Вы находитесь на странице: 1из 8

P.

Nu: JEAS 201712-1014

Higher Institute of Science and Technology – Al khums


Researches of the 6th Scientific Conference 28/12/2017

ATP-EMTP Simulation of Transient in Mechanically


Switched Capacitor with Damping Network
Adel M. Handi, Mohamed R. Elarqaa, Haziah Abdul Hamid
a
Electrical Department, Science and Technology Institute
Al-khums, Libya
b
School of Electrical Engineering System
University of Malaysia Perlis
*Corresponding Author: adel_handi@yahoo.com

Abstract:
A Mechanically switched capacitor with damping network (MSCDN) has designed to assist the
dual function of reactive power compensation and harmonic filtering; a simple and low-speed
solution for voltage control and network stabilization under heavy load conditions. Transient
disturbances in power systems lead to damage key equipment, and have a great influence on system
reliability. Therefor, to avoid harmonic resonance problems and unwanted voltage transients in
MSCDN. Transient studies were depended on the system configurations and the switching
operation on circuit breakers witch used to connect the unit to power systems. In this work, the
transient waves were investigated by analytical calculation and ATP-EMTP simulation software.
The analytical calculation was conducted by using Laplace and Laplace inverse to obtain on the
correlation of current and voltage across all MSCDN’s components. Besides, the simulation also
used to predict of the voltage and current across all system components. The study was presented
the comparison between analytical and simulation results. The simulation was given transient’s
results as in that happen in the real system. The optimized parameters of each component were
addressed, the best closing time of circuit breaker to get low disturbances was 5 ms in the main
capacitor.
Index Terms—MSCDN, transient, ATP-EMTP and Mathcad software.
: ‫الملخص‬
‫( صمم ليدعم الوظيفة مزدوجة لمعوض الطاقة الفعلي ومرشح‬MSCDN) ‫المكثف ذو التبديل الميكانيكي مع شبكة التخميد‬
‫ تؤدي االضطرابات‬.‫ بعتبر حل بسيط وذو سرعة قليلة للتحكم في الجهد وتثبيت الشبكة تحت ظروف الحمل الثقيل‬.‫التوافقيات‬
‫ لتجنب مشاكل الرنين‬،‫ لذلك‬.‫ ويكون لها تأثير كبير على موثوقية النظام‬،‫العابرة في أنظمة الطاقة إلى تلف المعدات الرئيسية‬
‫ تعتمد دراسات الحاالت العابرة على‬.‫التوافقي وعابرة الجهد غير المرغوب فيها في المكثف ذو التبديل الميكانيكي مع شبكة التخميد‬
.‫تركيبات النظام وعملية القفل في القواطع الدائرة والمستخدمة لتوصيل الوحدة إلى أنظمة الطاقة‬
‫( تم إجراء الحساب‬ATP). ‫ ا لموجات العابرة تم دراستها عن طريق الحسابات الرياضية التحليلة وبرنامج المحاكاة‬،‫في هذا البحث‬
‫التحليلي باستخدام البالس و البالس العكسي للحصول على عالقات التيار والجهد عبر جميع مكونات المكثف ذو التبديل الميكانيكي‬
‫ وقدمت الدراسة مقارنة‬.‫ استخدم ت المحاكاة أيضا للتنبؤ بالجهد والتيار عبر جميع مكونات النظام‬،‫ إلى جانب ذلك‬.‫مع شبكة التخميد‬
‫ افضل القيم لكل مكون وضعت‬.‫ أعطيت المحاكاة نتائج الحاالت العابرة كما تحدث في النظام الحقيقي‬.‫بين النتائج التحليلية والمحاكاة‬
.‫ مللي ثانية في مكثف الرئيسي‬5 ‫ وكان أفضل وقت إغالق القاطع للحصول على حاالت عابرة منخفضة هو‬،‫في البحث‬

‫ ( و برنامج‬ATP ( ‫ برنامج المحاكاة‬, ‫ الحاالت العابرة‬, ‫ المكثف ذو التبديل الميكانيكي مع شبكة التخميد‬:‫الكلمات المفتاحية‬
.‫الماتكاد‬

1
Adel M. Handi et al

equipment. Problems with switching of small capacitive


and inductive currents can be controlled by switching
Introduction time. For normal conditions, controlled switching reduces
A mechanically switched capacitor with damping voltage and current transients to a minimum value. The
network (MSCDN) is a version of mechanically switched main goal of this study is to recognize and investigate the
capacitor (MSC), which designed as C-type filter with single phase MSCDN at switching operations to control
additional damping circuit. MSCDN provides essentially and optimize voltage levels. The most important and
voltage support without increasing existing system recent study in MSCDN transient was carried out by
harmonics. Normally, MSCDN can be represented in a Abdul Hamid, Harid [3], who studied transient stresses
circuit form. MSCDN is a suitable reactive power during energization of an MSCDN in a 400 kV system
compensation system for HV energy transmission and the initial modelling validation was carried out
networks [1]. Due to that, it is able to stabilize the voltage through analytical solutions using a single-phase
and raises the transmission capacity to certify the equivalent circuit and Laplace transforms for the
availability of reactive power for feeding in the injection calculation of transient voltages and currents at all circuit
of reactive power at short notice [1]. The flexible nodes. Their paper described simulation results for
MSCDN system may eliminate any risk of a voltage transients occurring with corresponding ATP simulations
increase when required; where it supports high capacity during energization of an MSCDN. As expected,
voltage levels and on the other hand, may be switching made at an unfavourable time generates
disconnected from the grid at lower capacity. overvoltages at almost all circuit nodes, particularly at the
reactor and damping resistor, initiating their arrester
A transient phenomenon is generally an obvious operations [3].
appearance of an unexpected temporary change in the
system situations. This change in voltage or current The more recent paper on MSCDN was presented by
occurs over a short period of time. Transient phenomenon Zimmer, Dragon [4], They have given a brief insight of
is certain of 80% of all electrically-related interruption. the basic design considerations for MSCDN including the
Effective damping equipment of transient voltage can dimensioning of the basic components and the calculation
increase the life of electrical and electronic equipment. of operation voltages and currents using a simple
The previous transient studies were focused on several equivalent circuit diagram. They also discussed basic
cases; namely switching surge analysis, shunt reactor & switching phenomenon in MSCDN system which is
capacitor switching, vacuum circuit breaker switching, simulated using a MATLAB SimPowerSystems model.
power-electronic device switching and more which can There are some techniques to take control of transient
be viewed in reference [2]. overvoltage and to limit overvoltage at remote locations.
One of the techniques is by employing some devices at
Energisation transient is a transient overvoltage the utility’s switched capacitor bank as pre-insertion
originating from connecting some parts of the power resistors/inductors and MOV arresters [5], fixed inductors
system to a potential source which is incapable to store [6], series inrush-current-limiting reactors [7]. The other
technique is by using smaller size banks instead of a
energy. It is a power quality issue because it is one of the
capacitor bank [7], and also avoiding the application of
most frequent system-switching operations. During
capacitors at multi-voltage levels to eliminate the
normal energisation of the filter banks, the fast-fronted
possibilities of secondary resonance [8]. Another
voltage and current waveforms may be generated which approach is to control the time of switching the device by
lead to producing large rates-of-change in the voltage and closing it at the best possible time (when voltage across
current, which consequently may expose the filter the switch is zero) rather than altering the circuit
components to hazardous voltage stresses. Generally, parameters. By taking into consideration the complexity
when a capacitor bank is switched on to a supply, there is of the transient calculations (overvoltages and
a powerful current surge because, for the first instant, the overcurrents), it is suggested that the simulation is carried
capacitor bank appears as a short circuit to the network. out with Alternate Transients Program-Electromagnetic
In the MSCDN system, the disconnection of capacitor is Transient Program (ATP-EMTP) software, this software
usually made at an instant corresponding to the minimum is simple in use and has many options such as allow the
current of the system. Then, followed by the current complete representation of all the electrical elements.
interruption and the capacitor are charged to full system Dommel [9], [10] and [11] have explained the theory,
voltage. rules in modelling various components and expanded
capability of ATP tool in power system studies. There are
Generally, in the electrical operation, the voltage and many studies done which have used ATP-EMTP as a
current system does not remain within specified limits; simulation tool for transient studies such as Abdul
due to changes in the load conditions and system Hamid, Harid [3] and Ali [12].
configuration caused by switching operations that affect
the system voltage and current. Thus, the voltage rises in In this work, the main objective of this work is
the opening or closing events of a switching which should studying the observed transient in MSCDN system. The
not exceed the rating limits of the network system study presented an analytical procedure by using s-
2
Adel M. Handi et al

domain and time-domain for all components of single-


phase MSCDN and compared it with ATP-EMTP
simulation. Furthermore, to investigate, simulate and
compare the affects of energizing transient stresses
produced at all single phase MSCDN components. For
validation purposes, the simulation of the MSCDN circuit
was done to compare with the analytical calculation in
single phase case; where these analytical calculations
conducted by MathCAD program. The voltages and
currents profile of each MSCDN components were Figure 2. Proposed System Topology [13].
illustrate. The sample of simulation procedures by ATP-
EMTP program was presented, which help users to As a rule, in insulation coordination overvoltages and
understand simulation procedures. impulse voltages are defined in terms of peak value
(referred to earth). It is also convenient to consider the
I. METHODOLGY system voltage phase-to-earth peak value: that is, √2/√3 =
0.816 times the usual rms phase-to-phase voltage. The
The proposed methodology of this research is presented rms phase-to-phase voltage = 400 kV. The calculated
in Fig. 1 for MSCDN system. The transient in single voltage amplitude of 400 kV is equal to On the
phase-MSCDN was studied by mean of analytical other hand, MSCDN can be as single phase regarding to
calculation which is performed by MathCAD program, AC source type. The frequency is fixed to 50 Hz which
then the comparing with ATP-EMTP simulation results. can changed by simulation options. The surge arresters of
The analytical computation of transient stresses imposed MSCDN system is metal oxide type. The characterization
on MSCDN components during routine switching. of these arresters was taken from datasheet of [13]. The
Subsequently, ATP-EMTP simulation of MSCDN in the surge arresters are installed to protect power system
same initial conditions of analytical calculation was equipments as filter reactor and damping resistor in
investigated for the purpose of modelling validation. MSCDN from transient overvoltages.

TABLE 1. The impedances of system components in s-domain [13].


Components Value s-domain
Main capacitor, C1 4.54 µF

Auxiliary capacitor, C2 35.81 µF

Damped resistor, R 474.07 Ω 474.07


Filter reactor, L 282.94 mH (282.94 × 10-3) s
Resistor arrester, Sa 115 MΩ 115 × 106
300kV
Reactor arrester, La 2 mH (2 × 10-3) s
Resistor arrester, Sb 77 MΩ 77 × 106
200 kV
Reactor arrester, Lb 3 mH (3 × 10-3) s
Impedance, Zsc 2 Ω + j (2πf 2+0.0637 s
(63.7×10-3 H))
Impedance, Zsg 150 Ω 150

The MathCAD program [14] is used to simplify


complicated mathematical equations which were found
Figure 1. Flowchart of research steps. from finding the equivalent impedances, voltage and
currents of MSCDN circuit. The analytical calculation is
The supply network in this work (as shown in Fig. 2) used to model the equivalent circuit of MSCDN system
consists of a source voltage behind short circuit and surge (Fig. 3). The analytical calculations can be divided into a
impedances. As well, there are two surge arresters which calculation based on t-domain differential equations, and
were installed to MSCDN circuit, one on damped calculation based on s-domain complex frequency
resistance R side, and the other on filter rector L side. domain circuit models [15, 16].
MSCDN consist on main shunt capacitor C1, connected
to damping network (An auxiliary capacitor (C2), The analytical calculations for the computation of
damped resistor (R) and filter reactor (L). Fig. 2 shows currents and voltages of the circuit components was
the whole system arrangement and its components values achieved and implemented in Mathcad using the Laplace
were presented in Table 1. transform method [14]. The analytical calculation which
is considered a DC voltage source as zero initial
conditions was used to estimate the transient overvoltages
3
Adel M. Handi et al

of MSCDN; this means that the voltage source was


represented with DC source voltage in system circuit. The (2)
( )
DC source voltage gives a constant application of the
highest transient voltage event [13]. The voltage
amplitude of DC source is equal to the peak voltage of a
400 kV system. Furthermore, in analytical calculations,
the installed surge arresters are parallel to damped
resistor (R) and the filter reactor (L) is represented by
lumped resistances. These lumped resistances are Vout
specified based on the leakage current flows through the
arrester at a continuously-applied power frequency
voltage. In this study, the analytical calculation identified
voltages and currents waveforms of all elements in the
MSCDN circuit; this calculation allows simplification Figure 4. Simplified MSCDN circuit for analytical calculations.
using the Laplace transformation of the impedances of Similar procedure was done for the total in (source-
each component; i.e., these impedances were expressed in side) impedance; where it can be obtained from a parallel
terms s-domain as shown in Table 1. combination of the short circuit and surge impedances.
The equivalent impedance of the source-side is presented
as:

(3)

As a result, the final simplified circuit consists of a


voltage source (Vin) in series with the equivalent source-
Figure 3. Single-phase MSCDN circuit for analytical studies.
side impedance (Zin) and the equivalent load-side
impedance (Zout). According to voltage divider method,
The following equation represents the peak DC voltage in the load-side (out) voltage can be determined as in
the s-domain: Equation (4):

(1) ( ) (4)

The MSCDN circuit was first simplified based on


Kirchhoff's circuit laws; where these reductions were As in MSCDN circuit, the currents or voltages
done regarding to series or parallel connection of equations in time-domain can be obtained using inverse
MSCDN components. The results from these simplified Laplace transformation, which is basically used for
calculations were lead to determine the total impedance plotting the currents or voltage waveforms. Based on the
of the circuit [17] and then this lead to determine current reduced circuit which shown in Fig. 3, the current of
and voltage equation. The impedances of surge arrester is main capacitor (IC1) is the same current flow through the
equivalent to arrester resistance (Sa or Sb) connected equivalent impedance which represents the parallel
series with inductor (La or Lb). Then, found the ZeqL combination of the C2-ZeqL and ZeqR. Thus, the resulted
impedance is equivalent to the impedance of reactor (L) voltage is equal to the damping resistor voltage (VR), and
and parallel connected its surge arrester (Sa), on other is represented in s-domain and time domain.
side, the impedance ZeqR represents resulted impedance of Consequently, the resistor current is determined by
parallel connection between the damping resistor (R) and dividing the voltage of resistor by the resistance of
its surge arrester (Sb). After doing this simplification, the 474.07 Ω. The voltage of filter reactor can be obtained
resulted circuit was shown in Fig. 4. The circuit in Fig. 4 from voltage of equivalent impedance which is obtained
is an advance reduced by joining the two parallel from the combination of reactor and its arrester (ZeqL). In
impedances of C2-ZeqL and ZeqR. The resultant impedance addition, the filter reactor current was obtained by
was combined in series with the main capacitor (C1) of dividing the resulted voltage with its impedance of
MSCDN. 282.94 mH. After representing and calculating the
Then, by combining these impedances in series together, voltage and current of each MSCDN components in time
the total out (load-side) impedance, which also domain expressions based on equivalent impedances and
equivalents to the total impedance of the MSCDN, is simplification using MathCAD program, these
expressions were plotted and compared with the resulted
finally represented as:
voltage and current waveforms which was obtained from
ATP-EMTP simulation of MSCDN at the same initial
conditions.
( )

4
Adel M. Handi et al

Furthermore, the transient study was investigated in The response of voltage and current values of the
single phase MSCDN system by simulation using ATP damping resistor are presented in Fig. 6a by plotted
software. The energisation cases during single phase- resulted equations, the highest magnitude of the resistor
MSCDN were conducted for specified periods by setting current reached approximately 523 A. The resistor
the opening time of switch at 1 second as well as the voltage has a magnitude of 248 kV (0.76 p.u). According
closing time at 0, 3, 5, 7.5 and 10 ms. In this work, the to equations, the oscillation frequency is calculated to be
voltage and current transient of main and damped around 142.5 Hz. The response plots of the filter reactor
network components were plotted for various closing voltage and current are shown in Fig. 6b. The filter
time. Besides, the ideal and worst voltages and currents reactor voltage has a magnitude of approximately 248 kV
of each components were identified. The closing time of (0.76 p.u) and the oscillating at a frequency of 140.6 Hz.
switch were changed each run and then from resulted The amplitude of the current that flows through the filter
plots, the maximum overvoltages and overcurrents were reactor is approximately 809 A. The current magnitudes
observed. of the surge arrester at filter reactor-side as well as at
damping resistor-side were relatively small and were
found about 216 and 322 A respectively. As seen, the
magnitude voltages were high, where surge arresters are
II. RESULTS AND DISCUSSION used to absorb the overvoltage and protection purposes.

The responses of the main capacitor current and voltage Finally, the comparisons of resulted voltage and current
are plotted in Fig. 5a. The resulted waveform shows that waveforms in each components of MSCDN were
the maximum value of the capacitor current is about 950 conducted through two ways. The plotted graphs from
A at 1.1 ms. The peak of the capacitor voltage can be analytical computation using MathCAD program
calculated from Equation or from waveform in Fig. 5 and (MathCAD 14, 2007) were compared with the resulted
is found to be about 468.75 kV (1.44 p.u) at 3.25 ms. responses from ATP-EMTP program at the same initial
Besides, the frequency of oscillation can be determined conditions. The analytical calculation was presented the
from Fig. 5, and is found to be approximately 131 Hz. transient response as equations and graphs; but, ATP-
Similar to the main capacitor, the voltage and current EMTP simulation presented only graphs. The voltage and
values of the auxiliary capacitor are plotted in Fig. 5b. current waveform in Fig. 5 and Fig. 6 which resulted
The resulted waveform showed that the maximum value from analytical calculation and Fig. 7 from ATP-EMTP
of the auxiliary capacitor current is about 809.5 A at 1.6 simulation program had the same waveforms and the
ms. The peak of the capacitor voltage can be calculated calculated magnitudes of voltage peaks, current peaks,
from waveform in Fig. 6 and it is found to be about 52.3 and oscillating at a frequency are same for the main
kV (0.16 p.u) at 3.65 ms. The frequency of oscillation can capacitor, auxiliary capacitor, damping resistor, filter
be determined from Fig. 5b, and is found to be around reactor, filter reactor-side and damping resistor-side surge
133.3 Hz. arresters.

(a)
(a)

(b)
Figure 5. The voltage and current response using equivalent circuit and
Laplace transform method for (a) Main capacitor and (b) Auxiliary
capacitor.

(b)
5
Adel M. Handi et al

Figure 6. The voltage and current response using equivalent circuit and Figure 7. Voltage and current response of MSCDN components using
Laplace transform method for (a) Damping resistor and (b) Filter ATP-EMTP simulation program: (a) Main capacitor (b) Auxiliary
reactor. capacitor (c) Damping resistor (d) Filter reactor.

The same results means when substitute any time in Fig. 8 presents the voltage and current responses of
any equations was got voltage or current values which main capacitor of single-phase MSCDN during
were same values form ATP-EMTP’s graphs (read values energisation operation recorded at various closing time of
from figure or get from software). These results indicated the switch at 0, 3, 5, 7.5 and 10 ms. The overvoltage and
to that solving procedure of MSCDN’s circuit via ATP- overcurrent values of all MSCDN components were
EMTP simulation software was similar to analytical found from ATP-EMTP simulation program and
procedure. The comparison of voltage and current compared by plotting in Fig. 9. The maximum
responses obtained from the two calculation procedures overvoltages were in the main capacitor, especially at
(analytical and simulation) has produced satisfactory zero closing time of the switch.
results, which indicates the satisfactory representation of The worst case is considered based on the highest
the model. It was found that the analytical approach gives overvoltages and raising shape of voltage and current
a better understanding of the whole interrupting process waveforms, which they extracted and concluded as in
and gives a clear explanation of such complicated shapes Fig. 8 as an example for the main capacitor and Fig. 9 for
of transient voltages. However, ATP/EMTP simulation each MSCDN components. The resulting worst and ideal
gives more complete results considering all boundary cases of energisation transient across the main capacitor
conditions automatically. More importantly, chance to were at zero and 5 ms of closing time of the switch
make a mistake when putting in the input variables is also respectively as shown in Fig. 10 for voltage and current
much smaller when using ATP/EMTP program. responses. Note that the waveforms generated in the
worst switching cases are represented by the red line,
The aim of the obtaining simulated voltage and current while the green line represents waveforms obtained for
responses is to study the transient behavior of the the ideal switching cases. It can be seen that the highest
MSCDN components during energisation operation magnitude of the generated voltage in Fig. 10 is 382.57
(switch on). The voltage and current responses of each kV (1.1 p.u). The oscillation frequency is calculated at
MSCDN components were plotted and analyzed at approximately 58 Hz. The waveform of ideal-cases of
different closing times of the switch (i.e., 0, 3, 5, 7.5 and energisation transient slightly differs from the original
10 ms). This is to find the ideal and worst cases during sinusoidal waveform as shown in Fig. 10.
energisation operation. The overvoltages as well as rising
shapes are the most important factors to identify the worst 400

and ideal cases. The other factors are rising time, [kV]
250
oscillation frequency and steady state or settling time.
100

-50

-200

-350

-500
0 5 10 15 20 25 30 35 [ms] 40
noname3.pl4: v:XX0009-XX0001
noname33m.pl4: v:XX0009-XX0001
noname35ms.pl4: v:XX0009-XX0001
noname375ms.pl4: v:XX0009-XX0001
noname310m.pl4: v:XX0009-XX0001

1200
[A]
800

400

-400

-800

-1200
0 9 18 27 36 [ms] 45
noname3.pl4: c:XX0009-XX0001
noname33m.pl4: c:XX0009-XX0001
noname35ms.pl4: c:XX0009-XX0001
noname375ms.pl4: c:XX0009-XX0001
noname310m.pl4: c:XX0009-XX0001

6
Adel M. Handi et al

Figure 8. The voltage (up) and current (down) waveforms across main specified level [18, 19]. The simulation results were
capacitor registered at various closing times. investigated to study and simulate the voltage and current
response across filter reactor, as well as to identify the
The current response as shown in Fig. 10, the worst-cases ideal and worst closing time of switch.
of energisation transient has the magnitude overcurrent
about 1049 A. This is the highest value at zero closing
time of the switch compared to the other times across Main Capacitor
main capacitor of MSCDN. The ideal case with lowest
current was at 3 ms, but this waveform has more
disturbances than the waveform at 5 ms with small
difference in values, so, the ideal case considered is at 5
ms closing time of the switch. In addition, for damping
resistor, the ideal switching case has the current flowing
through of about 100 A. This value has greatly increased
to 518 A in the worst switching case as shown in Fig. 10.

Damping Capacitor Damping Resistor


Filter Reactor Main Capacitor

400

300 Damping Resistor


200

100
M…
F…
0 D…

0 3
D…

5 7.5 10

Damping Resistor Damping Capacitor


Filter Reactor Main Capacitor

400

300 Filter Reactor


200
M
100 a…
Fil
t…
0 D
a…

0 D
3 a…
5
7.5
10

Figure 9. Overvoltage (up) and overcurrent (down) values of MSCDN


components registered at various closing time.

Furthermore, Fig. 10 presents the ideal and worst of


voltage and current responses occurring across the filter
reactor during the energisation of MSCDN. The voltage Figure 10. Ideal and worst case of single-phase voltage (left) current
responses presented in Fig. 10 which showd that the (right) responses in the components of MSCDN.
reactor voltage is kept well below the rated value when
the energisation was made at an ideal time.
On the other hand, the controlled switching of circuit
However, if the MSCDN is energized at the worst time breakers is done by changing the closing and opening
instant during the cycles, the resulting voltage has the times of the switch so as to exanimate and to reduce
highest magnitude of 245.5 kV at zero close time. More switching transients. In the energisation studies, the
importantly, the generated transient manifests itself in the maximum overvoltage transient was 382.566 kV at zero
form of a voltage spike and persists for a short period of closing time. The voltage and current waveforms across
nanoseconds. The highest current generated at worst case each MSCDN components (main capacitor, auxiliary
is 941 A when set closing time of switch at 10 ms, the capacitor, damping resistor, filter reactor and both surge
ideal current was 530 A at closing time of switch is 5 ms. arresters) were presented and analyzed based on the
Generally, to avoid the external and internal deterioration significant factor as overvoltage, overcurrent peaks,
of the filter reactor, the voltage stress should be fixed at a peaks time and oscillation frequency. The finding results
compared with the rated values (1 p.u = 326.6 kV,
7
Adel M. Handi et al

Frequency = 50 Hz). The results of synchronous [4] Zimmer, H.; Dragon J.; and Hanson J. Basic design
energisation show that energisation of MSCDN at considerations for a mechanically switched capacitor with
random closing time of the switch produced the transients damping network (MSCDN) within a high-voltage-grid. in
at almost all components. As a result of the switching 15th European Conference Power Electronics and
Applications (EPE). 2013.
investigation, the main capacitor is identified as one of [5] Grebe, T.E. Application of Distribution System Capacitor
the MSCDN components that experience the maximal Banks and their Impact on Power Quality. IEEE
overvoltage. The interesting results for single phase (ideal Transactions on Industry Applications, 1996. 32, 714-719.
and worst cases) were addressed below. Where, the ideal [6] Duran-Gomez, J.L. and Enjeti P.N. A new approach to
closing time of switch across main capacitor was at 5 ms. mitigate nuisance tripping of PWM ASDs due to utility
capacitor switching transients (CSTs). IEEE Transactions
Ideal Worst Ideal Worst on Power Electronics, 2002. 17, 799 - 806.
Case Case Case Case [7] Cipcigan, L.; Chindris M.; Rull J.; Rusu A.; Sumper A.;
MSCDN Over- Over- Over- Over- Ramirez R.; and Alves R. Mitigation of Capacitor Bank
Component voltage voltage current current Energization Harmonic Transients. IEEE/PES
(kV) (kV) (A) (A) Transmission and Distribution Conference and Exposition
(Closing (Closing (Closing (Closing 20061-5.
time) time) time) time)
[8] McGranaghan, M.F.; Zavadil R.M.; Hensley G.; Singh T.;
Main 335.72 382.57 505.189 1049.33
capacitor (5 ms) (zero) (5 ms) (zero) and Samotyj M. Impact of Utility Switched Capacitors on
Auxiliary 42.54 49.96 529.506 941.002 Customer Systems-Magnification at Low Voltage
capacitor (zero) (10 ms) (5 ms) (10 ms) Capacitors. IEEE Transactions on Power Delivery,
Damping 47.19 245.47 99.538 517.78 1991908 - 914.
resistor (5 ms) (zero) (5 ms) (zero) [9] Dommel, H., EMTP Theory Book, ed. M.P.S.A.
Filter 90.18 245.47 529.506 941.002 Corporation. 1992, Vancouver, British Columbia.
reactor (5 ms) (zero) (5 ms) (10 ms) [10] Leuven, K.U., Alternative Transients Program Rule Book.
1991: Leuven EMTP Center, Haverlee, Belgium.
III. CONCLUSION [11] Martinez, J.A. and Martin-Arnedo J. Expanding
Capabilities of EMTP-like tools: from analysis to design.
The best understanding to the phenomenon of transient in IEEE Transactions on Power Delivery, 2003. 18, 1569-
the mechanically switched capacitor with damping 1571.
[12] Ali, S.A. Capacitor Banks Switching Transients in Power
network (MSCDN) was conducted via analytical Systems. Energy Science and Technology, 2011. 2, 62-73.
computation and simulation using ATP-EMTP program. [13] Abdul Hamid, H., Transients in reactors for power
The analytical computation was done just for single phase systems compensation, 2012, Cardiff University.
by simplified the MSCDN circuit to find the voltage and [14] Mathcad 13 User’s Guide. Mathsoft Engineering &
current equations and plot their responses in time domain, Education, Inc., 2005.
the simplified procedure was conducted using MathCAD [15] Ayadurai, V. Electrical Application Substation Design
program. Based on the analytical calculations Guide [Online]. Available:
investigations and simulation of transient voltages and http://www.scribd.com/doc/55158137/Electrical-
Application-Substation-Design-Guide. 2011.
currents of MSCDN components at switching operations
[16] Kalyuzhny, A.; Zissu S.; and Shein D. Analytical Study of
of circuit breakers, the resulted analytical calculations Voltage Magnification Transients Due to Capacitor
showed the similar simulation result which enhanced the Switching. IEEE Transactions on Power Delivery, 2009.
validation of ATP-EMTP simulations. In general, the 24, 797-805.
comparison among the simulation results of each [17] Xiao, Y.; Zhao J.; and Mao S. Theory for the Design of C-
MSCDN components leads to find the ideal cases (lowest type Filter. in 11th International Conference on
overvoltage and overcurrent), and emphasis which is the Harmonics and Quality of Power. 2004.
best switching time for each case. For single phase, the [18] British Standard BS EN 62068-1, Electrical insulation
ideal and worst cases were addressed; the ideal closing systems-Electrical stresses produced by repetitive
time of switch across main capacitor was at 5 ms. impulses-Part 1: General method of evaluation of
electrical endurance, 2003.
[19] Campos, R.C.; Lacerda D.O.; and Alves M.F.,
REFERENCES Mechanically Switched Capacitor with Damping Network
(MSCDN)-Engineering aspects of application, design and
[1] Siemens AG. Mechanical Switched Capacitor protection, in Transmission and Distribution Conference
and Exposition: Latin America (T&D-LA), 2010
(MSC/MSCDN). 2002-2014; Available from:
http://www.energy.siemens.com/us/en/power- IEEE/PES2010. p. 316 - 322.
transmission/facts/mechanical-switched-capacitor/.
[2] Electrotek Concepts Inc. Transient Studies. 2002-2014;
Available from:
http://www.electrotek.com/TransientStudies.htm.
[3] Abdul Hamid, H.; Harid N.; and Haddad A., Transient
Analysis during Switching of Mechanically Switched
Capacitor and Damping Network (MSCDN), in
UPEC20102010.

Вам также может понравиться