Schedule of Load Type of Service Schedule of Load Type of Service Schedule of Load Type of Service Schedule of Load Type of Service
(PPBA) 230 Volt, 3 wire 60hz (PPBB) 230 Volt, 3 wire 60hz (PPBC) 230 Volt, 3 wire 60hz (MDP) 230 Volt, 3 wire 60hz
Ckt. Load No. Of Volts Watts Ampere No. of Protection Wire Size Conduit in Ckt. Load No. Of Volts Watts Ampere No. of Protection Wire Size Conduit in Ckt. Load No. Of Volts Watts Ampere No. of Protection Wire Size Conduit in Ckt. Load No. Of Volts Watts Ampere No. of Protection Wire Size Conduit in
No. Outlets per ckt. Pole in ampere mm No. Outlets per ckt. Pole in ampere mm No. Outlets per ckt. Pole in ampere mm No. Outlets per ckt. Pole in ampere mm
1 LO 14 230 1400 6.09 2P 20AT/50AF Use 2-3.5 20mm 1 CO 16 230 5760 25.04 2P 30AT/50AF Use 2-5.5 20mm 1 1hp 1 230 760 4.13 2P 20AT/50AF Use 2-3.5 20mm A LO 40 230 4000 17.39 2P 20AT/50AF Use 2-3.5 20mm
MCCB mm^2 THW PVC MCCB mm^2 THW PVC CO MCCB mm^2 THW PVC MCCB mm^2 THW EMT
ACU
cooper wire conduit in cooper wire conduit in cooper wire conduit in
(25.05/30A)
cooper wire conduit in
(6.09/20A) pipe pipe (4.13/20A) pipe (17.39/20A) pipe
and
and 1-2mm^2 and 1-2mm^2 and 1-2mm^2
1-3.5mm^2
TW copper TW copper TW copper TW copper
wire for wire for wire for wire for
grounding grounding grounding grounding
2 LO 14 230 1400 6.09 2P 20AT/50AF Use 2-3.5 20mm 2 CO 14 230 5040 21.91 2P 30AT/50AF Use 2-5.5 20mm 2 1hp 1 230 760 4.13 2P 20AT/50AF Use 2-3.5 20mm B CO 30 230 10800 46.96 2P 50AT/50AF Use 2-14 25mm
MCCB mm^2 THW PVC MCCB mm^2 THW PVC CO MCCB mm^2 THW PVC MCCB mm^2 THW EMT
REF
cooper wire conduit in cooper wire conduit in cooper wire conduit in cooper wire conduit in
(6.09/20A) pipe (21.91/30A) pipe (4.13/20A) pipe pipe
(46.96/65A)
and
and 1-2mm^2 and 1-2mm^2 and 1-8mm^2
1-3.5mm^2
TW copper TW copper TW copper TW copper
wire for wire for wire for wire for
grounding grounding grounding grounding
3 LO 12 230 1200 5.22 2P 20AT/50AF Use 2-3.5 20mm TOT CO 30 230 10800 46.96 2P 50AT/50AF Use 2-14 25mm TOT 2hp 2 230 1520 8.26 2P 20AT/50AF Use 2-3.5 20mm C 2hp 2 230 1520 8.26 2P 20AT/50AF Use 2-3.5 20mm
MCCB mm^2 THW PVC AL MCCB mm^2 THW EMT AL MCCB mm^2 THW EMT MCCB mm^2 THW EMT
cooper wire conduit in cooper wire conduit in cooper wire conduit in cooper wire conduit in
(5.22/20A) pipe (46.96/65A) pipe (8.26/20A) pipe (8.26/20A) pipe
and 1-2mm^2 and 1-8mm^2 and 1-2mm^2 and 1-2mm^2
TW copper TW copper TW copper TW copper
wire for wire for wire for wire for
grounding grounding grounding grounding
TOT LO 40 230 4000 17.39 2P 20AT/50AF Use 2-3.5 20mm 7 1hp 1 230 760 4.13 2P 20AT/50AF Use 2-3.5 20mm D 20mm
PVC
LO 22 230 2200 9.57 2P 20AT/50AF Use 2-3.5
AL MCCB mm^2 THW EMT CO MCCB mm^2 THW EMT
ACU conduit in MCCB mm^2 THW
cooper wire conduit in cooper wire cooper wire conduit in
pipe Schedule of Load Type of Service Schedule of Load Type of Service (4.13/20A) pipe pipe
(17.39/20A) (9.57/20A)
(PPBE) 230 Volt, 3 wire 60hz (PPBF) 230 Volt, 3 wire 60hz and 1-2mm^2

PRODUCED BY AN AUTODESK STUDENT VERSION


and 1-2mm^2 and 1-2mm^2
PRODUCED BY AN AUTODESK STUDENT VERSION

TW copper TW copper TW copper


Ckt. Load No. Of Volts Watts Ampere No. of Protection Wire Size Conduit in Ckt. Load No. Of Volts Watts Ampere No. of Protection Wire Size Conduit in
wire for wire for wire for
No. Outlets per ckt. Pole in ampere mm No. Outlets per ckt. Pole in ampere mm
grounding grounding grounding
3 CO 16 230 5760 25.04 2P 30AT/50AF Use 2-5.5 20mm 3 1hp 1 230 760 4.13 2P 20AT/50AF Use 2-3.5 20mm
MCCB mm^2 THW PVC CO MCCB mm^2 THW PVC 8 1hp 1 230 760 4.13 2P 20AT/50AF Use 2-3.5 20mm E CO 48 230 17280 75.13 2P Use 2-22mm^2 25mm
conduit in REF
conduit in CO mm^2 THW 90AT/
cooper wire cooper wire MCCB PVC THW cooper EMT
(25.05/30A) pipe pipe
REF
cooper wire 100AF
(4.13/20A) conduit in wire conduit in
Type of Service and (4.13/20A) MCCB
Schedule of Load and 1-2mm^2 pipe (75.13/85A) pipe
230 Volt, 3 wire 60hz 1-3.5mm^2 and 1-2mm^2 and 1-14mm^2
(PPBD) TW copper
TW copper TW copper TW copper
Ckt. Load No. Of Volts Watts Ampere No. of Protection Wire Size Conduit in wire for wire for
wire for wire for
No. Outlets per ckt. Pole in ampere mm grounding grounding
grounding grounding
4 LO 11 230 1100 4.78 2P 20AT/50AF Use 2-3.5 20mm 4 CO 16 230 5760 25.04 2P 30AT/50AF Use 2-5.5 20mm 4 1hp 1 230 760 4.13 2P 20AT/50AF Use 2-3.5 20mm
MCCB mm^2 THW PVC MCCB mm^2 THW PVC CO MCCB mm^2 THW PVC 9 1hp 1 230 760 4.13 2P 20AT/50AF Use 2-3.5 20mm
ACU F 8hp 8 230 6080 33.04 2P 40AT/50AF Use 2-8 mm^2 32mm
cooper wire conduit in cooper wire conduit in cooper wire conduit in CO MCCB mm^2 THW PVC THW cooper EMT
(25.05/30A) ACU
conduit in MCCB
(4.78/20A) pipe pipe (4.13/20A) pipe cooper wire wire conduit in
and 1-2mm^2 and (4.13/20A) pipe
and 1-2mm^2 (33.04/45A) pipe
TW copper 1-3.5mm^2
TW copper and 1-2mm^2 and 1-5.5mm^2
TW copper
wire for wire for TW copper TW copper wire
wire for for grounding
grounding grounding grounding wire for
1hp grounding
5 LO 10 230 1000 4.35 2P 20AT/50AF Use 2-3.5 20mm 5 CO 16 230 5760 25.04 2P 30AT/50AF Use 2-5.5 20mm 5 1 230 760 4.13 2P 20AT/50AF Use 2-3.5 20mm
MCCB mm^2 THW PVC MCCB mm^2 THW PVC CO MCCB mm^2 THW PVC 10 1hp 1 230 760 4.13 2P 20AT/50AF Use 2-3.5 20mm
ACU
cooper wire conduit in cooper wire conduit in cooper wire conduit in CO MCCB mm^2 THW PVC
ACU TOT 150 230 41880 190.35 2P 200AT Use 2-80 mm^2 40mm
(4.35/20A) pipe (25.05/30A) pipe (4.13/20A) pipe cooper wire conduit in AL /225AF THW cooper RSC
and pipe
and 1-2mm^2 and 1-2mm^2 (4.13/20A) MCCB wire conduit in
1-3.5mm^2 (190.35/195A)
TW copper TW copper TW copper and 1-2mm^2 pipe
wire for wire for TW copper and 1-60mm^2
wire for TW copper wire
grounding grounding grounding wire for
for grounding
20mm 25mm 1hp grounding
TOT LO 22 230 2200 9.57 2P 20AT/50AF Use 2-3.5 TOT CO 48 230 17280 75.13 2P 90AT/ Use 2-22mm^2 6 1 230 760 4.13 2P 20AT/50AF Use 2-3.5 20mm
AL MCCB mm^2 THW EMT AL 100AF THW cooper EMT CO MCCB mm^2 THW PVC TOT 8hp 8 230 6080 33.04 2P 40AT/50AF Use 2-8 mm^2 32mm
ACU
cooper wire conduit in wire conduit in cooper wire conduit in AL MCCB THW cooper EMT
MCCB
(9.57/20A) pipe (75.13/85A) pipe (4.13/20A) pipe wire conduit in
and 1-14mm^2 (33.04/45A) pipe
and 1-2mm^2 and 1-2mm^2
TW copper and 1-5.5mm^2
TW copper TW copper TW copper wire
wire for
wire for grounding wire for for grounding
grounding grounding

Approved by: Rev Date By Description


PTR NO: 14-0008-790 TWO-STOREY BUILDING 5
SCHEDULE OF LOAD
iguel Construction Company TIN NO: 50479219 Engr. Chao-Wen M. Tsai 6
REE NO: 39922 Location: Owner: Evelyn M. Tsai Date Drawn:
Scale 10:1
RME NO: 0067432 Block 2 Lot 5 Tsai Subdivision Caticlan Address: Altavas, Aklan Kalibo City September 20, 2019