 09085396