Академический Документы
Профессиональный Документы
Культура Документы
Abstract:
This paper is intended as a review of current technology options and practices for the
effective treatment of the water and steam circuits in Ethylene Furnace Transfer Line
Exchangers (TLE’s) to assure optimum reliability, longevity, and efficiency.
Common TLE designs will be briefly reviewed, as well as the benefits and concerns with the
various boiler treatment approaches, as well as an alternative practice for cold start-up and
passivation of the Boiler System.
External treatment processes, including demineralization and condensate polishing, will
be reviewed from the perspective of minimizing contaminant ingress to reduce the potential
for deposition and corrosion in the high heat flux Transfer Line Exchangers.
Current boiler water treatment practices will also be reviewed with respect to ASME and
VGB application guidelines. This will include a discussion of the choices and selection criteria
for oxygen scavengers, as well as the review of the internal treatment chemistries, including
coordinated/congruent pH/phosphate control; alkaline phosphate; and all-volatile treatment.
The application and benefit of synthetic polymeric dispersants in TLE’s will also be briefly
discussed. Brief discussion on boiler cycles and retention times are included.
Steam/condensate treatment technology based on volatile alkalizing agents will also be
reviewed, along with steam purity guidelines and issues as they relate to steam turbine
reliability and integrity.
The adverse effects of low level chloride and sodium contaminants in the feedwater will
be reviewed and the results of computer studies to show effects on both low phosphate and
all volatile treatment programs, as compared to more conventional phosphate control levels.
In closing, there will be brief review of several internal metallurgical studies that will
highlight key discussion points in relation to low level contaminant intrusion resulting in boiler
system failures.
Page
607 2
Introduction to Boiler System Treatment:
Auditing an Ethylene Plant Boiler system is very important to assess the system and treatment
program basics, including identifying potential conditions that may effect plant reliability,
and/or determine the root cause of a specific problem.
Ethylene Plant Boiler system chemical treatment programs are determined by a number of
factors, including: the Boiler System Steam pressure; the heat flux; circulation rate; and the
specific design of the waste heat recovery system, the Cracking Furnace and the Transfer Line
Heat Exchangers (TLE’s).
The primary objectives of boiler system chemical treatment are: system protection; failure
prevention; operating reliability; and efficiency. These objectives are achieved by the
successful application of the optimum system treatment program, resulting in effective deposit
control; corrosion minimization; and maximizing steam purity.
Because of the emphasis of designing the most effective boiler treatment program on the
process system and equipment, a successful chemical treatment program will require
knowledge and understanding of the Ethylene Plant Unit Operations and Processes. For
example this will include knowledge of: External Treatment; Deaeration; Boiler system
operation, design and metallurgy; chemical treatment concerns and restrictions; Steam uses;
such as for Steam Turbine Drivers for Pumps and Compressors; and contamination issues
related to condensate recovery.
The paper will begin with a description and explanation of a typical Ethylene Furnace System;
and review typical designs of Transfer Line Exchangers (TLE’s); and their associated steam
drums and auxiliary equipment.
Following the introduction, we will review: a typical external treatment system; typical High
Pressure Boiler Treatment programs; Boiler Treatment Guidelines; and typical Boiler Failure
mechanisms. Also included will be a comparison and review of the internal treatment
programs considered (Phosphate based and All Volatile), considering both ASME and VGB
Guidelines, and with low level contaminants present in the feedwater.
We will briefly compare Utility Power Boilers, with Industrial Boilers.
An example of Cold Start Up Rinse/Passivation Procedure of the Boiler System will be
reviewed, including the use of polymeric dispersants for boiler system iron transport.
Lastly, GE Water Metallurgical Report summaries will be reviewed for examples of the various
boiler system failure mechanisms that have been observed.
Page
608 3
Typical Transfer Line Exchanger (TLE) Description:
Ethylene Cracking Furnace Transfer line Exchangers (TLE’s) are designed to recover the waste
heat (energy) from the Pyrolysis Furnace “Cracked Gas” ahead of the Quench Tower and
produce high pressure steam. The TLE WHB’s in Ethylene Plants are integrated into the
process and are an absolute necessity to the process operation.
This means that boiler deposition and corrosion issues, which may lead to failures of the waste
heat boilers, could simultaneously result in process shutdown and loss of production. In this
situation, unit reliability is essential from a plant operations standpoint, and total costs
associated with a single failure can exceed the total cost of the boiler.
Transfer Line Exchanger (TLE) Waste heat Boiler designs are generally considered as firetube
boilers, with process cracked gas stream on the tube side pass, and the boiler water on the
shell side, with natural (thermal) boiler water circulation from the steam drum.
There are a number of different design styles in Ethylene Plant TLE’s. The TLE geometry can
be vertical or horizontal, depending on plant requirements. Conventional designs include:
Shell/Tube, with boiler water usually on shell side; Double Tube/Oval Headers; and one design
includes a secondary quench exchanger (SQE) shell with bayonet and scabbard tube
configuration. Note Typical Examples below in Figure 1.
Shell/Bayonet/ScabbordTubes
BW Downcomer
BW Riser BW Riser
Bayonet Tubesheet
Furnace Gas
Scabbard Tubesheet
Outlet
Gas Deflection Baffle
Bayonet Tube
Refractory Liner
Scabbard Tube
Vertical Shell/Tube
Figure 1
Page
609 4
Typical boiler operating pressures in Ethylene Plants range from 600 to 1800 PSIG (40 – 125
Barg). Typical Boiler Feedwater makeup is mixed bed demineralized, and polished steam
condensate.
Ethylene Plant Boiler designs are based primarily on process unit considerations, while making
compromises on the waterside. Some High Pressure TLE WHB designs allow very little
tolerance for deposition, or deviations in boiler water purity.
Boiler failures in Transfer Line Exchangers (TLE’s), can be related to design; operation; water
treatment; or a combination of factors. To avoid internal corrosion, the water chemistry must
be within strictly controlled guidelines at all times. Even short-term contamination of the
feedwater, may lead to corrosion-induced failures within weeks or months, particularly if a
boiler system is considered to have deposition.
In most Ethylene plants, the External Treatment system will include: a Demineralizer System;
a Condensate and Boiler Blowdown Recovery System; Activated Carbon Filters on the return
condensate with Cation Polishers; and Mixed Bed Polishers on the combined stream of
condensate; demin makeup, and turbine condensate. The effluent from the mixed bed will be
preheated and then deaerated. A typical External Treatment System is shown in the following
drawing (Figure 2):
LP Condensate Mu Prehtr
O2 Scavenger
Steam Drum Flash Steam
& TLE’s
CBD Blowdown Condensate Deaerator
Flash Tank Receiver
Amine
60 M3/Hr
HP
FT
Export To
BFW
To DSG To Attemperation Steam
Waste Cond
To Waste CUF Drums
pH
Mixed
Turbine 2 Trains Micron
Bed
Condensate Filter
TOC Polisher
Figure 2.
Page
610 5
Note in the above Figure 2, this typical system design includes: on-line analyzers for
monitoring of: Conductivity and pH of the condensate returns; Total Organic Carbon (TOC)
monitoring of the combined outlet of the Steam Condensate Dilution Steam Generator
Condensate; the imported Demin Makeup, and the Turbine Condensate to the Mixed Bed
Polisher. The effluent from the Mixed Bed Polisher will typically include on-line Conductivity
and Silica measurement.
Cracked Gas
Steam Drum
CBD
LP Steam SQE
Deaerator
Amine
Oxygen Internal
Scavenger Treatment IBD
BFW
Attemporation
To Quench
SH HP Steam Water Tower
TLE
Dilution
Steam
Fuel Gas
IBD (Shell & Tube TLE’s) To BD
Flash Tank
Page
611 6
In the typical design in Figure 3, Intermittent Blowdown is noted from the steam drum and
the bottom tube sheet area of the vertical TLE’s, as may be typical in some “shell and tube”
TLE designs. However, other TLE designs, such as the “double tube” and the
“Bayonet/Scabbard tube” TLE’s, do not have Intermittent Blowdowns on the TLE Exchangers.
TLE designs, with boiler water on the tube side of the exchanger, are generally considered less
prone to deposition and corrosion, because of the higher velocities on the tube side compared
to shell side passes.
In the following drawing, Figure 4, is an example of a boiler water/steam circuit with vertical
Shell and Tube TLE’s, and the boiler water downcomers and risers to the steam drum. Also
note that in this particular design, the steam separation internals consists only of a baffle
system on the boiler water Risers and a demister pad for steam/water separation. Note also
the vortex breaker on the boiler water Downcomers, and the location of the Continuous and
Intermittent Blowdowns:
Sat Steam
Demister
to Superheater Pad
Typical
Typical
Steam TLE
TLEQuench
QuenchCooler
Cooler&&
Drum Steam
SteamDrum
DrumSystem
System
IBD Tube Sheet
CBD
Vortex Vent
BFW Preheater
Flow Breaker (SQE)
CBD
Page
612 7
Organic Oxygen Scavengers, are normally used because of the high purity makeup
feedwater water quality, as they do not contribute dissolved solids to the boiler water, and
most are also volatile. In addition, organic oxygen scavengers assure a reducing environment
for formation of protective magnetite to passivate and minimize feedwater iron entering the
steam drum.
Typical Organic oxygen scavenger molecules include, but are not limited to:
1. Carbohydrazide
2. Hydroxylamines
3. Hydroquinone
Boiler Internal Treatment Programs, are typically phosphate based, in most cases also
blended with dispersant polymers and caustic, to achieve a target sodium/phosphate ratio in
the boiler system - or the program is an All Volatile treatment.
1. Congruent pH/phosphate control
2. Alkaline pH/phosphate control, particularly if concerned with “acidic phosphate”
corrosion
• All Polymer programs are not typically used in Ethylene TLE Boiler System’s
All Volatile Treatment Programs and Steam/Condensate Amines Programs:
The three (3) primary physical and chemical properties used in selecting amine molecules
include:
• Neutralizing Capacity: Ability to neutralize acids (generally CO2), and is
primarily determined by the molecular equivalent weight.
• Basicity: Ability to elevate the pH of water after neutralizing the “acids”.
• Distribution Ratio: quantity of amine present in vapor phase versus liquid
phase.
1. With All Volatile (AVT) Internal Treatment Programs, usually the primary amine
molecule used will have a low distribution ratio, such as Monoethanolamine (MEA), to
protect the boiler water system.
• Typically in practice, the low distribution ratio amine (MEA) will be blended with
other amine molecules with higher distribution ratios and basicity; such as:
Cyclohexylamine; Dimethylaminiopropylamine; Methoxypropylamine (MOPA), and
Morpholine.
2. Neutralizing Amines are also used in most Boiler Treatment Programs for control and
elevation of feedwater and steam condensate for corrosion protection.
3. When internal treatment programs are based on phosphate or phosphate/polymer,
usually amine blends with higher distribution ratios and basicity are recommended to
maximize volatility in the steam to protect steam condensate systems. This includes
the amine molecules noted above.
Page
613 8
Boiler Treatment Guidelines:
Although there are many agencies that publish Guidelines on Boiler Treatment, the Guidelines
generally followed in the Ethylene industry are the American “ASME Consensus Guidelines
on Operating Practices”, and the German “VGB Standards”. In some cases, Boiler
Manufacturers may also issue Guidelines for Boiler Treatment.
The following Table, Figure 5, lists the ASME and VGB Guidelines for Ethylene Plants; and a
comparison to the guidelines as typically used internally by GE Water.
GE Water
ASME VGB Ethylene
Boiler Feed Water Notes:
Dissolved Oxygen <0.007 0.020 0.007 1. ASME Consensus Guidelines states: "in all
Cation Conductivity, umhos <0.20 cases where the makeup water is
pH 8.8 - 9.6 9 - 10 9.2 demineralized, and the operating pressure is
Total Hardness + CO2 ND ND 600 PSIG, or greater, the internal boiler water
TDS 0.1 0.1 max chemistry should follow either Congruent
Total Iron, as Fe <0.01 <0.020 <0.01 Phosphate-pH control; Coordinated
Total Copper, as Cu <0.01 0.003 <0.003 Phosphate-pH control; or All-Volatile
Chloride, as Cl 0.01 max Treatment. In such programs, Free
Sodium, as Na <0.010 0.01 max
Hydroxide Aalkalinity must be absent (not
Silica, as SiO2 <0.020 0.02 max
detectable) in the boiler water to prevent
Organics (non-volatile) <0.2 0.5 max
alkaline corrosion.“
Chemicals for Preboiler Protection VAM*
* Volatile Alkaline Materials
2. Alternative Guidelines: In certain boiler
Boiler Water systems, where there is primary concern with
Specific Conductivity, umhos < 80 < 50 < 50
"acidic phosphate corrosion“, GEWPT
pH 9.3 - 9.7 Congruent
recommends "Alkaline Phosphate Treatment"
Total Alkalinity, ppm as CaCO3 NS
with a 4 to 10 ppm ortho-phosphate control
Free OH Alkalinity, ppm as CaCO ND
range; pH consistent with a minimum 2.8
Phosphate, as PO4 6.0 4 - 10
Na:PO4 ratio (pH less than 10.0); and a
Silica, ppm as SiO2 PSIG Dependent maximum caustic level of 1.0 ppm as NaOH.
Continuous Blowdown, % 1 2 (Caustic corrosion is still possible with
deposition).
Steam
Cation Conductivity, umhos <0.02 <0.02
pH 8.5 - 9.2
TDS, ppm 0.1 0.08
Total Iron, as Fe <0.020
Total Copper, as Cu <0.003
Chloride, as Cl
Sodium, ppm as Na < 0.010 <0.010 <0.010 Figure 5.
Silica, ppm as SiO2 < 0.020 <0.020 0.020 max
Note, that steam purity Guidelines are included in the above Table, but are not included in the
scope of this paper for discussion. However, steam purity in Ethylene Plants is very important
in relation to steam turbine fouling and production limitations. Turbine fouling can be a result
of silica volatilization; boiler water carryover; and contaminated attemperating water. In many
cases, steam purity restrictions are specified by the “Steam Turbine Manufacturer”.
Page
614 9
The following Figure 6 includes the typical VGB Boiler Treatment Control Parameters for high
pressure boilers at 1500 PSIG (103 Barg), or above; and the “Low range Alkaline Phosphate
Treatment (PT)”as compared to “All Volatile Treatment (AVT)”.
Figure 6.
Note: Frequently, the Ethylene Plant Operator’s choice for internal treatment programs are
limited by the TLE Design manufacturer, in order for the boiler warranty to be in effect.
Therefore, there may be a requirement to follow the above VGB HP Boiler Standards.
Page
61510
Effect of DNB
on tube metal temperature
Figure 7.
Pitting - corrosion may be the result of dissolved oxygen in the feedwater; and/or poor
practices during “start-up” and “off-line boiler lay-up”.
Overheating – failures may occur as a result of waterside deposits; excessive heat flux;
or poor circulation, in shell/tube design exchangers.
Page
61611
However, in some boiler systems, at less than 2000 PSIG (138 Barg) pressure, failures were
not completely eliminated. With shell and tube design TLE’s, the high heat flux on the tube
side and low boiler water circulation rates on the shell side, may result in phosphate hideout.
As a result, these shell and tube design TLE’s are more susceptible to “acidic phosphate”
attack, resulting in severe localized corrosion on the boiler water tube shell side of the TLE’s.
The chemical reaction considered with acidic species is as follows:
HCl + Na3PO4 Na2HPO4 + NaCl
• Although hydrogen damage may be suspected from acidic phosphate corrosion, GE
Water is not aware of cases in Ethylene Plants where hydrogen damage has been
reported. In GE metallurgical examinations performed to date, we have not identified
hydrogen damage in Ethylene Plant TLE’s.
In high heat flux zones, boiler water is likely to concentrate due to evaporation in contact with
the magnetite surface, and phosphate species may exceed their solubility limits and precipitate
– and/or “hide-out”.
In phosphate based treatment programs, the presence of iron oxides, at temperatures of 320
C (608 F) and above - and particularly if phosphate hideout is observed; increases the
possibility of phosphate salt precipitation, and therefore increases the potential for under
deposit corrosion (UDC) of “any” kind. Therefore, the more oxides present, the greater the
probability of corrosion.
The exact corrosion mechanism, at a given bulk boiler water pH or Na:PO4 mole ratio, is
difficult to assess because of many variables, such as deposit accumulations; feedwater
contamination; heat flux; and steam/water ratios that may be involved.
However, because of the evaporation/concentration factor present in high heat flux zones, this
may result in locally induced precipitation that changes the Na:PO4 ratio. Therefore, this
increases the possibility of localized corrosion damage, because of the boiler operator being
unaware that localized pH levels are “different” from those in the bulk boiler water.
Page
61712
Comparison of Utility and Industrial Boilers:
Industrial Boilers:
With Industrial fired and waste heat boilers (including TLE’s), the questions are not as
easy to answer since an “effect” does not always follow a “cause”. With the presence of
magnetite (Fe3O4); phosphate hideout; and boiler water temperature above 320 C (608 F); a
solid precipitate will not always form, and/or a reaction occur:
1. PO4 hideout does not necessarily mean acid PO4 corrosion, or caustic
corrosion will occur:
a. When PO4 hideout occurs, with temperature greater than 320C (608F) and
Na/PO4 ratio less than 2.8, acid PO4 corrosion is possible, but does not always
occur.
b. With PO4 hideout at greater than 2.8 Na/PO4 ratio, caustic gouging corrosion is
possible, but does not always occur.
2. PO4 hideout can change the boiler bulk water Na:PO4 ratio (up or down)
thereby affecting bulk water pH.
Page
61813
3. PO4 hideout is promoted with iron oxide deposition and high heat flux,
because of the thermal energy present to form the solid, and the absorption
in the iron oxides.
4. PO4 hideout potential increases with increasing - boiler operating pressure;
PO4 residual level; and with iron oxide laden tubes or boilers.
a. PO4 hideout and corrosion mechanisms are minimized and/or eliminated, when a
clean, passive surface is present in the boiler.
The VGB TLE low range phosphate treatment program for HP Boilers, noted earlier in this
paper, is also considered to be “alkaline phosphate” control - with the ortho-phosphate control
range specified to be 1.0 to 3.0 ppm with the boiler water pH in the range of 9.3 to 9.7.
In addition, the very low level of phosphate in the VGB program requires very pure boiler
feedwater at all times; as low ppb levels of contamination will most likely result in either
“acidic phosphate corrosion”, or “caustic gouging”. Therefore, feedwater purity must be
closely monitored and controlled.
Comparisons of the theoretical control of the VGB low alkaline phosphate versus the typical
congruent pH/phosphate program as practiced by GE Water, will be shown and discussed in
the next section, including a discussion of the same concerns when using AVT.
Page
61914
All Volatile Treatment Programs (AVT):
All Volatile Treatment (AVT) programs are commonly used in many Ethylene plants. IF the
makeup water is always high purity water, AVT will result in acceptable treatment results in HP
Boilers.
However, AVT does not provide any “buffering” in the cycled boiler water to reduce the impact
of low-level contamination, and/or provide any deposit control. Contaminants are always
possible in the feedwater as a result of slippage of acidic or alkaline ions from the external
treatment system, and/or cooling water leaks into turbine condensate.
• There are distinct advantages in the use of AVT, as long as high purity make-up water
can be assured. For example, the injection of “all volatile” treatment programs does
not require sophisticated chemical feed equipment and can be injected into the
Deaerator storage or the common boiler feedwater, even ahead of Attemperation water
take-offs.
• In contrast, with phosphate based programs, the chemical feed systems are often
complex and expensive; require significant operator attention and monitoring; and
generally must be fed to each individual cracking furnace steam drum. However, the
phosphate-based programs are significantly more forgiving and protective of the boiler
system corrosion rate, with low-level contaminant intrusion, than All Volatile
Treatement.
Recall in the VGB Standards, that AVT programs are specified with a pH range of 8.8 to 9. 5
in the boiler water. This means that amines with low distribution ratios will be necessary for
as much amine as possible to remain in the boiler water, and also have a high basicity, which
is the ability to elevate pH after the boiler feedwater is neutralized. The amine molecule most
effective at achieving this is MEA, and the MEA may be blended with amine molecules with
higher distribution ratios to also protect the steam and condensate system.
Page
62015
Generally, the analytical results for low-level silica in the feedwater are not accurate, and the
volatility of silica is not taken into consideration in the boiler cycle calculations.
In application of phosphate-based programs, the most accurate cycle calculations are usually
determined by: steam or feedwater flow; the chemical product feedrate; phosphate residual;
and/or a tracer that has been added to the treatment program. Some facilities also have fairly
accurate blowdown flow meters.
In some cases, the on-site boiler water analytical results are questionable; and/or too variable
with time, in relation to the calculated boiler residence time. Causes may include sample
systems not having adequate cooling or a continuous flow; or because of excessive time lag in
the sample system.
From a technical standpoint, it is usually of value to know the “residence time” in the boiler
system, in relation to boiler cycles. Frequently the boiler system volume is known, or can be
determined. By knowing the system mass volume, calculations can be performed to
determine residence time; including decay by a molecule such as phosphate or a tracer; and
elapsed time between measurements. An example of a curve developed in an Ethylene Plant
Boiler system is shown below in Figure 8.
Ethylene Plant
Retention Time Calculations
Time Constant & Retention Time, Hrs
80
Basis:
70 Boiler PSIA = 1522
Steam, M Lb/Hr = 95
BW Density, Lb/Ft3 = 42.37
60 Mass Volume, M Lbs = 67
50
40
30
20
10
25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100
Boiler Water Cycles
Figure 8.
Note: In this system example and referring to 75 cycles in the graph, the Time Constant
(Mass/Blowdown) is about 52-hours and the Retention time to 50% decay of the initial
concentration would be about 37-hours. The time lag in the boiler blowdown sample system,
if known, should also be taken into consideration.
Page
62116
Comparison of Alternate Treatment Programs:
This section will compare the theoretical boiler chemistry results, and the effects of low level
feedwater contaminants in comparing the VGB phosphate control in the 1 to 3 ppm range,
with the more traditional phosphate control in the 4 to 8 ppm range. Also compared will be
the effect of the low level contaminants on an All Volatile Treatment.
The Basis for the boiler system Computer Modeling for the discussion in this paper
was as follows:
• Demineralized/Condensate Makeup, Mixed Bed Polished, at 6.5 pH to the Deaerator
• Boiler Pressure at 1500 PSIG (103 Barg), and Boiler Cycles at 50
• Boiler Concentration Cell (based on the FW) at 1000 cycles (Considered a conservative
estimate of potential under-deposit concentration mechanism, as this is only boiler
water cycled by 20X).
• In the computer model, all studies with both phosphate based and all volatile treatment
programs; the HP Boiler steam produced was controlled at a constant pH level of 9.0,
with an MEA/Diamine amine blend.
• Computer Model Studies with chloride or sodium contaminant concentration levels,
were determined in increments from 0 to 30 parts per billion (ppb).
Page
62217
• Bulk Boiler water pH levels were determined in the computer modeling both at “boiler
water temperature” and at “25 deg C (77 deg F)” - the ambient sample cooler outlet.
• Boiler water phosphate residual levels for control range were:
o VGB Standards = 1 to 3 ppm Phosphate
o Conventional Phosphate = 4 to 8 ppm
Steam
Concentration Cell
Simplified Diagram of Cycles = 1000
Computer Modeling System Conc Blr Cell
Cell pH 10.70
pH at T 8.84
Cndn OPO4 60.05
Sodium 46.33
Steam
Chloride 5.00
Demin MU
Steam
Organic Na Cl
Acid Deaerator
PO4 Boiler Cycles = 50
Amine Blr BD
Boiler pH 9.61
pH at T 7.53
CMS Modeling OPO4 3.00
BFW Cndn BFW Blr BD Blr Cell Steam Sodium 2.32
Lb/Hr 921506 9308 1020506 20408 1000000 Chloride 0.25
PSIG 1508 1508 1508
umhos 0.067 0.80 0.06 16.15 252 2.41
pH 7.0 5.7 7.2 9.6 10.7 9.0
pH at T 7.35 8.84
M Alk 2.5 2.5 2.5 6.92 66.1 3.3
OPO4 3.0 60.1
MEA 0.59 1.51 1.48 0.58
Diamine 0.30 0.07 0.06 0.30
Free CO2 0.001 0.411 0.001 0.001
NaHCO3 0.006 0.089 0.001 0
CO3 0 0 0 0
Na 0.003 0.003 2.32 46.33
Cl 0.005 0.25 5.0
Note in the following graph, Figure 9, the very acidic condition of the boiler water, particularly
with the 20 to 30 ppb chloride slippage in the 1 to 3 range of phosphate; compared to the
continued acceptable pH control in the range of 4 to 8 ppm phosphate.
Page
62318
Boiler Water pH at Temperature
Chloride Contamination
Boiler Water pH @ Temperture
8.00
7.50
7.00 GE Water
6.50
6.00
5.50 VGB
5.00
0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0 5.5 6.0 6.5 7.0 7.5 8.0 8.5
Ortho-phosphate, ppm
Chloride Level 0 ppb 5 ppb 10 ppb 20 ppb 30 ppb
Figure 9.
Note in the following graph, Figure 10, the same pH depression “at temperature” in the
boiler concentration cell in the 1 to 3 ppm phosphate range, as compared to the acceptable
control when in the 4 to 8 ppm phosphate range.
9.00
8.50
8.00
GE Water
7.50
7.00
6.50
6.00
5.50
VGB
5.00
4.50
4.00
3.50
0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0 5.5 6.0 6.5 7.0 7.5 8.0 8.5
Ortho-phosphate, ppm
Chloride Level 0 ppb 5 ppb 10 ppb 20 ppb 30 ppb
Figure 10.
Page
62419
Note in the graph below, Figure 11, the same pH depressions in the boiler water
concentration cell when using AVT. With AVT, and only 5 ppb of chloride contamination, the
boiler water pH “at temperature” is well below an acceptable pH range
7.0
6.5
6.0
5.5
5.0
4.5
4.0
0 5 10 15 20 25 30
Chlorides, ppb
25 Deg C At Temp
Figure 11.
Note: in, the graph below in Figure 12, the effect on pH level “at temperature”, even with 0
ppb sodium slippage for the 1 to 3 ppm phosphate range, versus the acceptable range in 4 to
8 ppm phosphate.
7.80
Temperature
7.70
7.60
7.50 GE Water
7.40
7.30
7.20
7.10
7.00
0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0 5.5 6.0 6.5 7.0 7.5 8.0 8.5
Ortho-phosphate, ppm
Sodium Level 0 ppb 5 ppb 10 ppb 20 ppb 30 ppb
Figure 12.
Page
62520
Note, in Figure 13 below, in the concentration cell, the elevated pH and alkaline conditions
with sodium.
9.10
Temperature
9.00
8.90
8.80
GE Water
8.70
8.60
8.50
8.40
8.30
0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0 5.5 6.0 6.5 7.0 7.5 8.0 8.5
Ortho-phosphate, ppm
Figure 13.
Note below in Figure 14, with AVT, any sodium contribution will elevate the boiler water pH
above the VGB control zone. Thus, most likely there will be free caustic present.
10.0
9.5
9.0
8.5
8.0
7.5
7.0
0 5 10 15 20 25 30
Sodium Contaminant, ppb
25 Deg C At Temp
Figure 14.
Page
62621
These studies demonstrate, that with low level feedwater contamination, there is negligible
buffering in the boiler water, and operation will be in the “acid phosphate” corrosion range
with chloride slippage and the “free caustic” zone with sodium slippage.
Page
62722
The best guide for Operations to monitor the iron levels in the system, and the startup
progress, may be by comparing Millipore filters to the Babcock & Wilcox Charts. However,
determining the iron levels in the various forms such as: suspended (particulate); soluble; and
total iron; will be very valuable, from a technical and reference standpoint, and is
recommended during the procedure.
Typically, the filling of the boiler system with deaerated boiler feedwater and charged with
polymer, is accomplished prior to initiating the normal Ethylene Plant Cold Start-up.
The boiler system valving will be lined up for a normal boiler fill using the procedure
established by the Customer Site. It is intended that this fill procedure, using boiler feedwater
containing the polymer product, will flush through the economizers; the Secondary Quench
Exchanger; into the TLE Steam drum and TLE’s.
Following is a typical drawings of the Ethylene Plant Cracking Furnace, Figure 15:
Deaerator
Amine BFW
Preheater Demister
Pad Steam
Drum
PO4
Injection PIPPA
BFW
LCV
Econ Vortex
CBD
Breaker
Flow
CBD
Attemporation Tube Sheet
Supr Htr Vent
SH HP Steam To Quench
Water Tower
Feedstock
TLE
Pyrolysis Furnace
Dilution
Steam
IBD
Page
62823
Note: the polymer product used in the rinse/passivation will be added downstream of the
attemperating water takeoff to the Cracking Furnace being started up, as other Units are in
operation during this period. Therefore, the polymer dispersant product will only be injected
into this system, downstream of the steam drum level control valve and Attemperation water
take off.
Vent
Example:
FI To Superheater
Continuous &
To SQE
Intermittent Blowdowns
Steam Drum
To DSG
BFW BW LP
TLE
SC steam
Downcomer
IBD
HP
Cracked gas IBD Fl Tk
To
(Shell & Tube)
Atm
LP
Fl Tk Condensate
Sewer
To Figure 16.
MB Polish
Typical Procedure:
• Pump in the required quantity of the designated polymer dispersant product from the
Chemical Dosing Unit to achieve the target level of active polymer in the boiler system
when the boiler is at normal liquid level. This will require knowledge of the approximate
boiler system volume.
Page
62924
• The quantity of chemical required will be based on the known or estimated system volume
to normal operating level. This will include volume in the piping to the boiler; the BFW
Economizer; the Secondary Quench Exchanger; and the Steam Drum to about 30% level;
and the shell side of the TLE Exchangers.
• During the Cold Start-up, the boiler water will be monitored for pH, iron, silica, phosphate;
and suspended solids, to determine the level of contaminants present, and of Polymer
remaining. If these parameters are within the limits, the Boiler steam pressure can be
slowly brought up to design operating pressure, according to the normal startup procedure
and curves.
• As the Steam pressure is increased to normal operating levels, initiate high blowdown rates
by alternating between Bottom blows and Continuous blowdown valves. As the Boiler
pressure increases, if the phosphonated polymer product is used, the molecule will begin to
dephosphorylize into ortho-phosphate.
• As Boiler pressure increases, continue to check Boiler chemistry for pH; iron; silica; and
phosphate; targeting the boiler water control parameters. The level of polymer remaining
in the boiler may be determined from the Boiler water analysis.
o At some point in the usual startup sequence, it may be necessary to begin the
transition from the supplemental polymer product to the normal phosphate based
product to begin bringing Boiler Water phosphate levels and chemistry within the
target control parameters. Most polymeric dispersants are compatible with
phosphate.
Page
63025
Brief Review of Dispersant Polymer Molecules considered:
The comparison of the PMA and PIPPA polymers are shown in Figure 17, below:
Polymethacrylate
CH 3 (PMA)
CH2 CH
C O
CH3
O-
CH2 CH
O P OH
Poly(isopropenylphosphonic acid)
(PIPPA)
O
Figure 17.
Page
63126
Iron Transport Study:
The boiler system in the following study was a 1500 PSIG (103 Barg) vertical TLE with an
existing treatment program based on Congruent pH/Phosphate - without polymer.
• 1st Trial Step was to obtain baseline data iron transport with PMA for 16-day period
with active polymer at levels shown in graph in upper left corner of Figure 18 (15 to
90 ppm).
• 2nd Step was performed with PIPPA for 20-days at active polymer levels shown in
graph in lower right corner of Figure 18 (12 to 40 ppm).
Typical Iron Transport Levels during the Study:
• No polymer – less than 5%
• PMA polymer – less than 20%
• PIPPA Polymer – Greater than 80%
Figure 18 below shows the results of iron transport in a boiler system with PIPPA versus
PMA:
30%
25%
Iron Transport
20%
PMA vs. PIPPA
15%
10%
5%
0%
15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90
Active PMA Polymer, ppm
200%
150%
100%
50%
0%
Figure 18. 10 15 20 25 30 35 40
Active PIPPA Polymer, ppm
Page
63227
GEWPT Metallurgical Report Summaries:
1. Malaysia
• Plant operated for several years prior to the first failure. The TLE failures were
associated with poor boiler chemical control from chemical feed system; and
feedwater contaminant as a result of slippage from Cation and Mixed Bed
Condensate Polishing. Failures appeared to be related to “acidic” corrosion gouging
with corrosion products primarily iron oxide, with some phosphorus present. No
evidence of over-heating was found. Failed TLE’s were either replaced or repaired.
Boroscope inspections during next turnaround indicated no new corrosion problems.
• Shortly after Turnaround startup, and a short period of operation, TLE failures
occurred again as result of low-level acidic contaminant slippage from the mixed bed
demineralizers. The slippage was associated with Mixed Bed Condensate Polisher
failures (loss of resin) and depressed feedwater pH. (Mixed Bed Regeneration with
HCl and NaOH). Again no overheating was evident in the metallurgical examination.
Iron oxide, sodium, and phosphorus was present in the deposit; and Maricite
(NaFePO4) was identified as being present in the deposit by x-ray diffraction.
2. Australia:
1. TLE failures appeared to be the result of acidic corrosion, with iron oxide and
significant level of chloride present, possibly associated with chloride intrusion.
2. A second failure was compounded by excessive chip scale from upstream of TLE
breaking loose during start-up and obstructing flow through bottom of Shell and
Tube TLE. The chip scale was primarily iron oxide, and again included significant
quantities of Chloride present.
3. Texas:
• Failure was in the horizontal BFW convection coil, rather than a TLE. Low flow is
very conducive to steam blanketing in horizontal tube passes. No evidence of over-
heating was noted. This corrosion mechanism may have been either acid or
alkaline. Iron, sodium, and phosphate were found, but not in the ratio expected for
maricite. The pattern of longitudinal gouging indicates the stratification of the
steam and water phases, and the evaporation above the water line concentrated the
normally soluble salts, forming a localized aggressive environment.
Page
63328
4. Louisiana:
• Failures were in a vertical Shell and Tube TLE near the inlet tube sheet. The deposit
within the gouged area was primarily iron, sodium, and phosphorus in a ratio
consistent with Maricite (NaFePO4). Therefore, the corrosion mechanism was
considered to be “acid phosphate” attributed to “under-deposit corrosion” (UDC) and
“departure from nucleate boiling” (DNB). No evidence of overheating damage.
5. Sweden:
• A number of failures of TLE Exchangers and Auxiliary Boiler Tubes occurred during a
9-month period. Treatment program was “All Volatile Treatment (AVT)”. Failures
were believed to be as a result of chloride intrusion. Although alkaline conditions
were reported to be maintained in the boiler water, the ability of AVT programs to
neutralize contaminants locally in a “concentration cell” is limited. Sources of
chloride ingress needed to be identified and eliminated.
• It was also suggested that chlorinated high MW organics might pass through the
demin plant and breakdown in the boiler to give higher than normal levels of
chlorides. AVT program cannot cope with suggested high BW chloride levels.
Page
63429
References:
1. American Society of Mechanical Engineers. “Consensus on Operating
Practices for the Control of Feedwater and Boiler Water Chemistry in Modern
Industrial Boilers”, 1994 with 1998 Editorial Corrections.
2. American Society of Mechanical Engineers. – “A Practical Guide to Avoiding
Steam Purity Problems in the Industrial Plant, 1995
3. “Considerations for High Pressure Boiler Chemical Treatment”, Setaro, Daniel
M., – Equipment and Chemistry, AIChE 2006.
4. “HTP-2, A New Iron Dispersant for Medium to High Pressure Industrial
Boilers”; Scott M. Boyette & Frederick A. Elliot; International Water
Conference, 1992
5. Internal GE Water Metallurgical Reports
6. “On-line Cleaning of Boilers Using a Novel Polymer Technology to Avoid
Acid”, Carter W. Brown, Mark A. Moore, Saleh A. AlBenHamad, and Michel
Didden; 4th Middle East Refining & Petrochemicals Conference and Exhibition,
October 2003, Kingdom of Bahrain
7. “Optisperse HTP-2 Polymer”, GEWPT Boiler Technical Marketing, Nov- 2006
8. Protection Against Caustic Embrittlement by Coordinated Phosphate pH
Control”, Whirl, S.F.; Purcell, T.E.; “International Water Conference,
(Engineers’ Society of Western Pennsylvania), Pittsburg, PA, 1945
9. “Tube Failures in Waste Heat Boilers: Case Histories”. NACE 05437,
Corrosion 2005, Hargrave, Robert, GE Water & Process Technologies. .
10. VGB Guidelines for Feedwater, Boiler Water and Steam Quality for
Power Plants/Industrial Plants; 2004.
Page
63530