3 Timber Separating Walls

CONSTRUCTION
DETAILS 246

INTRODUCTION This section only contains construction For an alternative separating wall
Timber double stud walls details for separating walls between system, use the innovative Knauf
are commonly used as dwellings. [For systems and InterHome system. [Refer to the latest
separating walls, providing installation, refer to Section 3.1.2] InterHome brochure on the website]
fire safety and acoustic
separation between
dwellings.

245
FIRE RATED
TIMBER SEPARATING WALL BASE AND SUSPENDED GROUND FLOOR – ELEVATION

FireShield

Skirting board
Fire sealant required
to maintain fire and
acoustic integrity
3.3.3 Timber Separating Walls

Fix 10-15mm from


sheet bottom 5-10mm clearance
to plasterboard

FIGURE 1 Separating Wall Base to Slab


Fill any gaps with fire sealant to
maintain fire and acoustic integrity.

FireShield

Skirting board
Fire sealant required
to maintain fire and
CONSTRUCTION DETAILS

acoustic integrity

Fix 10-15mm from


sheet bottom 5-10mm clearance
to plasterboard

Saw cut in flooring

Floor joists parallel


to separating wall

Floor joists perpendicular


to separating wall

Sacrifical solid timber blocking to maintain


fire rating. Additional to structural timber.
Use 1x45mm or 2x35mm thick for FRL 60.
Use 2x45mm or 3x35mm thick for FRL 90.

FIGURE 2 Separating Wall with Suspended Ground Floor

246 Technical Advice 1300 724 505 knaufplasterboard.com.au


TIMBER SEPARATING WALL WITH UPPER STOREY FLOOR – ELEVATION

FireShield

Skirting board
Fire sealant required
to maintain fire and
acoustic integrity

Fix 10-15mm from


sheet bottom 5-10mm clearance
to plasterboard

3.3.3 Timber Separating Walls


Half-saw cut
in flooring

Floor joists parallel


to separating wall Engineered
timber joist

Floor joists perpendicular Install trimmer for ceiling


to separating wall plasterboard perimeter support

Non-fire rated plasterboard


Sacrifical solid timber blocking to maintain
fire rating. Additional to structural timber.
Use 1x45mm or 2x35mm thick for FRL 60.
Use 2x45mm or 3x35mm thick for FRL 90.

Fill any gaps with fire sealant to


FIGURE 3 Separating Wall with Upper Storey Floor maintain fire and acoustic integrity.

CONSTRUCTION DETAILS
FireShield

Skirting board
Fire sealant required
to maintain fire and
acoustic integrity

Fix 10-15mm from


sheet bottom 5-10mm clearance
to plasterboard

Additional nogging
Half-saw cut
installed to support
in flooring
FireShield and fire
sealant
Floor joists perpendicular to
separating wall. Minimum joist
bearing must be maintained.

Floor joists parallel


to separating wall

Non-fire rated plasterboard


Sacrifical solid timber
Sacrifical solid timber blocking to maintain blocking to maintain fire
fire rating. Additional to structural timber. rating. Additional
Use 1x45mm or 2x35mm thick for FRL 60. to structural timber.
Use 2x45mm or 3x35mm thick for FRL 90. Use 1x45mm or 2x35mm
thick for FRL 60.
Use 2x45mm or 3x35mm
thick for FRL 90.

Floor joists
FIGURE 4 Separating Wall with Upper Storey Floor
perpendicular to
separating wall
PLAN VIEW

Technical Advice 1300 724 505 knaufplasterboard.com.au 247


TIMBER SEPARATING WALL ROOF DETAIL – ELEVATION

Fill with fire resistant mineral wool


to maintain FRL of wall system to
non-combustible roof lining

Roof sarking
3.3.3 Timber Separating Walls

Sacrifical solid timber blocking


Fill any gaps with fire sealant to to maintain fire rating.
maintain fire and acoustic integrity. Additional to structural timber.
Use 1x45mm thick for FRL 60.

Fix 10-15mm from


plasterboard edge
CONSTRUCTION DETAILS

Additional noggings installed to


support FireShield and fire sealant 5-10mm clearance to plasterboard.
Fill with fire sealant to maintain fire
and acoustic integrity

FireShield

FIGURE 5 Separating Wall with Perpendicular Roof Trusses

248 Technical Advice 1300 724 505 knaufplasterboard.com.au


TIMBER SEPARATING WALL ROOF DETAIL – ELEVATION

Roof battens can be


continuous over Fill with fire resistant mineral wool
Separating Wall. to maintain FRL of wall system to
non-combustible roof lining.

Fix 10-15mm from


plasterboard edges

Roof sarking

3.3.3 Timber Separating Walls


Separating wall
Truss parallel to continued through
separating wall roof cavity

CONSTRUCTION DETAILS
Install trimmer for ceiling
Non-fire rated plasterboard
plasterboard perimeter support

FireShield
Fill any gaps with fire sealant to
maintain fire and acoustic integrity.

FIGURE 6 Separating Wall with Parallel Roof Trusses

Technical Advice 1300 724 505 knaufplasterboard.com.au 249


TIMBER SEPARATING WALL ROOF DETAIL – ELEVATION

Fix 10-15mm from


plasterboard edge

External cladding
Fill any gaps with fire sealant to
maintain fire and acoustic integrity.
3.3.3 Timber Separating Walls

Roof sarking

Separating wall
Truss parallel to continued through
separating wall roof cavity
CONSTRUCTION DETAILS

Install trimmer for ceiling


Non-fire rated plasterboard
plasterboard perimeter support

FireShield

FIGURE 7 Separating Wall to Parapet Roof with Parallel Roof Trusses

250 Technical Advice 1300 724 505 knaufplasterboard.com.au


TIMBER SEPARATING WALL ROOF DETAIL WITH EXTERNAL WALL – ELEVATION

3.3.3 Timber Separating Walls


Fill with fire resistant
mineral wool to maintain
FRL of wall system to
non-combustible roof lining 2 layers of 16mm MultiShield to maintain FRL
60/60/60 external wall above separating wall

External cladding

Truss parallel to
separating wall

Roof sarking

Fix 10-15mm from


Non-fire rated plasterboard edge

CONSTRUCTION DETAILS
plasterboard

5-10mm clearance to plasterboard.


Fill with fire sealant to maintain fire
and acoustic integrity.
Separating wall
continued through
Additional nogging installed to
roof cavity
support MultiShield and fire sealant.

Fill any gaps with fire sealant to


maintain fire and acoustic integrity.

Install trimmer for ceiling


plasterboard perimeter support

FireShield

FIGURE 8 Separating Wall with External Wall Above

Technical Advice 1300 724 505 knaufplasterboard.com.au 251


TIMBER SEPARATING WALL ROOF DETAIL – ELEVATION
3.3.3 Timber Separating Walls

Fix 10-15mm from


Truss perpendicular Sacrifical solid timber blocking to maintain
plasterboard edge
to separating wall fire rating. Additional to structural timber.
Use 1x45mm or 2x35mm thick for FRL 60.
Use 2x45mm or 3x35mm thick for FRL 90.
5-10mm clearance to plasterboard.
Fire sealant required to maintain fire
and acoustic integrity Fill any gaps with fire sealant to
maintain fire and acoustic integrity.

FireShield

FIGURE 9 Separating Wall to Box Gutter with Perpendicular Roof Trusses


CONSTRUCTION DETAILS

Fill with fire resistant mineral wool


to maintain FRL of wall system to
non-combustible roof lining.

Top plate

Roof sarking over


Wall stud anti-ponding board

Separating wall continued


through roof cavity.

FireShield or other
non-combustible lining
Top plate continued over eaves

Wall stud

Eave lining

External
wall stud
Fill with fire resistant mineral
wool in cavity to maintain FRL.

FIGURE 10 Separating Wall Over Eaves Lining

252 Technical Advice 1300 724 505 knaufplasterboard.com.au


TIMBER SEPARATING WALL TO EXTERNAL WALL – ELEVATION

Non-fire rated
plasterboard
5-10mm clearance to plasterboard.
Fire sealant required to maintain
fire and acoustic integrity.
Fill with fire resistant mineral
Additional stud installed to support wool in cavity to maintain FRL
FireShield and fire sealant

3.3.3 Timber Separating Walls


Vertical damp
proof course

Sacrifical solid timber blocking to maintain


fire rating. Additional to structural timber.
Use 1x45mm or 2x35mm thick for FRL 60.
Use 2x45mm or 3x35mm thick for FRL 90.

Moisture barrier

FIGURE 11 Separating Wall to External Brick Wall

CONSTRUCTION DETAILS
Fill any gaps with fire sealant to
maintain fire and acoustic integrity.

Non-fire rated
plasterboard
5-10mm clearance to plasterboard.
Fire sealant required to maintain
fire and acoustic integrity
Vertical damp
proof course
Additional stud installed to support
FireShield and fire sealant

45mm min solid timber


blocking in wall cavity to
maintain fire rating

FireShield

Sacrifical solid timber blocking to maintain


fire rating. Additional to structural timber.
Use 1x45mm or 2x35mm thick for FRL 60.
Use 2x45mm or 3x35mm thick for FRL 90. Moisture barrier

FIGURE 12 Separating Wall to External Brick Wall

Technical Advice 1300 724 505 knaufplasterboard.com.au 253


TIMBER SEPARATING WALL TO EXTERNAL WALL – ELEVATION

Sacrifical solid timber blocking


to maintain fire rating.
Additional to structural timber. Fill with fire resistant mineral
Use 1x45mm or 2x35mm wool in cavity to maintain FRL
thick for FRL 60.
Use 2x45mm or 3x35mm
thick for FRL 90.
3.3.3 Timber Separating Walls

Vertical damp
proof course

Additional stud installed to support


FireShield and fire sealant 5-10mm clearance to plasterboard.
Fire sealant required to maintain
fire and acoustic integrity

Non-fire rated
plasterboard

FIGURE 13 Separating Wall to External Brick Wall with Return Moisture barrier
CONSTRUCTION DETAILS

Non-fire rated
plasterboard
5-10mm clearance to plasterboard.
Fire sealant required to maintain
fire and acoustic integrity If cladding battens are used,
fill cavity with fire resistant
mineral wool to maintain FRL
Additional stud installed to support
FireShield and fire sealant

External cladding

Fill any gaps with fire sealant to


maintain fire and acoustic integrity.

Breathable moisture barrier

FireShield

Sacrifical solid timber blocking to maintain


fire rating. Additional to structural timber.
Use 1x45mm or 2x35mm thick for FRL 60.
Use 2x45mm or 3x35mm thick for FRL 90. Cladding battens

FIGURE 14 Separating Wall to External Clad Wall