PROJECT

DD & DDD DDDDD, DDDD DDDDDDD.


DDD DDDDDDD DDDDDDDD DDDDDDDDD.

CLIENT
DDDDDD DDD DDDDDDDDDDD DDD., DDDDDDD.

CLIENT'S CONSULTANT
DDDDDDDDD DDDDD DDDDDDD, DDD DDDDD

CONTRACTOR
DD DDDD DDDDD DDDDDDD
DDDDDDD

DOCUMENT NO. : P063-C0004-3


NO. OF PAGES : 6 (Design)
Rev. : 0
Date. : 12-Apr-04
VA TECH WABAG LTD.
DEGASSED WATER STRG TANK

DESIGN OF RCC RING WALL FOUNDATION


DEGASSED WATER STORAGE TANK (91-T-415 A/B)

DESIGN DATA :
FFL = 100.00
Bottom of Tank above FFL (A) = 500 mm

Height of Tank (H) = 5700 mm


Diameter of Tank (D) = 5000 mm

Outer diameter of Ring wall (C) = 5300 mm

Foundation depth is considered 1800 mm below FFL


\Total height of Ring wall (h) = 2300 mm

Empty weight of SDG (W1) = 141 kN


Working weight of SDG (W2) = 1260 kN

Density of soil = 18 kN/m3


Safe Bearing capacity = 60 kN/m2

DESIGN CALCULATIONS :

Loadings -
Assume Ring wall 300 mm thick (t)
Assume width of wall footing = 3200 mm
Thk of wall footing = 300 mm

Loads :
Load of steel tank shell (w1) = W1 = 8.98 kN/m
and roof over Ring wall pxD
Load intensity due to (w2) = W2 = 56.99 kN/m2
fluid inside tank (p/4) x D2

Net soil pressure under tank(p1) = w2 + 18 h1


= 65.99 kN/m2

Bearing pressure for Static condition -


Net soil pressure under RCC ring wall = w1 w2 7h 25 h1
t 2
= 59.90 kN/m2 < S.B.C.
T'fore OK

DM_CPU PLANT 1
VA TECH WABAG LTD.
DEGASSED WATER STRG TANK

Reinforcement -
% of Circumferential reinf. reqd. = ( 0.33 w2 + 0.338 h ) R
(ka = 0.33) 230 t
= 0.091 %

Min. % of Circumferential reinf. reqd. = 0.20 %

Min. % of Vertical reinf. reqd. = 0.12 %

Total circumferential reinf. reqd. = 0.200 xtxh


100
= 1380.0 mm2
Circum. reinf. reqd. on each face = 1380.0 mm2
per meter height of wall 2xh
= 300 mm2

Total Vertical reinf. reqd. = 0.12 x t x 1000


per meter length of wall 100
= 360 mm2
Vertical reinf. reqd. on each face = 180 mm2

Provide 10F @ 200 c/c (= 314 mm2) circum. reinf. on each face
Provide 10F @ 320 c/c (= 245 mm2) vertical reinf. on both faces

For Settlement calculations refer enclosed Annexures

DM_CPU PLANT 2