Fig.

2-1-1 Explanation of Boiler control mode

Boiler control mode Control condition Remark


・Gen. Synchronized
Coordinate Control mode CC mode (Dry) Normal operating mode
・Turbine master control : auto ------------------------- MW control (MW target is set by operator or dispatch)
MW target is set by operator or dispatch
・Boiler input control : auto (as follows) –------------- follow to MWD and Pt control
Feed water flow control/ Fuel flow control/ Air flow control/ Furnace draft control : auto
・Water fuel ratio (WFR) control : auto --------------- Superheat rate of Twsi control
*BID = MWD + Pt control correction (MWD ~ MW target and load rate set)
・Gen. Synchronized
CC mode (Wet) Normal operating mode
・Turbine master control : auto ------------------------- MW control (MW target is set by operator or dispatch)
MW target is set by operator or dispatch
・Boiler input control : auto (as follows) -------------- follow to MWD
Feed water flow control/ Fuel flow control/ Air flow control/ Furnace draft control : auto
・Water fuel ratio (WFR) control : auto or HP-TB valve main steam press control : auto --------- Pt control
*BID = MWD (MWD ~ MW target and load rate set)
・Gen. Synchronized
Boiler Follow mode BF mode (Dry) Turbine master manual operation
・Turbine master control : manual
Boiler input follow to MW + Pt control
・Boiler input control : auto (as follows) -------------- follow to MW and Pt control
Feed water flow control/ Fuel flow control/ Air flow control/ Furnace draft control : auto
*MWD = MW (MW tracking)
*BID = MW(rate limited) + Pt control correction
・Gen. Synchronized
BF mode (Wet) Turbine master manual operation
・Turbine master control : manual
Boiler input follow to MW
・Boiler input control : auto (as follows) -------------- follow to MW
WFR or HP-TB –-- Pt control
Feed water flow control/ Fuel flow control/ Air flow control/ Furnace draft control : auto
・Water fuel ratio (WFR) control : auto or HP-TB valve main steam press control : auto --------- Pt control
*MWD = MW (MW tracking)
*BID = MW(rate limited)
・Gen. Synchronized
Boiler Input mode BI mode (Dry) Boiler input is set directly by operator
・not CC or BF mode
TM : auto ----- Turbine follow mode
・Feed water flow control : auto
(Pt control)
*MWD = MW (MW tracking)
TM : manual ----- Pt control is manual
*BID ~ BI target and load rate set (BI target is set by operator)
** In case of Runback, BI target is set to preset runback target load.
・Gen. Synchronized
BI mode (Wet) Boiler input is set directly by operator
・not CC or BF mode
TM : auto ----- Turbine follow mode
・Fuel flow control : auto
(Pt control)
*MWD = MW (MW tracking)
TM : manual ----- Pt control is manual
*BID ~ BI target and load rate set (BI target is set by operator)

・Feed water flow control : manual


Boiler manual mode BM mode (Dry) TM : auto ----- Turbine follow mode
*MWD = MW (MW tracking)
(Pt control)
*BID = Fx (Feed water flow) or MW (in case of Feed water flow signal fault)
TM : manual ----- Pt control is manual
Fx : Feed water flow is converted to Load index signal according to static character.

・not Gen. Synchronized


BM mode (Wet) TM : auto ----- Turbine follow mode
or
(Pt control)
・Fuel flow control : manual
TM : manual ----- Pt control is manual
*MWD = MW (MW tracking)
*BID = MW(rate limited)