Вы находитесь на странице: 1из 106

THS – FI022GB2K8v3 i

Industrial Metal Detector


THS
Serial number: .........................

Program Version: THSV3.390 ALMV1060 Rev.: FI 022 GB 2K8 v3 Date: 2004-10-26


II- INSTALLAZIONE

Instructions
THIS MANUAL IS TO BE READ BY THE FOLLOWING PERSONS:
- OWNER
- OPERATOR
- MAINTENANCE TECHNICIAN

Read this manual carefully before installing, operating or carrying out maintenance on the device. Keep the
manual in a safe place for future reference, and in perfect condition.
This manual must accompany the device described therein in the case of change of ownership, and until the
device is broken up.
• Follow the instructions contained in this manual for all • The device must be connected to a power supply circuit
operations relating to installation, use and maintenance of fitted with a switch or other device which allows the power
the device. to be cut off.
CEIA cannot be held responsible for any damage resulting • Ensure that replacement fuses are of the correct rating and
from procedures which are not expressly indicated in this of the prescribed type. Makeshift fuses and short-circuiting
manual, or from any lack of attention, either partial or total, of the fuse boards are strictly forbidden.
of the procedures described therein . • If the device is to be powered via an external
• Whenever there is any suggestion that the level of autotransformer to regulate the voltage, ensure that the
protection has been reduced, the device should be taken common terminal of the autotransformer is connected to
out of service and secured against any possibility of the neutral of the power-supply circuit.
unintentional use, and authorised service technicians • The power-supply plug must only be inserted into a socket
should be called. fitted with an earth/ground connection.
The level of protection is considered to have been reduced Any break in the safety conductor, either inside or outside
when: the device, or disconnection of the earth/ground safety
- the device shows visible signs of wear and tear; terminal, will render the device dangerous. Intentional
- the device does not operate correctly; cutting or disconnection is strictly forbidden.
- the device has been stored for long periods in sub-
optimal conditions; • To avoid damage due to lightning, disconnect the power-
- the device has suffered severe stress during transport; supply cable during storms.
- the device has come into contact with liquids. • This device contains electrical and electronic components,
and may therefore be susceptible to fire. Do not install in
• The final user is responsible for selecting the
explosive atmosphere or in contact with inflammable
appropriate sensitivity for their application. After this
material, Do not use water or foam in the case of fire when
selection has been made, and programming has been the device is powered up.
adjusted accordingly, it is also the final user's
• The device must be disconnected from all power sources
responsibility to verify calibration using the test
before undergoing any maintenance or cleaning, and
object(s) appropriate to the level of security selected.
before being moved.
Additionally, this test should be carried out
periodically to insure no changes have occurred in the • Do not wash the device with liquid detergents or chemical
equipment. substances. Any cleaning should be done using a slightly-damp,
non-abrasive cloth.
• Handle the device with care and without excessive force
during installation, use and maintenance. • Read the chapter on “Maintenance” carefully before calling
the service centre.
• After installation the device should be stable, and not Whatever the problem, only specialised service personnel
subject to vibration or accidental movement. All connecting authorised to work with CEIA equipment should be called.
cables should be properly fastened down, in order to avoid
knocks and accidental damage and to obtain optimum • Any damaged parts of the device should be replaced with
performance. original components only.
• Position the device as far as possible from sources of • Any maintenance or repair of the device while open and
electromagnetic interference, such as transformers or energised should be avoided, and in any case should only
motors. be carried out by trained personnel who are fully aware of
the risks which the operation entails, following the
• Before connecting the device to the power supply, ensure instructions given in the “Maintenance” section.
that the power supply voltage corresponds to that indicated
on the plate affixed to the device. • Disposal of parts with environmental impact: follow the
The device should be connected to the mains voltage only regulations in force in the country where the device is
after all connections required for full installation have been being used (refer to the “Maintenance” section).
carried out.

SYMBOLS
The equipment is marked with this symbol wherever the user should refer to this manual in order to
avoid possible damage.
The same symbol appears in the manual at points where warnings or particularly important instructions,
essential for safe, correct operation of the device, are given.
The equipment is marked with this symbol in the areas where there is dangerous voltage.
Only trained maintenance personnel should carry out work in these areas.

Warranty conditions
The Warranty on all CEIA equipment relates to goods delivered from our factory, under our general and specific
conditions of sale.
THS – FI022GB2K8v3 iii

Contents
INSTRUCTIONS ......................................................................................................................................................................................................................II
SYMBOLS ...............................................................................................................................................................................................................................II
WARRANTY CONDITIONS .....................................................................................................................................................................................................II
CONTENTS ............................................................................................................................................................................................................................III
DESCRIPTION.........................................................................................................................................................................................................................1
GENERAL INFORMATION ......................................................................................................................................................................................................1
POWER-SUPPLY AND CONTROL UNIT ................................................................................................................................................................................3
Control Power Box ............................................................................................................................................................................................................3
Conveyor Control System .................................................................................................................................................................................................4
METAL DETECTOR ................................................................................................................................................................................................................5
Models available ...............................................................................................................................................................................................................5
Options .............................................................................................................................................................................................................................9
THS-FB Conveyor Belt ..............................................................................................................................................................................................9
Features .............................................................................................................................................................................................................9
THS-FB conveyor belt options ..........................................................................................................................................................................10
Other optionals for THS metal detectors..................................................................................................................................................................11
THS metal detector accessories ..............................................................................................................................................................................12
TECHNICAL CHARACTERISTICS ........................................................................................................................................................................................13
INSTALLATION .....................................................................................................................................................................................................................15
GUIDE TO THE APPLICABLE INSTALLATION OPERATIONS ............................................................................................................................................16
General guidelines for mechanical installation ................................................................................................................................................................16
GENERAL GUIDELINES FOR ELECTRICAL INSTALLATION..............................................................................................................................................17
INSTALLATION OF A CEIA THS-FB INTEGRATED SYSTEM WITH CONVEYOR BELT.....................................................................................................19
Mechanical installation of THS-FB integrated system with conveyor belt........................................................................................................................19
Positioning the conveyor belt ...................................................................................................................................................................................19
Ejector: mounting the safety shield ..........................................................................................................................................................................19
Assembling the buzzer/flasher.................................................................................................................................................................................19
Adjusting the height of the belt.................................................................................................................................................................................19
ELECTRICAL INSTALLATION - GENERAL NOTES .............................................................................................................................................................20
Connecting to the mains power supply ...........................................................................................................................................................................20
Connection to the ground ........................................................................................................................................................................................20
Control Power Box...................................................................................................................................................................................................20
Conveyor Control System ........................................................................................................................................................................................20
Selection of the power supply voltage for the metal detector only - Control Power Box Power Supply Unit.............................................................21
CONNECTION OF THE COMPRESSED AIR SUPPLY .........................................................................................................................................................21
NON-INTEGRATED THS SYSTEM SUPPLIED WITHOUT CONVEYOR BELT: DETAILED CONSTRUCTION NOTES AND SELECTION OF
OPERATING PARAMETERS ................................................................................................................................................................................................22
Mechanical Installation....................................................................................................................................................................................................22
Controls ...................................................................................................................................................................................................................22
Mechanical installation of the metal detector ...........................................................................................................................................................22
Mechanical installation of the power supply unit ......................................................................................................................................................22
Mechanical installation of the THS/G probe.............................................................................................................................................................22
Proximity limits around the THS/G probe..........................................................................................................................................................22
THS/G : mounting the power supply unit ..........................................................................................................................................................23
Conveyor belt...........................................................................................................................................................................................................24
Inserting the conveyor belt on the THS/A model......................................................................................................................................................26
Transit speed ..................................................................................................................................................................................................................27
Accessory devices ..........................................................................................................................................................................................................29
Photocell – General rules ........................................................................................................................................................................................29
Photocell self-diagnosis ....................................................................................................................................................................................29
Ejector – General rules ............................................................................................................................................................................................29
THS/M – Specific instructions for ejector .................................................................................................................................................................30
Applications at high speed (belt speeds greater than 60 m/min).....................................................................................................................................31
Programming used in a few common types of installation...............................................................................................................................................31
Mechanical installation of a bar code reader...................................................................................................................................................................32
Safety precautions ...................................................................................................................................................................................................32
Barcode reader kit ...................................................................................................................................................................................................32
Distance between the reader and the metal detector probe and distance between packs.......................................................................................33
Position of the reader and the label in transit...........................................................................................................................................................33
Reading features .....................................................................................................................................................................................................34
Step-Ladder mode............................................................................................................................................................................................34
Picket-Fence mode...........................................................................................................................................................................................34
Kit installation procedure .........................................................................................................................................................................................35
ELECTRICAL INSTALLATION: DETAILED NOTES ..............................................................................................................................................................36
ALM card electrical connections .....................................................................................................................................................................................39
Conveyor Control System: Power-supply and motor connections ...................................................................................................................................41
MDT card.................................................................................................................................................................................................................41
MDL card ( ATTENTION: 230V 1~ only! ) ..............................................................................................................................................................42
Operation of the relays (J15 and J19 connectors) ..........................................................................................................................................................43
Ejector relay (Eject relay):........................................................................................................................................................................................43
Alarm relay ..............................................................................................................................................................................................................43
Malfunction relay (Fault relay)..................................................................................................................................................................................43
Upstream belt authorisation relay (Preceding conveyor relay) .................................................................................................................................43
Auxiliary relay for signalling when periodic test is due (TEST LAMP relay)..............................................................................................................43
Timing .............................................................................................................................................................................................................................43
Belt blocking with manual alarm reset (EM=B) ........................................................................................................................................................43
Conveyor Control System power supply unit ....................................................................................................................................................43
Control Power Box power supply unit ...............................................................................................................................................................43
Belt blocking with photocell synchronisation and manual alarm reset (EM=SB) ......................................................................................................43
Conveyor Control System power supply unit ....................................................................................................................................................44
Control Power Box power supply unit ...............................................................................................................................................................44
Automatic ejection with alarm synchronisation (EM=F)............................................................................................................................................44
Automatic ejection with photocell synchronisation (EM=S) ......................................................................................................................................45
Serial line connection (J3 and J4 connectors).................................................................................................................................................................46
Inputs..............................................................................................................................................................................................................................47
Bar-code reader.......................................................................................................................................................................................................47
Downstream belt authorisation (Following conveyor - Conveyor Control System only) ............................................................................................47
Photocell..................................................................................................................................................................................................................47
II- INSTALLAZIONE

Ejection confirmation (Eject confirmation)................................................................................................................................................................47


Container full (Full bin).............................................................................................................................................................................................47
Impulse encoder (Encoder)......................................................................................................................................................................................47
Alarm reset (Reset)..................................................................................................................................................................................................47
Inhibition ..................................................................................................................................................................................................................47
Air pressure sensor..................................................................................................................................................................................................47
Container absent (Bin absent) .................................................................................................................................................................................47
OPERATING INSTRUCTIONS ..............................................................................................................................................................................................48
LIST OF PRELIMINARY CHECKS.........................................................................................................................................................................................48
OPERATIONS DURING USE AND AREAS OF COMPETENCE ...........................................................................................................................................48
CONTROLS AND INDICATORS............................................................................................................................................................................................49
Power switch...................................................................................................................................................................................................................49
Control panel of the probe/electronics unit......................................................................................................................................................................49
Acoustical indicators ................................................................................................................................................................................................49
Controls ...................................................................................................................................................................................................................50
Conveyor Control System power supply unit control panel .............................................................................................................................................50
Visible/audible alarm signalling device............................................................................................................................................................................51
SWITCHING ON THE METAL DETECTOR...........................................................................................................................................................................51
Checking the safety features ..........................................................................................................................................................................................51
Signals at power-up ........................................................................................................................................................................................................52
SIGNALS GIVEN DURING USE ............................................................................................................................................................................................52
Indication of the received signal......................................................................................................................................................................................52
Checking for environmental electromagnetic interference...............................................................................................................................................53
Display Messages...........................................................................................................................................................................................................53
DISPLAY OF THE STATUS OF THE METAL DETECTOR....................................................................................................................................................54
USE OF THE CONVEYOR BELT ..........................................................................................................................................................................................54
Starting/stopping the conveyor belt .................................................................................................................................................................................54
Adjustment of the belt speed ..........................................................................................................................................................................................54
Emergency button...........................................................................................................................................................................................................55
Automatic stop ................................................................................................................................................................................................................55
ALARM RESET......................................................................................................................................................................................................................55
AUTOMATIC OPERATION USING A BAR-CODE READER .................................................................................................................................................55
PHOTOCELL SELF-DIAGNOSIS...........................................................................................................................................................................................56
PROGRAMMING THE METAL DETECTOR ACCORDING TO THE KIND OF PRODUCT....................................................................................................56
Procedure for minimising the "product effect" ..........................................................................................................................................................56
ANALYSIS MODE SELECTION CRITERIA ...........................................................................................................................................................................58
SENSITIVITY CHECK WITH REFERENCE SAMPLE ...........................................................................................................................................................59
Test using a sample defined by the customer.................................................................................................................................................................59
Test using a CEIA sample ..............................................................................................................................................................................................59
Periodic test management .......................................................................................................................................................................................59
Test procedure ........................................................................................................................................................................................................59
PROGRAMMING ...................................................................................................................................................................................................................61
GENERAL POINTS ON PROGRAMMING.............................................................................................................................................................................61
PROGRAMMING INSTRUCTION ..........................................................................................................................................................................................63
Products menu................................................................................................................................................................................................................63
Autolearn menu ..............................................................................................................................................................................................................64
Detection menu...............................................................................................................................................................................................................65
Ejection menu .................................................................................................................................................................................................................66
Ejection time menu ..................................................................................................................................................................................................67
Counters menu ...............................................................................................................................................................................................................68
Barcode reader menu .....................................................................................................................................................................................................68
THS Configuration menu.................................................................................................................................................................................................70
Date settings menu..................................................................................................................................................................................................72
Change Password menu..........................................................................................................................................................................................73
ALM Configuration menu ................................................................................................................................................................................................73
I/O Status menu..............................................................................................................................................................................................................77
MD Test menu ................................................................................................................................................................................................................77
Print menu ...............................................................................................................................................................................................................78
Print report menu .....................................................................................................................................................................................................79
Quality Control menu (Q.C.Report) .................................................................................................................................................................................80
Test Sensitivity menu (Test sensitiv.).......................................................................................................................................................................80
Commands accessible only in Remote Programming .....................................................................................................................................................81
REMOTE PROGRAMMING VIA SERIAL LINK......................................................................................................................................................................82
Communication parameter settings: ...............................................................................................................................................................................82
Entering remote programming ........................................................................................................................................................................................82
Connecting to a metal detector (via RS 232) ...........................................................................................................................................................82
Long-distance connection to a single metal detector (via RS 485) ..........................................................................................................................82
Network connection (via RS 485).............................................................................................................................................................................82
Connecting to a metal detector in a network............................................................................................................................................................83
3.13.3 - Displaying a parameter setting ...................................................................................................................................................................83
3.13.4 - Changing a parameter setting.....................................................................................................................................................................83
3.13.5 - Executing a function ...................................................................................................................................................................................83
MAINTENANCE.....................................................................................................................................................................................................................84
PERIODIC MAINTENANCE...................................................................................................................................................................................................84
SELF-DIAGNOSIS .................................................................................................................................................................................................................85
STORAGE .............................................................................................................................................................................................................................86
TRANSPORT AND MOVEMENT OF THE CONVEYOR BELT ..............................................................................................................................................86
ADJUSTMENT OF CONVEYOR BELT TENSION .................................................................................................................................................................86
Replacing the belt ...........................................................................................................................................................................................................87
DISPOSAL OF THE DEVICE AND OF CONSUMABLES WITH ENVIRONMENTAL IMPACT ..............................................................................................87
FUSES ...................................................................................................................................................................................................................................87
TROUBLESHOOTING ...........................................................................................................................................................................................................87
Self-resetting protections .........................................................................................................................................................................................87
Replacing Card SCD.......................................................................................................................................................................................................89
Procedure ................................................................................................................................................................................................................89
CHECKING ENVIRONMENTAL ELECTROMAGNETIC INTERFERENCE............................................................................................................................90
APPENDICES........................................................................................................................................................................................................................91
DECLARATION OF CONFORMITY CE .................................................................................................................................................................................91
SPARE PARTS, OPTIONS AND ACCESSORIES .................................................................................................................................................................92
Ordering spare parts .......................................................................................................................................................................................................92
THS standard model / THS/3F........................................................................................................................................................................................92
THS /A ............................................................................................................................................................................................................................92
THS – FI022GB2K8v3 v

THS/SL ...........................................................................................................................................................................................................................93
THS/MN ..........................................................................................................................................................................................................................93
THS/PH...........................................................................................................................................................................................................................94
THS/G.............................................................................................................................................................................................................................95
THS-FB...........................................................................................................................................................................................................................95
THS Accessories - Test pieces .......................................................................................................................................................................................99
THS Accessories - MD CAD - 27185 ............................................................................................................................................................................100

CEIA reserves the right to make changes, at any moment and without notice, to the models (including programming), their accessories and optionals, to
the prices and conditions of sale.
THS – FI022GB2K8v3 --- I -DESCRIPTION 1

DESCRIPTION

General Information
The THS is an extremely compact metal detector with very high sensitivity, controlled by a microprocessor and
designed for industrial use. The device is made up of:

the Metal Detector probe, complete with electronic control unit.

a power-supply and control unit, for connecting the device to mains power and to the external
supports (photocell, ejector, etc.)

1
1 probe- Metal Detector
2 power supply unit with conveyor belt control
4 (Control Power Box)
5 3 connecting cable
4 tunnel
5 control panel

Fig. I-1a - THS system (probe-electronics unit + Control


Power Box power supply unit) installed on a
3 CEIA conveyor belt.

1 probe- Metal Detector


2 power supply unit with conveyor belt control
(Conveyor Control System)
1
3 conveyor belt load-bearing structure
4 conveyor belt control panel
5 idler
5 6 motor roller

2 6
Fig. I-1b - THS system (probe- Metal Detector +
Conveyor Control System power supply unit)
4 installed on a CEIA THS-FB conveyor belt.

3
2 THS – FI022GB2K8v3 --- I - DESCRIPTION

Product set-aside ejection Air


alarm
Probe-Metal Detector transit ejector full confirm pressure
photocell sensor sensor sensor
malfunction

Alarm reset
THS-Control Power supply unit contact
Power Box (Control Power Box)
Computer Inhibition
or printer contact

Encoder
to measure belt
movement
buzzer/flashing light

bar-code
Flashing light
reader
indicating test due Conveyor
Belt
Fig I-2a - Block diagram of the system CEIA THS-Control Power Box system

Product set-aside ejection Air


transit ejector full confirm pressure
alarm
Probe-Metal Detector photocell sensor sensor sensor

malfunction

THS-Conveyor upstream Power supply unit


Inhibition
Control System belt contact
(Conveyor Control System) Alarm reset
authorisation
Motor driver card motor
downstream
belt author-
isation
Encoder
to measure belt
Computer buzzer/flashing light movement
or printer
bar-code
Flashing light indicating Conveyor
reader
test due
Belt
Fig I-2b - Block diagram of the system CEIA THS-Conveyor Control System.

Conveyor Belt THS-FB/1 THS-FB/2


CEIA THS-FB/3
Product set-aside ejection Air
transit ejector full confirm presssure
photocell sensor sensor sensor
THS-FB/1 Probe-Metal
Detector
Flashing light
indicating test due
upstream
belt
authorisation Power supply unit
(Conveyor Control System) Alarm reset
downstream
THS-FB/2 belt author- MDL inverter card motor
isation

Inhibition
buzzer/flashing light
contact
Computer
or printer
bar-code malfunction alarm
THS-FB/3
reader
Fig I-2c - Block diagram of a CEIA THS-FB integrated system including the conveyor belt, the THS
unit, the Conveyor Control System power supply unit and the sensors and actuators needed for
operation.
THS – FI022GB2K8v3 --- I -DESCRIPTION 3

Power-supply and control unit


The power-supply and control unit is housed in a watertight box in stainless steel which is designed to be attached by
means of four screws and through which pass the connecting cables. The power supply unit is available in two versions:

Control Power Box , containing the metal detector power supply section and designed to allow
connection of external sensors and slave devices

Conveyor Control System, with the same functions as the Control Power Box, but with the addition
of a conveyor belt motor driver/control section

Control Power Box

Fig. I-3a - Control Power Box in Fig. I-3b – Internal view of the ALM Fig. I-3c - Control Power Box with
stainless steel casing card RCU remote control panel (model
THS/G or other models on request)

The module contains only the electronics needed for supplying power to the probe and the connection terminals for
external sensors and slave devices. The card inside (card ALM), allows connections to be made to the following:
• metal detector probe
• mains power supply
• product transit photocell
• external activators and sensors
• personal computer

Fig. I-4 Control Power Box: rear and side views


4 THS – FI022GB2K8v3 --- I - DESCRIPTION

Conveyor Control System


In addition to the functions provided by the Control Power Box, this includes a module to drive the conveyor belt motor.
This module is available in two versions:
• Card MDT, for fixed-speed applications; in this case, a three-phase input power supply (230V or 400V) is
required;
• Card MDL, for variable-speed applications; in this case, a single-phase input power supply is required, as the
card incorporates an inverter with three-phase outputs.

The versions available, therefore, are the following:

Version Application Input Voltage Maximum Output voltage Maximum


power (motor power power of
absorbed supply) * motor
Conveyor Control System/MDT Fixed speed 230V -18% / +10%, three-phase 1250VA 230V -18% / +10%, 750W
with MDT module for 230V power supply without neutral, 48-62Hz three-phase 48-62Hz
Conveyor Control System/MDT Fixed speed 400V -18% / +10%, three-phase 2500VA 400V -18% / +10%, 1500W
with MDT module for 400V power supply with neutral, 48-62Hz three-phase 48-62Hz
Conveyor Control System/MDL Variable 230V ± 10% single-phase 48- 1000VA 230V three-phase 750W
with MDL module speed 62Hz 20-60Hz
* three-phase asynchronous motor , delta connection

N.B.: if the device is to be mounted on the customer’s own conveyor belt, please specify the power supply voltage in the order.

The unit also incorporates the main switch, the controls for activating the belt and the LED indicators needed for
operation (STC card).

ALM card MDT MDL card


card

2
STC card
ALM card

1 On/Off switch Fig. I-4b: Internal view of the Conveyor Fig. I-4c: Internal view of the
2 control panel Control System-MDT Conveyor Control System-MDL

Fig. I-4a: View of the Conveyor


Control System

Fig. I-5 Conveyor Control System: rear and side views


THS – FI022GB2K8v3 --- I -DESCRIPTION 5

Metal detector
The metal detector is enclosed in an extremely robust metal casing, in a tunnel shape (see fig. below), which is designed
to be mounted on the conveyor belt or other feed system.
The unit contains the sensitive antenna and the control panel.
A cable leads from the unit (on the side of the control panel) to connect up with the power supply unit.

Models available

Application
THS/STD Model for universal use, for mounting on a conveyor belt

Power-supply and control unit


• Power Control Box
• Conveyor Control System

Fig. I-7

Order code: 2204


THS-DWxDH (see table I-3)
Fig. I-8

TABLE I - 3 . THS/STD & THS/3F *


Model DW DH TH DL FHL TP FHP FHW DC TW
(opening)
Series A 200, 250, ..., 1000 100, 125, 395 290 190 105 TP+10 DW-20 205 DW+420
150,175 TP-30** DW+60**
Series B 350, 400, ..., 800 200, 225, ..,275 545 390 290 160 TP+10 DW-20 280 DW+520
Series C 450, 500, ..., 1000 300, 325, 350 635 490 390 210 TP+10 DW-20 320 DW+620
Series D 500, 600, ..., 1300 400, 450, 500 905 490 390 260 TP+10 DW-20 455 DW+720
* For customised versions with different dimensions, see the configuration card at the end of the booklet.
** The position of the support depends on the shape of the load-bearing structure.

Application
THS/3F multi-frequency model for mounting on a conveyor belt , for use with a variety of
products with significant chemico-physical differences (variable conductivity and
so on)

Application examples
• Semi-frozen products in aluminised packaging
• Products preserved in vinegar or oil, meat, fish etc.

Power-supply and control unit


• Power Control Box
• Conveyor Control System
Fig. I-9

Order code: Dimensions


THS/3F-DWxDH (see table I-3) As for the THS/STD model
6 THS – FI022GB2K8v3 --- I - DESCRIPTION

Application
THS/MN model for mounting on a conveyor belt, with high discrimination between
contaminating ferromagnetic metal and product, which can also be used with
product packed in non-magnetic metal containers

Application examples
• Products in packaging with a high aluminium content

Power-supply and control unit


The power supply group comprises two units: a standard power supply unit (PCB
or CCS) and a probe power-supply unit.
Fig. I-10 • Power Control Box
• Conveyor Control System
• Probe power-supply unit

Order code:
THS/MN-DWxDH (see table I-4)

pm2071ab

Fig.I-11

TABLE I - 4 .THS/M *
Model (opening) DW DH TH FHW TW
150 350, 550 150 570 DW+60 DW+620
200 350, 550 200 620 DW+60 DW+620
* For customised versions with different dimensions, see the configuration card at the end of the booklet.

Application
THS/SL SLIM LINE model for mounting on a conveyor belt , with extremely reduced
dimensions in the direction of transit

Application example
• Weighing machines

Power-supply and control unit


• Power Control Box
• Conveyor Control System

Fig. I-12

Order code:
THS/SL-DWxDH (see table I-5)

Fig. I-13 – Drawing M2202D

TABLE I - 5 .THS Slim Line*


Model opening) DW DH TH DL FHL TP FHP FHW TW
Series A 125, 150, ..., 450 100, 125 330 175 90 105 TP+10 DW- 20 DW+400
Series B 150, 200, ..., 450 150, 175, 200 405 175 90 105 TP+10 DW- 20 DW+400
* For customised versions with different dimensions, see the configuration card at the end of the booklet.
THS – FI022GB2K8v3 --- I -DESCRIPTION 7

Application
THS/A model for universal use, with a tunnel that can be opened if the conveyor belt can
not be interrupted for installation purposes

Application examples
• Plastic recycling, quarries, mines etc.

Power-supply and control unit


• Power Control Box
• Conveyor Control System

Fig. I-14

Order code:
THS/A-DWxDH (see table I-6)
m2205
Fig.I-15

TABLE I - 6 . THS/A*
Model DW DH TH DL DP FHL RW DS FHW TW
(opening)
50 285 290 100
Family A 250, 300, ..., 1500 100 335 290 DS+35 DL+50 30 100 DW-20 DW+150
150 385 290 100
200 535 390 150
250 585 500 30 150 DW+150
300 735 500 30 200 DW+150
350 785 600 50 200 DW+170
400 935 600 50 250 DW+170
Family B 500, 550, ..., 1500 450 985 600 DS+35 DL+50 50 250 DW-20 DW+170
500 1035 600 50 250 DW+170
550 1185 750 50 300 DW+170
600 1235 750 50 300 DW+170
650 1385 750 50 350 DW+170
* For customised versions with different dimensions, see the configuration card at the end of the booklet..

Application
THS/G model with circular tunnel for products transported in tubing
In the case of the THS/G model, the probe is designed to be fixed,
generally, in an inaccessible position. The detector controls are
therefore incorporated into the power supply unit, on the RCU card
fixed to the casing cover.

Application examples
• Installation between multi-head weighing machines and
packaging machines
• Gravitational and pneumatic product transport in
general: powders, granulated products, liquids etc.

Power supply unit


• Power Control Box

Fig.I-19 Order code: THS/G-T (see table I-7)


8 THS – FI022GB2K8v3 --- I - DESCRIPTION

Product set-aside ejection Air


Probe-Metal Detector transit ejector full confirm pressure
photocell sensor o sensor sensor

ALM Alarm reset contact

RCU Power supply unit Inhibition


(Control Power Box) contact

Buzzer/flashing
light

THS/G Flashing light


indicating test due

alarm

malfunction

Computer
or printer

Fig. I-20a - Model THS/G: ALM & RCU cards Fig. I-20b - Model THS/G: Block diagram

Fig. I-21 THS/G : probe dimensions (Drawing PM2581F)

TABLE I - 7 THS/G*
Model (opening) T TW DH VL HL
THS/G-50 50 380 250 205 226
THS/G-100 100 380 250 205 226
THS/G-150 150 430 300 255 276
THS/G-200 200 480 350 305 326
THS/G-250 250 530 400 355 376
* For customised versions with different dimensions, see the configuration card at the end of the booklet.
THS – FI022GB2K8v3 --- I -DESCRIPTION 9

Options
THS-FB Conveyor Belt
Belt with speed adjustment, robustly built and with simplified maintenance, available in several versions

Features
• Belt available in PVC approved for food handling.
• Adjustable speed: 19...58m/'.
• Electrical characteristics: see Conveyor Control System unit.
• Compressed air supply:
pressure: 200-1000 kPa;
airflow:
50 litres/min (piston ejector),
600 litres/min (airblow ejector, optional)
• Dimensions: see figures below.

Models * Application Features Models THS


Type (width x belt THS THS/M THS/3F
length) THS/SL

• • •
300 x 1500mm packaged or Conveyor belt with block.
500 x 1500mm loose product Devices included:
• photocell
• buzzer/flashing light
• two auxiliary emergency buttons
THS-FB/1

• • •
300 x 1500mm packaged Conveyor belt with piston ejector.
500 x 1500mm product Devices included:
• as THS-FB type 1
• piston ejector

THS-FB/2

• • •
300 x 1500mm packaged Conveyor belt with piston ejector and
500 x 1500mm product accessory devices.
Devices included:
• as THS-FB type 2
• ejection confirmation sensor
THS-FB/3 • full set-aside container sensor
• insufficient air-pressure sensor
• blue flashing light to indicate test due

“Supermarket compliant" system


* N.B.: the conveyor belt is available only for probes belonging to the A and B Series.

Fig. I-22a Photocell (A) and Fig. I-22b buzzer/flashing light Fig. I-22c auxiliary emergency Fig. I-22d ejector unit
retroreflector (B) button
A
A
B

Fig. I-22e detail of ejector Fig. I-22f ejection confirmation Fig. I-22g insufficient air Fig. I-22h blue flashing light to
piston sensor (A) and full set-aside pressure sensor indicate test due
container sensor (B)
10 THS – FI022GB2K8v3 --- I - DESCRIPTION

Fig. I-24a conveyor belt


with THS probe from
Family A

THS-FB conveyor belt options

Fig. I-23a - Product- Fig. I-23b – Castor Fig. I-23c - Foot


containment panels Code: 21548 Code: 21525
Code: 21533

Fig. I-23d – Mounting


kit for bar-code readers
(both types)

Code: 21613

Fig. I-23f – Airblow


ejector

Characteristics:
Max. weight of pack (for
pack with low sliding
friction): 1 kg;
Compressed air supply:
pressure 200-1000
kPa; min. airflow 600
litres/min

Code: 22477

Fig. I-24b conveyor belt with THS probe from


Family B
THS – FI022GB2K8v3 --- I -DESCRIPTION 11

Other optionals for THS metal detectors


Models THS

THS/SLSL
THS/STD
Option

THS/3F
THS/M

THS/G
Connecting cable between power supply unit and probe of non-standard
length (max. 40m)

• •••
Order code: 19992

RS485 interface, required for:


• network connection of several metal detectors
• connection of one or more metal detectors over long distances

Order code: 17828 • •••


Management of Picket-Fence barcode reader.

N.B.: the bar-code reader application is an alternative to use of the remote


control unit • • •
Order code: 18701
Management of Step-Ladder barcode reader.

N.B.: the bar-code reader application is an alternative to use of the remote


control unit • • •
Order code: 19012
Remote control unit on Control Power Box (for probes located in
inaccessible positions). Cable length: 2.5m

N.B.: the remote control unit application is an alternative to use of the bar-
code reader
Order code: 21560
• • •
Remote control unit on Conveyor Control System (for probes located in
inaccessible positions)
Cable length: 2.5m

N.B.: the remote control unit application is an alternative to use of the bar-
• • •
code reader
Order code: 21559
Power supply transformer unit

115/230V~ transformer unit, to be used to power a THS fitted with an MDL


module at 115V~. Order code: 23181 • • •
400/230V~ transformer unit, to be used to power a THS, whether fitted with
an MDL module or not, at 400V~. Order code: 23182 • •••
12 THS – FI022GB2K8v3 --- I - DESCRIPTION

THS metal detector accessories


Set of quality control test samples

Available in the following versions:

Code Samples in ferrous Samples in stainless Samples in non-ferrous


metal AISI 420 steel AISI 316 metal
18711 ø0.8mm ... ø2.5mm sphere ø1.0mm ... ø3.5mm sphere ---
22605 ø3.0mm ... ø5.5mm sphere ø4.0mm ... ø6.5mm sphere ---
22606 ø3.0mm ... ø5.5mm sphere --- ø4.0mm ... ø6.5mm sphere
22607 ø0.8mm ... ø2.5mm sphere --- ø1.0mm ... ø3.5mm sphere

MD Scope program
Remote control and programming with oscilloscope function

Order code: 26894


THS – FI022GB2K8v3 --- I -DESCRIPTION 13

Technical Characteristics

Control Power Box In watertight casing (grade of protection: IP65)


Standard power supply Dimensions: 250x150x300mm (wxdxh)
unit Power supply voltage: 115/230 V~ (+10 / -22%), single phase - 48/62 Hz
Maximum power absorbed: 60 VA (THS/MN: 200VA)

Conveyor Control In watertight casing (grade of protection: IP65)


System Dimensions: 250x180x300mm (wxdxh)
Power supply unit with
inverter card Models available
Version Application Input Voltage Maximum Output voltage Maximum
power (motor power supply) power of
absorbed * motor
Conveyor Control System/MDT Fixed speed 230V -18% / +10%, 1250VA 230V -18% / +10%, 750W
with MDT module for 230V power three-phase without three-phase 48-62Hz
supply neutral, 48-62Hz
Conveyor Control System/MDT Fixed speed 400V -18% / +10%, 2500VA 400V -18% / +10%, 1500W
with MDT module for 400V power three-phase with three-phase 48-62Hz
supply neutral, 48-62Hz
Conveyor Control System/MDL Variable speed 230V ± 10% single- 1000VA 230V three-phase 750W
with MDL module phase 48-62Hz 20-60Hz
* three-phase asynchronous motor , delta connection

Probe-electronics unit Tunnel-shaped metal structure containing the sensitive antenna and the control panel
Dimensions: see preceding pages.

Special features • Ultra-high sensitivity


• High immunity to environmental interference
• LCD display (4 lines of 20 characters each) to show data
• Remote or direct programming of the operating parameters (type of product,
immunity level, speed of transit, processing of signal, control over external
actuators, etc.) by means of keyboard
• Audio and visual detection indicators.
• Display of the signal level by means of bar-graph.
• Statistical analysis of the number of inspected and contaminated products
• ISO 9001 product quality control
• THS/A model: model with tunnel that can be opened
• Model THS/SL (Slim Line): extremely compact probe
• Model THS/3F: detector for magnetic and non-magnetic metals, for use with
different types of product thanks to selection of the operating frequency
• Model THS/PH: model especially designed for the pharmaceutical industry
• Model THS/M: detection of ferromagnetic metals when considerable quantities of
aluminium or other non-magnetic metals are present
• Model THS/G: probe with circular opening for checking material transported in
tubing.

Password 6 levels: operator / supervisor /engineer/ quality control operator / head of quality
control / remote programming

Stored sets of 250 sets of parameter settings may be stored, corresponding to 250 possible different
products
parameters
14 THS – FI022GB2K8v3 --- I - DESCRIPTION

Control inputs Connector for link-up to


• photocell
• manual reset button
• downstream belt authorisation
• ejection confirmation
• set-aside contained full sensor
• encoder to detect the belt speed
• emergency button
• barcode reader (on demand)
• compressed air pressure sensor (for ejection)
Serial interface RS232
Serial interface RS485 (on request)

Outputs 5 programmable relays (250Vac - 3A) to activate the external support units
•alarm relay
•malfunction relay
•ejector relay
•upstream belt authorisation relay
•auxiliary relay

Ejection The system can use the following types of ejector:


•compressed air jet
•piston
•retractable belt
Power: compressed air (200-1000 kPa), pressure: 600 litres/min (airblow ejector); 50
litres/min (piston ejector); 100 litres/min (retractable belt ejector).

Alarm signalling Visual: by means of indicator light on central electronics unit


Audio: by means of buzzer on central electronics unit
By means of output relays

Environmental Working temperature: 0-50°C


conditions Humidity: 5-90%, without condensation

System including Belt available in PVC approved for food handling on request.,
conveyor belt Dimensions, weight and accessories: see the configuration sheet at the end of the
manual.
THS – FI022GB2K8v3 --- V - MAINTENANCE 15

INSTALLATION

Observe current regulations regarding electrical and personal safety for both the operator and the installer
when installing the device.

BEFORE INSTALLING THE DEVICE READ THE SECTIONS "General


guidelines for mechanical installation" and " General guidelines for
electrical installation " CAREFULLY.
These sections contain some important information regarding sources of
electromagnetic interference which may exist in the installation
environment.

THEN MOVE ON TO INSTALL THE DETECTOR ACCORDING TO THE


FOLLOWING SECTIONS, WHICH DESCRIBE:

• OPERATIONS RELATING TO A CEIA INTEGRATED SYSTEM:


models mounted on a CEIA conveyor belt or models that do not
need any accessories to operate, such as the THS/PH.

• DETAILED OPERATIONS RELATING TO A NON-INTEGRATED


SYSTEM, CREATED BY THE CUSTOMER AROUND THE THS
DETECTOR (METAL DETECTOR + POWER-SUPPLY UNIT), with
guidelines on the location of accessory devices and their
programming. Reading of point 1 is nevertheless recommended
in this case as well.

FINAL CHECKS ON INSTALLATION AND PROGRAMMING


For the installation checks you need to be able to switch on the
system, understand the signals given during use and set the
applicable operating parameters. These operations are described in
the first part of the “USE” section.

In order to carry out installation operations properly,


refer to the information contained in the " Guide to
the applicable installation operations "
on the next page.
16 THS – FI022GB2K8v3 --- V - MAINTENANCE

Guide to the applicable installation operations

Operation Section / Paragraph to read


CEIA integrated system with Non-integrated THS system, without
conveyor belt conveyor belt

Unpacking the device and


checking that the various _
components of the system are all
there.
Reading the installation INSTALLATION SECTION INSTALLATION SECTION
instructions • General guidelines for mechanical • General guidelines for mechanical
installation installation
• General guidelines for electrical • General guidelines for electrical
installation installation
• Installation of a CEIA THS integrated • Mechanical installation of the model
system with conveyor belt THS/PH
• Electrical installation - General notes • Electrical installation - General notes
• Non-integrated THS system supplied
without conveyor belt: detailed
construction notes and selection of
operating parameters
• Electrical installation: detailed notes
Switching on and checking the OPERATING INSTRUCTIONS SECTION OPERATING INSTRUCTIONS SECTION
safety devices • Controls and indicators • Controls and indicators
• Switching on the metal detector • Switching on the metal detector
Preliminary operating checks: OPERATING INSTRUCTIONS SECTION INSTALLATION SECTION
Setting the applicable installation • Automatic operation using a bar-code • Non-integrated THS system supplied
parameters reader without conveyor belt: detailed
construction notes and selection of
PROGRAMMING SECTION operating parameters
• Programming instructions
Menus - Ejection PROGRAMMING SECTION
- THS Configuration • Programming instructions
- ALM Configuration Menus - Ejection
- I/O status - THS Configuration
- ALM Configuration
- I/O status
Preliminary operating checks: OPERATING INSTRUCTIONS SECTION
Functional check of the slave • Signals given during use
devices: motor, ejector, signalling • Use of the conveyor belt
devices etc. • Alarm reset

PROGRAMMING SECTION
• Programming instructions
Menus - Ejection
- THS Configuration
- ALM Configuration
- I/O status

The availability of the various parameters on various models is indicated. If a parameter is


specific to the current product it is identified.
.
Preliminary operating checks: OPERATING INSTRUCTIONS SECTION
Checking environmental • Checking for environmental electromagnetic interference
interference
Preliminary operating checks: OPERATING INSTRUCTIONS SECTION
Checking the sensitivity using a • Analysis mode selection criteria
sample supplied • Sensitivity check with reference sample

Memorisation of the products OPERATING INSTRUCTIONS SECTION


being used with possible use of • Analysis mode selection criteria
an autolearn process • Programming the metal detector according to the kind of product

PROGRAMMING SECTION
• Programming instructions (Prod. command).
• Automatic operation using a bar-code reader

General guidelines for mechanical installation


THS – FI022GB2K8v3 --- V - MAINTENANCE 17

• Load-bearing structure

During assembly the solidity of the load-bearing structure should be borne in mind, in order to ensure that
the detector does not oscillate, causing false alarms

• Metal structures surrounding the Metal Detector/conveyor belt system

Fixed metal structures


All the fixed metallic structures in proximity to the detector must be securely
fastened down with bolts and self-blocking nuts and, if they form intermittent
loops, soldered.
This is due to the fact that sporadic metallic contacts due to vibrations,
resulting in the intermittent short-circuiting of the voltages induced by the
probe, may lead to interference with subsequent false alarms in the device.

Fig. II-1 Fixed metal structures


THS/M
Installation of structures or equipment with ferromagnetic frames in the vicinity
of the Metal Detector is not recommended. If this proves unavoidable, they must
be placed at least distance D from each side of the probe.

Other THS models


Fixed metal structures (frames, metal furniture, etc.) must, in all cases, be
located at a distance that is at least equal to the height of the probe (A), on
both sides of the probe.

| Model THS/M THS/A Other models |


| |
| D ≥ 3 DH ≥ 2 DH ≥ DH |
| |
Fig. II-2 : Fixed metal structures
Moving metal structures
Such structures, especially when of a considerable mass (mills, hoppers,
etc.), must be located as far away as possible from the probe.

| Model THS/M THS/A Other models |


| |
| D ≥ 10 DH ≥ 10 DH ≥ 6 DH |
| |

Fig. II-3 Moving metal structures

General guidelines for electrical installation


Possible sources of electrical interference may be power supply cables (electromagnetic fields generated by alternating
currents) or impulsive electromagnetic sources (electrical motors with high start-up absorption of power and their
power supply cables, fluorescent lights, emergency generators, remote control devices, etc.) located near the probe.

• Power supply cables to other devices. The route of the conductors must never be allowed to create a large-scale
electromagnetic loop. The power supply cables must be distanced as far as possible from the probe and braided with
the shortest possible pitch. In general, it is advisable that the power supply cable harnesses be inserted into special
insulated channels. In the event that the conductors have to pass near the probe of the metal detector, it is advisable
that they be inserted into an iron tube, either electro-welded or drawn, which is at least 2 mm thick and has a suitable
diameter. N.B: this solution is only valid if the tube is not subject to vibrations; should it be subject to vibrations this
solution could even be counter-productive.

• Grounding. This connection must lead directly to the electrical power supply board and must not be derived from any
other electrical devices.
18 THS – FI022GB2K8v3 --- V - MAINTENANCE

M1 MD M2

QE

Fig.II-4. QE: electrical board; M1: machine 1; M2: machine 2; MD: metal detector.

ci
• Warning! If metal ducts are used for production line
power and control lines, it is advisable not to create an
electrical connection between the conveyor belt frame M1 MD M2
and other nearby devices through the same ducts: if this
is done, interference due to multiple ground returns
could be produced.
Fig. II-5. ci: ducts in insulating material; M1: machine 1; M2:
machine 2; MD: metal detector

• Impulsive sources. In general, impulsive sources must be distanced or eliminated.


It is therefore recommended that, during installation, the following procedures be carried out:

1 position as far as possible from the probe any motors, electrical power boards or electromagnetic actuators (it is
recommended that they be replaced with similar pneumatic devices); position fluorescent lights and their
respective reactors at a distance from the metal detector probe; where possible replace fluorescent lights with
filament lights.

2 equip electrical motors with special iron screens and mains filters of sufficient capacity. It is recommended that
motors running on alternating current be used as opposed to those running on direct current. The table that
follows provides some general guidelines for the distances to be placed between the probe and asynchronous
motors, depending on their power.

Table II-A
Recommended minimum distance between the probe and motors with alternating current
(without screening of the motor)
Power Minimum distance
THS/M & THS/A Other THS models
0,5 CV 5 x DH 3 x DH
1 CV 6 x DH 4 x DH
2 CV 8 x DH 5 x DH
3 CV 10 x DH 6 x DH
> 20 CV 15 x DH ( >10 x DH if screened) 10 x DH ( 6 x DH if screened)

2.1 In the immediate proximity of the metal detector, the motors may be screened by means of cylindrical
enveloping in iron; such cylinders must have a sufficiently large diameter in order to contain the motors and
a thickness of not less than 2 mm. The cylinders must be of the unwelded type.

3 fit the electromagnets, remote controls and continuous current motors with RC muffling nets (ask our technical
office for details of the dimensions) and braid the respective power supply cables with as short a pitch as possible.

Fix the cable which connects the probe to the power supply unit so that it can not oscillate or vibrate.
If the cable is too long, DO NOT CUT THE CABLE: COIL UP THE EXCESS!
THS – FI022GB2K8v3 --- V - MAINTENANCE 19

Installation of a CEIA THS-FB integrated system with conveyor belt

Disconnect the system from the various power sources before carrying out any movement.

Mechanical installation of THS-FB integrated system with conveyor belt


Positioning the conveyor belt
Use lift trucks or sling the load-bearing
structure, and ensure that the load is
balanced during movement. Avoid
deforming the structure or its component
parts. Keep the packaging materials for
possible future transport.

Never attach lifting gear to the


Metal Detector probe or the
actuators.
Fig II-6
Ejector: mounting the safety
shield
Fix the shield by tightening the knobs
provided.

Fig II-7a Fig II-7b


Assembling the buzzer/flasher
Fit the buzzer/flasher module into the
support and rotate clockwise.

Fig II-7c Fig II-7d


Adjusting the height of the belt
Raise or lower the adjustable feet or
castors of the load-bearing structure.

Fig II-8a - Adjusting a foot Fig II-8b - Adjusting a castor


20 THS – FI022GB2K8v3 --- V - MAINTENANCE

Electrical installation - General notes

Observe current regulations regarding electrical and personal safety for both the operator and the installer when installing
the device.
Connect the apparatus to the mains power supply only after first carrying out all the other connections needed for
complete installation.

These instructions for electrical installation apply to both the CEIA INTEGRATED THS SYSTEM, with conveyor belt, and
the CEIA NON-INTEGRATED THS SYSTEM, without conveyor belt.

Connecting to the mains power supply

Only make the connections to the internal terminals of the power supply unit when the unit is disconnected from the
mains

Connection to the ground

Connect a grounding conductor to the PE terminal ; the size of the


conductor should be in line with the safety standards in force.

Fig. II-9a Terminal PE

Control Power Box


• Connect directly to terminal board J17 on
card ALM.
• Conductor section: 1.5 mm2.

PE Put in a magnetothermic switch


upstream:

Fig. II-9b Control Power Box Voltage Current


250Vac 2A
115Vac 4A

Conveyor Control System


• Connect to S1 main switch input terminals.
• Conductor section: 2.5 mm2.

Put in a magnetothermic switch upstream (curves D) : 10A

Fixed-speed Conveyor Control System, with MDT card

IS • The connection is three-phase, and differs according to the voltage.

Check that the voltage corresponds to the voltage on the identification


plate (specify the power-supply voltage when ordering).

Fig. II-9c
THS – FI022GB2K8v3 --- V - MAINTENANCE 21

Voltage 400V 3~ with neutral conductor voltage 230V 3~ without neutral conductor

N
N

PE PE
2200
2199
Fig. II-9d Fig. II-9e

Variable-speed Conveyor Control System with card MDL

IS • Single-phase connection.

• Put in a ground fault interrupter upstream, provided that the trip current is at
least 300 mA.

Connect the safety conductor permanently (without intermediate plugs)


to terminal PE on the casing.

Fig. II-9f

Selection of the power supply voltage for the metal detector only - Control Power Box
Power Supply Unit

Using the I1 switch, it is possible to set the metal detector power


supply voltage to 115Vac or 230Vac. In the illustration, the selector
is positioned at 220-240Vac.

N.B.: the conveyor belt motor must be set up for the power supply
I1 voltage of the system: the power supply voltage should therefore
be specified at the time of ordering.

Fig.II-10

If the power supply to the device is different from that specified on the plate and/or
from that chosen at selector I1, permanent damage may be caused to the device.

CEIA will not be held responsible for damage to people, animals or objects caused
by failure to obey this instruction.
Verification that the power supply conforms to the values specified above and to the
regulations in force is the total responsibility of the customer.

Connection of the compressed air supply


Connect any components powered by compressed air to a source which complies with the specifications in the
“Technical characteristics” section, or otherwise specified in the configuration sheet enclosed with this manual.
22 THS – FI022GB2K8v3 --- V - MAINTENANCE

Non-integrated THS system supplied without conveyor belt: detailed


construction notes and selection of operating parameters
The following notes provide additional instructions necessary for installing the
detector on a conveyor belt or other transport system set up by the customer.
For the installation checks you need to be able to switch on the system, understand the signals given during use and set
the applicable operating parameters. These operations are described in the first part of the “USE” section.

Mechanical Installation
Controls
According to regulation EN60204-1, the main switch and the other controls to be used by the operator must be at a
height ranging from 600mm to 1,800mm from the flooring.
If it proves impossible to comply with this measurement due to the configuration of the system, an additional control unit
which complies with the regulations must be set up.

Mechanical installation of the metal detector


Mount and fix the probe onto the structure of the conveyor belt (use the four holes located on the base-plates. N.B.: on
some models the base-plates can be fixed in two different positions to adapt to the shape of the load-bearing structure).
The belt must pass through the tunnel.

The structure must be stable and not subject to vibrations.

Mechanical installation of the power supply unit


The power supply unit must be firmly attached to the load-bearing structure by means of four screws; it must be close to
the central electronics unit and to the external subsidiary devices connected to the unit (photocell, ejector, etc.).

Mechanical installation of the THS/G probe


Mount the probe on the pipe carrying the material to be inspected and fix it with screws and plastic spacers, using the
holes provided on underside ( see Fig. "Dimensions of the probe", dimension FHW).

Fix the control unit in a convenient position for use, within the limit set by the length of the probe connecting cable.

Fix the cable which connects the probe to the power supply unit so that it can not oscillate or vibrate.
If the cable is too long, DO NOT CUT THE CABLE: COIL UP THE EXCESS!

Proximity limits around the THS/G probe


The distance between the probe and fixed or moving masses depends on the sensitivity selected and on the size of the
masses. The figure below shows:
• the minimum distance D between the probe S and the support plate P
• the minimum distance H between the probe S and the deflector f, based on a sensitivity setting of 280 and a flap-
type deflector in stainless steel. If the sensitivity or the type of deflector is changed, this minimum distance may
decrease: using the procedure for checking environmental interference (see “Maintenance” section), check that
activation of the deflector does not influence operation of the metal detector.
THS – FI022GB2K8v3 --- V - MAINTENANCE 23

D: distance between probe S and support plate


P
d: rigid plastic spacer;
f: steel flap deflector (dim. 290x200x2mm);
H: distance between probe S and deflector f
p: stainless steel support plate;
S: probe.
T: diameter of the probe.
t: plastic pipe

Fig. II-12 – fixing the THS/G probe

THS/G : mounting the power supply unit


The power supply unit must be firmly fixed to the supporting structure with four screws, near the electronics unit and the
slave devices connected to the power supply unit (photocell, ejector etc.). For the location of the holes provided for fixing
the unit, see Figure I-14a.
24 THS – FI022GB2K8v3 --- V - MAINTENANCE

Conveyor belt

The distances quoted below are indicative only, and subject to variation according to the sensitivity required and to the
type of probe. When installation has been completed, therefore, correct operation should be checked.

Load-bearing structure of the conveyor belt

The load-bearing structures of the conveyor belt must be stable and not subject
to detectable vibration during movement of the belt.

THS/M
The structure of the belt must be in non-magnetic steel (e.g. non-magnetic AISI
304).
Fig. II-13 Load-bearing structure
Rollers of the conveyor belt
In general, it is advisable that any rollers located near the antenna be of
insulating material. In which case, there must be an electrical connection on only
one side of the roller, in order to allow the discharge of any electrostatic charges.

DH
| Model THS/M THS/A Other models |
| |
| D ≥ 3 DH * ≥ 3 DH * ≥ 1,5 DH ** | D
| |

* use nonmagnetic steel bearings. I


** plastic roller with fixed nonmagnetic steel axle and nonmagnetic steel bearings.
C
B
N.B.: the bearings must be placed at the ends of the rollers, never in the middle. Fig. II-14. Rollers in insulating
material with metallic
bearings
I: insulated support
C: non-insulated support; B: bearing
Metal rollers , pulling or free, must be located at a distance D, to both sides of
the antenna. Such rollers must also be insulated on a single supporting piece in
order to avoid forming electromagnetic coils and allow the discharge of any DH
electrostatic charges.
D

I
C
| Model THS/M THS/A Other models | Fig. II-15a. Free metal rollers
| | I: insulated support C: non-
| D ≥ 6 DH ≥ 4 DH * ≥ 2 DH | insulated support
| |
DH

C: non-insulated support
I: insulated support D
S: screening
I

C
Fig. II-15b. Pulling metal rollers

Metal rollers must be perfectly concentric.

YES! NO!
Fig. II-16
THS – FI022GB2K8v3 --- V - MAINTENANCE 25

The motors must be located at a distance D from the antenna, adopting measures
identical to those described for the rollers above.

DH
Fit electrical motors with special iron screens and mains filters of sufficient
capacity. It is recommended that motors running on alternating current be used
rather than those running on continuous current. The table that follows provides
some general guidelines for the distances to be placed between the probe and
asynchronous motors, depending on their power
D

Minimum distance advisable between the probe and motors with alternating I
current (without motor screening)

| Models THS/M THS/A Other models | S


| |
| D 0,5 CV ≥ 5 DH ≥ 5 DH ≥ 3 DH |
| 1 CV ≥ 6 DH ≥ 6 DH ≥ 4 DH |
| | C
• In the immediate proximity of the metal detector, the motors may be screened Fig. II-17. motors
by means of cylindrical enveloping in iron; such cylinders must have a
sufficiently large diameter to contain the motors and a thickness of not less C: non-insulated support
than 2 mm. The cylinders must be of the unwelded type I: insulated support
• The table indicates distance measurements corresponding to a high S: screening
sensitivity level; for lower sensitivity levels, distance D may be reduced.
Attention: Rollers for V-shaped belts, if attached to the frame on one side
only, do not require the insulation of the pin.

DH
As in the preceding case, their distance from the probe must be at least equal to
D, to both sides of the antenna

| Models THS/M THS/A Other models | D


| |
| D ≥ 9 DH ≥ 6 DH ≥ 3 DH |
| |
C
Fig. II-18. Metal rollers for V-
shaped belts
C: non-insulated support
Examples of roller insulation I R
Insulation of the pin of a roller.

I: ferrule in insulating material; P: side bulkhead of the belt frame;


R: roller. P
Fig. II-19a
I
R
Insulation of the pin support of a roller.

I: bearing support in insulating material;


P: side bulkhead of the belt frame; R: roller.
P
Fig. II-19b

Insulation of the bearing support of a roller pin.

I: ferrule and spacer in insulating material. I

Fig. II-19c
26 THS – FI022GB2K8v3 --- V - MAINTENANCE

Position of the conveyor belt inside the probe


• The conveyor belt must pass as close as possible to the lower surface of
the tunnel. In order to prevent it from accidentally rubbing against the
probe it is advisable that it be supported within the probe by means of a
sheet of insulating material , which is thick enough to support the weight
of the material being transported (approximately 5-20 mm). It is necessary pi n
to take this measure when the belt is of considerable length and must

DH
therefore be supported, while at the same time prevented from vibrating.
The sheet must not touch the probe (in the illustration an intervening D
distance of 5-10 mm is shown); if it were to touch the probe it could send
vibrations to the antenna. In any event, if there is a supporting metal layer
for the belt, when it arrives at the probe, it must be interrupted for a
pm
distance D, to both sides of the antenna.
n
| Models THS/M THS/A Other models |
| |
| D ≥ 4 DH ≥ 3 DH ≥ 2 DH |
| |

pi
N.B.: THS/M Model: if the product is contained in an aluminium tray, the Fig. II-20. Position of the conveyor
optimum distance between the bottom of the tray and the surface of the belt inside the probe
tunnel is 20-30mm.
pi: sheet of insulating material; pm:
N.B.: In the standard structure, the conveyor belt passes through the probe in layer of metal material; n: belt
both directions to avoid having to cut and rejoin it if the probe is replaced. If
necessary, carry out the join as described in the “Maintenance” section.

Side panels to contain the material in transit


• Near the probe, such edges must be made of insulating material (plastic,
wood, etc.).

Fig. II-21 Side panels for containing


the material in transit

Inserting the conveyor belt on the THS/A model


The THS/A model allows the installation of one side of
the conveyor belt through the probe, without cutting S
the belt itself. The probe has a short section on its A
side which can be removed to insert the belt.

Procedure
• Remove screws S.
• Remove section A. B
• Move the belt into the probe, or the probe over
the belt, depending on the requirements of the
structure.
• Fix section A in place again using screws S.

Fig. II-22
THS – FI022GB2K8v3 --- V - MAINTENANCE 27

Transit speed
Programming Generally-applied setting
Meaning
parameters THS/STD THS/SL THS/3F THS/M THS/G THS/PH
Transit speed
BS 2 - 250m/’ 2 - 250m /’ 2 - 250m /’ 20 - 70m/’ 2 - 250m /’ 2 - 250m /’
Minimum transit speed
BL 2 m/’ 2 m/’ 2 m/’ 20 m/’ 2 m/’ 20 m/’
Maximum transit speed
BM 250 m/’ 250 m/’ 250 m/’ 70 m/’ 250 m/’ 250 m/’
transmission constant of KT = transit speed .
KT the motor reducer unit motor driver frequency
_ _
DI = ø roller + 2 x (thickness of belt)
DI Diameter of roller _ _

Encoder constant
KE (impulses per revolution)
0-1000 impulses per revolution _ _

Maximum motor
MI operating frequency
60-100 (Hz) - -

Maximum motor current


CU consumption
0.000 - 7.000 A - -

The programming parameters must be properly defined depending on the type of installation.

Fixed-speed application, BS should be assigned the true value of the transit speed.
without inverter card,
without encoder (KT=0.000,
KE=0)

Fixed-speed application, BS should be assigned the true value of the transit speed.
with MDT card but with
encoder (KT=F, KE=0)

Variable-speed application, speed detected by the encoder. The speed limits (BL e BM) must be
selected.
with encoder, without The KT parameter is 0.000.
inverter card Assign to the KE parameter the number of pulses per revolution of the
encoder.
Assign to the DI parameter the value of the diameter of the motor roller (see
V table above)
28 THS – FI022GB2K8v3 --- V - MAINTENANCE

Variable-speed application • BS should be assigned the desired value of the transit speed (the current
speed is detected by the system based on the working location of the
with inverter card, with inverter, or via an encoder if fitted).
encoder • Assign to the KE parameter the number of pulses per revolution of the
encoder.
V • Assign to the DI parameter the value of the diameter of the motor roller
(see table)
• Assign the maximum motor operating frequency to parameter MI.
• Assign the maximum motor current consumption to parameter
CU.
Variable-speed application
with inverter card, without Some structural relationships must be observed:
encoder
BL ≤ BS ≤ BM
BL ≥ 20 x KT
BM ≤ 60 x KT
V

The parameter KT depends on the system configuration, and can be


determined using the following procedure (it is necessary to obtain a transit
speed measurement device):

1. set KT=1.000
2. set BS=50
3. activate the motor and measure the speed of transit Vn
4. calculate KT = Vn/50

By changing the value of BS, the speed can vary between 40% and (2 x
MI)% of the nominal value of the motor (corresponding to operation at 50Hz).

N.B.: by modifying the value of KT, the parameters BL and BM are


automatically set to nominal values, respectively 20 x KT and MI x KT.
BL and BM can also be modified manually.

Example:
Motor: operating frequency 50Hz ; maximum frequency 60Hz; maximum
current 3A;
Encoder 100 impulses/rev.;
Roller diameter 60mm, belt thickness 2mm;
Desired speed 45m/', minimum 25m/', maximum 50 m/'.

• Set: MI=60, CU=3.000, DI=60+(2x2)=64


• Determine KT via the procedure described above:
KT=1.000, BS=50 measured Vn =55 m/' KT=55/50=1.100
• Set BL=25 (correct value to give 20KT=22)
• Set BM=50 (correct value to give MI x KT=66)
• Set desired speed BS=45

N.B.: The BS parameter is memorised individually for each type of product defined. If
required, several speed parameters may be set for the same material by defining an
equal number of product types.
THS – FI022GB2K8v3 --- V - MAINTENANCE 29

Accessory devices

Photocell – General rules

Programming Meaning Generally applied setting


parameters
THS/STD THS/SL THS/3F THS/G THS/M THS/PH
PD Distance between metal At the entrance to the probe: 0-2000 mm 50-2000 _
detector and photocell At the exit from the probe: see table II-C mm
PH Position of the photocell IN : installed at the entrance to the probe IN _
relative to the probe OUT: installed at the exit from the probe
IP Type of “Photocell” input NC,NO _

The photocell should naturally be placed at a height whereby it can have a clear view of the objects on the conveyor belt.

Photocell installed at the entrance to the probe When installed at the entrance to the probe, the
PD
photocell distance should be within the range 50mm to
2m
S

F
N

Photocell installed at the exit from the probe When installed at the exit from the probe, the photocell
PD distance (PD in the figure) depends on the belt speed,
but should not in any case be less than that indicated in the
S following table:

F Table II-C
N
Belt speed (metres/min) Minimum distance photocell-
electronics unit (mm)
< 20 50
20 50
Fig.II-24. N: conveyor belt; S: electronics unit; F: photocell; 30 60
d: distance photocell- electronics unit 40 100
50 130
60 160
70 190
80 230
90 260
>100 290

Photocell self-diagnosis
If the photocell is in a continuously active state for a long period, this is interpreted as a malfunction of the sensor by the
self-diagnosis system. There are many possible causes (wrong position, short-circuited wiring etc.).
The self-diagnosis message may appear:
- in the case of a conveyor belt without encoder or with Power Control Box, with the belt stopped or moving
- in the case of a conveyor belt without encoder or with Conveyor Control System, with the belt moving.

The system is not designed to signal a pack which is stuck for some reason in front of the photocell. For this reason,
when the system can detect whether or not the conveyor belt is moving (i.e. when it is equipped with an encoder or with
the Conveyor Control System power supply unit), the self-diagnosis function gives an alarm only if the photocell is in a
state of malfunction when the belt is moving.
On systems without encoder or with the Control Power Box, it is the installer’s and operator’s responsibility to ensure that
material does not remain in front of the photocell when the belt is stopped: if it does, the photocell will be continuously
active even though it is not malfunctioning. If the foregoing situation can not be avoided, it is advisable to disable
photocell self-diagnosis (Parameter PA)
Ejector – General rules
30 THS – FI022GB2K8v3 --- V - MAINTENANCE

Programming Meaning Generally applied setting


parameters
THS/STD THS/SL THS/3F THS/G THS/M THS/PH
PL Length of _ 5-80cm _
product pack
EM Ejection mo Mode B: halting of the production line and manual elimination of the
contaminated material
Mode F: automatic set-aside of contaminated material with alarm _
synchronisation
Mode S: automatic set-aside of contaminated material with photocell
synchronisation
Mode SB: halting of the production line with photocell synchronisation
and manual elimination of the contaminated material
ED Distance of 0-6000mm
ejector from
probe or Application with photocell: set Dfe parameter (see the following figures)
photocell Application without photocell: set Dse parameter
ET Ejection relay
activation time 0-3200 hundredths of a second
The programming parameters which relate to the ejector are CE, CT, EJ, IE, IL and LF (see Programming section).

Position the ejector E at the exit point of the central electronics unit.
In general, the ejector position is constrained by the following formulas:
S Dp
Dfe ≤ 20 x ( PL + Dp)
F E
N Dse > 0.5 x (L + PL)
PL

L Fig.II-25: synchronisation with photocell at the entrance to


Dse the probe
Dfe

S Dp

Dfe ≥ 0.5 x PL
F E
N
Dse ≤ 20 x ( PL + Dp)
PL

L Dfe Fig.II-26: synchronisation with photocell at the exit from the


Dse probe

S Dp
Dse ≤ 20 x ( PL + Dp)
E
Dse > 0.5 x (L + PL)
N
PL Fig.II-27 synchronisation with Metal Detector
L
Dse

S probe/electronics unit of the metal detector L length of probe


N conveyor belt Dfe distance photocell-ejector
F photocell Dse distance probe-ejector
PL length of package Dp distance between packs
E ejector
The ejection time ET must be determined by experimentation, as it depends on the type of ejector
To minimise the number of packs rejected at each alarm, it is recommended that Dp is longer than L, so that
only one pack is ejected each time the ejector is activated.

THS/M – Specific instructions for ejector


Rule Note
BS BS: transit speed, in m/min
Dse ≥ PL + 0,5xL + 60 x (ejector response time)

For accurate analysis, the previous product must have left


Dp = 1,2 x (PL + L) the tunnel before the next one passes through
THS – FI022GB2K8v3 --- V - MAINTENANCE 31

Applications at high speed (belt speeds greater than 60 m/min)


In this case, the response times of the photocell, metal detector and ejector can not be ignored. We would generally
advise users to check operation of the ejector experimentally, changing its position and adjusting parameter ED.

Programming used in a few common types of installation

Belt block without ejector Photocell at entrance, with ejector


pd
ed
ed

parameter description value parameter description value


code code
EM ejection mode B, BS (belt block) EM ejection mode S (synchronised)
BS speed belt speed (m/min) BS speed belt speed (m/min)
EJ ejection ON PL pack length length of pack (cm, only for THS/M)
ED ejection distance ed (mm) pack stop position IP photocell input NO: normally open /NC: norm. closed
ET ejection time ejection time (hundredths of a second)
LO input logic N: negative / P: positive
EJ ejection ON
ED ejection distance ed (mm)
PD dist. ph.- metal det. pd (cm)
PH photocell position IN

Photocell at exit, with ejector Retractable belt


pd ed
ed

parameter description value parameter description value


code code
EM ejection mode S (synchronised) EM ejection mode F (flap)
BS speed belt speed (m/min) BS speed belt speed (m/min)
IP photocell input NO: normally open NC: norm. closed ET ejection time ejection time (cs)
ET ejection time ejection time (hundredths of a sec) EJ ejection ON
LO input logic N: negative / P: positive ED ejection distance ed (mm)
EJ ejection ON
ED ejection distance ed (mm)
PD dist. ph.- metal det. pd (cm)
PH photocell position OUT

Fig.II-28 F: photocell E: ejector


32 THS – FI022GB2K8v3 --- V - MAINTENANCE

Mechanical installation of a bar code reader


Safety precautions
Although the power of the laser beam used in this barcode reader is very low, it can be dangerous to the human eye if
stared into for long periods of time. Careful attention must be paid to the warnings on use of the laser. These warnings
refer to regulations enforced by local authorities.

IEC regulations
Warning labels indicating laser radiation and the reader classification are applied to the body of the reader:

Fig.II-29

The device is classified as a Class 2 laser product according to the rules indicated in IEC publication N. 825-1 (1993).

Turn the power off when opening the reader during maintenance or installation to avoid dangerous laser radiation.

Barcode reader kit


The barcode reader can also be installed on the THS system at a later date: a special kit is available for this purpose,
and includes an enabling code.
The reader is available in two versions:
• Picket-Fence, optimised for codes with vertical bars
• Step-Ladder, optimised for codes with horizontal bars

1 reader
2 Bar code test chart (PCS 0.9)
3 Mounting kit: - bracket- screws Fig.II-30b dimensions
Fig.II-30a composition of the barcode reader kit
THS – FI022GB2K8v3 --- V - MAINTENANCE 33

Distance between the reader and the metal detector probe and distance between packs
The reader is mounted upstream of the probe in order to read a code stamped on the pack. If the code is recognised, the
reader sends a command to the metal detector to select the relevant product type. The time required by the THS to
process the barcode is usually insignificant, but becomes important if the band is changed due to a modification in the
type of product.. When the metal detector receives the signal to change product type, an internal adjustment procedure is
activated the length of which determines the minimum distance between two packs with different codes, that is to say
containing different products.
Model / Event Distance between the Distance between the
packs barcode reader and the THS
probe
Dp THS/3F
S with change of band
BR
(BA parameter) Dp ≥ L + 3000 mm Dsbr ≥ 3000 mm
N
between one product
L
and the other
Dsbr
Dp THS/3F
S without change of
BR
band (BA parameter) Dp ≥ L + 300 mm Dsbr ≥ 300 mm
between one product
N
and the other
Dsbr L
Dp
S
BR
Other THS models Dp ≥ L + 300 mm Dsbr ≥ 300 mm
N

Dsbr L

S probe/electronics unit of the metal detector L length of probe


N conveyor belt Dsbr Distance THS probe-barcode reader
BR Barcode reader Dp Distance between the packs of different products

Position of the reader and the label in transit

A non-rigid mounting, using anti-vibration supports, should be adopted for the reader.
The two types of reader should be mounted as shown in the figures below.
Attention must be paid to the position of the pack in transit, in order to ensure that the barcode can be read (angles P, S
and T in the following figures).
D P =˜ 0˚ D

P =˜ 0˚
P =˜ 0˚ P =˜ 0˚

S = 10 - 30˚
S = 10 - 30˚

S = 10 - 30˚
S = 10 - 30˚ S = 10 - 30˚

T =˜ 0˚ T =˜ 0˚ T =˜ 0˚ T =˜ 0˚

Fig. II-31a Step-Ladder reader: mounting Fig. II-31b Picket-Fence reader: mounting
34 THS – FI022GB2K8v3 --- V - MAINTENANCE

Reading features
The number of scans performed on the code by the reader, and therefore its decoding capability, is influenced by the
following parameters:
• number of scans per second
• code motion speed
• label dimensions
• scan direction in respect to code motion

At least 5 scans during the code passage should be allowed to ensure a successful read.

Step-Ladder mode
BCR bar code reader

CMD code motion direction at LS speed

LB laser beam

Fig. II - 32

If scanning is perpendicular to the code motion direction ( “step ladder” mode), the number of effective scans
performed by the reader is given by the following formula:

SN = ((LH/LS) * 350) - 2
These symbols signify:
SN = number of effective scans
LH = label height (in mm)
LS = label movement speed (in mm/s)

For example, the reader for a 25 mm high code moving at 500 mm/s performs:

SN = ((25/500) * 350) - 2 = 15 effective scans

Suitable values for LH and LS should therefore be chosen, so that:

LH/LS > 0.02

Picket-Fence mode
BCR bar code reader

CMD code motion direction at LS speed

LB laser beam

Fig. II -33
If scanning is parallel to the code motion, (“picket fence” mode), the number of effective scans is given by:

SN = (((FW-LW)/LS) * 350) - 2
These symbols signify:
SN = number of effective scans
FW = reading field width (in mm)
LW = label width (in mm)
LS = label movement speed
THS – FI022GB2K8v3 --- V - MAINTENANCE 35

Reading field width depends on the distance between the label and the reader.
The following figure gives the reading diagram for the following conditions::
• code = interleaved 2/5 or code 39
• PCS = 0.90
• P angle = 0°
• S angle = 10°
• T angle = 0°

Reader - label distance

reader axis

Distance of the label


from the reader axis
Fig. II -34 width of the reading field

For example, for a code 50 mm wide moving through at 1500mm/s at a distance from the reader corresponding to a
reading field of 200mm, we get:

SS = (((200-50) /1500) * 350) - 2 = 33 effective scans

The position of the reader must therefore be chosen so that FW is at maximum, based on the reading diagram, and LW e
LS should be chosen so that

(FW-LW)/LS > 0.02

Kit installation procedure


1. Mechanical mounting, including determination of:
• Distance between reader and metal detector probe
• code transit speed
• label dimensions
2. Electrical connection to the ALM card
3. Assignment of the CEIA enabling code to parameter BE
4. Selection of parameters from the "barcode reader" menu
5. Selection of the corresponding product type, or creation of a new one if necessary
6. Execution of barcode acquisition procedure (command LC)
7. Repetition of steps 5 and 6 for all products being used
36 THS – FI022GB2K8v3 --- V - MAINTENANCE

Electrical installation: detailed notes

Fig. II -35a : Diagram of model THS connections


THS – FI022GB2K8v3 --- V - MAINTENANCE 37

Fig. II -35c : Diagram of model THS/G connections


38 THS – FI022GB2K8v3 --- V - MAINTENANCE

Fig. II -35d : Diagram of model THS-FB connections


THS – FI022GB2K8v3 --- V - MAINTENANCE 39

Observe current regulations regarding electrical and personal safety for both the operator and the installer
when installing the device.
Connect the apparatus to the mains power supply only after first carrying out all the other connections needed
for complete installation.

ALM card electrical connections


Table II-D ALM card connections
Connector Pin Label Input/ Type Range /Max. value Function
Output
ALM-J1 - - - - - Reserved
ALM-J2 - - - - - Reserved
ALM-J3 7-8 - Input N.C. contact - Emergency button
ALM-J4 1 NC - NC RS 485 serial connection
2 ISO GND - ground (see next table)
3 RX- Input RX-
4 RX+ Input RX+ N.B.. the ground contact is insulated from the power
5 TX+ Output TX+ supply unit ground, and is provided for connection of
6 TX- Output TX- RS485 cable shielding (if required)
ALM-J5 1 -V Output -V 0V Bar-code reader
2 -V Output -V 0V
3 TXD Output TXD -
4 RXD Input RXD -
5 +VB Output +VB 20-26Vcc, 0.15A
ALM-J6 2 - Input RXD - RS 232 serial connection
3 - Output TXD - (see next table)
5 - - ground -
6 - Input DTR -
ALM-J7 - - - - - reserved
ALM-J8 - - - - - reserved
ALM-J9 - - - - - reserved
ALM-J10 1 +Vin - +V 20-26Vcc, ** +V (high logic level/sensor power supply)
2 lid full Input N.O. contact* 0V... +Vin container full
3 -V - ground - 0V (low logic level/ power supply ground)
4 +Vin - +V 20-26Vcc, ** +V (high logic level/ sensor power supply)
5 eject confirm . Input N.O. contact* 0V... +Vin ejection confirmation
6 -V - ground - 0V (low logic level/ power supply ground)
7 +Vin - +V 20-26Vcc, ** +V (high logic level/ sensor power supply)
8 photocell Input N.O. contact* 0V... +Vin photocell
9 -V - ground - 0V (low logic level/ power supply ground)
10 +Vin - +V 20-26Vcc, ** +V (high logic level/ sensor power supply)
11 follow.conveyor Input N.O. contact 0V... +Vin downstream belt authorisation
12 -V - ground - 0V (low logic level/ power supply ground)
ALM-J11 - - - - - reserved
ALM-J12 1 +Vin - +V 20-26Vcc, ** +V (high logic level)
2 Inhibition Input N.O. contact 0V... +Vin inhibition
3 -V - ground - 0V (low logic level)
4 +Vin - +V 20-26Vcc, ** +V (high logic level)
5 Reset Input N.O. contact 0V... +Vin alarm reset
6 -V - ground - 0V (low logic level)
7 +Vin - +V 20-26Vcc, ** +V (high logic level/sensor power supply)
8 Encoder Input N.O. contact 0V... +Vin encoder impulses
9 -V - ground - 0V (low logic level/ power supply ground)
10 terra - ground - ground
ALM-J14 - - - - - reserved
ALM-J15 1 common Output common 250Vca 3A auxiliary relay for test due notification
2 Cont. NC Output N.C. contact 250Vca 3A
3 Cont. NA Output N.O. contact 250Vca 3A
4 common Output common 250Vca 3A authorisation upstream belt relay
5 Cont. NC Output N.C. contact 250Vca 3A
6 Cont. NA Output N.O. contact 250Vca 3A
ALM-J16 - - - - - reserved
ALM-J17 1 L0 Input - 230Vac ± 10% 48-62Hz mains power supply***
3 L1 Input - 230Vac ± 10% 48-62Hz
4 PE - ground - safety ground PE ****
40 THS – FI022GB2K8v3 --- V - MAINTENANCE

Connector Pin Label Input/ Type Range /Max. value Function


Output
ALM-J18 - - - - - reserved
ALM-J19 1 terra - ground - ground
2 C1 Output common 250Vca 3A malfunction relay
3 NC1 Output N.C. contact 250Vca 3A
4 NA1 Output N.O. contact 250Vca 3A
5 C2 Output common 250Vca 3A ejector relay
6 NC2 Output N.C. contact 250Vca 3A
7 NA2 Output N.O. contact 250Vca 3A
8 C3 Output common 250Vca 3A alarm relay
9 NC3 Output N.C. contact 250Vca 3A
10 NA3 Output N.O. contact 250Vca 3A
ALM-J20 - - - - - reserved
ALM-J21 - - - - - reserved (connection of metal detector)
ALM-J22 1 +Vo Output +Vo 20-26Vcc, ** reserved
2 +Vo Output +Vo 20-26Vcc, ** reserved
3 -V Output -V 0V ground (external contacts)
4 -V Output -V 0V ground (external contacts)
5 +VDD Output +VDD - reserved
6 -V Output -V 0V ground (external contacts)
7 +VDD2 Output +VDD2 - reserved
8 -V Output -V 0V ground (external contacts)
9 OUT 1 Output OUT 1 18-30Vcc,0..2A motor stop alarm (EM=B)
10 OUT 2 Output OUT 2 18-30Vcc,0..2A reserved
11 PE - ground - safety ground
N.C. contact: normally closed contact; N.O. contact: normally open contact

* IE=NO, IL=NO, IP=NO

** The +Vin outputs can provide an overall maximum current of 150mA ; the +Vo outputs can provide an
overall maximum current of 150mA

*** On the model with conveyor belt, connect the power supply line to the main switch (see diagram below)

**** IMPORTANT! In the case of the Conveyor Control System , connect the safety conductor permanently
(without intermediate plugs) to terminal PE on the casing.

N.B.: the J7, J10 and J12 inputs can be connected to switch contacts or to transistors (in this case the saturation voltage
must be < 0,4V). Their logic is determined by the LO parameter (Input logic, see Programming section).

+Vin
+Vin +Vin +Vin

0V 0V 0V 0V

LO=N: contact LO=P: contact LO=N: transistor LO=P: transistor


Fig. II-36

Make all connections relating to input lines using screened cable, connecting the shielding only at the THS
system end to the contacts marked with the symbol which are provided on the various connectors. Lay the
cables at a good distance from power lines.
THS – FI022GB2K8v3 --- V - MAINTENANCE 41

Conveyor Control System: Power-supply and motor connections


MDT card
E2199

N
N

PE PE
E2199

Fig. II-37a MDT card connections for 230V power supply Fig. II-37b MDT card connections for 400V power supply

Table II-E: MDT card connections for three-phase 230V power supply
Connector Pin Label Input/ Type Range /Max. value Function
Output
MDT-J23 1 1 - Ground - safety ground PE
2 2 - Neutral - Not used
3 3 Input L3 Phase 230V -18% / +10% , 48-62Hz Power supply
4 4 Input L2 Phase 230V -18% / +10%, 48-62Hz Power supply
5 5 Input L1 Phase 230V -18% / +10%, 48-62Hz Power supply
MDT-J24 1 1 Output W Phase Input voltage and frequency, 5A (8A breakaway current) Motor power supply
2 2 Output V Phase Input voltage and frequency, 5A (8A breakaway current) Motor power supply
3 3 Output U Phase Input voltage and frequency, 5A (8A breakaway current) Motor power supply
4 4 - - - Not connected
5 5 - Ground - safety ground
MDT-J25 1 1 Input NA Cont. 0 - 26Vcc Normally open motor thermal
2 2 Input NA Cont. 0 - 26Vcc protection contact
3 3 - Shield Shield
4 4 Input NC Cont. 0 - 26Vcc Normally closed motor thermal
5 5 Input NC Cont. 0 - 26Vcc protection contact
MDT-J26 1 1 Output L3 Phase 230V -18% / +10% , 48-62Hz ALM card power supply
5 5 Output L2 Phase 230V -18% / +10% , 48-62Hz ALM card power supply

Table II-F: MDT card connections for three-phase +neutral 400V power supply
Connector Pin Label Input/ Type Range /Max. value Function
Output
MDT-J23 1 1 - Ground - safety ground PE
2 2 - Neutral - Neutral
3 3 Input L3 Phase 400V -18% / +10% , 48-62Hz Power supply
4 4 Input L2 Phase 400V -18% / +10%, 48-62Hz Power supply
5 5 Input L1 Phase 400V -18% / +10%, 48-62Hz Power supply
MDT-J24 1 1 Output W Phase Input voltage and frequency, 5A (8A breakaway current) Motor power supply
2 2 Output V Phase Input voltage and frequency, 5A (8A breakaway current) Motor power supply
3 3 Output U Phase Input voltage and frequency, 5A (8A breakaway current) Motor power supply
4 4 - - - Not connected
5 5 - Ground - safety ground
MDT-J25 1 1 Input NA Cont. 0 - 26Vcc Normally open motor thermal
2 2 Input NA Cont. 0 - 26Vcc protection contact
3 3 - Shield Shield
4 4 Input NC Cont. 0 - 26Vcc Normally closed motor thermal
5 5 Input NC Cont. 0 - 26Vcc protection contact
MDT-J26 1 1 Output L3 Phase 230V -18% / +10% , 48-62Hz ALM card power supply
2 2 Output Neutral 230V -18% / +10% , 48-62Hz ALM card power supply

MDT - 400Vac: ALM card power supply: pay attention to the connections at connector J26, illustrated in the
figure: power supply to card ALM (230V) uses one input phase and the neutral connection. WARNING! incorrect
connection may cause permanent damage to the ALM card.
42 THS – FI022GB2K8v3 --- V - MAINTENANCE

Dimensioning of the motor: the voltage and frequency values of the motor must correspond to the mains voltage
available. The current limit values are shown in the table.

Motor overload protection: to safeguard the motor, it must be fitted with a suitable thermic relay or a magnetothermic
switch (see the diagram shown in the figure)

Fig. II-37b: motor protection. connection of a normally closed Fig. II-37c: motor protection. connection of a normally open
contact contact: note the jumper on contacts 4 and 5 of connector J25.

MDL card ( ATTENTION: 230V 1~ only! )

Fig. II-37e MDL card connections.

Table II-G: MDL card connections


Connector Pin Label Input/ Type Range /Max. value Function
Output
MDL-J6 1 ground - ground - Shield
2 ground - ground - Protection ground PE
3 U Output U phase 230V – 2,7A (6 A max breakaway current) motor power supply
4 V Output V phase 230V – 2,7A (6 A max breakaway current) motor power supply
5 W Output W phase 230V – 2,7A (6 A max breakaway current) motor power supply

The power supply voltage to the Conveyor Control System with ALM card must be within the range 230Vac ± 10%,
48-62Hz .

Motor overload protection: the motor is protected from overload directly by the card software:: select the motor
nominal current value for parameter CU (see Programming section).

WARNING! Do not connect the cable shielding at the motor end.


THS – FI022GB2K8v3 --- V - MAINTENANCE 43

Operation of the relays (J15 and J19 connectors)


Ejector relay (Eject relay):
Programmable relay with delayed action (with respect to the detector alarm); capacity; the programming parameters that
relate to the functioning of this relay are ED, EM and ET (see Programming chapter).
Alarm relay
programmable relay with immediate action (with respect to the detector alarm); capacity; the programming parameter that
relates to the functioning of this relay is AT.
Malfunction relay (Fault relay)
Safety operation relay (contacts NA and C connected in correct operation); capacity; the programming parameter that
relates to the functioning of this relay is FR.
Malfunction conditions are described in the Maintenance section.
N.B.: when the device is switched on, the relay is not activated (malfunction condition) for about 6 seconds.
Upstream belt authorisation relay (Preceding conveyor relay)
Safety operation relay (contacts NA and C connected in correct operation); capacity 3A.
Auxiliary relay for signalling when periodic test is due (TEST LAMP relay)
Programmable relay ; 3A current-carrying capacity ; the programming parameters relating to operation of this relay are
LB and the parameters of the QA configuration menu (see Programming section).

Timing
Belt blocking with manual alarm reset (EM=B)
Operation with halting of the production line, manual elimination of the contaminated material and manual reset by the operator.
N.B.: The metal detector does not check if there are any subsequent fragments in the material immediately following: all material under the probe
must therefore be eliminated along with the part that caused the alarm. To minimise waste of material it is advisable to select a low setting for the
ED parameter.
Product: loose or packaged
Models: All models except THS/PH

Conveyor Control System power supply unit


Signal Waveform Function
Preceding conveyor relay Upstr. belt authorisation

Alarm relay Signalling

Ejection relay* Belt block

Stop/start/reset button Alarm reset/Restart

Output OUT1 Buzzer/flashing light


Fig. II-38a *:output not activated if MDT or MDL module is fitted

Control Power Box power supply unit


Signal Waveform Function
Alarm relay Signalling

Ejection relay Belt block


ED/BS
Stop/start/reset button Alarm reset

Output OUT1 Buzzer/flashing light


Fig. II-38b N.B.: BS = transit speed

Belt blocking with photocell synchronisation and manual alarm reset (EM=SB)
Operation with halting of the production line synchronised by photocell, manual elimination of the contaminated material and manual reset by the
operator. Allows precise positioning of the material to be rejected.
44 THS – FI022GB2K8v3 --- V - MAINTENANCE

N.B.: The metal detector does not check if there are any subsequent fragments in the material immediately following: all material under the probe
must therefore be eliminated along with the part that caused the alarm. To minimise waste of material it is advisable to select a low setting for the
ED parameter.
Product: loose or packaged
Models: All models except THS/PH

Conveyor Control System power supply unit


Signal Waveform Function
Preceding conveyor relay Upstr. belt authorisation

Alarm relay Signalling

Ejection relay* Belt block

Stop/start/reset button Alarm reset/Restart

Output OUT1 Buzzer/flashing light


Fig. II-39a N.B.: *: output not activated if MDT or MDL module is fitted

Control Power Box power supply unit


Signal Waveform Function
Alarm relay Signalling

Ejection relay Belt block

Stop/start/reset button ED/BS Alarm reset

Output OUT1 Buzzer/flashing light

Fig. II-39b N.B.: BS = transit speed

Automatic ejection with alarm synchronisation (EM=F)


Operation with automatic set-aside of contaminated material. The set-aside method can vary: an ejector may be used – without halting the
production line – or the material can be eliminated by using a retractable belt or by inverting the direction of the belt. This application is typically
used for loose material.
The mode allows the following settings to be selected:
–- alarm relay activation time (AT parameter);
– ejection distance (ED parameter);
– selection of activation time of the ejection relay (ET parameter).

Product: loose
Models: All models except THS/PH

Signal Waveform Function


Preceding conveyor relay None

Alarm relay t1 Signalling

Ejection relay Ejection


ED/BS t1 ET
Output OUT1 Ejection
Fig. II-29c N.B.:
NOTE: BS = transit speed
Parameter AT is set to automatic (AT=A);
t1= alarm time, generally corresponding to the transit of the metal mass through the probe.
THS – FI022GB2K8v3 --- V - MAINTENANCE 45

Model THS/PH
This model uses a dedicated line (OUT2) instead of the ejection relay. N.B.: standard values for parameters ED and AT
are ED=0 and AT=A.

Signal Waveform Function


Preceding conveyor relay None

Alarm relay t1 Signalling

Ejection relay Ejection

Output OUT2 Ejection


ED/BS t1 ET

Fig. II-29d N.B.: BS = transit speed. t1= alarm time, generally corresponding to the transit of the metal mass through the
probe

Automatic ejection with photocell synchronisation (EM=S)


Operation with automatic set-aside of contaminated material, synchronised by photocell. Very similar to the above application, this mode can be
used for packaged products.
The mode allows the following settings to be selected:
– alarm relay activation time (AT parameter);
– ejection distance (ED parameter);
– selection of activation time of the ejection relay (ET parameter);
– selection of the distance between metal detector and photocell (PD parameter).
– selection of the position of the photocell (PH parameter)

Product: packaged
Models: All models except THS/PH

Photocell at entrance
Signal Waveform Function
Photocell Synchronisation

Alarm relay Signalling


AT

Ejection relay Ejection


ED/BS ET
Output OUT1 None
Fig. II-29e N.B.: BS = transit speed

Photocell at exit
Signal Waveform Function
Photocell Synchronisation

Alarm relay Signalling


AT

Ejection relay Ejection


ED/BS ET
Output OUT1 None
Fig. II-29f N.B.: BS = transit speed
46 THS – FI022GB2K8v3 --- V - MAINTENANCE

Serial line connection (J3 and J4 connectors)


Connect the serial communication cable to the terminal board: contacts for both RS485 and RS232 standards are
catered for.

The RS 485 connection allows:


• long-distance connection of a personal computer to a THS metal detector
• connection of a personal computer to several metal detectors linked in a network

The RS 232 connection allows:


• connection of a personal computer to a single THS metal detector only
• connection of a printer fitted with a serial interface

RS 485 connections RS 232 connections

THS personal computer


(25p)
RX (SI) 2 2 TX
TX(SO) 3 3 RX
personal computer THS GND 5 7 GND
6 J6
RX- TX-
RX+ 5
TX+ THS personal computer
TX+ 4
RX+ (9p)
TX- 3
RX-
RX (SI) 2 3 TX
TX(SO) 3 2 RX
J4 GND 5 5 GND
J6
Fig. II –40a
Fig. II –41a

personal computer
J4 THS 1
RX- 6
TX- THS printer
RX+ 5
TX+ (25p)
TX+ 4
RX+ RX (SI) 2 2 TX
TX- 3
RX- TX(SO) 3 3 RX
DTR 6 20 DTR
GND 5 7 GND
J4 THS 2
J6
6
TX- THS printer
5
TX+ (9p)
4
RX+ 2 3 TX
3 RX (SI)
RX-+ TX(SO) 3 2 RX
DTR 6 4 DTR
GND 5 5 GND

J6
to the next THS
N.B.: Select DTR=H mode on the THS
Fig. II –40b
Fig. II –41b
THS – FI022GB2K8v3 --- V - MAINTENANCE 47

Inputs

Make all connections relating to input lines using screened cable, connecting the
shielding only at the THS system end to the contacts marked with the symbol
which are provided on the various connectors.

Bar-code reader
The bar-code reader is supplied upon request: for connection, follow the indications in the plan on the previous pages.
Downstream belt authorisation (Following conveyor - Conveyor Control System only)
When active, this input indicates that the downstream belt is operating and can accept the product.
Photocell
When active, this input indicates the passage of the product in front of the photocell. The input is monitored by the self-
diagnosis system.
Ejection confirmation (Eject confirmation)
When active, this input indicates the passage of the product into the set-aside container. The input is monitored by the
self-diagnosis system.
Container full (Full bin)
When active for at least 5 seconds, this input indicates that the set-aside container is full (the malfunction relay is
activated).
Impulse encoder (Encoder)
This input is used to measure the speed of the conveyor belt if an encoder has been installed. The sensor must provide
impulses, the amplitude of which is indicated in the table “Electrical connections”, with a minimum frequency of 2 Hz and
a maximum frequency of 1kHz. It may be contact type, open collector (NPN o PNP) or push-pull. For correct operation a
coefficient KE must be determined during installation and set-up, as per the procedure described in the para. “ Transit
speed “.
Alarm reset (Reset)
When active, this input forces the Metal Detector to exit from the alarm state (used in the case of operation with belt
block and manual reset).
Inhibition
When active, this input disables the detector: it is generally used to avoid false alarms caused by the start-up of the
conveyor belt when it is not possible to adjust the mechanical structure of the belt.

Alarm inhibition when belt is switched on


If the start-up of the belt is accompanied by interference which is serious enough to cause a false alarm, the alarm can
be inhibited:

• Control Power Box:


• connect a contact which is activated at start-up to the inhibition input;
• set the IN parameter to a suitable value determined by experiment (see “Programming” section).

• Conveyor Control System: simply set the IN parameter to a suitable value determined by experiment (see
“Programming” section).

Air pressure sensor


When active, this input indicates that the compressed air pressure is sufficient for the ejector.

Container absent (Bin absent)


When active for at least 5 seconds, this input indicates that the set-aside container is not in its place (the malfunction
relay is activated).
48 THS – FI022GB2K8v3 --- V - MAINTENANCE

Operating instructions

List of preliminary checks


If the equipment is being switched on for the first time, some checks must be carried out and the value of some
operating parameters must be set. These operations, which are listed on the first page of the INSTALLATION
section, are described in the subsequent paragraphs in this section.

Operations during use and areas of competence


The system is designed to be managed by 6 different operators with different areas of competence:
• operator
• supervisor
• engineer
• quality-control operator
• head of quality control
• remote programmer

Access to programming differs between the various types of user (operator, supervisor, etc.) according to the following
table (see Programming section).

Operation to be carried out Programming access Parameters or menus used


level
• Adjustment of sensitivity Operator (if enabled) Sensitivity Parameter

Supervisor Product Menu


Engineer

• Choice of product Operator Product Parameter

Supervisor Product Menu


Engineer

• Memorisation of new products Supervisor Product Menu


• Autolearn Engineer Autolearn Menu
• Counter management Counter Menu

• Setting up periodic tests and test Head of quality control MD Test Menu
reports QA Configuration Menu

• Carrying out periodic tests Quality-control operator Test MD Menu


Head of quality control
• Printing test reports Head of quality control Print Menu

• Setting detection and ejection Supervisor Rec. parameters Menu (receiver)


parameters Engineer Ejec. parameters Menu (ejector)

• Setting of installation parameters Engineer Barcode reader Menu


THS Configuration Menu
ALM Configuration Menu

• Checking of status of sensors and Engineer I/O Status Menu


actuators
* menu available only when a barcode reader is fitted.

N.B.: all the parameters shown in the table are accessible in remote mode
THS – FI022GB2K8v3 --- V - MAINTENANCE 49

Controls and indicators

Power switch
On the Conveyor Control System model, the On/Off switch is located on the power supply unit cover; in the case of
the Control Power Box, an external switch must be fitted.

Switch

Fig. III-1a - Conveyor Control Fig. III-1b - Control Power Box Fig. III-1b - Control Power Box in the
System version for the THS/G

Control panel of the probe/electronics unit


The control panel, containing the optical indicators and the metal detector controls, is located on one side of the
electronics unit:

a green indicator indicates the


A POWER presence of power

a red indicator indicates the metal


B ALARM detector alarm (detection of a metal
fragment or breakdown)

4 lines, of 20 characters each,


Alphanumeric display the messages relating to use,
C display programming and self-diagnosis of
the device

Control panel

Acoustical indicators
In the Power Control Box is included an acoustical indicator that is activated in case of alarm for the detection of metallic
fragments, for the signalization of a fault or for the request of an operator intervention.
50 THS – FI022GB2K8v3 --- V - MAINTENANCE

Controls
The control of the Metal Detector and the setting of the device parameters are performed through the control panel
keyboard, as shown below:

Key Function

Access and exit from the programming phase


Return back from the submenus to the main menu
Exit from the Metal Detector Status visualization
Scroll through the sequence of instructions
Choice of the parameters to be changed
Modification of the parameter values

Metal Detector Status visualization

Selection of the selected submenu from the main menu


Confirmation of the data entered
Reset of some kinds of fault

Conveyor Control System power supply unit control panel


On the power supply unit Conveyor Control System, the container cover incorporates a motor control panel.
In the case of operation with stopping of the belt and manual resetting, the motor start/stop button also functions as the
alarm reset.
The motor speed control keys have different functions depending on the version.

Fixed-speed Conveyor Control System


Key Status of motor
Motor on Motor off
No function Manual advance *
No function Manual reverse *
* if parameter MM = ON

Variable-speed Conveyor Control System


Parameter MM = OFF Parameter MM = ON
Key Status of motor Status of motor
Motor on Motor off Motor on Motor off
Increase in speed No function No function Manual advance
Decrease in speed No function No function Manual reverse

Scheda MDLindicator
Power Motor on indicator

Motor malfunction Motor off indicator


indicator
Speed increase button

Speed decrease button

Metal detector alarm


indicator detector
Motor start/stop and alarm
reset button

Fig. III-3: commands and indicators on the power unit with inverter card Conveyor Control System
THS – FI022GB2K8v3 --- V - MAINTENANCE 51

Visible/audible alarm signalling device


The signalling device comprises a flashing light and a buzzer. The sound volume and the type of sound can be selected
via minidips.

1 volume & sound selectors

Fig. III-4

Switching on the metal detector


If the device is stored for a long period in temperatures outside the operating range, wait for the temperature of the
detector to come back within that range before switching on

Power supply unit


There are dangerous voltages inside the power supply unit. Close the cover and keep the key safe so that it is only
available for use by trained personnel (Regulation EN 60204)

Conveyor belt motor


The motor can reach high temperatures during use: do not touch the motor or bring inflammable materials close to it
while it is operating or immediately afterwards. Ensure that the cooling air intakes are not obstructed, and that there is
free air circulation
WARNING: do not set the motor in motion without the conveyor belt: this may lead to damage due to excess revolutions
and consequent overheating.

Checking the safety features


Before switching on, check that the safety devices with which the system is fitted are in good condition:
1. rollers: protection crankcase for the pin
2. rollers: lower protection panels
3. ejector: protection panels (if fitted)

Also check operation of the emergency button with the belt in motion.

1 1

1
3 3

2
3
2

Fig. III-5 roller safety protection


52 THS – FI022GB2K8v3 --- V - MAINTENANCE

It is strictly forbidden to start up the system if all safety features are not properly functional. Tampering with the safety
features is also forbidden, and voids all responsibility of the manufacturer for any damage caused.

Keep the power supply unit panel closed. The key must always be in the possession of an authorised person.

Fig. III-6

Signals at power-up
The detector is designed to be switched on directly from the electrical panel that controls the production line.
The power supply unit does however contain an auxiliary switch I2, which is normally in the ON position.
The presence of mains power supply is signalled by the lighting up of the indicator located on
the control panel (Conveyor Control System) ...

Fig. III-7a

... or of the green LED L2 located on card ALM, near switch I2 (Control Power Box).

I2 L2 Fig. III-7b

When it is first powered up, the Metal Detector’s configuration includes 5 factory-set passwords (shown in the
test card at the end of the manual).
It is extremely important that the person in charge of the detector modifies the passwords in order to avoid
unauthorised access to programming.
When the device is turned on, the display lights up, as do the indicators located on the front of the
electronics unit.
More specifically, the display shows, in sequence, the serial number and the version of the software program that drives
the power supply unit; after that the following is displayed:

in which:
THS identifies the model

Product
THS V3.xxx
productname
V3.xxx identifies the software version of the metal detector
| productname indicates the type of programming, specific to one product,
which may be chosen from among 250 stored sets, of which
249 can be defined by the user (see Programming chapter);
Fig.III-8 each stored programming set is customised and relates to a
specific product to be monitored.

Signals given during use

On models where there is a control panel on both the probe and the power supply unit (because the probe is installed in
a position which is inaccessible to the operator), the electronics unit display is disabled (the message “Disabled”
appears).

Indication of the received signal


On the fourth line of the display the signal being received is displayed by means of a horizontal illuminating bar,
subdivided into 20 sections. When the signal increases, the bar extends towards the right. The alarm threshold
corresponds to 10 illuminated sections: the sections from 1 to 10 are bars, those from 11 to 20 are asterisks
THS – FI022GB2K8v3 --- V - MAINTENANCE 53

THS V3.xxx THS V3.xxx THS V3.xxx


Product productname Product productname Product productname
| | | | | | | | | | | | | | | | | | | | | * * * * *
Fig.III-9a. Example: signal well below Fig.III-9b. Example: signal just below Fig.III-9c Example: signal above the
the threshold level the threshold level threshold level (alarm).

Checking for environmental electromagnetic interference


The THS Metal Detector has very high immunity to electromagnetic interference. However, it may happen that electrical
devices, usually power devices, cause interference which is strong enough to lead to false alarms. To identify these
sources of interference the indication of the signal received from the probe, which the detectors normally shows on the
display, can be used. Under normal conditions, the indication on the display should correspond to that in Fig. III-9a.

Display Messages
The Metal Detector display shows messages relating to its current mode of operation:

DISPLAY MEANING

Normal functioning
The Metal Detector is in normal operating mode:
THS V3.xxx On the fourth line of the display the signal being received
Product productname
|
is displayed by means of a horizontal illuminating bar,
subdivided into 20 sections. When the signal increases,
the bar extends towards the right.

Metallic mass detection


The Metal Detector is in normal operating mode: it has
THS V3.xxx just detected a metal object and activates connected
Product productname
slave devices. The alarm threshold corresponds to 10
| | | | | | | | *
illuminated sections: the sections from 1 to 10 are bars,
those from 11 to 20 are asterisks.

access code Programming access phase


000000 The Metal Detector requests a password to be entered.

Programming
Sensitivity 265 <-
Products The Metal Detector has been set to programming mode:
accessible parameters can be modified.

Test procedure
**TEST** The Metal Detector requires an operational test to be
Product productname
|
carried out (see “Periodic test management” section in
this manual).

Self diagnosis
The device, when a possible functional problem is
**BIN FULL**
Product productname detected, shows on the display the problem kind and
| utters the alarm signal, asking for the intervention of the
operator.
54 THS – FI022GB2K8v3 --- V - MAINTENANCE

Display of the status of the Metal Detector

If the (increase) key is pressed when the display shows normal operation, a list of information relating to the Metal
Detector’s status is shown:
THS/M
Sensitivity 265
THS/MN V3.xxx Cur Alar. 10
Product productname Cur. Obj. 156
Time 12:34
Date 24/10/97
|
Next test 15:00
Fig. III-11a

Other THS models:


Sensitivity 265
TX program 0
THS V3.xxx Cur Alar. 10
Product productname Cur. Obj. * 156
Time 12:34
Date 24/10/97
| Next test 15:00
Fig. III-11b
* not present on THS/G models

Use of the conveyor belt

Starting/stopping the conveyor belt


With the correct power supply and with the motor stopped, check that the LED indicators are on or off as
shown in the following table:

Indicator Status
mains voltage on
motor on off
motor off on
motor malfunction ! M off
metal detector alarm ! off

• Press the start/stop button to switch on the motor: check that it starts up, and that the “motor
on” indicator comes on and the “motor off” indicator goes off.

• To stop the motor press the start/stop button again: check that it stops, and that the “motor
on” indicator goes off and the “motor off” indicator comes on.

• Fixed-speed Conveyor Control System: check the manual movement of the motor using the and keys
(if parameter MM=ON).

Adjustment of the belt speed


The motor speed control keys have different functions according to the value of parameter MM (see Programming
section).
The speed of the conveyor belt can be adjusted by:
• programming the BS parameter on the metal detector
• simply pushing the keys located on the Conveyor Control System, if parameter MM=OFF.

N.B.: during programming of the metal detector, the Conveyor Control System keypad is disabled. Vice-versa, while the
Conveyor Control System keys are being used, metal detector programming is disabled.
THS – FI022GB2K8v3 --- V - MAINTENANCE 55

Display of the metal detector Keypad of the Comment


Conveyor Control
System
Belt lower sp. 20 The “Speed” reading indicates the speed set, and varies
Belt speed 40 <-
Belt maximum sp. 60 in real time when the and keys are pressed.
Any variation in speed is memorised as a parameter
specific to the current product type.

Emergency button
An extra emergency button is mounted on the conveyor belt to stop it in case of malfunction or danger.

If necessary, the main system switch can also be used for this purpose.

Display Control Comment

* * EMERGENCY * * emergency The alarm indicators are activated


Product productname button

Automatic stop
If nothing passes through the metal detector for the length of time set by parameter ST (see Programming section), the
conveyor belt stops automatically.

Alarm reset
In the case of an alarm, the contaminated product is ejected from the product conveyor according to the type of operation
which has been selected:

• in operation with automatic ejection, the belt is not stopped and the contaminated product is sent into a set-aside
container which should be emptied periodically by the operator. In this case, the detector resets automatically.
• in operation where the conveyor belt is blocked, the belt is stopped and the contaminated product is positioned in the
exit area of the metal detector for manual removal by the operator (N.B. all material between the probe and the stop
line must be removed!).
S

fig. III-13

In this case, the belt only restarts when the operator pushes the appropriate button. In the case of the Conveyor
Control System, this button is incorporated into the control panel:

Action Indicators and results


the metal detector alarm indicator goes off
press once to reset the metal detector alarm
the motor restarts
press again to restart the motor

Automatic operation using a bar-code reader


The THS system can, upon request, incorporate a bar-code reader for automatic selection of the specific parameters of
the product in transit. This avoids having to halt the production line frequently. The reader is installed upstream of the
probe so as to read a code stencilled on the pack. If the code is recognised, the reader sends a command to the metal
detector to select the analysis programme.

If the code is not recognised due to lack of legibility or because it is not on the list of enabled codes (see parameter CD in
the Programming section), the reader does not send any signal to the metal detector and the analysis program remains
that selected for the last pack). In this case, also, the pack can be expelled automatically from the production line by
enabling parameter NE

When the metal detector receives the signal to change product type, an internal adjustment procedure is activated the
length of which determines the minimum distance between two packs with different codes, that is to say containing
different products. This distance is as follows:
56 THS – FI022GB2K8v3 --- V - MAINTENANCE

THS/3F D min = (probe length) + 3000 mm


with change of band (BA parameter) between one product and the
other
THS/3F D min = (probe length ) + 300 mm
without change of band (BA parameter) between one product and the
other
Other THS models D min = (probe length ) + 300 mm

Attention must be paid to the position of the pack, or rather of the label, while in transit: this should be parallel
to the direction of transit so as to ensure that the barcode is legible.

Photocell self-diagnosis
If the photocell is in a continuously active state for a long period, this is interpreted as a malfunction of the sensor by the
self-diagnosis system. There are many possible causes (wrong position, short-circuited wiring etc.).
For details see the “Self-diagnosis” paragraph in the Maintenance section.

On systems without encoder or with the Control Power Box, it is the installer’s and operator’s responsibility to
ensure that material does not remain in front of the photocell when the belt is stopped: if it does, the photocell will
be continuously active even though it is not malfunctioning. If the foregoing situation can not be avoided, it is advisable to
disable photocell self-diagnosis (Parameter PA)

Programming the metal detector according to the kind of product


The operating mode of the metal detector according to the kind of product is determined by the following parameters:
• TX program (TP parameter) except for THS/MN
• Sensitivity (SE parameter)
• Analysis mode (AM parameter)
• Band - only on the THS/3F multi-frequency model (BA parameter)

The factory settings are suitable for dry products (biscuits, pasta, dry frozen food,...).
We would remind you that:
• in the case of products with "difficult" characteristics, it is advisable to call CEIA's Technical Department in order
to request production of specially-designed equipment.
• it is always advisable to optimise installation in line with the criteria described above in order to obtain maximum
sensitivity and maximum rejection of environmental interference.

Procedure for minimising the "product effect"


The goal of this procedure is to obtain the following operating mode:
a the detector does not set off an alarm when the conveyor system is active and some of the pure product,
without any metallic contamination (with aluminium tray onTHS/MN), passes through the probe.
b the detector sets off an alarm when some of the product containing a metallic sample passes through the
probe
It is important to make sure that the product always passes through the probe at the same point and with the
same orientation, in order to obtain the best results from this procedure:
Procedure for automatic product acquisition (not applicable to the THS/M model)
This procedure comprises the automatic acquisition of product characteristics in order to identify the contribution to the
received signal due to the metal mass to be detected. The characteristics are acquired progressively by making the
product pass through the metal detector several times.
The procedure alters the settings of the following parameters:
• SE and TP, if TN>1 (only SE on THS/MN)
• Only TP if TN=1
• BA, on model THS/3F if MB=ON

The procedure must be completed once started. Do not change any parameter setting during the procedure.

1 It is advisable to create a new product using the command New P.


2 Set the Analysis Mode parameter to a suitable value (see the “Analysis Mode Selection Criteria” section). In the
case of the THS/3F model, the correct value of the MB parameter must be selected (ON: autolearn with automatic
selection of the operating band; OFF: autolearn with operating band pre-set using the BA command). In the case
THS – FI022GB2K8v3 --- V - MAINTENANCE 57

of multi-band operation(MB=ON), select the desired value for the OS parameter.


3 Set “Autolearn=ON”. Exit from the programming phase and follow the display instructions.
4 Make the product pass several times through the metal detector, according to the value of the Transits
parameter (N.B.: in the case of loose product, the device automatically proceeds to analyse it correctly). N.B.: in
the case of model THS/3F, if MB=ON, carry out 3 x TN transits, with TN=2,3....
The message “Pass product” appears on the display, and the buzzer is activated (if enabled).
5 At the end of the transits the detector exits from the autolearn phase and the standard message appears on the
display.
6 Final operating check
6.1 Pass some pure product through the detector: the device should not set off any alarm.
6.1.1 Pass some of the product with a metallic sample: the detector should give an alarm. In such a
case, the procedure has been successfully concluded.
6.1.2 Otherwise, increase sensitivity and check that the bar-graph indication is not higher than 8 points
during the transit of uncontaminated product.
6.2 If the detector gives an alarm whenever some of the pure product passes through the probe, decrease the
“Sensitivity” parameter until the detector does not give an alarm (this is probably due to non-uniformity of
the product).
7 If a periodic test on the product is required, set the effective diameter of the metal mass used in the relevant
parameter in the MD Test menu: parameter FD if the sample is of ferromagnetic metal, parameter SD if stainless
steel, or parameter ND if diamagnetic. In this way, the test report will show this value next to the result of the test
carried out.

N.B.: if the product can vary significantly in its electromagnetic characteristics, adjust parameter SA (Sensitivity
Adjustment)
58 THS – FI022GB2K8v3 --- V - MAINTENANCE

Analysis mode selection criteria


The THS detector offers the possibility of choosing between three different types of detection, using the command
Analysis mode AM:

Selection criteria
Analysis Preferential applications
mode AM THS/M Other THS models

always Distance between products at least 1.5 times the depth of


the tunnel (DL ).

Distance between products can be less than 1.5 times the


depth of the tunnel (DL) with product characterised by a
not applicable
TP setting (from autolearn procedure) in the range 200 to
1000.
3
4 not applicable Reserved

5 not applicable Reserved

6 not applicable
As analysis mode 2, with improved immunity
against vibrations
7 not applicable
As analysis mode 3, with improved immunity
against vibrations

In each case it is advisable to check operation with all types of detection, and to choose the one which provides
the highest level of sensitivity.
THS – FI022GB2K8v3 --- V - MAINTENANCE 59

Sensitivity check with reference sample


It is important to check proper operation (sensitivity and ejection of material) of the metal detector periodically by carrying
out a sensitivity test with a reference sample.

Test using a sample defined by the customer


The reference sample is identified at the end of the installation phase based on the customer’s specifications; the
sensitivity, trajectory and orientation of the sample must be noted if it is not spherical.
This sample should be kept under constant conditions, and is used periodically for the test, which should be carried
out under the same conditions as the end-of-installation test.

Test using a CEIA sample


The reference sample is one of the CEIA spherical samples available in various sizes and in three types of metal
(ferrous, non-ferrous and stainless steel)
Determine by experiment the sensitivity needed to detect the sample, or carry out the procedure for minimising the
product effect
Enter the diameter of the sample in the FD parameter (or SD, or ND, depending on the type of metal used)
Set the intervals and the waiting period for carrying out the test, and whether or not the malfunction relay is activated
if the test is not performed (see QA Configuration menu)
Periodic test management

At the end of the period Test interv. (from when the metal detector is switched on),
a message requesting a test is displayed:. ( this can also be signalled via an
optional lamp).
** TEST **
The check can be carried out either by the Quality-control Operator or the Head of Product productname
Quality Control. | |

N.B.: to exclude the reminder to carry out the test periodically, set parameter Test
int.= 0.

Test procedure
The procedure described below refers to the FE test; the other two tests follow the same procedure.

Display Comment

Test FE <
Test SS Enter programming phase, select Test FE function and press
Test Non-FE
key.

Test FE WAIT <


Test SS
Test Non-FE Wait

Test FE PASS <


Test SS
Test Non-FE
Pass a sample through the probe
within 20 seconds.
TEST SAMPLE

Test FE OK <
Test SS
Test Non-FE
The positive outcome is recorded in
memory.
TEST SAMPLE
60 THS – FI022GB2K8v3 --- V - MAINTENANCE

If the test fails, one of the following messages will be seen at point 4:

Display Comment

Test FE
Test SS
NULL < The sample is considered too large to carry out a valid test,
Test Non-FE with a signal amplitude >400% of the SE alarm threshold.
The result of the test is recorded as NO.

Possible causes:
- No transit has been detected for 20 seconds
Test FE
Test SS
NO < - The signal from the sample is below the SE alarm
Test Non-FE threshold
- Three consecutives passages were giving negative result
- The system of ejection is enabled, but ejection has not
been confirmed via the “ejection confirmation” input

The outcome of the test, whether positive or negative, is always stored in memory.

In the case of abnormal operation, carry out a test using the sample indicated on the Configuration Sheet enclosed with each unit after selecting the
“default” product.
THS – FI022GB2K8v3 --- V - MAINTENANCE 61

Programming
General points on programming
The control of the Metal Detector and the setting of the device parameters are performed through the control panel
keyboard, as shown below:

Key Function
Access and exit from the programming phase
Return back from the submenus to the main menu
Exit from the Metal Detector Status visualization
Scroll through the sequence of instructions
Choice of the parameters to be changed
Modification of the parameter values

Metal Detector Status visualization

Selection of the selected submenu from the main menu


Confirmation of the data entered
Reset of some kinds of fault

A password is requested upon entry to programming mode.


When it is first powered up, the Metal Detector’s configuration includes 6 factory-set passwords (shown in the following
table). The standard values are:

Access level Password


Operator 000001
Supervisor 000002
Engineer 000003
Control Quality Operator 000004
Head of Control Quality 000005
Remote programming 000006

Every level of programming allows access to various groups of operating parameters.

Only the engineer and the remote programmer can alter the passwords to the various levels.

It is extremely important that the person in charge of the detector modifies the passwords in order to avoid unauthorised access to
programming.

Programming mode is accessed by pressing


key .
Access Code
The Metal Detector requests a password to be
000001
entered:

The password is entered by selecting one character at a time via the and keys, confirming each selection with
the key.

After the password has been entered, access to programming is given, and the display shows the parameters available
for the programming level.
62 THS – FI022GB2K8v3 --- V - MAINTENANCE

Example of display output Parameter


during operator-level Parameter
name value
programming.
Sensitivity 265 <-
Products

Cursor

Example of display during


programming: supervisor Parameter
level. name
Products ->
Autolearn
Detection
Ejection Cursor
indicating
presence of
submenu

- The parameters are selected via the (increase) and (decrease) keys, and are activated via the
(Enter) key: when this happens, the current setting begins to flash.
- Submenus are selected via , and accessed via
- The parameter settings are modified via
- The modifications are confirmed by pressing
- Returns to the previous menu and exits from programming mode via .

If the sensitivity value does not begin to flash after has been pressed, it means that the parameter in
question is not accessible from the current programming level. The product named “Defalut” cannot be
modified.

Every level of programming allows access to various groups of operating parameters, as shown in the following table:

Livello Menu / Comandi disponibili


Sensitivity
1 Operator level
Products
Products
Autolearn
Detection
2 Supervisor level
Ejection
Ejection time
Counters
Products
Autolearn
Detection
Ejection
Counters
3 Engineer level Bar-code reader*
THS Configuration
Date setting
Change password
ALM Configuration
I/O status
4 Quality Control operator level MD Test
MD Test
Print
5 Head of Quality Control level Print report
Q-C Config.
Test sensitivity
6 Remote programming level All the commands at Engineer and Head of Quality Control levels.
* menu available only when a bar-code reader is fitted.

The structure of the programming menus is tree-type. The individual parameters are described in the “Programming
Instructions” table, along with the menu/submenu sequence via which they can be selected.
THS – FI022GB2K8v3 --- V - MAINTENANCE 63

Every level of programming allows access to various groups of operating parameters, as shown below:

Operation Programming access level Parameters or Menu used


Operator (if authorized) Sensitivity parameter
Sensitivity adjustment
Supervisor, Engineer Products Menu
Operator Product parameter
Product choice
Supervisor, Engineer Products Menu
Storing of new products Products Menu
Autolearn Supervisor, Engineer Autolearn Menu
Counters management Counters Menu
Setting of periodical tests and test MD Test Menu
Head of Quality Control
reports QA Settings Menu
Quality Control Operator
Performing of periodical tests MD Test Menu
Head of Quality Control
Print of Test reports Head of Quality Control Print Menu
Settings of detection and ejection Detection Menu
Supervisor, Engineer
parameters Ejection Menu
THS Configuration Menu
Settings of Installation parameters Engineer
ALM Configuration Menu
Control of Sensors and Actuators
Engineer I/O Status Menu
status

Programming instruction

Products menu
Remote Possible settings Standard setting Parameter
Prod. 12 alphanumeric
PI characters
- Global
Description Models
Type of product selected
Selection of a product previously entered and saved.
Local programming #PI<ENTER>
The various defined products are shown on the display when the Default
arrow keys are pressed. Choose the desired product by pressing Prod_A
the key. > Prod_B
Prod_C
All models
Remote programming
This command displays the list of products: the current product #PI=Prod_A<ENTER>
is shown by the “>” cursor. #PI<ENTER>
To change the current product, assign the corresponding value Default
to the PI setting.
> Prod_A
Prod_B
Prod_C
Example:
#

Remote Possible settings Standard setting Parameter


P.Name 12 alphanumeric Related to the current
PN characters
- product
Description Models
Product name
Changes the name of a product already in memory.
All models
Note: always enter 12 characters (including spaces). Select each character via the
(increase) e (decrease) keys and confirm by pressing the (ENTER) key.

Remote Possible settings Standard setting Parameter


New P. 12 alphanumeric Related to the current
NW characters
- product
Description Models
Name of a new product
Create a new product. The initial parameters of the new product will be the same of the product selected when the
new product is created. Up to 249 products can be created.
All models
Note: always enter 12 characters (including spaces). Select each character via the
(increase) e (decrease) keys and confirm by pressing the (ENTER) key.
64 THS – FI022GB2K8v3 --- V - MAINTENANCE

Remote Possible settings Standard setting Parameter


Erase 12 alphanumeric Related to the current
EP characters
- product
Description Models

Elimination of a product
Elimination of an existing product: select the desired product in the list displayed using the arrow keys, and confirm All models
with the key.

Autolearn menu
Remote Possible settings Standard setting Parameter
Autolearn
LE ON / OFF OF-F Global
Description Models
Autolearn
Select ON and exit from programming to activate the autolearn procedure. The parameter returns to OFF All models
automatically at the end of procedure. See paragraph “Programming the metal detector according to the kind of
product” in the Instructions manual.

Remote Possible settings Standard setting Parameter


Optimise SS
OS ON / OFF ON Global
Description Models

Inclusion of stainless steel in the metals for which the signal/product ratio is optimised
THS/3F
ON: frequency optimisation for stainless steel; OFF: frequency optimisation for iron
Signal/product ratio: metal signal / product signal. This parameter operates only during autolearn, if MB=ON.

Remote Possible settings Standard setting Parameter


Multi-band
MB ON / OFF OFF Global
Description Models

Multi-band
THS/3F
ON: autolearn with automatic selection of the operating band; OFF: autolearn without modification of the current
operating band (BA). See paragraph “Programming the metal detector according to the kind of product”.

Remote Possible settings Standard setting Parameter


Transits
TN 1 – 10 2 Global
Description Models
Number of product transits for autolearn
In the case of non-uniform products, increase TN so as to obtain a more accurate mean.
All models,
If TN=1 the autolearn will change only the TP value.
except THS/MN
If TN>1 the autolearn will change both TP and SE.
The number of product transits requested for autolearn is 3xTN. Selecting MB=ON. On THS/3F with MB=ON, if TN=1
the value is automatically changed to 2.

Remote Possible settings Standard setting Parameter


Sensitivity adj.
SA 10 – 30 15 Global
Description Models
Margin of sensitivity
Margin of sensitivity below the limit used to set SE during the autolearn procedure: by lowering the sensitivity, false
alarms are avoided in the case of significant variations in the characteristics of the product. All models
If the value of SA is increased, the sensitivity determined by the autolearn procedure decreases.
The standard value of 15 corresponds to a ratio of 2 between the effective signal (alarm signal) and the interference
due to the product.
THS – FI022GB2K8v3 --- V - MAINTENANCE 65

Detection menu
Remote Possible settings Standard setting Parameter
Sensitivity Related to the current
SE 0 - 299 - product
Description Models
Sensitivity
All models
Alarm trigger threshold: the smaller the object to be detected, the greater the sensitivity must be.
The parameter can be modified at operator level if parameter OA=ON

Remote Possible settings Standard setting Parameter


TX program Related to the current
TP 0 - 1799 0 product
Description Models
Analysis parameter of received signal
This parameter determines the optimum point of operation to minimise the signal generated by the product, and is set All models,
automatically by the detector during the autolearn process. except THS/MN
For example, for a dry product the choice of TP=0 is the optimum, for a wet product a value around 900 is the
optimum.

Remote Possible settings Standard setting Parameter


Band Related to the current
BA High / Medium / Low High product
Description Models
Operating band
High: high band; Medium: medium band; Low: low band.
THS/3F
Parameter determined automatically by the system during the autolearn procedure. (if parameter MB =ON).
The parameter can also be adjusted manually: in general, the band should get lower as the product increases in
humidity or if a metallic film is present.

Remote Possible settings Standard setting Parameter


Analysis mode 6 Related to the current
AM 2-7
(2 on THS/MN) product
Description Models
Received signal analysis mode
AM THS/MN Other THS models
2 Standard recovery time after an alarm
3 Fast recovery time after an alarm
4 Not applicable Reserved All models
5 Not applicable Reserved
Standard recovery time after an alarm, with
6 Not applicable
improved immunity against vibrations
Fast recovery time after an alarm, with improved
7 Not applicable
immunity against vibrations
66 THS – FI022GB2K8v3 --- V - MAINTENANCE

Ejection menu
Remote Possible settings Standard setting Parameter
Ejection mode Related to the current
EM B / F / S / SB - product
Description Models
Ejection mode
Selection of ejection mode for contaminated material.
Used for loose product and belt stop. No photocell required.
This includes halting of the production line, manual elimination of the contaminated material and
manual reset by the operator.(See also parameters ED and ET).
Mode B Note: The metal detector does not check if there are any subsequent fragments in the material
immediately following: all material under the probe must therefore be eliminated along with the part
that caused the alarm. To minimise waste of material it is advisable to select a low setting for the
ejection relay activation delay. All models
Used for loose product and ejection effected using retracting band or flap. No photocell required
Mode F
Includes automatic set-aside of contaminated material. (See also parameters ED and ET)
Used for packed product and ejection effected using pusher. Photocell required.
Mode S Includes automatic set-aside of contaminated material with photocell synchronisation. (See also
parameters ED, ET, PD, PH)
Used for packed product and ejection effected with belt stop. Photocell required.
This includes halting of the production line with photocell synchronisation, manual elimination of the
Mode SB
contaminated material and manual reset by the operator.. (See also “Timing” section and parameter
ED)

Remote Possible settings Standard setting Parameter


Ej. distance Related to the current
ED 0 – 6000 mm - product
Description Models
Distance of ejector from probe or photocell
This parameter determines the activation delay of the relay relative :
If EM=S or EM=SB : Distance between the photocell and the ejector.
If EM=F or EM=B : Distance between the alarm (usually center of the probe) and the ejector.
All models
This delay is approximately :

ED (distance between ejector and antenna or photocell)


BS (transit speed)

Remote Possible settings Standard setting Parameter


Rev. detection Related to the current
RD ON / OFF OFF product
Description Models
Reverse detection
Detection of lack of metal parts, with inverted operation of both output relays. This requires a photocell to be mounted
before or after the probe. This function is normally used, for example, to detect and reject packages without closing
clip.
Example with photocell at exit:
AT =A AT≠A

All models
THS – FI022GB2K8v3 --- V - MAINTENANCE 67

Remote Possible settings Standard setting Parameter


Belt lower sp.
BL See below - Global
Description Models
Minimum transit speed
This parameter appears only if the variable speed inverter module (MDL) is fitted (KT > 0.000) or an encoder is
connected (KE>0). In case an encoder without MDL is fitted, the range is 2 < BL < 250 m/min. In case MDL is fitted All models,
then 20KT < BL < BM. except THS/G
The parameter is not applicable in case of fixed-speed, MDT card fitted (KT=F) or no conveyor belt.
With MDL: select the minimum operating speed
If MDL is fitted, BL ≥ 20KT; Alteration of parameter KT results in automatic assignment of BL=20KT.

Remote Possible settings Standard setting Parameter


Belt Speed Related to the current
BS 2 – 250 m/min. - product
Description Models
Transit speed
In case of conveyor belt with fixed speed or models without conveyor belt, insert the real value of the product transit
All models
speed.
If KE>0 and KT=0.000 (with encoder, without MDL inverter card), the parameter is not applicable. If the MDL is fitted,
sets the real conveyor speed within the range BL - BM..

Remote Possible settings Standard setting Parameter


Belt max. sp.
BM See below - Global
Description Models
Maximum transit speed
This parameter appears only if the variable speed inverter module (MDL) is fitted (KT > 0.000) or an encoder is
connected (KE>0). In case an encoder is fitted instead of the MDL, the range is BL – 250 m/min.
BL ≤ BM ≤ (MI x KT) All models,
except THS/G
The parameter is not applicable in case of fixed-speed or no conveyor belt.
Variable-speed conveyor belt: select the maximum operating speed.
If the inverter is fitted, BM ≤ MI x KT ; Alteration of parameter KT or MI results in automatic assignment of BM= MI x
KT

Ejection time menu

Remote Possible settings Standard setting Parameter


Alarm relay time
AT 0 – 20 s / A A Global
Description Models
Alarm relay activation time
When set to A (automatic) the alarm relay is activated only for the time that the signal exceeds the alarm threshold. All models
If AT>0, the alarm relay is activated for the time that the signal exceeds the alarm threshold plus AT seconds.
If AT=0 the relay is not activated.

Remote Possible settings Standard setting Parameter


Ej. relay time 1 – 3000
ET hundredths of a second
- Global
Description Models
Ejection relay activation time
If EM=S this parameter represents the ejection relay activation time after an alarm. All models
If EM=F: this parameter represents the minimum ejection relay activation time, because the relay is activated for a
length of time given by the sum of the alarm time (the transit time of the metal mass through the probe) and time ET.

Remote Possible settings Standard setting Parameter


Confirm time 0 – 6000
CT hundredths of a second
- Global
Description Models
Confirm ejection time
With the Ejection Confirmation activated (CE=ON), after activation of the ejection relay the status of the “eject
confirmation” input is checked; if, after time CT, the input has not been activated (see parameter IE), the “fault
ejection” status is activated (fault relay, visible and audible indicators activated, message “Fault: ejection” displayed). All models
This may be caused by the failure to move a contaminated pack into a storage container. The “fault ejection” status is
activated if the input remains active for a few seconds – e.g. if a pack is jammed. The alarm is reset by pressing the
key.
68 THS – FI022GB2K8v3 --- V - MAINTENANCE

Counters menu
Remote Possible settings Standard setting Parameter
Cur. alar. Related to the current
CA 0 – 999999999 - product
Description Models
Number of alarms caused by the current product (since last reset)
All models
To reset this counter select the parameter, press the key and press the (increase) key; in remote
programming execute the CR command.

Remote Possible settings Standard setting Parameter


Cur. obj. Related to the current
CO 0 – 999999999 - product
Description Models
Number of transits of packs of current product (since last reset)
This count is performed through the photocell input. All models
To reset this counter select the parameter, press the key and press the (increase) key; in remote
programming execute the CR command.

Remote Possible settings Standard setting Parameter


Alar. cnt.
AC 0 – 999999999 - Global
Description Models
Number of alarms (since last reset)
This counter increases with all products. To reset this counter select the parameter, press the key and press the All models
(increase) key; in remote programming execute the AR command.

Remote Possible settings Standard setting Parameter


Obj. cnt.
OC 0 – 999999999 - Global
Description Models
Number of packs (since last reset)
This count is performed through the photocell input. All models
This counter increases with all products. To reset this counter select the parameter, press the key and press the
(increase) key; in remote programming execute the OR command.

Barcode reader menu


This menu is available only with barcode reader fitted and BE parameter set to the right values.

Remote Possible settings Standard setting Parameter


Code
CD See below - Global
Description Models
Selection of type of coding
type of code recognised by the bar-code reader. Possible settings: All models,
CODE 2/5 INTER, CODE 39 STAND, CODE 39 FULL, CODE 32, C.I.P., CODEBAR, CODE 128, EAN 128, CODE except THS/G
93 STAND, EAN13, EAN8, UPCA, UPCE, EAN13 ADD ON 2, EAN8 ADD ON 2, UPCA ADD ON 2, UPCE ADD ON
2, EAN13 ADD ON 5, EAN8 ADD ON 5, UPCA ADD ON 5, UPCE ADD ON 5, PLESSEY, ALL EAN UPC

Remote Possible settings Standard setting Parameter


Code length
CL 1 – 48 / A A Global
Description Models
Number of characters in the code All models,
except THS/G
A = Automatic

Remote Possible settings Standard setting Parameter


Decodes number
DN 1 - 10 - Global
Description Models
Number of decodings with same result All models,
except THS/G
Number of consecutive identical readings for a code to be considered valid.
THS – FI022GB2K8v3 --- V - MAINTENANCE 69

Remote Possible settings Standard setting Parameter


Window start
WS 1 - 48 - Global
Description Models
First of product identification characters
First character of series used to identify the product within the code.
All models,
Example: If on an EAN13 code (code length 13 digits) we want to ignore the first 2 digits, except THS/G
we must set WS=3 and WE=13. In this case code 7004040090011 is considered the same
of code 8004040090011.

Remote Possible settings Standard setting Parameter


Window end
WE 1 - 48 - Global
Description Models
Last of product identification characters
Last character of series used to identify the product within the code.
All models,
Example: If on an EAN13 code (code length 13 digits) we want to ignore the last 2 digits, except THS/G
we must set WS=1 and WE=11. In this case code 8004040090011 is considered the same
of code 8004040090022.

Remote Possible settings Standard setting Parameter


Learn code Related to the current
LC ON / OFF OFF product
Description Models
Activation of code/product association phase
Command which allows a code to be associated with a product. When activated (LC=ON), the message “Pass Code”
appears on the display. After the barcode is passed in front of the reader, the message “ENTER to confirm” and the All models,
except THS/G
code read both appear on the display. Press to associate the code read with the current product, press key
to cancel the operation. if one of the arrow keys is pressed, a new request to pass the barcode in front of the reader
is made.

Remote Possible settings Standard setting Parameter


Barc-MD dist.
BD 300 – 5000 mm - Global
Description Models
Distance between reading point and antenna
The reader is mounted upstream of the probe in order to read a code printed on the package. If the code is
recognised, the reader sends a command to the metal detector to select the relevant product type. The time required
by the THS to process the barcode is usually insignificant, but becomes important if the band is changed due to a
modification in the type of product. When the metal detector receives the signal to change product type, an internal
adjustment procedure is activated the length of which determines the minimum distance between two packages with
different codes, that is to say containing different products.

Dp Dp

S S
BR
BR

N N

Dsbr L Dsbr L

All models,
Other THS models and THS/3F without except THS/G
THS/3F with change of band (BA parameter)
Model / Event change of band (BA parameter) between one
between one product and the other
product and the other
Distance
between the Dp ≥ L + 3000 mm Dp ≥ L + 300 mm
packs
Distance
between the
barcode reader Dsbr ≥ 3000 mm Dsbr ≥ 300 mm
and the THS
probe

S probe/electronics unit of the metal detector L length of probe


N conveyor belt Dsbr Distance THS probe-barcode reader
BR Barcode reader Dp Distance between packs of different products
70 THS – FI022GB2K8v3 --- V - MAINTENANCE

Remote Possible settings Standard setting Parameter


No code eject
NE ON / OFF OFF Global
Description Models
Ejection of packs with wrong code
When activated, the packages without barcodes or with invalid barcodes are ejected. If deactivated, there is no
action. This command is available only if the barcode reader function is enabled. All models,
except THS/G
Note: In order to function, a photocell for synchronisation of the packs must be installed.
This photocell can be installed before or after the THS probe; HOWEVER, IT MUST BE
INSTALLED AFTER THE BARCODE READER

THS Configuration menu


Remote Possible settings Standard setting Parameter
Line ID
ID 1000 - 9999 9999 Global
Description Models
ID of individual metal detector in network of devices linked via RS485 All models
When connected via RS485, on each metal detector must be set a different value of ID. Maximum of units: 32.

Remote Possible settings Standard setting Parameter


Operator access
OA ON / OFF ON Global
Description Models
Operator access to sensitivity setting All models
If OA is set to ON the operator can change the sensitivity.

Remote Possible settings Standard setting Parameter


Sound
SO ON / OFF ON Global
Description Models
Activation of the built-in buzzer All models

Remote Possible settings Standard setting Parameter


TP follower
FO ON / OFF OFF Global
Description Models
Automatic adjustment of variations in the characteristics of the product All models,
If activated, in case of product with chemical-physical characteristics which can vary gradually with time, the detector except THS/MN
automatically determines the best point of operation and varies the TP parameter accordingly.

Remote Possible settings Standard setting Parameter


Language
LG See below - Global
Description Models
Language for messages
The last character of the software versione indicates the group of THSVxxxa GB / D / F / I
selectable languages, following the table beside, where the THSVxxxb GB / D / NL / S All models
International Codes are used to identify each language. THSVxxxc GB / P / E / JP
THSVxxxd GB / D / F / H

Remote Possible settings Standard setting Parameter


Inhib. time 0 – 3000
IN hundredths of a second
0 Global
Description Models
Inhibition time
Inibiths the metal detector alarm for a certain time. All models
If KT=0.000 (MDL or MDT not fitted), the time refers to the activation of the “Inhibition input”. If KT≠0.000, the time
refers to the conveyor startup.
THS – FI022GB2K8v3 --- V - MAINTENANCE 71

Remote Possible settings Standard setting Parameter


Barcode enab.
BE 6 alphanum. characters - Global
Description Models
Enabling code for operation with bar-code reader All models,
6-character code which enables the THS to work with the bar-code reader: this is supplied by CEIA on delivery of an except THS/G
upgrade kit.

Remote Possible settings Standard setting Parameter


Phcell position
PH IN / OUT - Global
Description Models
Position of the photocell relative to the probe All models
IN: photocell located at the entrance to the probe; OUT: photocell located at exit of the probe.

Remote Possible settings Standard setting Parameter


Phcell-MD dist.
PD 0 – 2000 mm - Global
Description Models
Distance between metal detector and photocell All models
The distance must be measured from the center of the photocell to the side of the probe.

Remote Possible settings Standard setting Parameter


K trans.
KT 0.000 – 9.999 / F - Global
Description Models
Transmission constant
KT= (transit speed)/(motor frequency) ; KT=0.000: no inverter
All models,
Note: when the value of KT is altered, parameters BL and BM are automatically set to nominal
except THS/G
values 20 x KT and MI x KT respectively. BL and BM can nevertheless be altered manually as
well.
Parameter KT must be set to “F” if the system configuration includes an MDT card.

Remote Possible settings Standard setting Parameter


K encoder
KE 0 – 1000 pulses / revol. 0 Global
Description Models
Encoder constant All models,
except THS/G
Number of pulses per revolution. If set to 0 the encoder is not present.

Remote Possible settings Standard setting Parameter


Diameter
DI 10 – 250 mm - Global
Description Models
Diameter of encoder roller All models,
except THS/G
Diameter of encoder roller. Correlated parameter: K encoder.

Remote Possible settings Standard setting Parameter


TP adjustment
TA 0 – 1799 - Global
Description Models
Correction of the received signal analysis parameter All models,
This parameter is specific to each device. This parameter must be automatically set up using the TL parameter in except THS/MN
case the SCD card is replaced.

Remote Possible settings Standard setting Parameter


TA autolearn
TL ON / OFF - Global
Description Models
Autolearn of parameter TA
Select ON to activate the autolearn procedure (see TA parameter) and exit from programming. All models,
except THS/MN
Note: TL=OFF automatically at the end of procedure. See paragraph “Replacement of SCD card

72 THS – FI022GB2K8v3 --- V - MAINTENANCE

Remote Possible settings Standard setting Parameter


Transmission
TX ON / OFF ON Global
Description Models
Enabling of the transmitter
All models,
If set to OFF it is possible to understand if a noise is electrical or mechanical. Refers to the Instructions manual.
except THS/MN
When TX=OFF the THS does not detect metals. The parameter is automatically set to ON if the THS is switched off
and on again.

Remote Possible settings Standard setting Parameter


TX channel
CH 1/2 1 Global
Description Models
Transmission channel All models,
Selection of different channels on adjacent detectors for automatic synchronisation. This parameter is not available except THS/MN
on some models.

Remote Possible settings Standard setting Parameter


Display contrast
DC 0 – 50 0 Global
Description Models
Display contrast All models
Display contrast can vary with changes in environmental temperature.

Remote Possible settings Standard setting Parameter


Time
TM HH:MM - Global
Description Models
Current time All models
HH = Hours; MM = Minutes. In remote programming #TM=HH:MM

Date settings menu

Remote Possible settings Standard setting Parameter


Year Last two figures
- of the year
- Global
Description Models
Year All models
For remote programming, see parameter DA.

Remote Possible settings Standard setting Parameter


Month
- 1 - 12 - Global
Description Models
Month All models
For remote programming, see parameter DA.

Remote Possible settings Standard setting Parameter


Day
- 1 - 31 - Global
Description Models
Day All models
For remote programming, see parameter DA.
THS – FI022GB2K8v3 --- V - MAINTENANCE 73

Change Password menu

Remote Possible settings Standard setting Parameter


Operator
US 6 alphanum. characters 000001 Global
Description Models
Operator’s password
All models
Select each character via the (increase) e (decrease) keys and confirm by pressing the key.

Remote Possible settings Standard setting Parameter


Supervisor
SU 6 alphanum. characters 000002 Global
Description Models
Supervisor’s Password
All models
Select each character via the (increase) e (decrease) keys and confirm by pressing the key.

Remote Possible settings Standard setting Parameter


Engineer
EG 6 alphanum. characters 000003 Global
Description Models
Engineer’s Password
All models
Select each character via the (increase) e (decrease) keys and confirm by pressing the key.

Remote Possible settings Standard setting Parameter


Q-C Op.
QU 6 alphanum. characters 000004 Global
Description Models
Quality control operator’s password
All models
Select each character via the (increase) e (decrease) keys and confirm by pressing the key.

Remote Possible settings Standard setting Parameter


Q-C Head
QH 6 alphanum. characters 000005 Global
Description Models
Head of quality control’s password
All models
Select each character via the (increase) e (decrease) keys and confirm by pressing the key.

Remote Possible settings Standard setting Parameter


Remote Prog.
RM 6 alphanum. characters 000006 Global
Description Models
Password for remote programming
All models
Select each character via the (increase) e (decrease) keys and confirm by pressing the key.

ALM Configuration menu


Remote Possible settings Standard setting Parameter
Input logic
LO P/N P Global
Description Models
Input logic
Applies to all inputs. If set to P (positive logic) all inputs are read as active when they are pulled to +V (with pull-down
All models
incorporated on card ALM).
If set to N (negative logic) all inputs are read as active when they are pulled to -V (with pull-up incorporated on card
ALM).

Remote Possible settings Standard setting Parameter


BIN_FULL input
IL NC / NO NO Global
Description Models
Type of device connected to the “BIN_FULL” input
NC: Normally Closed; NO: Normally Open All models
If set to NO the Metal Detector gives an alarm when the BIN_FULL input is closed.
If set to NC the alarm is given when the input is open.
74 THS – FI022GB2K8v3 --- V - MAINTENANCE

Remote Possible settings Standard setting Parameter


BIN_ABS input
IA NC / NO NO Global
Description Models
Type of device connected to the “BIN_ABSENT” input
NC: Normally Closed; NO: Normally Open. All models
If set to NO the Metal Detector gives an alarm when the BIN_ABSENT input is closed.
If set to NC the alarm is given when the input is open.

Remote Possible settings Standard setting Parameter


EJ_CONF input
IE NC / NO NO Global
Description Models
Type of device connected to “Ejection confirmation” input
NC: Normally Closed; NO: Normally Open All models
If set to NO the Metal Detector read an “Ejection confirmation” when the EJ_CONF input is closed. If set to NC the
confirmation is given when the input is open.

Remote Possible settings Standard setting Parameter


PHOTO input
IP NC / NO NO Global
Description Models
Type of device connected to the “Photocell” input
NC: Normally Closed; NO: Normally Open All models
If set to NO the Metal Detector read the passage of a pack when the photocell input is closed. If set to NC the
passage is read when the input is open.

Remote Possible settings Standard setting Parameter


FOLL_CONV. input
IW NC / NO NO Global
Description Models
Type of device connected to the "FOLL_CONV" input
NC: Normally Closed; NO: Normally Open All models
If set to NO the Metal Detector stops when the FOLL_CONV input is open.
If set to NC the stop is happening when the input is closed.

Remote Possible settings Standard setting Parameter


LOW_PRESS. input
I1 NC / NO NO Global
Description Models
Type of device connected to the "LOW_PRESSURE" input
NC: Normally Closed; NO: Normally Open All models
If set to NO the Metal Detector gives an alarm when the LOW_PRESSURE input is closed.
If set to NC the alarm is given when the input is open.

Remote Possible settings Standard setting Parameter


PHOTO Alarm
PA ON / OFF ON Global
Description Models
Enabling of photocell alarm
If set to ON, in case of photocell fault (continuously activated), the system goes into malfunction mode. If set to OFF,
the system does not go into malfunction mode.
If the photocell is in a continuously active state for a long period, this is interpreted as a malfunction of the sensor by
the self-diagnosis system. There are many possible causes (wrong position, short-circuited wiring etc.)
All models
On systems without encoder or with the Control Power Box, it is the installer’s and operator’s
responsibility to ensure that material does not remain in front of the photocell when the belt is
stopped: if it does, the photocell will be continuously active even though it is not malfunctioning. If
the foregoing situation can not be avoided, it is advisable to disable photocell self-diagnosis.

Remote Possible settings Standard setting Parameter


Conf. Ejec. Al.
CE ON / OFF OFF Global
Description Models
Enabling of “Confirm ejection ” alarm
If set to OFF, the confirm ejection is deactivated.
If set to ON, after activation of the ejection relay, the status of the “confirm ejection” input is checked; if, after time CT All models
(hundredths of a second), the input has not been activated (see parameter IE), the “fault ejection” is activated. This
may be caused by the failure to move a contaminated pack into a storage container. The fault relay is activated if the
input remains active for a few seconds – e.g. a package is jammed. The alarm is reset by pressing the key.
THS – FI022GB2K8v3 --- V - MAINTENANCE 75

Remote Possible settings Standard setting Parameter


Bin.Full al.
LF ON / OFF OFF Global
Description Models
Enabling of “BIN_FULL” alarm
If the input remains active for more than 5 seconds, the malfunction signal is activated. All models
The alarm is reset by pressing the key.

Remote Possible settings Standard setting Parameter


Bin Absent alarm
LA ON / OFF OFF Global
Description Models
Enabling of “BIN_ABS” alarm
If the input remains active for more than 5 seconds, the malfunction signal is activated. All models
The alarm is reset by pressing the key.

Remote Possible settings Standard setting Parameter


Air pressure al.
AP ON / OFF OFF Global
Description Models
Alarm in case of insufficient air pressure
All models
OFF: LOW_PRESS input ineffective; ON: if the LOW_PRESS input is active the system goes into “Low Pressure”
fault mode.

Remote Possible settings Standard setting Parameter


Motor alarm
MA ON / OFF - Global
Description Models
Motor overheating alarm All models,
OFF: alarm disabled (configuration without motor driving or with MDL card) except THS/G
ON: Version with MDT card: only alarm if the thermic protection sensor, connected to J25 of MDT card, is active

Remote Possible settings Standard setting Parameter


Ejection
EJ ON / OFF ON Global
Description Models
Ejection All models
Enabling/disabling of ejection, used only for servicing purposes.

Remote Possible settings Standard setting Parameter


Ejec. queue reset
QR ON / OFF ON Global
Description Models
Reset of the ejection queue
OFF: ejection queue is never reset. If the belt stops and a contaminated package is placed between the antenna and All models,
the ejector, the package is ejected when the belt is started again; except THS/G
ON: if there is an MDL card or an encoder, the ejection queue is reset when the belt stops, whether by command or
as the result of a fault.

Remote Possible settings Standard setting Parameter


Fault relay
FR ON / OFF OFF Global
Description Models
Enabling of fault relay All models
If FR=ON, and in case of fault the “fault relay” and flashing indicator, connected to J22 pin 8 and 9, are activated.

Remote Possible settings Standard setting Parameter


DTR protocol
DT N/H N Global
Description Models
DTR protocol
Use of DTR line to communicate with printer. All models
N = line not used; H = line used, handshake mode, high active line.
The metal detector stop sending data to the serial port, in case the line is not pulled up.
76 THS – FI022GB2K8v3 --- V - MAINTENANCE

Remote Possible settings Standard setting Parameter


Enable UP/DOWN
UD ON / OFF - Global
Description Models
Enabling of arrow keys to change the speed All models,
Enables the motor speed command from the power unit control panel. excepts THS/G
If MM=ON the changing of the speed is not activated, whatever is the value of UD.

Remote Possible settings Standard setting Parameter


Manual movement
MM ON / OFF OFF Global
Description Models
Enabling of manual movement of the belt
Only for models with
ON: if the motor is off, pressing keys and moves the motor forwards or backwards at speed BS. During Conveyor Control System
movement the alarm and the ejection are disabled.

Remote Possible settings Standard setting Parameter


PREC_CONV Enab.
PC ON / OFF OFF Global
Description Models
Enable “preceding conveyor” relay Only for models with
ON: the relay is activated when the motor is running; Conveyor Control System
OFF: the relay is deactivated

Remote Possible settings Standard setting Parameter


FOLL CONV Enab.
FC ON / OFF OFF Global
Description Models
Enable “following conveyor” input
ON: with MDL or MDT, only if the following conveyor belt is running the THS belt is activated;
with KT=0.000 (no MDL or MDT fitted) and KE=0 (no encoder fitted) or with THS/G if FC=ON, the metal detector All models
stops incrementing the delay counter in case the “following conveyor” input is not active. This functionality can be
used for example on a pipeline to stop the delay counting in case the pump that runs the liquid is stopped.
OFF: the motor can be activated whatever is the status of following conveyor input.

Remote Possible settings Standard setting Parameter


Autom. restart
RE ON / OFF OFF Global
Description Models
Belt restart if there is “following conveyor” input reactivation
If FC= OFF, the parameter has no effect; If FC=ON:
- RE=OFF: if the belt is stopped by the “following conveyor” input deactivation, when the FOLL-CONV input
reactivated the THS belt must be restarted manually. All models,
- RE=ON: if the belt is stopped by the “following conveyor” input deactivation, when the FOLL-CONV input excepts THS/G
reactivates the THS belt restarts automatically unless the STOP key has been pressed in the meantime.

When the belt is stopped because of the following conveyor, the light flashes.

Remote Possible settings Standard setting Parameter


Stop on fault
SF ON / OFF OFF Global
Description Models
Belt stop in case of fault All models,
excepts THS/G
SF=ON: if there is a fault in the THS, the belt stops; SF=OFF: if there is a fault the belt continues to run.

Remote Possible settings Standard setting Parameter


Stop Time
ST 0 – 99 min 0 Global
Description Models
Belt auto-stop time All models,
This functionality is available only if a photocell is fitted: if no passages are detected for a time ST, the conveyor belt excepts THS/G
stops automatically (No signal is given).
THS – FI022GB2K8v3 --- V - MAINTENANCE 77

Remote Possible settings Standard setting Parameter


Motor current
CU 0.000 – 5.000 A - Global
Description Models
Nominal motor current
Set the nominal value for the motor connected to the MDL (this parameter is only significant on the version with MDL All models,
card). except THS/G
If the current drained to the motor is greater than CU, the belt stops and the “motor alarm” fault is given, both by the
display and light. Usually CU must be set to the nominal current of the motor.

Remote Possible settings Standard setting Parameter


Max Inv. freq.
MI 60 – 100 - Global
Description Models
Maximum inverter operating frequency All models,
Sets the maximum nominal value of the motor operating frequency (this parameter is only significant on the version except THS/G
with MDL card)

Remote Possible settings Standard setting Parameter


Lamp blinking
LB ON / OFF OFF Global
Description Models
Lamp flash option
All models
OFF: when activated, the beacon connected to J22 pins 8 and 9, or the “test relay” are constantly activated.
ON: when activated, the beacon or the “test relay” are flashing (interval = 1s)

I/O Status menu


Remote Possible settings Standard setting Parameter
-
- H/L - Global
Description Models
Display shows list of input and output lines with indication of their status
Example of display: FAULT relay H
EJECT relay L All models
The inputs and outputs are shown on the display in real time. ALARM relay L
PREC_CONV relay H

MD Test menu
Remote Possible settings Standard setting Parameter
FE test
- - - Global
Description Models
Activation of the test for the standard iron reference sample
All models
Test procedure: see “Periodic test management” section of the Instructions manual.

Remote Possible settings Standard setting Parameter


SS test
- - - Global
Description Models
Activation of the test for the reference sample in stainless steel All models,
Test procedure: see “Periodic test management” section of the Instructions manual. except THS/MN

Remote Possible settings Standard setting Parameter


Non_FE test
- - - Global
Description Models
Activation of the test for the reference sample in diamagnetic metal All models,
Test procedure: see “Periodic test management” section of the Instructions manual. except THS/MN
78 THS – FI022GB2K8v3 --- V - MAINTENANCE

Print menu

Remote Possible settings Standard setting Parameter


Print parameters
PT - - Global
Description Models
Print list of parameters with their current settings All models
The data are sent to the RS232 interface, if the #PT<ENTER>
command is activated by local programming or
via RS232. PN P2
The data are sent to the RS485 if the command is SE 203
request via RS485.
TP 0
Example:
BA MEDIUM
AM 2
EM B
ED 500
RD OFF
BS 250
...
JR ON
MR ON
TR ON
RT 0:10
TM 2:58
DA 01/03/00
SN 999999
PV THS/3F V3.390a - ALM V1.060
FIN 013A---a - 001A----

#
Remote Possible settings Standard setting Parameter
Print buffer
PB - - Global
Description Models
Print list of memorised events
The data are sent to the RS232
interface, if the command is activated QUALITY REPORT 28/02/00 - 20:14:00
by local programming or via RS232. Serial number 999999
The data are sent to the RS485 if the Line ID 1013
command is request via RS485.
>Change product 28/02/00 - 20:13:13
The metal detector stores up to 1000 P.Name P2
events. An event could be a certain Operator ENGINEER
parameter modification (SE, TP ecc.),
>Test Metal Detector 28/02/00 - 20:13:38
a test result, an ejection (the result of P.Name P2
the ejection is memorized). Fe diameter 1.0
Test OK YES All models
Operator Q-C OPERATOR
Example:
>Test Metal Detector 28/02/00 - 20:13:49
P.Name P2
SS diameter 1.5
Test OK NO
Operator Q-C OPERATOR
>Statistics
END QUALITY REPORT
--------------------------------------------
THS – FI022GB2K8v3 --- V - MAINTENANCE 79

Print report menu

Remote Possible settings Standard setting Parameter


Ejection report
JR ON / OFF ON Global
Description Models
Include Ejections in the personalized report All models

Remote Possible settings Standard setting Parameter


Param. mod. rep.
MR ON / OFF ON Global
Description Models
Include Parameters modifications in the personalized report All models

Remote Possible settings Standard setting Parameter


Test report
TR ON / OFF ON Global
Description Models
Include Quality Control Tests results in the personalized report All models

Remote Possible settings Standard setting Parameter


Recent time
RT 00:00 – 23:59 1:00 Global
Description Models
Choose the time of the personalized report
All models
Events printed on the Quality report (PR) are referred to this parameter. With RT = 2.00, for example, the printed
report refers to the last 2 hours of working.

Remote Possible settings Standard setting Parameter


Print Report
PR ON / OFF OFF Global
Description Models
Print personalized report
The data are sent to the RS232
interface, if the command is QUALITY REPORT 28/02/00 - 20:14:00
activated by local programming or Serial number 999999
via RS232. Line ID 1013
The data are sent to the RS485 if
>Change product 28/02/00 - 20:13:13
the command is request via P.Name P2
RS485. Operator ENGINEER
The printer report is filtered
>Test Metal Detector 28/02/00 - 20:13:38
according to JR, MR, TR and RT P.Name P2
parameters. Fe diameter 1.0 All models
Test OK YES
Operator Q-C OPERATOR
Example:
>Test Metal Detector 28/02/00 - 20:13:49
P.Name P2
SS diameter 1.5
Test OK NO
Operator Q-C OPERATOR
>Statistics
END QUALITY REPORT
--------------------------------------------
80 THS – FI022GB2K8v3 --- V - MAINTENANCE

Quality Control menu (Q.C.Report)


Remote Possible settings Standard setting Parameter
Print period
PP 00:00 – 23:59 00:00 Global
Description Models
Frequency of automatic printing of personalised report
If PP=00:00 the automatic printing
is disabled. QUALITY REPORT 28/02/00 - 20:13:00
If PP>00:00, an automatic print of Serial number 999999
the report is automatically sent to Line ID 1013
the RS232. The printed report
>Change parameter 28/02/00 - 20:12:18
includes the events selected with Sensitivity 202 -> 203
JR, MR, TR, and a final statistic. P.Name P2
The interval which the data refers Operator ENGINEER
to is related to the last automatic >Ejection 28/02/00 - 20:12:31
print. P.Name P2
For example, setting PP=01.00, Ejection OK
each hour are printed the data >Ejection 28/02/00 - 20:12:44
related to the last hour. P.Name P1
All models
Ejection OK
>Change product 28/02/00 - 20:12:45
P.Name P1
Operator ENGINEER
>Ejection 28/02/00 - 20:12:49
P.Name P1
Ejection OK

>Statistics
Example of personalized report: P.Name P2
n. allarms 1
n. objects 8
Alarm rate 12.50 %
END QUALITY REPORT
-------------------------------------------

Remote Possible settings Standard setting Parameter


Test period
TE 00:00 – 23:59 00:00 Global
Description Models
Pre-defined interval between Quality Control tests All models
If TE=00:00 the tests are disabled. If TE>00:00 a test is requested every TE interval.

Remote Possible settings Standard setting Parameter


Test delay
TD 00:00 – TE 00:00 Global
Description Models
Waiting time for test to be carried out
Time within the operator should carry out test every TE interval. All models
Note: the need to carry out a test is signalled on the display.

Remote Possible settings Standard setting Parameter


Fault time out
FT ON / OFF ON Global
Description Models
Activation of fault status if maximum time for test expires without performing the test All models

Test Sensitivity menu (Test sensitiv.)

Remote Possible settings Standard setting Parameter


FE diameter FD 0.0 – 25.0 - Global
Description Models
Diameter of iron sample sphere used to perform the test
Datum that must be set for inclusion in the test report. All models
Note: The value is printed in the Q.C. report and does not effect the sensitivity.
THS – FI022GB2K8v3 --- V - MAINTENANCE 81

Remote Possible settings Standard setting Parameter


SS diameter SD 0.0 – 25.0 - Global
Description Models
Minimum detectable diameter for stainless steel sample sphere
Datum that must be set for inclusion in the test report. All models,
except THS/MN
Note: The value is printed in the Q.C. report and does not effect the sensitivity.

Remote Possible settings Standard setting Parameter


Non_FE diameter ND 0.0 – 25.0 - Global
Description Models
Minimum detectable diameter for diamagnetic metal sample sphere
Datum that must be set for inclusion in the test report. All models,
except THS/MN
Note: The value is printed in the Q.C. report and does not effect the sensitivity.

Commands accessible only in Remote Programming


Remote Possible settings Standard setting Parameter
- PE - - Global
Description Models
Exit from remote programming All models
In case the remote programming is not used for 3 minutes, the PE command is sent automatically by the THS

Remote Possible settings Standard setting Parameter


- PV - - Global
Description Models
Software version
Provides the software version loaded on the THS. All models
#PV <ENTER>
THS/STD V3.390a – ALM V1.060

Remote Possible settings Standard setting Parameter


- HE - - Global
Description Models
Help All models
Provides the list of commands available, their meanings and their current settings

Remote Possible settings Standard setting Parameter


- DP - - Global
Description Models
Cancellation of all products
All models
The command delete ALL products defined by the user, leaving only the “Default” product.

Remote Possible settings Standard setting Parameter


- DA DD/MM/YY - Global
Description Models
Current date insertion
DD = Day, MM = Month All models
#DA=18/02/04 <ENTER>
YY = last two figures of the year #
82 THS – FI022GB2K8v3 --- V - MAINTENANCE

Remote Possible settings Standard setting Parameter


Related to the current
- CR - - product
Description Models
Reset of the current product counters All models
Resets the alarm and object counters for the current product.

Remote Possible settings Standard setting Parameter


- AR - - Global
Description Models
Reset total alarm counter All models

Remote Possible settings Standard setting Parameter


- OR - - Global
Description Models
Reset total pack transit counter All models

Remote programming via serial link


Programming is carried out through a remote computer fitted with an RS232 or RS485 interface, using a standard
communications program (e.g. Windows™ Terminal) or the CEIA MDScope program, available on request.

Communication parameter settings:


• Baud rate = 9600 bit/s (to be set on the computer)
• 8 data bits
• NO parity
• 1 stop bit
• no communication protocol
• CR -> CR+LF
• Local echo = OFF
• Terminal: VT 100 (ANSI)

Entering remote programming


Connecting to a metal detector (via RS 232)
- Run the communications program
(password) <ENTER>
- Enter the password and key ENTER. The command #
prompt will appear

Note: each password accesses programming at the appropriate level (operator, supervisor, …)

Long-distance connection to a single metal detector (via RS 485)


Identical to the above.

Network connection (via RS 485)


Using RS 485 transmission, several metal detectors can be connected in a network. In this case, the PC acts as master
and the metal detectors as slaves. So as to allow each individual metal detector to be identified, the following steps must
be taken:
Set a password on each metal detector (N.B.: the password can be the same if so desired).
Set a different Line ID identification code for each metal detector (line ID parameter ID=1001, 1002, 1003, .).
THS – FI022GB2K8v3 --- V - MAINTENANCE 83

Connecting to a metal detector in a network


- Run the communications program
- Execute the PE command #PE <ENTER>*
(LineID)(password)<ENTER>
- On the same line, enter the ID code and password (Head of
#
Quality Control) and key ENTER. The command prompt
will appear

* ENTER = ASCII code 013 Note: LineID always > 1000

3.13.3 - Displaying a parameter setting


Type the code of the parameter and press ENTER: the parameter #SE<ENTER>
setting will appear next to it. #SE 30

3.13.4 - Changing a parameter setting


Type the code of the parameter followed by the “=” character or a #SE=35<ENTER>
space, the new value and ENTER. #
#SE 35<ENTER>
#

3.13.5 - Executing a function


Key in the parameter code and press ENTER. #PR<ENTER>
#
84 THS – FI022GB2K8v3 --- V - MAINTENANCE

Maintenance

Any maintenance or repair of the device while open and energised should be avoided, and in any case should
only be carried out by trained personnel who are fully aware of the risks which the operation entails, following
the instructions given in the “Maintenance” section.

When the mains is disconnected using the main switch S1 of the Conveyor Control System, the power supply
section is deactivated, but the contacts which are connected permanently to the mains, e.g. the relay outputs,
remain energised.
N.B. When the I2 service switch is turned off, most components remain energised.

S1

I2

fig. V -1a fig. V -1b

Removal of the safety protections fitted to the device is strictly prohibited.

Periodic maintenance
Table V-1
Operation Period Operator
detection check • beginning of each shift • Quality-control operator
• on changing product type • Head of quality control
• periodically
cleaning of conveyor belt beginning of each shift Operator

belt tension adjustment 6 months or when necessary maintenance personnel

locking of terminals used to connect 6 months maintenance personnel


control panels
Cleaning of barcode reader (if fitted) 6 months or when necessary Operator
with a non-abrasive cloth dampened N.B.: clean when the device is
with alcohol switched off

The operator must monitor the condition of the system and its suitability for use, and consult the maintenance
personnel if necessary.
THS – FI022GB2K8v3 --- V - MAINTENANCE 85

Self-diagnosis
The internal diagnostic system monitors the operational status of the metal detector. If a fault is detected, the following
are activated in addition to a message on the display:
• the illuminating alarm indicators
• the buzzer (if activated)
• the fault relay (if Fault relays parameter is ON)
• flashing light (if Fault relays parameter is ON)

Fault status can only be reset by eliminating the cause of the fault.

Table V-2
Message Probable cause Action
Test time out Time-out for pre-programmed Carry out the test
test.
Fault: power Power-supply section faulty Contact service technician

Fault: probe Antenna connection broken Contact service technician

Fault: ejection ** Ejection of material not • Check that the ejection times are correct.
carried out • Check that the ejector is not blocked
• Check photocell operation (positioning, connections
etc.)
• Check the Confirm Ejection input connections
When the cause of the fault has been eliminated, press the
E key to reset the alarm status.
Bin full Storage container full Empty it
Press E key to reset the alarm status
Fault: communication Fault in communication Check that the power-supply voltage is stable and
between SCD and ALM cards corresponds to the values on the identification plate.
Check the wiring
If the wiring is correct, replace the cards
Fault: motor alarm Overloading of the belt motor Remove the cause of overloading and press E key.

("motor alarm" indicator Wrong setting of CU Set a proper value of CU parameter and press E key.
activated) parameter
Fault: air pressure Compressed air pressure too Check the compressed air connection.
low When the cause of the fault has been eliminated, press the
E key
Photocell fault *** Photocell malfunction or pack • check there is no pack stuck in front of the photocell
stuck in front of photocell • check the photocell connections
• Check the positions of the photocell and the
retroreflector
• replace the photocell
When the cause of the fault has been eliminated, press the
E key to reset the alarm status ****
Memory card not Memory faulty or absent Check presence and connections of the SPM external
installed (THS system memory card (see para. "Replacement of SCD card"
not operative)
Compatibility error SCD card incompatible with Use compatible SCD card (ask service personnel)
the data stored in the SPM
memory card
*Enabled by the Fault relays parameter

**Enabled by the Ejection confirmation parameter

*** Enable via the PHOTO Alarm parameter

**** The self-diagnosis message may appear:


- in the case of a conveyor belt without encoder or with Power Control Box, with the belt stopped or moving
- in the case of a conveyor belt without encoder or with Conveyor Control System, with the belt moving

The system is not designed to signal a pack which is stuck for some reason in front of the photocell. For this
reason, when the system can detect whether or not the conveyor belt is moving (i.e. when it is equipped with an
encoder or with the Conveyor Control System power supply unit), the self-diagnosis function gives an alarm only if
the photocell is in a state of malfunction when the belt is moving.
On systems without encoder or with the Control Power Box, it is the installer’s and operator’s responsibility to
ensure that material does not remain in front of the photocell when the belt is stopped: if it does, the photocell
will be continuously active even though it is not malfunctioning. If the foregoing situation can not be avoided, it is
advisable to disable photocell self-diagnosis (Parameter PA)
86 THS – FI022GB2K8v3 --- V - MAINTENANCE

Storage
Store the system in its original packaging, or in a way that protects it adequately from atmospheric agents or other
possible causes of damage (moving objects, weights, solvents etc.).

Storage temperature (Regulation EN 60204): -25°C - +55°C long-term, +70°C for 24 hours maximum.

Transport and movement of the conveyor belt

Disconnect the system from the various power sources before carrying out any movement.

Use lift trucks or sling the load-bearing structure, and ensure that the load is balanced during movement. Avoid
deforming the structure or its component parts.

Never attach lifting gear to the Metal Detector probe or the actuators.

Keep the packaging materials for possible future transport.

Fig. V-2

Adjustment of conveyor belt tension


This is carried out on the roller on the side opposite the motor roller. To adjust the belt tension, loosen screws A on both
sides by the same number of turns, so that the slack in the belt at the entrance to the probe appears as in the figure
(about 0.02 x length of the belt, s=0.02 D).

Fig. V-3a Fig. V-3b


THS – FI022GB2K8v3 --- V - MAINTENANCE 87

Replacing the belt


If the belt has to be joined, this should be done along a diagonal or, even better, in a zigzag, in order to minimise the
increase in thickness due to the joint.

Fig. V-5a : diagonal join Fig. V-5b: zigzag join

Disposal of the device and of consumables with environmental impact


For disposal follow the regulations in force in the country where the device is being used. The following components
should be taken into consideration:
Table V-3
Component Specifications
battery incorporated on card SCD Lithium 3.6V type CR1/2 AA
lubricant for motor drum EP SAE 90 oil for gears, or equivalent

Fuses
The figure shows the position and rating of the fuses fitted to the device.

Table V-4
Ref. Type Description
F1-F2 250V 10A, fast 5x20mm card power supply protection
P1 250V 3,15A fast 5x20mm upstream belt relay common contact protection
P2 250V 3,15A fast 5x20mm auxiliary relay common contact protection
P3 250V 3,15A fast 5x20mm metal detector alarm relay common contact protection
P4 250V 3,15A fast 5x20mm ejector relay common contact protection
P5 250V 3,15A fast 5x20mm malfunction relay common contact protection
F3-F4-F5 500V 10A, fast 6.3x32mm card MDT power supply protection

P1
F2
F1 P2
F3 F4 F5
P3
P4
P5

Fig V-6a - ALM and MDL card fuses Fig V-6b - MDT card fuses

Troubleshooting
Self-resetting protections
• The ALM card power supply inputs are protected by self-resetting components PTC.
• The MDL inverter card outputs are electronically protected against short circuit between two phases.
• The ALM card inputs are protected against wrong connection up to the voltages present on the card itself, with the
exception of the mains voltage.

Table V-5
88 THS – FI022GB2K8v3 --- V - MAINTENANCE

Symptom Probable cause Action


Power supply unit- Malfunction of the power supply Switch off, wait a few minutes to let any self-resetting
metal detector section components inside cool down, then switch on the system
system off again. If the problem persists, replace card ALM

Check the power supply connections


No line voltage
Check insertion of the ALM card connectors
Unstable or partial connections
Power supply unit- Malfunction of the power supply As above
metal detector section
system alternates
between on and
off
Metal detector Carry out the following operations in sequence:
does not give an
alarm in the Metal detector inhibition Set IN=0
presence of metal
masses of the Disconnect the ALM card connectors which do not link up to
same type as the Wrong detection parameters for the the power supply or probe.
reference sample current product
and of equal or Select the “Default” product and check, with the sample
greater mass provided with the device, that the detector gives an alarm.
Carry out the autolearn procedure. Check the settings of the
Product effect detection parameters (SE, TP, etc.)

SCD card malfunction Carry out the autolearn procedure.

If the procedure is not successful, replace the SCD card.


Metal detector Environmental interference Carry out the “ Checking for environmental electromagnetic
gives false alarms interference” procedure.
with no product in
transit SCD card malfunction Deactivate all electrical and mechanical devices surrounding
the detector, or move it into a place which is guaranteed free
of interference.
Disconnect the ALM card connectors which do not link up to
the power supply or probe.
If the interference signal remains the same, replace the SCD
card.

Line voltage insufficient or unstable Check.

MDT card MDT card


L1 F5 Forward / L1 F5 Forward /
L2 backward L2 backward
4 motor 4 motor
L3 F4 switching L3 F4 switching
F3 module N F3 module

STC card STC card


Keyboard and signals Sensors/Actuators Keyboard and signals Sensors/Actuators

Metal Metal
Controller Detector Controller Detector

Switch Switch
SCD card SCD card
I2 I2
L2 L2

Voltage Voltage
Switch I1 Switch I1
regulators regulators
115/230V 115/230V

Voltage Emergency Voltage Emergency


regulators switch regulators switch
ALM card ALM card

Fig. V-8a block diagram of the THS system with MDT card, Fig. V-8b block diagram of the THS system with MDT card,
230V~ power supply 400V~ power supply
THS – FI022GB2K8v3 --- V - MAINTENANCE 89

MDL card
F1 Variable
L0 frequency
4 motor
L1 3-phases
F2 generator

STC card
Keyboard and signals Sensors/Actuators

Metal
Controller Detector

Switch I2
SCD card
L2

Voltage
Switch I1
regulators
115/230V

Voltage Emergency
regulators switch
ALM card

Fig. V-8c block diagram of the THS system with MDL card

Replacing Card SCD


If the control card has to be replaced, the serial number of the device must be quoted in the order; the card will only be
able to be used with that same detector.
Procedure
• Switch off the device
• The card is attached to the detector control panel. Remove the control panel by unscrewing the fixing screws, taking
care not to pull on the internal connecting wires.
• Disconnect the card and connect the internal wires to the replacement card.
• Plug the SPM memory card from the old control card into the new one. N.B.: the memory card contains all the
device’s stored programming, product and event data.
• Reassemble the control panel.
• Switch on the detector and reset the programming.
• Carry out the TL Autolearn procedure:
• The procedure must be carried out in an interference-free environment: deactivate the THS conveyor belt and any
other power devices in the area.
• Set the parameter TL Autolearn = ON and exit from programming.
• The message “Pass” will appear on the display: press forcibly for at least a second on the probe (see figs. below –
press in the middle of the belt width at either the entrance or the exit, but NOT in the centre). In the case of
models THS/PH and THS/G, make the probe vibrate. Repeat TL autolearn for each band (BA) and for each
channel (CH).

• N.B.: in the case that the procedure is not carried out, or is carried out improperly, compensation for the products
may not be correct. As a check, select the “default” product and make some tests with the sample indicated in the
test card enclosed with this manual.
• Check that the system operates properly with all the products stored in memory.

The SCD card stores the values of all the operating parameters, including those of the power-supply and control
unit. If the power supply unit is replaced, therefore, it is not necessary to reprogram the system..
90 THS – FI022GB2K8v3 --- V - MAINTENANCE

Checking environmental electromagnetic interference


The existence of interference is indicated by false alarms or by the display of several segments on the bar-graph when
the conveyor belt is stopped and there is no product in transit:

THS/STD V3.290 THS/STD V3.290 THS/STD V3.290


Product productname Product productname Product productname

I I I I I I I I I I I I I I I I I I I I I* * * * *

Fig.V-9a. Example: signal well below Fig.V-9b. Example: signal just below Fig.V-9c Example: signal above the
the threshold level the threshold level threshold level (alarm).

For correct operation, the bar-graph indicator should not have more than THREE bars lit.
To eliminate the interference, the first thing to do is to identify whether it is electrical or magnetic:

1 Set parameter TX=OFF. . (NB: on model THS/MN, set the switch on the internal card of the probe power-supply unit to OFF)

2 If the interference remains the Examples of sources of electrical interference: electric motors, inverters, power cables, lighting
same, it is electrical
3 If the interference decreases, it Examples of sources of mechanical interference: unstable anchoring of the metal detector
is of a mechanical nature (vibrations), metal masses moving in the vicinity of the probe, intermittent loops, metal
fragments in the conveyor belt.
To increase immunity to mechanical interference, adjust the AM parameter (see paragraph “Analysis mode selection criteria” ).

To eliminate sources of interference, refer to the illustrated notes in the Installation section.
THS – FI022GB2K8v3 --- VI - APPENDICES 91

APPENDICES

DECLARATION OF CONFORMITY CE

DECLARATION OF CONFORMITY CE
DECLARATION DE CONFORMITE CE KONFORMITÄTSERKLÄRUNG CE
DECLARACION DE CONFORMIDAD CE DICHIARAZIONE DI CONFORMITÁ CE

Manufacturer CEIA S.p.A.


Fabricant / Hersteller / Fabricante / Costruttore: Zona industriale Viciomaggio 54/G 52040
Viciomaggio - Arezzo - ITALY
Declares that the product
déclare que ce produit / erklärt, daß das Produkt / declara que el producto / dichiara che il prodotto:

Product name:
Nom du produit: / Produktname: Electronic Metal Detector
Nombre del producto: / Nome: Détecteur de métaux / Elektronischer Metalldetektor
Electronic Metal Detector / Metal Detector Elettronico
all model
Model THS tous modèles/ alle Modelle
Série / Serie / Serie / Modello: todos los modelos/ tutti i modelli
conforms to the following Product Specifications
est conforme aux spécifications suivantes / folgenden Produktspezifikationen entspricht
es conforme a las siguientes especificaciones / è conforme alle seguenti specifiche di prodotto:

Safety / Sécurité / Sicherheit / Seguridad / Sicurezza: EMC


EN 55011: Group 1 - Class A
EN 61000-4-2
EN 60204 - 1 EN 61000-4-3
EN 61000-4-4
EN 61000-4-5
EN 61000-4-6
This product complies with the requirements of the Low EN 61000-4-11
Voltage Directive 73/23/EEC and following modifications ENV50204
indicated in the 93/68/EEC Directive.
Le produit ci-dessus répond aux exigences de la Directive Dieses Produkt entspricht den Anforderungen der EMC-Norm
73/23/CEE et aux modifications suivantes mentionnées dans 89/336/EEC und nachfolgender in den Normen 92/31/EEC und
la Directive 93/68/CEE concernant la basse tensions. 93/68/EEC angegebener Änderungen.
Dieses Produkt entspricht den Anforderungen an El producto indicado cumple los requisitos de la Directiva EMC
Niederspannungsgeräte gemäß der Norm 73/23/EEC und 89/336/CEE y siguientes modificaciones indicadas en las
nachfolgender, in der Norm 93/68/EEC angegebener Directivas 92/31/EEC y 93/68/EEC.
Änderungen. Il prodotto è conforme alle norme della direttiva EMC
El producto indicado cumple los requisitos de la Low Voltage 89/336/EEC e successive modifiche indicate nelle direttive
Directive 73/23/CEE y siguientes modificaciones indicadas en 92/31/EEC e 93/68/EEC.
la Directiva 93/68/EEC.
Il prodotto è conforme alle norme della direttiva 73/23/EEC e
successive modifiche indicate nella direttiva 93/68/EEC sulla
bassa tensione.

SpA

Arezzo, 2003-12-15 Person in charge Lab. EMC


Resp. Laboratoire EMC / Laborattaché EMC
Resp. Laboratorio EMC / Resp. Lab. EMC
Ing. E. Sorini
92 THS – FI022GB2K8v3 --- VI - APPENDICES

Spare parts, Options and Accessories

Ordering spare parts


When ordering spare parts please specify the following:
•company details with exact address where the parts are to go
•serial number of the device
•description of the part
•quantity ordered
•shipping method

CEIA is not responsible for any error in shipping due to incomplete and/or inaccurate orders.

When ordering any component, please indicate the serial number of the device!

THS standard model / THS/3F


Validity: revision 3.30, 09/06/2003
Spare parts
Description Quantity Code
Control panel 1 30270
SPM module 1 21853
Cable connecting the probe to the power supply unit: length 3 metres (family A) 1 18940
Cable connecting the probe to the power supply unit: length 3.5 metres (family B) 1 18941
Cable connecting the probe to the power supply unit: length 4 metres (family C, D) 1 18942
Cable connecting the probe to the power supply unit: custom length (max. 40m) 1 19992
Power supply unit with motor control - Conveyor Control System - variable speed version 1 20999
Power supply unit with motor control - Conveyor Control System - fixed-speed version 1 21000
Power supply unit without motor control - Control Power Box 1 21001
Power supply card 00208ALM 1 18939
Motor control panel - card 00208STC 1 18944
Motor control card 00208MDL 1 18943
Motor control card 00208MDT 1 19946
Remote control card 00208RCU 1 18945
Compact power supply unit without motor control 1 22626
Power supply card 00208AL_ 1 22569
Connector kit for Power supply card 00208AL_ 1 22616
Picket-Fence bar code reader (code with vertical bars) 1 17823
Step-Ladder bar code reader (code with horizontal bars) 1 18700
Options
Description Quantity Code
RS 485 interface 1 17828
Remote control module for Conveyor Control System 1 21559
Remote control module for Control Power Box 1 21560
115/230Vca Transformer Box 1 23181
400/230Vca Transformer Box 1 23182
Protection against high-pressure water cleaning 1 24775
Ethernet Module 1 29756
Accessories
Description Quantity Code
MDScope 1 26894
MDCAD 1 27185
THS REPORT 1 27184
RS232/RS485 converter 1 21540

THS /A
Validity: revision 3.300, 09/06/2003
Spare parts
Description Quantity Code
Control panel 1 16804
SPM module 1 21853
Cable connecting the probe to the power supply unit: length 3 metres 1 18940
Cable connecting the probe to the power supply unit: custom length (max. 40m) 1 19992
Power supply unit with motor control - Conveyor Control System - variable speed version 1 20999
Power supply unit with motor control - Conveyor Control System - fixed-speed version 1 21000
Power supply unit without motor control - Control Power Box 1 21001
THS – FI022GB2K8v3 --- VI - APPENDICES 93

Power supply card 00208ALM 1 18939


Motor control panel - card 00208STC 1 18944
Motor control card 00208MDL 1 18943
Motor control card 00208MDT 1 19946
Remote control card 00208RCU 1 18945
Picket-Fence bar code reader (code with vertical bars) 1 17823
Step-Ladder bar code reader (code with horizontal bars) 1 18700
Options
Description Quantity Code
RS 485 interface 1 17828
Remote control module for Conveyor Control System 1 21559
Remote control module for Control Power Box 1 21560
115/230Vca Transformer Box 1 23181
400/230Vca Transformer Box 1 23182
Protection against high-pressure water cleaning 1 24775
Ethernet Module 1 29756
Accessories
Description Quantity Code
MDScope 1 19795
MDCAD 1 27185
THS REPORT 1 27184
RS232/RS485 converter 1 21540

THS/SL
Validity: revision 3.300, 09/06/2003
Spare parts
Description Quantity Code
Control panel 1 16804
SPM module 1 21853
Cable connecting the probe to the power supply unit: length 3 metres 1 18940
Cable connecting the probe to the power supply unit: custom length (max. 40m) 1 19992
Power supply unit with motor control - Conveyor Control System - variable speed version 1 20999
Power supply unit with motor control - Conveyor Control System - fixed-speed version 1 21000
Power supply unit without motor control - Control Power Box 1 21001
Power supply card 00208ALM 1 18939
Motor control panel - card 00208STC 1 18944
Motor control card 00208MDL 1 18943
Motor control card 00208MDT 1 19946
Remote control card 00208RCU 1 18945
Compact power supply unit without motor control 1 22626
Power supply card 00208AL_ 1 22569
Connector kit for Power supply card 00208AL_ 1 22616
Picket-Fence bar code reader (code with vertical bars) 1 17823
Step-Ladder bar code reader (code with horizontal bars) 1 18700
Options
Description Quantity Code
RS 485 interface 1 17828
Remote control module for Conveyor Control System 1 21559
Remote control module for Control Power Box 1 21560
115/230Vca Transformer Box 1 23181
400/230Vca Transformer Box 1 23182
Protection against high-pressure water cleaning 1 24775
Ethernet Module 1 29756
Accessories
Description Quantity Code
MDScope 1 19795
MDCAD 1 27185
THS REPORT 1 27184
RS232/RS485 converter 1 21540

THS/MN
Validity: revision 3.30, 09/06/2003
Spare parts
Description Quantity Code
Control panel 1 30270
SPM module 1 21853
Cable connecting the probe to the power supply unit: length 3 metres 1 23395
Power supply unit with motor control - Conveyor Control System - variable speed version 1 20999
Power supply unit with motor control - Conveyor Control System - fixed-speed version 1 21000
Power supply unit without motor control - Control Power Box 1 21001
Power supply card 00208ALM 1 18939
Motor control panel - card 00208STC 1 18944
94 THS – FI022GB2K8v3 --- VI - APPENDICES

Motor control card 00208MDL 1 18943


Motor control card 00208MDT 1 19946
Remote control card 00208RCU 1 18945
Auxiliary power supply unit 1 23400
Power supply card 00208MAG 1 23240
Picket-Fence bar code reader (code with vertical bars) 1 17823
Step-Ladder bar code reader (code with horizontal bars) 1 18700
Options
Description Quantity Code
RS 485 interface 1 17828
Remote control module for Conveyor Control System 1 21559
Remote control module for Control Power Box 1 21560
115/230Vca Transformer Box 1 23181
400/230Vca Transformer Box 1 23182
Protection against high-pressure water cleaning 1 24775
Ethernet Module 1 29756
Accessories
Description Quantity Code
Set of quality control test samples (AISI 420 steel (ferromagnetic) and AISI 316 Stainless steel) High 1 18711
sensitivity
Set of quality control test samples (AISI 420 steel (ferromagnetic) and AISI 316 Stainless steel) - Low 1 22605
sensitivity
Sample with a ø 0.8 mm in AISI 420 steel sphere (ferromagnetic) 1 18124
Sample with a ø 1.0 mm in AISI 420 steel sphere (ferromagnetic) 1 18125
Sample with a ø 1.2 mm in AISI 420 steel sphere (ferromagnetic) 1 18126
Sample with a ø 1.5 mm in AISI 420 steel sphere (ferromagnetic) 1 18127
Sample with a ø 2.0 mm in AISI 420 steel sphere (ferromagnetic) 1 18128
Sample with a ø 2.5 mm in AISI 420 steel sphere (ferromagnetic) 1 18129
Sample with a ø 3.0 mm in AISI 420 steel sphere (ferromagnetic) 1 18130
Sample with a ø 3.5 mm in AISI 420 steel sphere (ferromagnetic) 1 18131
Sample with a ø 4.0 mm in AISI 420 steel sphere (ferromagnetic) 1 20251
Sample with a ø 4.5 mm in AISI 420 steel sphere (ferromagnetic) 1 20252
Sample with a ø 5.0 mm in AISI 420 steel sphere (ferromagnetic) 1 22056
Sample with a ø 5.5 mm in AISI 420 steel sphere (ferromagnetic) 1 22057
Sample with a ø 6.0 mm in AISI 420 steel sphere (ferromagnetic) 1 22058
Sample with a ø 6.5 mm in AISI 420 steel sphere (ferromagnetic) 1 22059
MDScope 1 19795
MDCAD 1 27185
THS REPORT 1 27184
RS232/RS485 converter 1 21540

THS/PH
Validity: revision 1.102, 12/04/2001
Spare parts
Description Quantity Code
Control panel 1 18657
SPM module 1 21853
Deflector 1 18743
Infeed conveyor 1 16332
Support assembly 1 16043
Cable connecting the probe to the power supply unit 1 18938
Power supply unit 1 18744
Power supply card 00208ALM20 1 18939
Included sample - Stainless steel (ø0.3mm sphere) 1 17052
Included sample - Iron (ø0.3mm sphere) 1 17051
Included sample - Blank 1 16793
Short discharge conveyor 1 16335
Long discharge conveyor 1 19803
Deflector cover 1 16344
Deflector white basis in PETG 1 16333
Deflector flap position sensor 1 15286
Flap actuator 1 23541
Steel deflector flap 1 23542
Options
Description Quantity Code
RS 485 interface 1 17828
Accessories
Description Quantity Code
MDScope 1 19795
THS – FI022GB2K8v3 --- VI - APPENDICES 95

THS/G
Validity: revision 3.300, 30/06/2003
Spare parts
Description Quantity Code
Control panel 1 18736
SPM module 1 21853
Cable connecting the probe to the power supply unit: length 3 metres 1 18940
Cable connecting the probe to the power supply unit: custom length (max. 40m) 1 19992
Power supply unit 1 21141
Power supply card 00208ALM 1 18939
Remote control card 00208RCU 1 18945
Options
Description Quantity Code
RS 485 interface 1 17828
400/230Vca Transformer Box 1 23182
Protection against high-pressure water cleaning 1 24775
Ethernet Module 1 29756
Key for flange mounting 1 23376
Accessories
Description Quantity Code
MDScope 1 19795
MDCAD 1 27185
THS REPORT 1 27184
RS232/RS485 converter 1 21540
Infeed conveyor øin 330mm - øout 126.5mm PM2034A 1 23435
Infeed conveyor, part 1 code 2-37, øin 330mm, øout 161mm 1 23353
Infeed conveyor, part 2 code 2-39, øin 172mm, øout 126.5mm 1 23223
Infeed conveyor øin 330mm - øout 102.5mm PM2035A 1 23434
Infeed conveyor, part 1 code 2-37, øin 330mm, øout 165mm 1 23353
Infeed conveyor, part 2 code 2-41, øin 161mm, øout 152mm 1 23221
Infeed conveyor, part 3 code 2-42, øin 147mm, øout 142mm 1 23356
Infeed conveyor, part 4 code 2-43, øin 142mm, øout 126mm 1 23355
Infeed conveyor, part 5 code 2-44, øin 134mm, øout 102.5mm 1 23354
Infeed conveyor øin 330mm - øout 82mm PM2036A 1 23433
Infeed conveyor, part 1 code 2-37, øin 330mm, øout 165mm 1 23353
Infeed conveyor, part 2 code 2-38, øin 161mm, øout 110mm 1 23222
Infeed conveyor, part 3 code 2-40, øin 111mm, øout 82mm 1 23357

THS-FB
Validity: revision 1.06, 10/05/2002

Spare parts
Description Quantity Code
Belt 1 2 Tab. A
Trespa support plate - long part 1 7 Tab. A
Trespa support plate - short part 1 8 Tab. A
Plate spacer/support 1 9 Tab. A
Plate and reflektor spacer/support 1 10 Tab. A
Power supply unit and blinking light support kit 1 11 Tab. A
Reflektor support 1 12 Tab. A
Drum motor with wiring 1 15 Tab. A
250mm Drum motor 1 24922
300mm Drum motor 1 24715
350mm Drum motor 1 24923
400mm Drum motor 1 24716
450mm Drum motor 1 24918
500mm Drum motor 1 24717
600mm Drum motor 1 24718
Photocells 1 18486
Orange blinking light module 1 21280
Buzzer module 1 21281
Support for buzzer/blinking light 1 21282
Support for blinking light 1 20359
Supports for Free roller 1 21428
Bearing for Free roller and Bend roller 1 24605
Supports for Drum motor 1 21429
00208SCN connection card 1 21917
Casing for connectio card - drum motor side 1 21623
Casing for connectio card - supply box side 1 21622
Roller tilting support - right side 1 20803
Roller tilting support - left side 1 20804
Drum motor support - right side 1 20805
Drum motor support - left side 1 20806
General purpose support 1 21243
6mm diameter blue air rubber pipe 1 20958
8mm diameter blue air rubber pipe 1 21601
PG9 plug 1 22315
96 THS – FI022GB2K8v3 --- VI - APPENDICES

Accessories and Options


Description Quantity Code
Feet for 1000mm - 1500mm belt 4 21525
Castors for 1000mm - 1500mm belt 4 21548
Feet for 2000mm & THS/MN belt 4 24802
Castors for 2000mm & THS/MN belt 4 24803
Bar-code reader mounting kit 1 21613
Insufficient air-pressure sensor kit 1 21614
Piston ejector - 200mm 1 21610
Air group protection casing 1 21121
Air adiustment group 1 21604
Connection and solenoid valve kit 1 21602
Piston ejector - 350mm 1 21611
Air group protection 1 22397
Air adiustment group 1 21604
Connection and solenoid valve kit 1 21602
Air-jet ejector 1 22477
Protection casing 1 26282
Valve kit 1 26270
Set-aside container with support 1 21423
Plastic container 1 19139
Ejection confirmation sensor and full set-aside container sensor kit 1 21612
Protective panel set at the exit of the antenna - belt width 1500 x 200 mm for Family A 1 24739
Cover - belt width 200mm for Family A 1 24862
"U" protection for cover - belt width 3200mm for Family A 1 24861
Protective panel set at the exit of the antenna - belt width 2000 x 200 mm for Family A 1 24741
Cover - belt width 200mm for Family A 1 24862
"U" protection for cover - belt width 3200mm for Family A 1 24864
Protective panel set at the exit of the antenna - belt width 1500 x 300 mm for Family A 1 21412
Thermoformed cover - belt width 300mm for Family A 1 23262
"U" protection for Thermoformed cover - belt width 300mm for Family A 1 23140
Protective panel set at the exit of the antenna - belt width 2000 x 300 mm for Family A 1 24743
Thermoformed cover - belt width 300mm for Family A 1 23262
"U" protection for Thermoformed cover - belt width 300mm for Family A 1 24866
Protective panel set at the exit of the antenna - belt width 1500 x 400 mm for Family A 1 24745
Cover - belt width 400mm for Family A 1 24842
"U" protection for cover - belt width 400mm for Family A 1 24868
Protective panel set at the exit of the antenna - belt width 2000 x 400 mm for Family A 1 24747
Cover - belt width 400mm for Family A 1 24842
"U" protection for cover - belt width 400mm for Family A 1 24869
Protective panel set at the exit of the antenna - belt width 1500 x 500 mm for Family A 1 21413
Cover - belt width 500mm for Family A 1 21371
"U" protection for cover - belt width 500mm for Family A 1 21362
Protective panel set at the exit of the antenna - belt width 2000 x 500 mm for Family A 1 24749
Cover - belt width 500mm for Family A 1 21371
"U" protection for cover - belt width 500mm for Family A 1 24871
Protective panel set at the exit of the antenna - belt width 1500 x 200 mm for Family B 1 24740
Cover - belt width 200mm for Family B 1 24863
Protective panel set at the exit of the antenna - belt width 2000 x 200 mm for Family B 1 24742
Cover - belt width 200mm for Family B 1 24863
"U" protection for cover - belt width 200mm for Family B 1 24865
Protective panel set at the exit of the antenna - belt width 1500 x 300 mm for Family B 1 23527
Cover - belt width 300mm for Family B 1 21242
Protective panel set at the exit of the antenna - belt width 2000 x 300 mm for Family B 1 24744
Cover - belt width 300mm for Family B 1 21242
"U" protection for cover - belt width 300mm for Family B 1 24867
Protective panel set at the exit of the antenna - belt width 1500 x 400 mm for Family B 1 24746
Cover - belt width 3400mm for Family B 1 24843
Protective panel set at the exit of the antenna - belt width 2000 x 400 mm for Family B 1 24748
Cover - belt width 400mm for Family B 1 24843
"U" protection for cover - belt width 400mm for Family B 1 24870
Protective panel set at the exit of the antenna - belt width 1500 x 500 mm for Family B 1 23526
Cover - belt width 500mm for Family B 1 21372
Protective panel set at the exit of the antenna - belt width 2000 x 500 mm for Family B 1 24750
Cover - belt width 500mm for Family B 1 21372
"U" protection for cover - belt width 500mm for Family B 1 24872
Protective panel set at the exit of the antenna - belt width 2000 x 300 mm per THS/MN DH 150mm 1 24909
Cover - belt width 300mm per THS/MN DH 150mm 1 23262
"U" protection for cover - belt width 300mm per THS/MN DH 150mm 1 23533
Protective panel set at the exit of the antenna - belt width 2000 x 300 mm per THS/MN DH 200mm 1 24910
Cover - belt width 300mm per THS/MN DH 200mm 1 21242
"U" protection for cover - belt width 300mm per THS/MN DH 200mm 1 24857
Protective panel set at the exit of the antenna - belt width 2000 x 500 mm per THS/MN DH 150mm 1 24911
Cover - belt width 500mm per THS/MN DH 150mm 1 21371
Protective panel set at the exit of the antenna - belt width 2000 x 500 mm per THS/MN DH 200mm 1 24912
Cover - belt width 500mm per THS/MN DH 200mm 1 21372
Protective panel set at the exit of the antenna - belt width 2000 x 500 mm for Family C 1 22855
Cover - belt width 500mm for Family C 1 21364
"U" protection for cover - belt width 500mm for Family C 1 20398
THS – FI022GB2K8v3 --- VI - APPENDICES 97

Table A • Components
Item 3 7 8 9 10 11 12 15
support plate -

support plate -

Power supply
and
and

blinking light

Drum motor
spacer/suppor

spacer/suppor

with wiring
support kit

0.5m/sec.
short part

Reflektor
long part

reflektor

support
Trespa

Trespa

Plate

Plate
Belt

unit
t

t
Quantity 1 1 1 1 1 1 1 1

1000 X 200 X 875 ± 50 24690 24721 24729 22956 22956 24661 21244 24715
1500 X 200 X 875 ± 50 24691 24722 24730 20354 21240 21351 21244 24715
2000 X 200 X 875 ± 50 24692 24723 24731 20354 21240 24987 21244 24715

1000 X 300 X 875 ± 75 21801 24217 24218 22956 22956 24661 21244 24716
1500 X 300 X 875 ± 75 21316 17841 17842 20354 21240 21351 21244 24716
2000 X 300 X 875 ± 75 23532 24724 24732 20354 21240 24987 21244 24716

800 X 400 X 875 ± 75 25776 25771 25772 no no 25361 25505 24717


1000 X 400 X 875 ± 75 24694 24725 24733 22956 22956 24661 21244 24717
1500 X 400 X 875 ± 75 24695 24726 24734 20354 21240 21351 21244 24717
2000 X 400 X 875 ± 75 24696 24727 24735 20354 21240 24987 21244 24717

1000 X 500 X 875 ± 75 24697 24728 24736 22956 22956 24661 21244 24718
1500 X 500 X 875 ± 75 21359 21370 21369 20354 21240 21351 21244 24718
2000 X 500 X 875 ± 75 24650 24620 24621 20354 21240 24987 21244 24718
2000 X 500 X 875 ± 75 Fam. C 24650 24915 24916 20354 21240 25361 21244 24718

2000 X 300 X 875 ± 75 per THS/MN 23532 23382 23383 20354 21240 25361 21244 24716
2000 X 500 X 875 ± 75 per THS/MN 24650 24938 24939 20354 21240 25361 21244 24718

Table B - Compatibility, Options and Spare parts

Part A
Options
THS Family

(feet)

Insufficient air-
pressure sensor

Piston ejector
compatibility

Bar-code reader

kit

Air-jet ejector
conveyor belt

Castors

Fam. A protection
Complete

Belt supports

Blue blinking lamp


for test request

mounting kit

panel set
Antenna fixing kit

Side panels kit

Quantity 1 1 1 1 1 1 1 1 1 1
98 THS – FI022GB2K8v3 --- VI - APPENDICES

1000 X 200 x 875 ± 50 SL A 24658 21525 21548 Tab. D 21279 21613 no 21553 no no no
1500 X 200 x 875 ± 50 AB 24659 21525 21548 Tab. C 21279 21613 21614 21553 21610 22477 24739
2000 X 200 x 875 ± 50 AB 24660 24802 24803 Tab. C 21279 21613 21614 21553 21610 22477 24741

1000 X 300 x 875 ± 75 SL A 24130 21525 21548 Tab. D 21279 21613 no 21553 no no no
1500 X 300 x 875 ± 75 AB 21761 21525 21548 Tab. C 21279 21613 21614 21553 21610 22477 21412
2000 X 300 x 875 ± 75 AB 25341 24802 24803 Tab. C 21279 21613 21614 21553 21610 22477 24743

1000 X 400 x 875 ± 75 SL A 24662 21525 21548 Tab. D 21279 21613 no 21553 no no no
1500 X 400 x 875 ± 75 AB 24663 21525 21548 Tab. C 21279 21613 21614 21553 21611 22477 24745
2000 X 400 x 875 ± 75 AB 24664 24802 24803 Tab. C 21279 21613 21614 21553 21611 22477 24747

1000 X 500 x 875 ± 75 SL A 24665 21525 21548 Tab. D 21279 21613 no 21553 no no no
1500 x 500 x 875 ± 75 AB 21762 21525 21548 Tab. C 21279 21613 21614 21553 21611 22477 21413
2000 X 500 x 875 ± 75 AB 24666 24802 24803 Tab. C 21279 21613 21614 21553 21611 22477 24749
2000 X 500 x 875 ± 75 Fam.C C 25773 24802 24803 Tab. E 21279 21613 21614 21553 21611 22477 24749

2000 X 300 x 875 ± 75 per THS/MN 23540 24802 24803 Tab. E 21279 21613 21614 21553 21610 22477 Tab. E
2000 X 500 x 875 ± 75 per THS/MN 24956 24802 24803 Tab. E 21279 21613 21614 21553 21611 22477 Tab. E

Table B - Compatibility, Options and Spare parts

Part B
Options Spare parts
Family

Set-aside container

sensor and full set-


container
LARGE

Fam. B protection

LARGE

Set-aside
with

Ejection confirmation
protection panel set

protection panel set

Piston ejector
compatibility

with support

Bend roller

Free roller
A

sensor kit
container
panel set

LARGE

support

aside
Fam.

Fam.
THS

Quantity 1 1 1 1 1 1 1 1

1000 X 200 x 875 ± 50 SL A no no no no no no no 24884 24808 no


1500 X 200 x 875 ± 50 AB no 24740 no 21423 no no 21612 24884 24808 21598
2000 X 200 x 875 ± 50 AB on req. 24742 on req. 21423 on req. on req 21612 24884 24808 21598

1000 X 300 x 875 ± 75 SL A no no no no no no no 24876 20371 no


1500 X 300 x 875 ± 75 AB no 23527 no 21423 no no 21612 24876 20371 21598
2000 X 300 x 875 ± 75 AB on req. 24744 on req. 21423 on req. on req 21612 24876 20371 21598

1000 X 400 x 875 ± 75 SL A no no no no no no no 24885 24809 no


1500 X 400 x 875 ± 75 AB no 24746 no 21423 no no 21612 24885 24809 21599
2000 X 400 x 875 ± 75 AB on req. 24748 on req. 21423 on req. on req 21612 24885 24809 21599

1000 X 500 x 875 ± 75 SL A no no no no no no no 24886 21360 no


1500 x 500 x 875 ± 75 AB no 23526 no 21423 no no 21612 24886 21360 21599
2000 X 500 x 875 ± 75 AB on req. 24750 on req. 21423 on req. on req 21612 24886 21360 21599
2000 X 500 x 875 ± 75 Fam.C C no 24750 no 21423 no no 21612 24886 21360 21599

2000 X 300 x 875 ± 75 per THS/MN no Tab. E no 21423 no no 21612 22962 20371 21598
2000 X 500 x 875 ± 75 per THS/MN no Tab. E no 21423 no no 21612 24897 21361 21599

Table C - Fam. A & B antenna fixing kit for belt length of 1500 mm and 2000 mm
Metal Detector aperture height Code
100 mm 21414
125 mm 21415
150 mm 21416
175 mm 21417
200 mm 21427
225 mm 21418
250 mm 21419
275 mm 21420

Table D - THS/SL and Fam. A antenna fixing kit for belt length of 1000 mm
Metal Detector aperture height THS/SL Fam. A
THS – FI022GB2K8v3 --- VI - APPENDICES 99

100 mm 24899 24900


125 mm 24899 24901
150 mm 24899 24902
175 mm 24899 24903
200 mm 24899 --

Table E - THS/MN and Fam C fixing kit


Metal Detector aperture height Code
THS/MN DH 150 24904
THS/MN DH 200 24905
Fam. C with aperture heigth 300 mm 24906
Fam. C with aperture heigth 325 mm 24907
Fam. C with aperture heigth 350 mm 24908

Table F - Exit Protective panel set for Fam C and THS/MN


Metal Detector aperture height Code
THS/MN H 150 on belt with width 300mm 24909
THS/MN H 200 on belt with width 300mm 24910
THS/MN H 150 on belt with width 500mm 24911
THS/MN H 200 on belt with width 500mm 24912
Fam. C with aperture heigth 300 mm 24913

THS Accessories - Test pieces


Validity: revision 1.01, 30/10/2002
Description Quantity Code
Set of quality control test samples (AISI 420 steel (ferromagnetic) and AISI 316 Stainless steel) - High sensitivity 1 18711
Set of quality control test samples (AISI 420 steel (ferromagnetic) and non ferrous metal) - High sensitivity 1 22607
Set of quality control test samples (AISI 420 steel (ferromagnetic) and AISI 316 Stainless steel) - Low sensitivity 1 22605
Set of quality control test samples (AISI 420 steel (ferromagnetic) and non ferrous metal) - Low sensitivity 1 22606
Sample with a ø 0.8 mm in AISI 420 steel sphere (ferromagnetic) 1 18124
Sample with a ø 1.0 mm in AISI 420 steel sphere (ferromagnetic) 1 18125
Sample with a ø 1.2 mm in AISI 420 steel sphere (ferromagnetic) 1 18126
Sample with a ø 1.5 mm in AISI 420 steel sphere (ferromagnetic) 1 18127
Sample with a ø 2.0 mm in AISI 420 steel sphere (ferromagnetic) 1 18128
Sample with a ø 2.5 mm in AISI 420 steel sphere (ferromagnetic) 1 18129
Sample with a ø 3.0 mm in AISI 420 steel sphere (ferromagnetic) 1 18130
Sample with a ø 3.5 mm in AISI 420 steel sphere (ferromagnetic) 1 18131
Sample with a ø 4.0 mm in AISI 420 steel sphere (ferromagnetic) 1 20251
Sample with a ø 4.5 mm in AISI 420 steel sphere (ferromagnetic) 1 20252
Sample with a ø 5.0 mm in AISI 420 steel sphere (ferromagnetic) 1 22056
Sample with a ø 5.5 mm in AISI 420 steel sphere (ferromagnetic) 1 22057
Sample with a ø 6.0 mm in AISI 420 steel sphere (ferromagnetic) 1 22058
Sample with a ø 6.5 mm in AISI 420 steel sphere (ferromagnetic) 1 22059
Sample with a ø 1.0 mm in AISI 316 Stainless steel sphere 1 18118
Sample with a ø 1.5 mm in AISI 316 Stainless steel sphere 1 18119
Sample with a ø 2.0 mm in AISI 316 Stainless steel sphere 1 18120
Sample with a ø 2.5 mm in AISI 316 Stainless steel sphere 1 18121
Sample with a ø 3.0 mm in AISI 316 Stainless steel sphere 1 18122
Sample with a ø 3.5 mm in AISI 316 Stainless steel sphere 1 18123
Sample with a ø 4.0 mm in AISI 316 Stainless steel sphere 1 20254
Sample with a ø 4.5 mm in AISI 316 Stainless steel sphere 1 20253
Sample with a ø 5.0 mm in AISI 316 Stainless steel sphere 1 22052
Sample with a ø 5.5 mm in AISI 316 Stainless steel sphere 1 22053
Sample with a ø 6.0 mm in AISI 316 Stainless steel sphere 1 22054
Sample with a ø 6.5 mm in AISI 316 Stainless steel sphere 1 22055
Sample with a ø 1.0 mm in non ferrous material sphere 1 21485
Sample with a ø 1.5 mm in non ferrous material sphere 1 21486
Sample with a ø 2.0 mm in non ferrous material sphere 1 21487
Sample with a ø 2.5 mm in non ferrous material sphere 1 21488
Sample with a ø 3.0 mm in non ferrous material sphere 1 21489
Sample with a ø 3.5 mm in non ferrous material sphere 1 21490
Sample with a ø 4.0 mm in non ferrous material sphere 1 21491
100 THS – FI022GB2K8v3 --- VI - APPENDICES

Sample with a ø 4.5 mm in non ferrous material sphere 1 21492


Sample with a ø 5.0 mm in non ferrous material sphere 1 21493
Sample with a ø 5.5 mm in non ferrous material sphere 1 21494
Sample with a ø 6.0 mm in non ferrous material sphere 1 21495
Sample with a ø 6.5 mm in non ferrous material sphere 1 21496

THS Accessories - MD CAD - 27185


Validity: revision 1.0, 17/09/2002
Spare parts
Description Quantity Code
Cable 60387 1 26895

Вам также может понравиться